17thEditionIETWiringRegulations
Inspection,TestingandCertification
Fullyup-to-datewiththelatestamendmentstothe17thEditionoftheIETWiringRegulations
SimplifiestheadvicefoundintheWiringRegulations,explaininghowtheyapplytoworkingpracticeforinspection,testingandcertification
Expert advice from an engineering training consultant, supported with colourdiagrams,examplesandkeydata
Thispopularguideclarifiestherequirementsforinspectionandtesting,explaininginclearlanguagethosepartsoftheWiringRegulationsthatmostneedsimplifying.Inadditiontothedescriptiveanddiagrammatictestmethodsthatarerequired,explanationsofthetheoryandreasoningbehindtestproceduresaregiven,togetherwithusefultablesforthecomparisonoftestresults.Thebookalsoprovidesessentialinformationonthecompletionofelectricalinstallationcertificates,withastep-by-stepguideontheentriesthatneedtobemadeandwheretosourcedata.
WiththecoveragecarefullymatchedtothesyllabusoftheCity&GuildsCertificatesinInspection,TestingandCertificationofElectricalInstallations(2394-10and2395-10)andFundamentalInspection,TestingandInitialVerification(2392-10),andcontainingsamplepapersandsuggestedsolutions,itisalsoanidealrevisionguide.
BrianScaddan,IEng,MIET,isaconsultantforandanHonoraryMemberofCity&Guildswithover40years’experienceinFurtherEducationandtraining.HeisDirectorofBrianScaddanAssociatesLtd,anapprovedCity&Guildstrainingcentreofferingcoursesonallaspectsofelectrical installationcontracting including theC&G2382-15,2392-10,2377-22,2394-01,2395-01and2396-01.Heisalsoaleadingauthorofbooksforthesecourses.
![Page 3: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/3.jpg)
17thEditionIETWiringRegulations
Inspection,TestingandCertificationEighthEdition
BrianScaddan
![Page 4: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/4.jpg)
Eightheditionpublished2015byRoutledge2ParkSquare,MiltonPark,Abingdon,OxonOX144RN
andbyRoutledge711ThirdAvenue,NewYork,NY10017
RoutledgeisanimprintoftheTaylor&FrancisGroup,aninformabusiness
©2015BrianScaddan
TherightofBrianScaddantobeidentifiedasauthorofthisworkhasbeenassertedbyhiminaccordancewithsections77and78oftheCopyright,DesignsandPatentsAct1988.
Allrightsreserved.Nopartofthisbookmaybereprintedorreproducedorutilisedinanyformorbyanyelectronic,mechanical,orothermeans,nowknownorhereafterinvented,includingphotocopyingandrecording,orinanyinformationstorageorretrievalsystem,withoutpermissioninwritingfromthepublishers.
Trademarknotice:Productorcorporatenamesmaybetrademarksorregisteredtrademarks,andareusedonlyforidentificationandexplanationwithoutintenttoinfringe.
Firsteditionpublished1996byNewnes,animprintofElsevierSeventheditionpublished2011byNewnes,animprintofElsevier
BritishLibraryCataloguinginPublicationDataAcataloguerecordforthisbookisavailablefromtheBritishLibrary
LibraryofCongressCataloging-in-PublicationDataScaddan,Brian.17theditionIETwiringregulations.Inspection,testingandcertification/BrianScaddan.—8thedition.pagescmIncludesindex.1.Electricwiring,Interior—Safetyregulations—GreatBritain—Handbooks,manuals,etc.2.Electricwiring,Interior—Insurancerequirements—GreatBritain—Handbooks,manuals,etc.3.Electricwiring,Interior—Inspection—Handbooks,manuals,etc.4.Electricwiring,Interior—Testing—Handbooks,manuals,etc.I.Title.II.Title:Inspection,testing,andcertification.III.Title:IETwiringregulations,inspection,testingandcertification.TK3271.S26922015621.319‘24021841—dc232014048613
ISBN:978-1-138-84886-3(pbk)ISBN:978-1-315-72595-6(ebk)
TypesetinKuenstler480andTradeGothicby
![Page 5: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/5.jpg)
ServisFilmsettingLtd,Stockport,Cheshire
![Page 6: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/6.jpg)
ContentsPREFACEINTRODUCTIONCHAPTER1AnOverviewStatutoryandNon-StatutoryRegulationsElectricalSystemsandEquipmentTheBuildingRegulationsPart‘P’InstrumentsCHAPTER2InitialVerificationCircumstancesWhichRequireanInitialVerificationGeneralReasonsforInitialVerificationInformationRequiredDocumentationRequiredandtobeCompletedSequenceofTestsCHAPTER3TestingContinuityofProtectiveConductors(Low-ResistanceOhmmeter)CHAPTER4TestingContinuityofRingFinalCircuitConductors(Low-ResistanceOhmmeter)CHAPTER5TestingInsulationResistance(InsulationResistanceTester)CHAPTER6SpecialTestsProtectionbyBarriersorEnclosuresProtectionbyNon-ConductingLocationCHAPTER7TestingPolarity(Low-ResistanceOhmmeter)CHAPTER8TestingEarthElectrodeResistance(EarthElectrodeResistanceTesterorLoopImpedanceTesters)Method1:ProtectionbyOvercurrentDeviceMethod2:ProtectionbyaResidualCurrentDeviceCHAPTER9TestingEarthFaultLoopImpedanceTesterExternalLoopImpedanceZe
CHAPTER10AdditionalProtection(RCDTester)RCD/RCBOOperationRequirementsforRCDProtectionCHAPTER11ProspectiveFaultCurrent(PFC/PSCCTester)CHAPTER12CheckofPhaseSequence(PhaseSequenceIndicator)CHAPTER13FunctionalTestingCHAPTER14VoltageDrop(ApprovedVoltmeter)CHAPTER15PeriodicInspectionPeriodicInspectionandTesting
![Page 7: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/7.jpg)
CircumstancesWhichRequireaPeriodicInspectionandTestGeneralReasonsforaPeriodicInspectionandTestGeneralAreasofInvestigationDocumentationtobeCompletedSequenceofTestsCHAPTER16CertificationElectricalInstallationCertificateElectricalInstallationConditionReportObservationCodesMinorElectricalInstallationWorksCertificateContentsofaTypicalScheduleofTestResultsScheduleofInspections(asperBS7671)APPENDIX12394SamplePaperSectionASectionB2395SamplePaperSectionASectionBAPPENDIX22394SamplePaper(Answers)SectionASectionB2395SamplePaper(Answers)SectionASectionBAPPENDIX32394/5SampleMCQPaperandAnswersAnswersINDEX
![Page 8: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/8.jpg)
PrefaceThis book is primarily for use as a study resource for the City & Guilds 2394 InitialVerificationandC&G2395PeriodicInspectionandTestingcourses.
However, it is also a useful reference for C&G 2382-15, 17th Edition; C&G 2392-10,FundamentalInspectionandTesting,andC&G2396,Design.
BrianScaddan
![Page 9: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/9.jpg)
IntroductionMany candidates embarking on the 2394 and 2395 courses find difficulty in eitherunderstandingwhattheExaminerisaskingforinquestions,orhowtoexpressthemselveswhenanswering.The samplepapersandanswersat theendof thisbook shouldhelp toalleviatethesedifficulties.
One of the common problems is a lack of understanding of some basic principles andincorrect use of technical wording. In many instances it may be unfair to quote‘misunderstanding’when it is probably just a caseofhaving forgotten thedetails of the17thEdition,etc.
