We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ©ABB Industrie AG
Based on Based on Project Standard Project SONGIFA Issued M. Zeta 07.11.2003 Client Draw No. Released R. Zürcher 07.11.2003 Order No. 1-2012957 Doc. kind Interlocking Diagram Doc. =1N1LG02 Item Title Liquid Starter for MV-Motor 1N1R042 des. des. Resp. dept. ATBPM Document number Lang. Rev. ind. Page 1
ABB Switzerland Ltd 3BHS197704 en 0 No. of p. 23 I:\01\Plant\Orders\Song Gianh\2 Design Documents\040 Equipment Documents\010 HV & MV Equipment\MV_Motor_Starters\1N1R042\1N1LG02_0_Liquid_Starter_Interlocking_CheckList_1N1R042.doc
Customer: Midland Construction Corporation
Project: SONGIFA Song Gianh Cement Plant
Title: Interlocking Diagram Liquid Starter for MV-Motors 1N1R042/S-No. 6984/8
STATUS: ISSUED FOR: APPROVED INFORMATION
COMMENTED COMMENT AS BUILT APPROVAL
FINAL CONSTRUCTION x Approval signatures
Approved by Customer Project Manager Design Leader
Rev. Signature Date Signature Date Signature Date 0 Werner Wappel 07.11.2003 R. Zürcher 07.11.2003
Doc. kind Interlocking Diagram Project SONGIFA 1-2012957 Title Liquid Starter for MV-Motor 1N1R042 Client Draw No. Doc. 1N1LG02 Document number Lang. Rev. ind. Pages 2
ABB Switzerland Ltd 3BHS197704 en 0 No. of p. 23 I:\01\Plant\Orders\Song Gianh\2 Design Documents\040 Equipment Documents\010 HV & MV Equipment\MV_Motor_Starters\1N1R042\1N1LG02_0_Liquid_Starter_Interlocking_CheckList_1N1R042.doc
Rev. Index
Page (P) Chapter (C)
Description Date Dept./Init.
0 First issue 07.11.2003 M. Zeta
List of content 1. Circuit Connection 13 Pages Date of Issue 25.06.2003/Rev.00 2. Check List 07 Pages Date of Issue 18.06.1999/Rev.01 3. Example Test Protocol 01 Page Date of Issue 30.04.1998/Rev.00
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
1
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
001
002
003
004
005
006
T01
over-run 1
I03___
Travel Range
M01
fault
I05___
Temp. > 85°C
I11___
ACS140 fault
M01___
fault
Q05
Trip
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
2
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
Shorting contactor K2is closed!
Travel RangeLimit switchcross, use handcrank!
Attention! over-run time s switch off!
T1: Istwert
Attention! Temperature > 85 degreesCelsius!
ACS140 faultRead error code on ACS display!
Liquid levelunder limit!Fill up water!
