1848D-CS-13-00003 FM-200 Calculations 21.02.14

download 1848D-CS-13-00003 FM-200 Calculations 21.02.14

of 5

description

fm

Transcript of 1848D-CS-13-00003 FM-200 Calculations 21.02.14

coverHyder Consulting Middle East Ltd.& W.S. Atkins Overseas(JV)P.O.Box 1854Doha, State of State QatarTel. +974 4429 555Fax +974 4428 874CALCULATIONPROJECT NO.1848DCALCULATION NO.1848D-CS-13-00003PROJECTFire ProtectionBP# 1G-D Education City- North East Car Park

SUBJECTSHEET No.FM-200 Calculation1OF2

ISSUETOTAL SHEETAUTHORDATECHECKED BYDATEAPPROVED BYDATECOMMENTS

12AK11.03.14BB11.03.14ES11.03.14IFC

SUPERSEDES DOC No.DATE

DESIGN BASIS STATEMENT (Inc. sources of info/data, assumptions made, standards, etc.)

NFPA 2001 Standard on Clean Agent and Fire Extinguishing System

FM 200 AGENT QUANTITY CALCULATIONS

The amount of FM-200 clean agent required to achieve the design concentration shall be calculated based on NFPA 2001, table A-3-5.1 as follows:

W = ( V/S ) x ( C/ ( 100-C ) )where:W=FM-200 weight, kgV=net volume of the hazard, m3S=specific volume of superheated FM-200 at atmospheric pressure and temperatureS=0.1373m3/kgC=FM-200 design volumetric concentration, 7% by volume

DOCUMENT No. (Project/ Doc)SHEET No.1 OF PROJECT TITLE

NECP FM-200 calcs (2)Hyder Consulting Middle East Ltd.& W.S. Atkins Overseas(JV)P.O.Box 1854Doha, State of State QatarTel. +974 4429 555Fax +974 4428 874CALCULATIONCALCULATION NO.Cylinder Size kg.1848D-CS-13-00003MetricLowHighSHEET NO.4.53.64.52OF29.15.49.5SUBJECTFire Protection15.91017.2FM-200 Calculation27.216.82945.326.345.456.733.157.697.555.897.517097.5170.1ROOM NAMEROOM NAMEROOM SPACEV, HAZARD VOLUMEkgW, MINIMUM WEIGHT OF AGENT REQUIREDkgNUMBER OF CYLINDERS CYLINDER SIZEkg295168.7294.8LENGTHmWIDTHmAREAm2HEIGHTm454259.9454.5

1TECH. ROOM SIG & COMW/ FLOOR VOIDUPPER BASEMENTGRID J/2611.75.506535145

2TECH. ROOM CUUPPER BASEMENTGRID J/2616.375.509049156

DOCUMENT No. (Project/ Doc)SHEET No.1 OF PROJECT TITLE