1800V DC Positive Traction Cables-railway cables DC Positive Traction Cables.pdf1800V DC Positive...

2
174 www.addison-cables.com 1800V DC Positive Traction Cables Applications These DC power cables are used for urban railways for 1500V DC traction power system wit h feedback current and return current, suitable for fixed installation. The cables are suitable for installations in ducts, tunnels, and cable troughs or on the cable bridges etc. Standard IEC60092 BS 7655 IEC60502 BS 6883 Type 657 SW4 Construction Conductor: Class 2 stranded annealed bare copper conductors to BS EN 60228: 2005 (previously BS 6360). Core Wrapping: PETP (Polyet h ylene Terephthalate). Insulation: EPR, GP8 to BS 6899 / BS 7655 RS2 / ICEA S-95-658. Sheath: Thermosetting LSZH compound SW4 or LRS1 to BS 7655 / ICEA T-33-655, with enhanced oil resistance, and minimum tear resistance. Electrical Characteristics at 20℃ Nominal Conductor Cross Section mm² 70 95 120 150 185 240 300 400 500 Maximum DC Conductor Resistance Ω/km 0.277 0.21 0.164 0.132 0.108 0.0817 0.0654 0.0495 0.0391 Minimum Insulation Resistance MΩ.km 539 472 433 390 355 313 280 245 221 Assigned Continuous Current Rating A 330 400 464 530 612 648 853 1010 1195 Conductor Short Circuit Current 1s kA 10.0 13.5 17.1 21.4 26.4 34.3 42.9 57.2 71.5 Voltage Rating KV 1.8 Mechanical and Thermal Properties Minimum Bending Radius: 6×OD Temperature Range: -40to +90(during operation); -25to +60(during installation) Stranded Annealed Copper Conductor Themosetting LSZH Sheath PETP EPR Insulation

Transcript of 1800V DC Positive Traction Cables-railway cables DC Positive Traction Cables.pdf1800V DC Positive...

Page 1: 1800V DC Positive Traction Cables-railway cables DC Positive Traction Cables.pdf1800V DC Positive Traction Cables Applications These DC power cables are used for urban railways for

174 www.addison-cables.com

1800V DC Positive Traction Cables

Applications These DC power cables are used for urban railways for 1500V DC traction

power system with feedback current and return current, suitable for fixed

installation. The cables are suitable for installations in ducts, tunnels, and cable

troughs or on the cable bridges etc.

Standard IEC60092 ●

BS 7655 ●

IEC60502 ●

BS 6883 Type 657 SW4 ●

Construction Conductor: Class 2 stranded annealed bare ●

copper conductors to BS EN 60228: 2005 (previously

BS 6360).

Core Wrapp ing: PETP (Po lye thy lene ●

Terephthalate).

Insulation: EPR, GP8 to BS 6899 / BS 7655 RS2 / ICEA S-95-658. ●

Sheath: Thermosetting LSZH compound SW4 or LRS1 to BS 7655 / ICEA T-33-655, with enhanced oil resistance, ●

and minimum tear resistance.

Electrical Characteristics at 20℃ Nominal Conductor Cross Section mm² 70 95 120 150 185 240 300 400 500

Maximum DC Conductor Resistance Ω/km 0.277 0.21 0.164 0.132 0.108 0.0817 0.0654 0.0495 0.0391

Minimum Insulation Resistance MΩ.km 539 472 433 390 355 313 280 245 221

Assigned Continuous Current Rating A 330 400 464 530 612 648 853 1010 1195

Conductor Short Circuit Current 1s kA 10.0 13.5 17.1 21.4 26.4 34.3 42.9 57.2 71.5

Voltage Rating KV 1.8

Mechanical and Thermal Properties Minimum Bending Radius: 6×OD ●

Temperature Range: -40℃ to +90℃ (during operation); -25℃ to +60℃ (during installation) ●

Stranded Annealed Copper Conductor

Themosetting LSZH Sheath

PETP

EPR Insulation

Page 2: 1800V DC Positive Traction Cables-railway cables DC Positive Traction Cables.pdf1800V DC Positive Traction Cables Applications These DC power cables are used for urban railways for

175

Caledonian Railway Cableswww.caledonian-cables.co.uk

Dimensions and Weight

Cable Code

No. of cores& Nominal

Conductor Cross Sectional Area

No.×mm²

No. & Nominal

Diameter of StrandsNo/mm

Nominal Insulation Thickness

mm

Nominal Sheath

Thicknessmm

Nominal Overall

Diametermm

Nominal Weightkg/km

Polarity

RF6883-DZ1-U-1800P-1G70 1×70 19/2.14 4.0 2.0 20.3 1371 PositiveRF6883-DZ1-U-1800P-1G95 1×95 19/2.52 4.0 2.0 21.7 1641 PositiveRF6883-DZ1-U-1800P-1G120 1×120 37/2.03 4.0 2.2 23.6 1958 PositiveRF6883-DZ1-U-1800P-1G150 1×150 37/2.25 4.0 2.2 19.3 2295 PositiveRF6883-DZ1-U-1800P-1G185 1×185 37/2.52 4.0 2.3 27.3 2682 PositiveRF6883-DZ1-U-1800P-1G240 1×240 61/2.25 4.0 2.3 30.7 3341 PositiveRF6883-DZ1-U-1800P-1G300 1×300 61/2.52 4.0 2.4 33.3 4016 PositiveRF6883-DZ1-U-1800P-1G400 1×400 61/2.85 4.0 2.4 40.3 5071 PositiveRF6883-DZ1-U-1800P-1G500 1×500 91/2.65 4.0 2.5 42.3 6275 PositiveRF6883-DZ1-U-1800P-1G630 1×630 127/2.52 4.0 2.5 43.4 6980 PositiveRF6883-DZ1-U-1800P-1G800 1×800 127/2.85 4.0 2.7 50.6 8785 Positive

Flame RetardantNF C32-070-2.1(C2)

IEC 60332-1/EN 50265-2-1NF C32-070-2.2(C1)

IEC 60332-3/EN50266

Fire Retardant Zero HalogenIEC 60754-1/NF C20-454

EN 50267-2-1

Zero

Low Smoke EmissionIEC 61034/NFC20-902EN 50268/NF C32-073

EN 50267-2-2/NF C32-074IEC 60754-2/NF C20-453

Low Corrosivity Low Toxicity

RAILFEEDER RAILWAY POWER & CONTROL CABLES

UK NETWORK RAIL Standard