007
008
009
010
011
012
I12
SCC closed
D01
SCC closed
I03___
Travel Range
D02
travel range
T01
over-run 1
D03
Over-run
M07___
Text Display
I05___
Temp. > 85°C
D04
Temp. > 85°C
I11___
ACS140 fault
D05
ACS140 fault
I07___
Liquid level
D06
Liquid level
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
3
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
Electrodes drive to Rmin
Electrodes drive to Rmax
013
014
015
016
017
018
Q01
Start ACS140
Q02
Rmax/Rmin
D07
drive Rmin
Q02___
Rmax/Rmin
D08
drive Rmax
M01
fault
I07___
Liquid level
I01
Pos Rmax
M03
Ready start
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
4
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
019
020
021
022
023
024
I12
SCC closed
M03___
Ready start
M01___
fault
SQ04
Availibility
M01
fault
RQ04
Availibility
T01
over-run 1
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
5
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
Parameteranzeige = einTimertyp = ImpulsSollwert = 0 s . 10 ms
025
026
027
028
029
030
I08___
Start/Stop
M04___
factory test
M03
Ready start
TT04
Starttrigger
M01
fault
T04
Starttrigger
SM05
Ref.-Point
I08___
Start/Stop
M04___
factory test
I01
Pos Rmax
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
6
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
031
032
033
034
035
036
I12
SCC closed
I01___
Pos Rmax
RM05
Ref.-Point
M03___
Ready start
I08
Start/Stop
SM06
Motor Start
M04
factory test
M01
fault
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
7
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
Parameteranzeige = einTimertyp = RückfallverzögerungSollwert = 1 s . 0 ms
037
038
039
040
041
042
I02___
Pos Rmin
RM06
Motor Start
I08___
Start/Stop
M04___
factory test
I02___
Pos Rmin
SQ03
SCC close
T02___
delayed open
RQ03
SCC close
I08
Start/Stop
TT02
delayed open
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
8
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
043
044
045
046
047
048
M04
factory test
M05
Ref.-Point
RQ02
Rmax/Rmin
M06
Motor Start
SQ02
Rmax/Rmin
M01___
fault
M05
Ref.-Point
Q01
Start ACS140
M06
Motor Start
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
9
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
Parameteranzeige = einTimertyp = AnsprechverzögerungSollwert = 40 s . 0 ms
049
050
051
052
053
054
Q01
Start ACS140
TT01
over-run 1
T01
over-run 1
P02___
Reset
T03
press time
SM02
factory stat
P02
Reset
RM02
factory stat
C01
100 loops
P01___
factory test
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
10
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
Parameteranzeige = einTimertyp = AnsprechverzögerungSollwert = 1 s . 0 ms
Parameteranzeige = einSollwert = 100
Parameteranzeige = einTimertyp = AnsprechverzögerungSollwert = 3 s . 0 ms
Parameteranzeige = einSollwert = 100
055
056
057
058
059
060
P04
Test mode
M02
factory stat
T05___
test on/off
M04
factory test
I12
SCC closed
TT05
test on/off
M04
factory test
CC01
100 loops
P01
factory test
TT03
press time
RC01
100 loops
A B C D E F G H ICircuit Con. Parameters
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
11
13 / 1
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
061
062
063
064
065
066
P03
Disp. on/off
M07
Text Display
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
12
13 / 1
Operand Comment Circuit Con.
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
I1 Pos Rmax 18A, 30E, 32AI2 Pos Rmin 37A, 40AI3 Travel Range 2A, 8EI5 Temp. > 85°C 3A, 10EI7 Liquid level 12E, 17AI8 Start/Stop 25A, 30A, 34C, 38A, 42AI11 ACS140 fault 4A, 11EI12 SCC closed 7E, 19A, 31A, 57CQ1 Start ACS140 13C, 47G, 49AQ2 Rmax/Rmin 13E, 14E, 45G, 46GQ3 SCC close 40G, 41GQ4 Availibility 21G, 23GQ5 Trip 5GP1 factory test 54C, 59AP2 Reset 50C, 53AP3 Disp. on/off 62AP4 Test mode 55AM1 fault 2G, 5A, 16A, 21C, 23A, 28A, 36A, 47AM2 factory stat 52G, 53G, 56AM3 Ready start 18G, 21A, 25E, 34AM4 factory test 25C, 30C, 35C, 38C, 43A, 56G, 58AM5 Ref.-Point 29G, 32G, 45A, 47CM6 Motor Start 34G, 37G, 46A, 48CM7 Text Display 10A, 62GT1 over-run 1 1A, 9E, 24A, 49G, 50AT2 delayed open 41A, 42GT3 press time 52A, 59GT4 Starttrigger 27G, 29AT5 test on/off 56C, 57GC1 100 loops 54A, 58G, 60GD1 SCC closed 7GD2 travel range 8G
25.06.03
Friedrich
ABB Schweiz
Song Gianh
101-2348237
6984/8
Friedrich
13
13 / 1
Operand Comment Circuit Con.