Below is a list of commonwords, phrases and acceptable abbreviations that candidatesreallyshouldbeawareof,astheyoftenappearinexaminationquestions:
StatutoryDocuments
TheHealthandSafetyatWorkAct(H&SWA).Affectseveryoneatwork.TheElectricityatWorkRegulations (EAWR).Affects those atwork involvedwith
electricalsystems. The Building Regulations Part ‘P’.Affects those who install electrical systems in
domesticpremises. TheElectricity Safety,Quality andContinuityRegulations (ESQCR).Thesereally
onlyaffectthesuppliersofelectricalenergytopremises.
Non-StatutoryDocuments
BS7671.TheIETGuidanceNote3(GN3).ThisisspecificallyforInspectionandTesting.TheH&SGuidanceNoteGS38(GS38).Thisdealswithelectricalinstruments,etc.Anyotherdocumentsthatrelatetoinspectionandtesting.
Electrical System This is defined in the EAWR as anything that generates, stores,transmits, uses, etc. electrical energy (e.g. a power station or a torch battery or a testinstrument,etc.).
DutyHolderThisistheEAWRTitleofanyonewhohascontrolofanelectricalsystem.
CompetentPersonThisistheEAWRStatusofaDutyHolder.
BasicProtectionProtectionagainstelectricshockunderfault-freeconditions(touchinganintentionallylivepart)
MethodsofProvidingBasicProtectiononly:
Insulationofliveparts.
![Page 10: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/10.jpg)
Barriersorenclosures.Obstacles(notcommon,onlyforuseunderthesupervisionofskilledpersons). Placing out of arms’ reach (not common, only for use under the supervision of
skilledpersons).
FaultProtectionProtectionagainstelectricshockundersingle-faultconditions(touchingaconductivepartmadeliveduetoafault).
MethodsofProvidingFaultProtectiononly:
AutomaticDisconnectionofSupply(ADS).ThisisEarthing,Bondingandensuringprotectivedevicesoperateinthedesignatedtime.
MethodsofProvidingbothBasicandFaultProtection:
DoubleorReinforcedinsulation.SELVorPELV.ElectricalSeparation(foroneitemofequipment,e.g.shaverpoint).
ExposedConductivePartCasingofClassIequipmentormetalconduit/trunking,etc.
ExtraneousConductivePartStructuralsteelwork,metallicgas,water,oilpipes,etc.
Additional Protection Used in the event of failure of Basic and/or Fault protection orcarelessnessbyusers.
MethodsofProvidingAdditionalProtection:
RCD,30mAorlessandoperatingwithin40msatfivetimesitsratingSupplementaryEquipotentialBonding.
ProtectiveConductors:
TheEarthingconductorConnectstheMainEarthingTerminal(MET)tothemeansofearthing.(TheMainEarthingconductorisincorrectterminology.)
MainProtectiveBondingconductorsConnecttheMETtoextraneousconductiveparts.
CircuitProtectiveconductors(cpc)ConnecttheMETtoexposedconductiveparts. Supplementary Protective Bonding conductors Connect together exposed and
extraneousconductiveparts in locationssuchasbathrooms,swimmingpools,etc.orwheredisconnectiontimescannotbemetalthoughRCDsareusuallyusedinthiscase.
![Page 11: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/11.jpg)
TheIETWiringRegulationsBS7671
Beforeweembarkonthesubjectofinspectionandtesting,itis,perhaps,wisetoexamineinmoredetailsomeofthekeytopicspreviouslylisted.
Clearly, the protection of persons and livestock from shock and burns, etc. and theprevention of damage to property are priorities. In consequence, therefore, thoroughinspection and testing of an installation and subsequent remedialworkwherenecessarywillsignificantlyreducetherisks.
Soletusstartwithelectricshock;thatis,thepassageofcurrentthroughthebodyofsuchmagnitude as to have significant harmful effects. Figure 0.1 illustrates the generallyacceptedeffectsofcurrentpassingthroughthehumanbody.
Howthenareweatriskofelectricshock,andhowdoweprotectagainstit?
Therearetwowaysinwhichwecanbeatrisk:
1.Touchinglivepartsofequipmentorsystemsthatareintendedtobelive.2.Touching conductivepartswhicharenotmeant tobe live, buthavebecome live
duetoafault.
FIGURE0.1Shocklevels.
1–2mA Barelyperceptible,noharmfuleffects5–10mA Throwoff,painfulsensation
![Page 12: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/12.jpg)
10–15mA Muscularcontraction,can’tletgo20–30mA Impairedbreathing50mAandabove Ventricularfibrillationanddeath
The conductive parts associated with the second of these can either be metalwork ofelectricalequipmentandaccessories(ClassI)andthatofelectricalwiringsystemssuchasmetallic conduit and trunking, etc. called exposed conductive parts, or other metalworksuchaspipes,radiators,girders,etc.calledextraneousconductiveparts.
Letusnowconsiderhowwemayprotectagainstelectricshockfromwhateversource.
![Page 13: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/13.jpg)
ProtectionagainstShockfromBothTypesofContact
Onemethodofachievingthisisbyensuringthatthesystemvoltagedoesnotexceedextralow(50Va.c.,120Vripple-freed.c.),andthatallassociatedwiring,etc.isseparatedfromallothercircuitsofahighervoltageandearth.Suchasystemisknownasaseparatedextralowvoltage (SELV). If a SELV system exceeds 25V a.c., 60V ripple-free d.c., then extraprotectionmustbeprovidedbybarriers,enclosuresandinsulation.
![Page 14: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/14.jpg)
BasicProtection
ApartfromSELV,howcanwepreventdangertopersonsandlivestockfromcontactwithintentionallyliveparts?Clearlywemustminimizetheriskofsuchcontact,andthismaybeachievedinoneormoreofthefollowingways:
1.Insulateanyliveparts.2.Ensurethatanyuninsulatedlivepartsarehousedinsuitableenclosuresand/orare
behindbarriers.3.Placeobstaclesintheway.(Thismethodwouldonlybeusedinareaswhereskilled
and/orauthorizedpersonswereinvolved.)4.Placinglivepartsoutofreach.(Onceagain,onlyusedinspecialcircumstances,e.g.
liverailsofoverheadtravellingcranes.)
Aresidualcurrentdevice(RCD)maybeusedasadditionalprotectiontoanyoftheothermeasurestaken,providedthatitisratedat30mAorlessandhasanoperatingtimeofnotmorethan40msatatestcurrentoffivetimesitsoperatingcurrent.
It should be noted that RCDs are not the panacea for all electrical ills, they canmalfunction,but theyareavalidandeffectiveback-upto theothermethods.Theymustnotbeusedasthesolemeansofprotection.
![Page 15: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/15.jpg)
FaultProtection
How can we protect against shock from contact with unintentionally live, exposed orextraneous conductive parts whilst touching earth, or from contact betweenunintentionally live exposed and/or extraneous conductive parts? The most commonmethod is by protective earthing, protective equipotential bonding and automaticdisconnectionincaseofafault.
Allextraneousconductivepartsareconnectedwithamainprotectivebondingconductorand connected to the main earthing terminal, and all exposed conductive parts areconnectedtothemainearthingterminalbythecircuitprotectiveconductors(cpc).Addtothisovercurrentprotectionthatwilloperatefastenoughwhenafaultoccursandtheriskofsevereelectricshockissignificantlyreduced.
Othermeansoffaultprotectionmaybeused,butarelesscommonandsomerequireverystrictsupervision.