Date:
Editor:
Checked:
Customer:
Customer Doc. No.:
Order No.:
Factory No.:
Document No.:
Author:Sheet:of Sheet:
D3 Over-run 9GD4 Temp. > 85°C 10GD5 ACS140 fault 11GD6 Liquid level 12GD7 drive Rmin 13GD8 drive Rmax 14G
ELEKTROSCHALTGERÄTE MEERANE GMBH Reg.-Nr.: FB 013/QB Release 23.04.97 Rev. 1 / 18.06.1999Elektroschaltgeräte Meerane GmbH, Postfach 1251, 08384 Meerane
Hausanschrift Bankverbindung Elektroschaltgeräte Meerane GmbHKarl-Schiefer-Straße 1, 08393 Meerane Volksbank Meerane (BLZ 870 959 74) Konto 300 144 292 Geschäftsführer: Werner Heinicke, Werner RabeTelefon (03764) 7912 0, Fax (03764) 7912 79 Sparkasse Chemnitz (BLZ 870 500 00) Konto 3633001050 Registrier-Nr. 1016, Registergericht Chemnitz
Page 1 / 7
CHECK LIST
PROJECT: Song Gianh, Vietnam, Cement MillLiquid Rotor Starter
ABB No.: 1N1R042
TYPE: 6270.021/7 – S
SERIAL NO.: 6984/8
ELEKTROSCHALTGERÄTE MEERANE GMBHReg.-Nr.: FB 013/QB Release 23.04.97 Rev. 1 / 18.06.1999Elektroschaltgeräte Meerane GmbH, Postfach 1251, 08384 Meerane
Hausanschrift Bankverbindung Elektroschaltgeräte Meerane GmbHKarl-Schiefer-Straße 1, 08393 Meerane Volksbank Meerane (BLZ 870 959 74) Konto 300 144 292 Geschäftsführer: Werner Heinicke, Werner RabeTelefon (03764) 7912 0, Fax (03764) 7912 79 Sparkasse Chemnitz (BLZ 870 500 00) Konto 3633001050 Registrier-Nr. 1016, Registergericht Chemnitz
Page 2 / 7
Elektroschaltgeräte Meerane GmbHKarl - Schiefer - Straße 1
D - 08393 Meerane
Check List for Liquid Starter
IMPORTANT NOTICE: This Check List has to be filled-in before commissioning and must then be returned to the above mentioned address!
REQUIREMENT: Fill-in of check list and commissioning of the starter should be done only by qualified personnel!
REMARKS: 1. Do not fill-up the starter with electrolyte and do not connect the rotor cables with the corresponding terminals K, L and M before checking the starter.
2. Fill-up the starter and attach the rotor and control cables according to the „INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS“!
3. Make sure, that the first start will be executed at minimum load from the driven machine.
All instructions in the check list framed like this should be executed as described in the„INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS“!
ELEKTROSCHALTGERÄTE MEERANE GMBHReg.-Nr.: FB 013/QB Release 23.04.97 Rev. 1 / 18.06.1999Elektroschaltgeräte Meerane GmbH, Postfach 1251, 08384 Meerane
Hausanschrift Bankverbindung Elektroschaltgeräte Meerane GmbHKarl-Schiefer-Straße 1, 08393 Meerane Volksbank Meerane (BLZ 870 959 74) Konto 300 144 292 Geschäftsführer: Werner Heinicke, Werner RabeTelefon (03764) 7912 0, Fax (03764) 7912 79 Sparkasse Chemnitz (BLZ 870 500 00) Konto 3633001050 Registrier-Nr. 1016, Registergericht Chemnitz
Page 3 / 7
Device: Three - Phase Liquid Rotor StarterType: 6270.021/7- SSerial No.: 6984/8
Provided for starting a slip-ring motor with the following data:
Nominal Power: 7900 kWRotor standstill voltage u20: 2540 VNominal rotor current i2: 1870 A
Driven machine: Cement Mill
Built-in sequence control: EASY4210-4218.DWG dated 01.07.03Outline drawing: 6270.021/7-S / M7E0217S.DWG
3-phase voltage supply: 3 x 380 V, 50 Hz1-phase voltage supply: 1 x 220 V, 50 Hz
Will the starting procedure take place under the same conditions and with the same technical data forwhich the starter has been calculated and designed?
Please confirm: YES
Have steps been taken to prevent overload of motor and starter?
Please confirm: YES
1. Measuring Insulation Resistance
Measuring insulation resistance between the 3 rotor cable connection terminals K, L, M and theearthing point. The measured value should be higher than 10 MΩΩΩΩ (minimum is 2000 Ω / V, related tothe rotor standstill voltage u20).
Please enter the values (Test voltage 500 V or 1000 V): K - Earth ………… MΩL - Earth ………… MΩM - Earth ………… MΩ
ELEKTROSCHALTGERÄTE MEERANE GMBHReg.-Nr.: FB 013/QB Release 23.04.97 Rev. 1 / 18.06.1999Elektroschaltgeräte Meerane GmbH, Postfach 1251, 08384 Meerane
Hausanschrift Bankverbindung Elektroschaltgeräte Meerane GmbHKarl-Schiefer-Straße 1, 08393 Meerane Volksbank Meerane (BLZ 870 959 74) Konto 300 144 292 Geschäftsführer: Werner Heinicke, Werner RabeTelefon (03764) 7912 0, Fax (03764) 7912 79 Sparkasse Chemnitz (BLZ 870 500 00) Konto 3633001050 Registrier-Nr. 1016, Registergericht Chemnitz
Page 4 / 7
• Connect the rotor cables and the earthing cable to the corresponding terminals.• Remove the top cover(s) of the starter.• Remove all inner covers (013/014/015-series) and remove, if there is any, corrosion protection
material inside the electrolyte tank (BRANOrost-Chip).• In case of movable electrodes are standing in the lower end position, take the hand-crank and lift
the electrodes to the upper end position by using the emergency hand drive.
2. General Test Procedure
2.1. Have all mechanical and electrical safety regulation and other laws that are in force at site been observed? YES
2.2. Have rotor and earthing cables been connected? YES
2.3. Testing of thermostat settings:
- B5 should be set to 5°C YES or- B3 should be set to 85°C YES or- B6 (if installed) should be set to 75°C for temperature alarm YES
2.4. Have you found any deformations or destruction’s of built-inmechanical or electrical components during a visual inspection? YES NO
If the answer is YES immediately contact Elektroschaltgeräte Meerane GmbH!
3. Functional Test
3.1 Mechanical test of electrode setting mechanism.Use the hand-crank and the emergency hand drive to move the electrodes from the upper end position to the lower end position and then back.
3.1.1 There is no force between the electrodes and there guiding pins inany position between the two end position. Please confirm: YES
3.1.2 Check the unchanged setting of the limit switches and / or proximityinitiators. Red seals o.k.? Please confirm: YES
ELEKTROSCHALTGERÄTE MEERANE GMBHReg.-Nr.: FB 013/QB Release 23.04.97 Rev. 1 / 18.06.1999Elektroschaltgeräte Meerane GmbH, Postfach 1251, 08384 Meerane
Hausanschrift Bankverbindung Elektroschaltgeräte Meerane GmbHKarl-Schiefer-Straße 1, 08393 Meerane Volksbank Meerane (BLZ 870 959 74) Konto 300 144 292 Geschäftsführer: Werner Heinicke, Werner RabeTelefon (03764) 7912 0, Fax (03764) 7912 79 Sparkasse Chemnitz (BLZ 870 500 00) Konto 3633001050 Registrier-Nr. 1016, Registergericht Chemnitz
Page 5 / 7
• Connect the control cables and the cables of the voltage supply with the corresponding terminals ofthe starter. Make sure that all fuses and circuit breakers are switched on. At ambient temperaturesof ≤ 5°C disable or disconnect voltage supply for electrolyte heaters (if installed)!