![Page 16: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/16.jpg)
UseofClassIIEquipment
Oftenreferredtoasdouble-insulatedequipment,thisistypicalofmodernapplianceswherethereisnoprovisionfortheconnectionofacpc.Thisdoesnotmeanthatthereshouldbenoexposedconductivepartsandthatthecasingofequipmentshouldbeofaninsulatingmaterial; it simply indicates that live parts are sowell insulated that faults from live toconductivepartscannotoccur.
![Page 17: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/17.jpg)
Non-ConductingLocation
Thisisbasicallyanareainwhichthefloor,wallsandceilingareallinsulated.Withinsuchanarea theremustbenoprotectiveconductors,andsocketoutletswillhavenoearthingconnections.
It must not be possible simultaneously to touch two exposed conductive parts, or anexposed conductive part and an extraneous conductive part. This requirement clearlypreventsshockcurrentfrompassingthroughapersonintheeventofanearthfault,andtheinsulatedconstructionpreventsshockcurrentfrompassingtoearth.
![Page 18: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/18.jpg)
Earth-FreeLocalEquipotentialBonding
This is inessenceaFaradaycage,whereallmetalsarebondedtogetherbutnot toearth.Obviously, great care must be taken when entering such a zone in order to avoiddifferencesinpotentialbetweeninsideandoutside.
Theareasmentionedinthisandthepreviousmethodareveryuncommon.Wheretheydoexist,theyshouldbeunderconstantsupervisiontoensurethatnoadditionsoralterationscanlessentheprotectionintended.
![Page 19: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/19.jpg)
ElectricalSeparation
ThismethodreliesonasupplyfromasafetysourcesuchasanisolatingtransformertoBSEN61558-2-6whichhasnoearthconnectiononthesecondaryside.Intheeventofacircuitthatissuppliedfromasourcedevelopingalivefaulttoanexposedconductivepart,therewouldbenopathforshockcurrenttoflow(seeFigure0.2).
FIGURE0.2Electricalseparation.
Table0.1IPCodes
FirstNumeral MechanicalProtection
0Noprotectionofpersonsagainstcontactwithliveormovingpartsinsidetheenclosure.Noprotectionofequipmentagainstingressofsolidforeignbodies.
1Protectionagainstaccidentalorinadvertentcontactwithliveormovingpartsinsidetheenclosurebyalargesurfaceofthehumanbody,forexample,ahand,butnotprotectionagainstdeliberateaccesstosuchparts.
2Protectionagainstingressoflargesolidforeignbodies.ProtectionagainstContactwithliveormovingpartsinsidetheenclosurebyfingers.Protectionagainstingressofmedium-sizesolidforeignbodies.
3Protectionagainstcontactwithliveormovingpartsinsidetheenclosurebytools,wiresorsuchobjectsofthicknessgreaterthan2.5mm.Protectionagainstingressofsmallforeignbodies.
4Protectionagainstcontactwithliveormovingpartinsidetheenclosurebytools,wiresorsuchobjectsofthicknessgreaterthan1mm.Protectionagainstingressofsmall-sizesolidforeignbodies.
5
Completeprotectionagainstcontactwithliveormovingpartsinsidetheenclosure.Protectionagainstharmfuldepositsofdust.Theingressofdustisnottotallyprevented,butdustcannotenterinanamountsufficienttointerferewithsatisfactoryoperationoftheequipmentenclosed.
6 Completeprotectionagainstcontactwithliveormovingpartsinsidetheenclosures.Protectionagainstingressofdust.
SecondNumeral LiquidProtection
0 Noprotection.
![Page 20: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/20.jpg)
1 Protectionagainstdropsofcondensedwater.Dropsofcondensedwaterfallingontheenclosureshallhavenoharmfuleffect.
2 Protectionagainstdropsofliquid.DropsOffallingliquidshallhavenoharmfuleffectwhentheenclosureistiltedatanyangleupto15°fromthevertical.
3 Protectionagainstrain.Waterfallinginrainatanangleequaltoorsmallerthan60°withrespecttotheverticalshallhavenoharmfuleffect.
4 Protectionagainstsplashing.Liquidsplashedfromanydirectionshallhavenoharmfuleffect.
5 Protectionagainstwaterjets.Waterprojectedbyanozzlefromanydirectionunderstatedconditionsshallhavenoharmfuleffect.
6Protectionagainstconditionsonships’decks(deckwithwatertightequipment).Waterfromheavyseasshallnotentertheenclosuresunderprescribedconditions.
7 Protectionagainstimmersioninwater.Itmustnotbepossibleforwatertoentertheenclosureunderstatedconditionsofpressureandtime.
8 Protectionagainstindefiniteimmersioninwaterunderspecifiedpressure.Itmustnotbepossibleforwatertoentertheenclosure.
X Indicatesnospecifiedprotection.
Onceagain,greatcaremustbetakentomaintaintheintegrityofthistypeofsystem,asaninadvertentconnection toearth,or interconnectionwithothercircuits,wouldrender theprotectionuseless.
AdditionalprotectionbyRCDsisausefulback-uptoothermethodsofshockprotection.
The use of enclosures is not limited to protection against shock from contact with liveparts;theyclearlyprovideprotectionagainsttheingressofforeignbodiesandmoisture.Inorder to establish to what degree an enclosure can resist such ingress, reference to theIndexofProtection(IP)code(BSEN60529)shouldbemade.Table0.1illustratespartoftheIPcode.
ThemostcommonlyquotedIPcodesinthe17theditionareIPXXBorIP2X,andIPXXDorIP4X.TheXdenotes that protection is not specified, not that there is noprotection. Forexample,anenclosure thatwas tobe immersed inwaterwouldbeclassified IPX8, therewouldbenopointusingthecodeIP68.
NoteIPXXBdenotesprotectionagainstfingercontactonly.IPXXDdenotesprotectionagainstpenetrationby1mmdiameterwifeonly.
![Page 21: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/21.jpg)
CHAPTER1AnOverview
Importantterms/topicscoveredinthischapter:
StatutoryandNon-StatutoryRegulationsElectricalsystemsTheBuildingRegulationsPart‘P’Instruments
Bytheendofthischapterthereadershould:
be aware of the Statutory and Non-Statutory Regulations that are relevant toinstallationwork,
knowtherangeofinstrumentsrequired,knowtherequirementsregardingtheuseandperformanceoftestequipment.
So,hereyouareoutside thepremises,armedwith lotsof test instruments,aclipboard,apadofdocumentsthatrequirecompleting,theIETRegulations,GuidanceNotes3andaninstruction to carryoutan inspectionand testof theelectrical installation therein.Deadeasy,you’vebeentold,pieceofcake,justpokeaboutabit,‘Megger’thewiring,writetheresultsdown,signthetestcertificateandyoushouldbeontothenextjobwithinthehour!
Oh!Ifonlyitwerethatsimple!Whatiflethaldefectsweremissedbyjust‘pokingabout’?What if other tests should have been carried out which may have revealed seriousproblems?WhatifthingsgowrongafteryouhavesignedtosayallisinaccordancewiththeRegulations?Whatifyouwerenotactuallycompetenttocarryouttheinspectionandtest in the first place?What if … and so on, the list is endless. Inspection, testing andcertificationisaseriousand,inmanyinstances,acomplexmatter,soletuswindtheclockbacktothepointatwhichyouwereabouttoenterthepremisestocarryoutyourtests,andconsidertheimplicationsofcarryingoutaninspectionandtestofaninstallation.
What are the legal requirements in all of this?Wheredoyou stand if thingsgowrong?Whatdoyouneedtodotoensurecompliancewiththelaw?