• Make sure the power supply to the stator side of the slip-ring motor continues to remaininterrupted, also in event of switching ON the slip-ring motor!
Execution of electrical test is depending on the starters design. Is this starterequipped with a built-in sequence control? YES NO
If the answer is NO continue with item 3.2. If the answer is YES continue with item 3.3.
3.2 Electrical test of starters without a built-in sequence control.
3.2.1 All control cables connected to the starters connection terminalaccording to the valid diagrams? Please confirm: YES
3.2.2 Is the customer-made starter sequence control designed to satisfythe general requirements given in the „INSTALLATION,OPERATING AND MAINTENANCE INSTRUCTIONS“ chapter 2.1!
Please confirm: YES NO
In case of NO write down the differences on a separate sheet ofpaper and attach it to this check list.
3.2.3 Confirm the execution of a successful test run. YES
3.2.4 Correspond the measured starting time with the startingtime engraved in the wide framed ta-field of the rating plate (± 10 %)? YES
Continue with item 4!
3.3 Electrical test of starters with a built-in sequence control.
3.3.1 All control cables connected to the starters connection terminalaccording to the valid control diagrams? Please confirm: YES
3.3.2. Connect the connecting terminals ground electrode “C” and minimalelectrode “MIN” for the liquid level controller -B4 in order to simulatea sufficient electrolyte level.Execute a test run by using an external or internal start signal. Checkall control-relevant functions and compare the results with the functionsdetermined by the control diagrams. Please confirm no deviations: YES
ELEKTROSCHALTGERÄTE MEERANE GMBHReg.-Nr.: FB 013/QB Release 23.04.97 Rev. 1 / 18.06.1999Elektroschaltgeräte Meerane GmbH, Postfach 1251, 08384 Meerane
Hausanschrift Bankverbindung Elektroschaltgeräte Meerane GmbHKarl-Schiefer-Straße 1, 08393 Meerane Volksbank Meerane (BLZ 870 959 74) Konto 300 144 292 Geschäftsführer: Werner Heinicke, Werner RabeTelefon (03764) 7912 0, Fax (03764) 7912 79 Sparkasse Chemnitz (BLZ 870 500 00) Konto 3633001050 Registrier-Nr. 1016, Registergericht Chemnitz
Page 6 / 7
In case of deviations contact Elektroschaltgeräte Meerane GmbH!
Reconnect the jumper wire for the liquid level controller -B4.
3.3.3 Correspond the measured starting time with the startingtime engraved in the wide framed ta-field of the rating plate (± 10 %)? YES
• Fill up the starter with electrolyte.• Enable or reconnect the voltage supply for electrolyte heaters if disabled or disconnected before.
4. Electrolyte basic filling
Have you filled up the starter according to the instructions given inthe „INSTALLATION, OPERATING AND MAINTENANCEINSTRUCTIONS“ chapter 1.3 and the documentation part „Resistancedata for Three - Phase Liquid Rotor Starter“ Please confirm: YES
5. Readjustments
5.1 Change of starting time ta
If it is necessary to change the starting time because there has been a change in operating characteristics proceed as follows (select the applicable item 5.1.1 or 5.1.2):
5.1.1 Starting time of starters equipped with an electrode setting motor with two separate windings(8-4-pole version) can be changed by modifying the wiring of the motor connection terminal(see instructions inside the motor connection box). The second available starting time is engraved in the thin framed ta-field of the rating plate!
5.1.2 Starting time of starters equipped with a standard electrode setting motor (standard version4- or 8-pole) and a frequency converter can be changed by modifying the setting of the frequency converter. The allowed setting time range is engraved in the thin framed ta-field of the rating plate. How to change the parameter „maximum output frequency“ is described in the „Users Manual“ of the frequency converter.
Starting time supervision (installed or appropriated by the user) must be changed accordingly!Setting on new starting time ta + 5 seconds (currently time T1 in logic module, 35+5=40s).