ItisprobablybestatthispointtoconsiderthetypesofInspectionandTestthatneedtobeconductedandthecertificationrequired.
Therearetwotypes:
1.InitialVerification.2.PeriodicInspectionandTesting.
![Page 22: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/22.jpg)
InitialVerificationisrequiredfornewworkandalterationsandadditions(coveredinCity&Guilds2392-10andthemoreadvanced2394-01).
Periodic Inspection and Testing is required for existing installations (this and InitialVerificationarecoveredinCity&Guilds2395-01).
The certification required for (1) (above) is an Electrical Installation Condition Report(EICR).
Thecertificationrequiredfor(2) (above) isaPeriodicInspectionReport(PIR).ThiscouldbereferredtoasaConditionReport.
Bothmustbeaccompaniedbyascheduleoftestresultsandascheduleofinspections.
In thecaseofanadditionor simplealteration thatdoesnot involve the installationofanew circuit (e.g. a spur from a ring final circuit), tests must be conducted but thecertificationrequiredisaMinorElectricalInstallationWorksCertificate(MEIWC).
TheseareallcoveredingreaterdetailinChapter16.
![Page 23: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/23.jpg)
StatutoryandNon-StatutoryRegulations
Thestatutoryregulationsthatapplytoelectricalworkare:
TheHealthandSafetyatWorkEtc.Act(HSWA)TheElectricityatWorkRegulations(EAWR)TheBuildingRegulationsPart‘P’(applicabletodomesticinstallations).
Non-statutoryregulationsincludesuchdocumentsasBS7671:2008andassociatedguidancenotes,GuidanceNoteGS38ontestequipment,etc.
TheIETWiringRegulations(BS7671:2008)andassociatedguidancenotesarenotstatutorydocuments; they can, however, be used in a court of law to prove compliance withstatutory requirements such as the Electricity atWorkRegulations (EAWR) 1989,whichcover all work activity associated with electrical systems. A list of other statutoryregulationsisgiveninAppendix2oftheIETRegulations.However,itistheEAWRthataremostcloselyassociatedwithBS7671,andas such it isworthgivingsomeareasacloserlook.
IntheEAWRthereare33Regulationsinall,12ofwhichdealwiththespecialrequirementsofmines and quarries, onewhich dealswith extension outsideGreat Britain, and threewhich deal with effectively exemptions. We are only concerned with the first 16Regulations,andRegulation29,thedefenceregulation,whichweshallcomebacktolater.Letusstartthenwithacommentonthemeaningofelectricalsystemsandequipment.
![Page 24: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/24.jpg)
ElectricalSystemsandEquipment
AccordingtotheEAWR,electricalsystemsandequipmentcanencompassanythingfrompowerstationstotorchorwrist-watchbatteries.Abatterymaynotcreateashockrisk,butmay cause burns or injury as a result of attempting to destroy it by fire, wherebyexplosions may occur. A system can actually include the source of energy, so a testinstrumentwithitsownsupply,forexample,acontinuitytester,isasysteminitself,andaloop impedance tester, which requires an external supply source, becomes part of thesystem intowhich it isconnected.Fromtheprecedingcomments itwillbeobvious thenthat, inbroad terms, if something is electrical, it isor ispartofanelectrical system.So,wheredoesresponsibilitylieforanyinvolvementwithsuchasystem?
The EAWR requires that every employer, employee and self-employed person beresponsible for compliance with the Regulations with regard to matters within theircontrol,andas suchareknownasdutyholders.Where thendoyou standas thepersonabouttoconductaninspectionandtestofaninstallation?Mostcertainly,youareadutyholder inthatyouhavecontrolof the installation insofarasyouwillultimatelypass theinstallationassafeormakerecommendationstoensureitssafety.Youalsohavecontrolofthetestinstrumentswhich,asalreadystated,aresystemsinthemselves,andcontroloftheinstallationwhilsttestingisbeingcarriedout.
AnybreachoftheRegulationsmayresultinprosecution,andunliketheotherlaws,undertheEAWRyouarepresumedguiltyandhavetoestablishyourinnocencebyinvokingtheDefence Regulation 29. Perhaps some explanation is needed here. Each of the 16Regulationshasastatus,inthatitiseitherabsoluteorreasonablypracticable.
Regulations that are absolute must be conformed to at all cost, whereas those that arereasonablypracticableareconformedtoprovidedthatallreasonablestepshavebeentakento ensure safety. For the contravention of an absolute requirement, Regulation 29 isavailable as a defence in the event of criminal prosecution, provided the accused candemonstratethattheytookallreasonableanddiligentstepstopreventdangerorinjury.
Noonewantstoendupincourtaccusedofnegligence,andsoweneedtobesurethatweknowwhatwearedoingwhenweareinspectingandtesting.
![Page 25: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/25.jpg)
![Page 26: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/26.jpg)
TheBuildingRegulationsPart‘P’
Part ‘P’ of the building regulation requires that installations in dwellings be designed,installed and inspected and tested to the requirements of the current edition of the IETWiringRegulations,BS7671.
Details of some suchwork need to be notified to the Local Authority Building Control(LABC).Thisisalegalrequirement.
Notifiablework
AnynewcircuitfedfromtheconsumerunitReplacementofaconsumerunitAnywork,additionsoralterationsinabath/showerroom,saunaorswimmingpool.
Non-notifiablework
Any other work that involves replacements, additions or alterations anywhere elseincludinggardens.
Certification
Allelectricalworkhastobeinspected,testedandcertifiedwiththeissueofeither:
AnElectrical InstallationCertificate (EIC) for all newcircuits and consumerunitreplacements
A Minor Electrical Installation Works Certificate (MEIWC) for small additionsand/oralterationsthatdonotcompriseanewcircuit
AnElectrical InstallationConditionReport (EICR)where the inspector isnot theinstaller.
Ifaninstallerbelongstoa‘CompetentPersons’scheme(i.e.isaDomesticInstallerwithanapprovalbody,say,theNICEIC,ELECSA,etc.),he/shecanself-certifytheworkandissuetheappropriatecertificatetothepersonorderingthework.TheapprovalbodywillnotifytheLABC.
Ifaninstallerisnotregisteredona‘CompetentPersons’scheme,butisqualifiedtoinspectand test, he/she should issue the appropriate certificate to theLABC.Theywill take theinspector’squalificationsintoaccountanddecideifanyfurtheractionneedstobetaken.
![Page 27: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/27.jpg)
Aninstallerwhoisnotqualifiedtoinspectandtestmayappointa‘RegisteredCompetentPerson’tocarryouttheinspectionandtest.InthiscaseonlyanEICRcanbeissuedtothepersonorderingthework.
Apartfromtheknowledgerequiredcompetentlytocarryouttheverificationprocess,theperson conducting the inspection and test must be in possession of test instrumentsappropriatetothedutyrequiredofthem.
![Page 28: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/28.jpg)
Instruments
Inordertofulfil thebasicrequirementsfortestingtoBS7671, thefollowinginstrumentsareneeded:
1.Alow-resistanceohmmeter(continuitytester).2.Aninsulationresistancetester.3.Aloopimpedancetester.4.Aresidualcurrentdevice(RCD)tester.5.Aprospectivefaultcurrent(PFC)tester.6.Anapprovedtestlamporvoltageindicator.7.Aprovingunit.8.Anearthelectroderesistancetester.
Manyinstrumentmanufacturershavedevelopeddualormulti-functioninstruments;henceitisquitecommontohavecontinuityandinsulationresistanceinoneunit,loopimpedanceand PFC in one unit, loop impedance, PFC and RCD tests in one unit, etc. However,regardless of the various combinations, let us take a closer look at the individual testinstrumentrequirements.
Low-resistanceohmmeters/continuitytesters
Bells, buzzers, simple multimeters, etc. will all indicate whether or not a circuit iscontinuous,butwillnotshowthedifferencebetweentheresistanceof,say,a10mlengthof 10mm2 conductor and a 10m length of 1mm2 conductor. I use this example as anillustration,asitisbasedonarealexperienceoftestingthecontinuityofa10mm2mainprotective bonding conductor between gas andwater services. The services, some 10mapart,wereateitherendsofadomesticpremises.The10mm2conductor,connectedtobothservices,disappearedunder the floor,andameasurementbetweenbothends indicatedaresistancehigherthanexpected.Furtherinvestigationrevealedthatjustunderthefloorateachend, the10mm2 conductorhadbeen terminated in a connector block and the joinbetween the two, about 8 m, had been wired with a 1 mm2 conductor. Only a milli-ohmmeterwouldhavedetectedsuchafault.
Alow-resistanceohmmetershouldhaveano-loadsourcevoltageofbetween4Vand24Va.c.ord.c.,andbecapableofdeliveringana.c.ord.c.short-circuitcurrentofnotlessthan200mA.Itshouldhavearesolution(i.e.adefeasibledifferenceinresistance)ofatleast0.01mV.
![Page 29: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/29.jpg)
Insulationresistancetesters
Aninsulationresistancetestisthecorrecttermforthisformoftesting,notameggertest,asmeggerisamanufacturer’stradename,notthenameofthetest.
Aninsulationresistancetestermustbecapableofdelivering1mAwhentherequiredtestvoltageisappliedacrosstheminimumacceptablevalueofinsulationresistance.
Hence, an instrument selected for use on a low-voltage (50 V a.c.–1000 V a.c.) systemshouldbecapableofdelivering1mAat500Vacrossaresistanceof1MΩ.
Loopimpedancetester
Thisinstrumentfunctionsbycreating,ineffect,anearthfaultforabriefmoment,andisconnectedtothecircuitviaaplugorby‘flyingleads’connectedseparatelytoline,neutralandearth.
The instrument shouldonlyallowanearth fault toexist foramaximumof40ms,and a resolution of 0.01 V is adequate for circuits up to 50 A. Above this circuitrating, the ohmic values become too small to give such accuracy using a standardinstrument,andmorespecializedequipmentmayberequired.
RCDtester
Usuallyconnectedbytheuseofaplug,although‘flyingleads’areneededfornon-socketoutlet circuits, this instrumentallowsa rangeofout-of-balancecurrents to flow throughtheRCDtocauseitsoperationwithinspecifiedtimelimits.
Thelistinstrumentshouldnotbeoperatedforlongerthan2s,anditshouldhavea10percentaccuracyacrossthefullrangeoftestcurrents.
Earthelectroderesistancetester
Thisisa3-or4-terminal,battery-poweredresistancetester.ItsapplicationisdiscussedinChapter4.
PFCtester
![Page 30: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/30.jpg)
ThisiseitherpartofacombinedPFC/Looptesteroramulti-functioninstrument.ItisusedtomeasureProspectiveShort-CircuitCurrent(PSCC)linetoneutral,orProspectiveEarthFaultCurrent(PEFC)linetoearth.
Approvedtestlamporvoltageindicator
Aflexiblecordwithalampattachedisnotanapproveddevice,norforthatmatteristheubiquitous‘testascope’or‘neonscrewdriver’,whichencouragesthepassageofcurrent,atlowvoltage,throughthebody!
AtypicalapprovedtestlampisshowninFigure1.1.
TheHealthandSafetyExecutive,GuidanceNoteGS38,recommendsthattheleadsandprobes,associatedwithtest, lamps,voltageindicators,voltmeters,etc.havethefollowingcharacteristics:
1. Theloadsshouldbeadequatelyinsulatedand,ideally,fused.2. Theleadsshouldbeeasilydistinguishedfromeachcitherfaycolour.3. Theleadsshouldbeflexibleandsufficientlylongfortheirpurpose,4. Theprobesshouldincorporatefingerbarriers,topreventaccidentalcontact
withliveparts.5. Theprobesshouldbe insulatedandhaveamaximumof2mmofexposed
metal,butpreferablyhavespring-loadedenclosedtips.
Provingunit
Thisisanoptionalitemoftestequipment,inthattestlampsshouldbeprovedonaknownlivesupplywhichcould,ofcourse,beanadjacentsocketorlightingpoint,etc.However,toproveatestlamponsuchaknownlivesupplymayinvolveentryintoenclosureswiththeassociated hazards that such entry could bring. A proving unit is a compact device notmuchlargerthanacigarettepacket,whichiscapableofelectronicallydeveloping230Vd.c.across which the test lamp may be proved. The exception to this are test lampsincorporating 230 V lamps which will not activate from the small power source of theprovingunit.
![Page 31: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/31.jpg)
FIGURE1.1Approvedtestlamp.
Test lamps must to proved against a voltage similar to that to be tested. Hence,provingtestlampsthatincorporateaninternalcheck;thatis,shortingouttheprobestomakeabuzzersoundisriotacceptableifthevoltagetobefetedishigherthanthatdeliveredbythetestlamp.
Careoftestinstruments
TheEAWR(1989)requiresthatallelectricalsystems,andthisincludestestinstruments,bemaintained to prevent danger. This does not restrict such maintenance to just a yearlycalibration,butrequiresequipmenttobekeptingoodconditioninorderthatitissafetouse at all times. In consequence it is important to ensure the continual accuracy ofinstrumentsbycomparing test readingsagainstknownvalues.This ismostconvenientlyachievedbytheuseof‘checkboxes’whicharereadilyavailable.
Whilst test instruments and associated leads, probes and clips, etc. used in the electricalcontracting industry are robust in design andmanufacture, they still need treatingwithcareandprotectingfrommechanicaldamage.Keeptestgearinaseparateboxorcaseawayfromtoolsandsharpobjects,andalwayscheckthegeneralconditionofatesterandleadsbeforetheyareused.
Questions
1.Statethestatutorydocumentmostrelevanttoinspectionandtesting.2.Whatistheminimumshort-circuitcurrenttobedeliveredbyalowresistance
ohmmeter?3.Whatcurrentmustbedeliveredaninsulationresistancetesterwhenusedat
500Vacrossaresistanceof1MΩ?
![Page 32: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/32.jpg)
4.StatethetwotestscarriedoutbyaRFCtester.5. What is the maximum length of exposed tip on the leads of a voltage
indicator?
Answers
1.ElectricityatWorkRegulations(1989).2.200mA.3.1mA.4.ProspectiveShort-CircuitCurrent(PSCC)andProspectiveEarthFaultCurrent
(PEFC).5.2mm.
![Page 33: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/33.jpg)
CHAPTER2InitialVerification
Importantterms/topicscoveredinthischapter:
InitialverificationdocumentationSequenceoftestsInspectionchecklist
Bytheendofthischapterthereadershould:
knowthecorrectsequenceofteststobecarriedout,beawareoftheinformationrequiredbyaninspector,beawareoftheextentoftheinspectionsrequired.
![Page 34: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/34.jpg)
CircumstancesWhichRequireanInitialVerification
Newinstallationsoradditionsoralterations.
![Page 35: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/35.jpg)
GeneralReasonsforInitialVerification
1.Toensureequipmentandaccessoriesaretoarelevantstandard.2.ToprovecompliancewithBS7671.3.Toensurethattheinstallationisnotdamagedsoastoimpairsafety.