ELEKTROSCHALTGERÄTE MEERANE GMBHReg.-Nr.: FB 013/QB Release 23.04.97 Rev. 1 / 18.06.1999Elektroschaltgeräte Meerane GmbH, Postfach 1251, 08384 Meerane
Hausanschrift Bankverbindung Elektroschaltgeräte Meerane GmbHKarl-Schiefer-Straße 1, 08393 Meerane Volksbank Meerane (BLZ 870 959 74) Konto 300 144 292 Geschäftsführer: Werner Heinicke, Werner RabeTelefon (03764) 7912 0, Fax (03764) 7912 79 Sparkasse Chemnitz (BLZ 870 500 00) Konto 3633001050 Registrier-Nr. 1016, Registergericht Chemnitz
Page 7 / 7
5.2 Changes of other parameters or set-points
Changes of other parameters or set-points requires approval by Elektroschaltgeräte Meerane GmbH. Not approved modifications may effect guarantee loss.
After completion of changes run through the check list once again beginning with item 3!
If serious deviations are found in any section of the checking procedure the starter may only beput to work on receipt of a written approval by Elektroschaltgeräte Meerane GmbH!
This check list was filled-in by:
Company: ...............................................................................
Name / Signature: ................................ / ................................
Place of issue, Date: ................................................................
Please return this check list as soon as possible to:
Elektroschaltgeräte Meerane GmbHKarl - Schiefer - Straße 1
Sales Department
D - 08393 MeeraneGermany
F:\ESM\PROJEKTE\ABB-SW\6984_SON\6984_8\CHECK.DOC
ELEKTROSCHALTGERÄTE MEERANE GMBHElektroschaltgeräte Meerane GmbH, Karl-Schiefer-Straße 1, D - 08393 Meerane Tel.: ++ 49 3764 7912-0 Fax: ++ 49 3764 7912-79
6984/8 TEST PROTOCOL according to Standard DIN VDE 0660 / IEC 17 BReg.-No.: FB 014/QB Issue: 30.04.98
Project: SONGIFA ABB no.: 1N1R042Code:
Order no.: 101-2348237 Date: 05.06.03Contract no.: 6984 Date: 10.06.03
GENERAL DATA Degree of Protection:Starter type: 6270.021/7-S (DIN VDE 0470 / IEC 144) Starter: IP 43Article code: 9817900 Rotor cable connection: IP 54Serial no.: 6984/8 Control / auxiliary devices: IP 54
Motor power: 7900 kW Voltage supply: 3-phase: 380/50 V / HzRotor voltage: 2540 V 1-phase: 220/50 V / HzRotor current: 1870 A Internal control voltage: - V / HzStarting factor f: 1,4
Paint coating: RAL 5014 X ok Dimensions: 2700x2140x2350 mm (LxBxH)Language: english X ok Weight: 2750 kg
STARTERWelding / tightness test: X ok Shop Test Standard: 6260/10/94Paint coating test: X ok Shop Test Standard: 6260/20/94Insulation / High voltage test: X ok Shop Test Standard: 6260/40/94
Test voltage: 10.000 V Standard: DIN 57660Testing time: 60 s part 105 / IEC 17 B)
Functional test: X ok Shop Test Standard: 6260/50/94Final test: X ok Shop Test Standard: 6260/60/94Shipping / Packing inspection: X ok according to FB 007/QB and VA 003/KV
CONTROL / CONTROL DEVICESStarting time: 35 s X ok Built-in sequence control (Y/N): YTemperature controller Source: EASY4210-4218.DWG
- B5: 5°C X ok Issue date: 01.07.03 - B3: 85°C X ok - B6: 75°C X ok For starters without sequence control:
Connection terminal:Limit switches / Proximity initiators: X ok Issue date:Heaters: 2x 3000 W X ok
Manufacturer certifies: Fabrication of appliance agree with mentioned Standards.Used materials agree with valid DIN StandardsFunction of appliance meets requirements fixed in the contract.
REMARKS Name : Andreas HofmüllerDate: 05.01.04