![Page 36: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/36.jpg)
InformationRequired
Assessmentofgeneralcharacteristicssections311,312and313togetherwithinformationsuchasdrawings,charts,etc.,inaccordancewithRegulation514.9.1(seeBS7671:2008).
![Page 37: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/37.jpg)
DocumentationRequiredandtoBeCompleted
Electrical Installation Certificate (EIC) signed or authenticated for the design andconstructionandthenfortheinspectionandtest(couldbethesameperson).AscheduleoftestresultsandascheduleofinspectionsmustaccompanyanEIC.
![Page 38: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/38.jpg)
SequenceofTests
TheIETRegulationsindicateapreferredsequenceoftestsandstatethatif,duetoadefect,compliancecannotbeachieved,thedefectshouldberectifiedandthetestsequencestartedfrom the beginning. The tests for ‘Protection by separation’ and ‘Insulation of non-conductingfloorsandwalls’allrequirespecialistequipmentandinconsequencewillnotbediscussedhere.Thesequenceoftestsforaninitialinspectionandtestisasfollows:
1.Continuityofprotectiveconductors.2.Continuityofringfinalcircuitconductors.3.Insulationresistance.4.Protectionagainstdirectcontactbybarriersorenclosures.5.Polarity.6.Earthelectroderesistance.7.Earthfaultloopimpedance.8.Additionalprotection(RCDs).9.Prospectivefaultcurrentbetweenliveconductorsandtoearth.10.Phasesequence.11.Functionaltesting.12.Voltagedrop(notnormallyrequiredforinitialverification).
BS 7671:2008 requires tests 1-5 to be carried out in that order before the installation isenergized and, if there is an earth electrode, its testing should be included. It does notrequirethelivetests7-11tofollowasequenceanditem12isnotusuallyrequiredforaninitialverification.
Even though no sequence is specified, itwould always be appropriate to conduct test 7beforetest8ashighvaluesofloopimpedanceortheabsenceofanearthpathcouldresultin dangerous voltages appearing between exposed and extraneous conductive parts andpersonsshouldbetoldnottotouchmetalworkwhilstthetestisbeingconducted.
OneothertestnotincludedinPart6oftheIETRegulationsbutwhichneverthelesshastobecarriedoutisexternalearthfaultloopimpedance(Ze).
Beforeanytestingiscarriedout,adetailedphysicalinspectionmustbemadetoensurethatall equipment is to a relevant British or Harmonized European Standard, that it iserected/installedincompliancewiththeIETRegulations,andthatitisnotdamagedsuchthat it could cause danger. In order to complywith these requirements, the Regulationsgiveachecklistofitemsthat,whererelevant,shouldbeinspected.
However, before such an inspection, and test for that matter, is carried out, certaininformation must be available to the verifier. This information is the result of theassessmentoffundamentalprinciplesBS7671Section131andtheAssessmentofGeneral
![Page 39: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/39.jpg)
Characteristics required by IETRegulations Part 3, sections 311, 312, 313, and drawings,charts and similar information relating to the installation. It is at this point that mostreaders who work in the real world of electrical installation will be lying on the floorlaughinghysterically.
Let us assume that the designer and installer of the installation are competentprofessionals,andalloftherequireddocumentationisavailable.
Interestingly,oneoftheitemsonthechecklististhepresenceofdiagrams,instructionsandsimilarinformation.IfthesearemissingthenthereisadeviationfromtheRegulations.
Anotheritemonthelististheverificationofconductorsforcurrent-carryingcapacityandvoltagedropinaccordancewiththedesign.Howonearthcanthisbeverifiedwithoutallthe information?A30ATypeBcircuitbreaker (CB)orType2miniaturecircuitbreaker(MCB)protectingalengthof4mm2conductormaylookreasonable,butisitcorrect,andareyoupreparedtosigntosaythatitisunlessyouaresure?Letuslookthenatsomeitemsthatwouldneedinspecting.
1.Connectionofconductors:Areterminationselectricallyandmechanicallysound?Is insulation and sheathing removed only to a minimum to allow satisfactorytermination?
2. Identification of conductors: Are conductors correctly identified in accordancewiththeRegulations?
3. Routing of cables: Are cables installed such that account is taken of externalinfluencessuchasmechanicaldamage,corrosion,heat,etc.?
4.Conductor selection: Are conductors selected for current-carrying capacity andvoltagedropinaccordancewiththedesign?
5. Connection of single pole devices: Are single pole protective and switchingdevicesconnectedinthelineconductoronly?
6.Accessoriesandequipment:Areallaccessoriesanditemsofequipmentcorrectlyconnected?
7.Thermaleffects:Are fire barriers presentwhere required and protection againstthermaleffectsprovided?
8. Protection against shock: What methods have been used to attain both basicprotectionandfaultprotection?
9.Mutual detrimental influence: Arewiring systems installed such that they canhave no harmful effect on non-electrical systems, or those systems of differentcurrentsorvoltagesaresegregatedwherenecessary?
10.Isolationandswitching:Arethereappropriatedevicesforisolationandswitchingcorrectlylocatedandinstalled?
11.Undervoltage:Whereundervoltagemaygiveriseforconcern,arethereprotectivedevicespresent?
12.Labelling: Are all protective devices, switches (where necessary) and terminals
![Page 40: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/40.jpg)
correctlylabelled?13.Externalinfluences:Haveall itemsofequipmentandprotectivemeasuresbeen
selectedinaccordancewiththeappropriateexternalinfluences?14.Access:Areallmeansofaccesstoswitchgearandequipmentadequate?15.Noticesandsigns:Aredangernoticesandwarningsignspresent?16.Diagrams: Are diagrams, instructions and similar information relating to the
installationavailable?17. Erection methods: Have all wiring systems, accessories and equipment been
selectedandinstalledinaccordancewiththerequirementsoftheRegulations,andarefixingsforequipmentadequatefortheenvironment?
Alldefectsandomissions,etc.innewworkmustberectifiedand,inthecaseofanadditionsuchas,say,ashowercircuit,defectsfoundintheexistinginstallationthatareunrelatedtothenewworkshouldberecordedontheEIC.
Questions
1.Aninstallationistohavethefollowingtestsconducted:(1) loopimpedance,(2)polarity, (3) ringcircuitcontinuity,and (4) insulationresistance.What isthecorrectsequenceforcarryingoutthetests?
2.Whichtestisnotnormallyrequiredforaninitialverification?3.ThedetailsofwhichsectionsofBS7671arerequiredtobemadeavailabletoa
personcarryingputinspectionandtestingofaninstallation?4.Whatinspectionchecklistitemrelatestodamagetocables?
Answers
1.(3),(4),(2),(1).2.Voltagedrop.3.131,311,312,313.4.Routingofcables.
![Page 41: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/41.jpg)
CHAPTER3TestingContinuityofProtectiveConductors
(Low-ResistanceOhmmeter)Importantterms/topicscoveredbythischapter:
ProtectivebondingconductorsCircuitprotectiveconductorsParallelearthpaths(R1+R2)values
Bytheendofthischapterthereadershould:
knowwhattestinstrumenttouse,understandtheimportanceofdisconnectingprotectiveconductorsfortesting, know the importance of isolation, where protective conductors cannot be
disconnected,beawareoftheeffectsofparallelearthpaths, be able to determine the approximate value of a protective conductor, given its
length,knowthepreferredmethodofcpccontinuitytesting,knowwhy(R1+R2)valuesareimportant.
All protective conductors, including main protective and supplementary bondingconductors, must be tested for continuity using a low-resistance ohmmeter. A visualinspectionissufficientforshortlengthswheretheconductorsarevisiblethroughouttheirlength.
Formainprotectivebondingconductorsthereisnosinglefixedvalueofresistanceabovewhich the conductorwould be deemed unsuitable. Eachmeasured value, if indeed it ismeasurable for very short lengths, should be compared with the relevant value for aparticularconductorlengthandsize.SuchvaluesareshowninTable3.1.
Where a supplementary bonding conductor has been installed between simultaneouslyaccessibleexposedandextraneousconductivepartsasan
Table3.1Resistance(inΩ)ofCopperConductorsat20°C
![Page 42: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/42.jpg)
additiontofaultprotectionandthere isdoubtas totheeffectivenessof theequipotentialbonding,thentheresistance(R)oftheconductormustbeequaltoorlessthan50/Ia.So,R≤50/Iawhere50isthevoltageabovewhichexposedmetalworkshouldnotrise,andIaistheminimumcurrentcausingoperationofthecircuitprotectivedevicewithin5s.
Forexample,supposea45ABS3036fuseprotectsacookercircuit,thedisconnectiontimeforthecircuitcannotbemet,andsoasupplementarybondingconductorhasbeeninstalledbetweenthecookercaseandanadjacentcentralheatingradiator.Theresistance(R)ofthatconductorshouldnotbegreaterthan50/Ia,andIainthiscaseis145A(seeFigure3.2BoftheIETRegulations);thatis,50/145=0.34Ω.
Howthendoweconductatesttoestablishcontinuityofmainorsupplementarybondingconductors?Quitesimplereally:justconnecttheleadsfromalow-resistanceohmmetertotheendsof thebondingconductor(Figure3.1).Oneendshouldbedisconnected fromitsbondingclamp,otherwiseanymeasurementmayincludetheresistanceofparallelpathsofotherearthedmetalwork.Remember tozero/null the instrument firstor, if this facility isnot available, record the resistance of the test leads so that this value can be subtractedfromthetestreading.
FIGURE3.1Testingmainprotectivebonding.
ImportantNoteIf the installation is in operation, then never disconnect protective bondingconductorsunlessthesupplycanbeisolated.Withoutisolation,personsandlivestock
![Page 43: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/43.jpg)
areatriskofelectricshock.Inthisinstance,orwheretheconnectionstoextraneousconductive parts are not accessible, the test is conducted either between theconnected bonding conductors or between extraneous conductive parts. Theresistancevalueobtainedshouldbenogreaterthan0.05Ω.
Thecontinuityofcircuitprotectiveconductorsmaybeestablishedinthesameway,butasecondmethodispreferred,astheresultsofthissecondtestindicatethevalueof(R1+R2)forthecircuitinquestion.
Thetestisconductedinthefollowingmanner:
1.Temporarilylinktogetherthelineconductorandcpcofthecircuitconcernedinthedistributionboardorconsumerunit.
2. Test between line and cpc at each outlet in the circuit. A reading indicatescontinuity.
3.Recordthetestresultobtainedatthefurthestpointinthecircuit.Thisvalueis(R1+R2)forthecircuit,andisimportantforusewiththeformulaZs=Ze+(R1+R2)forconfirmingmeasuredvaluesofZsorforcalculationwhereZscannotbemeasured.Itshouldalsobenotedthatforlightingcircuitsthetestshouldbecarriedoutattheswitches,asthesearethefurthestpointforeachluminaire.
Figure3.2illustratestheabovemethod.
Theremaybesomedifficultyindeterminingthe(R1+R2)valuesofcircuitsininstallationsthatcomprisesteelconduitandtrunking,and/orsteel-wire-armoured(SWA)andmineral-insulatedmetal-sheathed(MIMS)cables,becauseoftheparallelearthpathsthatarelikelytoexist.Inthesecases,continuitytestsmayhavetobecarriedoutattheinstallationstagebeforeaccessoriesareconnectedorterminationsmadeoffaswellasaftercompletion.
Althoughitisnolongerconsideredgoodworkingpracticetousesteelconduitortrunkingas a protective conductor, it is permitted, and hence its continuitymust be proved. Theenclosure must be inspected along its length to ensure that it is sound and then thestandardlow-resistancetestisperformed.
FIGURE3.2Testingcpccontinuity.
![Page 44: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/44.jpg)
Questions
1.Whatinstrumentisusedfortestingthecontinuityofprotectiveconductors?2. What would be the approximate resistance value of a 10 mm2 protective
bondingconductor,15mlong?3. What may be the effect on a resistant test reading taken between the
connectedendsofaprotectivebondingconductor?4.Where,onalightingcircuit,shouldacpccontinuitytestbeconducted?5.WhatisthesignificanceofthereadingattheendofthecircuitinQ.4above?6.Whyisavalueof(R1+R2)important,otherthanconfirmingcpccontinuity?
![Page 45: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/45.jpg)
Answers
1.Low-resistanceohmmeter.2.0.03Ω.3.A lowervalueof resistance than the actual conductorvaluedue toparallel
earthpaths.4.Atallpointsonthecircuit.5.Itis(R1+R2forthecircuit.6.ItcanbeusedintheformulaZs=Ze+(R1+R2)toconfirmameasuredvalue
ofZsoftocalculateaZsvaluewheremeasurementisnot-possible.
![Page 46: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/46.jpg)
CHAPTER4TestingContinuityofRingFinalCircuitConductors(Low-ResistanceOhmmeter)
Importantterms/topicscoveredinthischapter:
Low-resistanceohmmeterRingfinalcircuitinterconnectionsSpurs(R1+R2)valuesInterpretationoftestvalues
Bytheendofthischapterthereadershould:
knowthereasonsforconductingaringfinalcircuitcontinuitytest,understandtheproblemsthatinterconnectionsmaycreate,understandwhyinitialconductorcross-connectionsaremadeforthetest,knowhowincorrectinitialcross-connectionsarerevealed,knowwhyLtocpcvaluesforflat-sheathedcablesvaryslightlyduringthetest,beabletointerprettestresults.
Therearetwomainreasonsforconductingthistest:
1.Toensurethattheringcircuitconductorsarecontinuous,andindicatethevalueof(R1+R2)forthering.
2.Toestablishthatinterconnectionsintheringdonotexist.
Whatthenareinterconnectionsinaringcircuit,andwhyisitimportanttolocatethem?Figure4.1showsaringfinalcircuitwithaninterconnection.
Themost likelycauseofthesituationshowninFigure4.1 iswhereaDIYenthusiasthasaddedsocketsP,Q,RandStoexistingringsA,B,C,D,EandF.
FIGURE4.1RingCircuitwithaninterconnection.
![Page 47: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/47.jpg)
FIGURE4.2Measurementacrossdiameterofacircle.
Initselfthereisnothingwrongwiththis.Theproblemarisesifabreakoccursat,say,pointY,ortheterminationsfailinsocketCorP.ThentherewouldbefoursocketsallfedfromthepointXwhichwouldthenbecomeaspur.
So, how do we identify such a situation with or without breaks at point Y? A simpleresistance test between the ends of the line, neutral or circuit protective conductorswillonlyindicatethatacircuitexists,whetherthereareinterconnectionsornot.Thefollowingtestmethodisbasedonthephilosophythattheresistancemeasuredacrossanydiameterofaperfectcircleofconductorwillalwaysbethesamevalue(Figure4.2).
Theperfectcircleofconductorisachievedbycross-connectingthelineandneutrallegsofthering(Figure4.3).Thetestprocedureisasfollows:
FIGURE4.3Measurementacrossdiameterofaringcircuit.
FIGURE4.4Ringcircuitcross-connectionsL—N.
1. Identifytheopposite legsof thering.This isquiteeasywithsheathedcables,but
![Page 48: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/48.jpg)
with singles, each conductor will have to be identified, probably by takingresistancemeasurementsbetweeneachoneandtheclosestsocketoutlet.Thiswillgivethreehighreadingsandthreelowreadings,thusestablishingtheoppositelegs.
2.Takearesistancemeasurementbetweentheendsofeachconductorloop,r1,rnandr2.Recordthesevalues.
3.Cross-connecttheoppositeendsofthelineandneutralloops(Figure4.4).4.Measurebetweenlineandneutralateachsocketonthering.Thereadingsobtained
shouldbe,foraperfectring,substantiallythesame,andapproximatelyhalfofthereadingof individual loops. IfaninterconnectionexistedsuchasshowninFigure4.1, then sockets A—F would all have similar readings, and those beyond theinterconnectionwouldhavegraduallyincreasingvaluestoapproximatelythemidpoint of the ring, then decreasing values back towards the interconnection. If abreakhadoccurredatpointYthenthereadingsfromsocketSwouldincreasetoamaximumatsocketP.Oneortwohighreadingsarelikelytoindicateeitherlooseconnectionsorspurs.Anullreading,thatis,anopencircuitindication,isprobablyareversepolarity,eitherline-orneutral-cpcreversal.Thesefaultswouldclearlyberectified and the test at the suspect socket(s) is repeated. If the reading increasesdramatically to the centre of the ring and then decreases again, it is likely thatincorrectinitialcross-connectionsofthelegsoftheringhavebeenmadeatStep3.
5.Repeat theaboveprocedure,but in thiscasecross-connect the lineandcpc loops(Figure4.5).
Inthisinstance,ifthecableisoftheflattwintype,thereadingsateachsocketwillincreasevery slightlyand thendecreasearound the ring.Thisdifference,due to the lineandcpcbeingdifferent sizes,willnotbe significantenough tocauseanyconcern.Themeasuredvalueisveryimportant;itisR1+R2forthering.
Asbefore,looseconnections,spursand,inthiscase,L—Ncross-polaritywillbepickedup.
FIGURE4.5Ringcircuitcross-connectionsL—cpc.
ThedetailsinTable4.1aretypicalapproximateohmicvaluesforahealthy70mringfinalcircuitwired in 2.5mm2/1.5mm2 flat twin and cpc cable. (In this case the cpc will beapproximately1.673theLorNresistance.)
As already mentioned, null readings may indicate a reverse polarity. They could alsoindicatetwistedconductorsnot intheir terminalhousing.TheexamplesshowninFigure
![Page 49: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/49.jpg)
4.6mayhelptoexplainthesesituations.
Table4.1ResistanceValuefora70mRingCircuit
L1-L2(r1) N1-N2(rn) cpc1-cpc2(r2)Initialmeasurements 0.52 0.52 0.86Readingateachsocket 0.26 0.26 0.32-0.34Forspurs,eachmetreinlengthwilladdthefollowingresistancetotheabovevalues
0.015 0.015 0.02
FIGURE4.6Reasonsfornullreadings.
![Page 50: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/50.jpg)
Questions
1.Statethereasonsforconductingaringfinalcircuitcontinuitytest.2.WhatinstrumentistobeusedforthetestinQ1above?3.Whyareinterconnectionsinringcircuitsunacceptable?4.Whyaretheendsofcircuitconductorscross-connectedfortestpurposes?5.Whataretheeffectsontestresultsofcorrectandincorrectinitialconductor
cross-connections?6.Whatmayanullreadingatasocketoutletindicate?7.WhatdoestheL—cpcreadingateachsocketoutletonaringsignify?8.Whywill the L—cpc readings increase slightly and thendecrease around a
ringcircuitwiredinflatsheathedcable?9.Aringfinalcircuit iswiredin2.5mm2 singles (L,Nandcpc) inconduit. If
eachloophasanend-to-endvalueof0.4Ω,whatwouldbetheapproximateexpectedvalueof(R1+R2)?
![Page 51: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/51.jpg)
Answers
1.Ensuringtheringiscontinuousandwithnointerconnections,andtoestablishavaluefor(R1+R2).
2.Alow-resistanceohmmeter.3.Abreakintheringbeyondaninterconnectionmayleavetwoormoresocket
outletsonaspur.4.Tocreateaperfectcircleofconductor,theresistanceacrossanydiameterof
whichwillgivethesamevalue.5. Correct cross-connections give the same reading at each socket outlet,
incorrectwill result ingreatly increasedanddecreased readingsaround thering.
6.Twistedortouchingconductorsnotinthesocketoutletterminalorareversepolarity.
7.(R1+R2)forthering.7.Becausethecpcissmallerinsizethanthelineconductor.8.0.2Ω.
![Page 52: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/52.jpg)
CHAPTER5TestingInsulationResistance(Insulation
ResistanceTester)Importantterms/topicscoveredinthischapter:
InsulationresistancetesterParallelresistancesDisconnectionofequipmentTestprocedureTestvaluesSELV,PELVandFELVcircuitsSurgeprotectivedevices
Bytheendofthischapterthereadershould:
beawareofwhythetestisrequired,knowthetestinstrumenttobeused,understandthatinsulationisameasureofresistancesinparallel,knowbetweenwhichconductorsthemeasurementsshouldbemade,knowthetestvoltagesandminimumvaluesofinsulationresistance,beawareoftheneedtotestoncircuits/equipmentthathavebeenisolated,beawareofthereasonsfordisconnectingvariousitemsofequipment, beable to calculateoverallvaluesof insulation resistancegiven individual circuit
values.
This isprobably themostusedandyetabused testof themall.Affectionatelyknownas‘meggering’,aninsulationresistancetestisperformedinordertoensurethattheinsulationof conductors, accessories and equipment is in a healthy condition, and will preventdangerousleakagecurrentsbetweenconductorsandbetweenconductorsandearth.Italsoindicateswhetheranyshort-circuitsexist.
Insulationresistance,asjustdiscussed,istheresistancemeasuredbetweenconductorsandismadeupofcountlessmillionsofresistancesinparallel(Figure5.1).
![Page 53: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/53.jpg)
FIGURE5.1Parallelresistanceofcableinsulation.
The more resistances there are in parallel, the lower the overall resistance, and, inconsequence, the longer a cable, the lower the insulation resistance.Add to this the factthatalmostallinstallationcircuitsarealsowiredinparallel,anditbecomesapparentthattests on large installationsmay, ifmeasured as awhole, give pessimistically lowvalues,eveniftherearenofaults.
Underthesecircumstances, it isusualtobreakdownsuchlargeinstallationsintosmallersections, floorby floor,distributioncircuitbydistributioncircuit, etc.Thisalsohelps, inthecaseofperiodictesting,tominimizedisruption.Thetestprocedureisasfollows:
1.Ensurethesupplytothecircuit/sinquestionisisolated.2.Disconnectallitemsofequipmentsuchascapacitorsandindicatorlampsasthese
are likely togivemisleadingresults.Removeany itemsofequipment likely tobedamagedby the test, suchasdimmer switches, electronic timers, etc.Removealllampsandaccessoriesanddisconnectfluorescentanddischargefittings.Ensureallfusesareinplace,andcircuitbreakersandswitchesareintheonposition.Insomeinstances itmaybe impracticable to remove lamps,etc.and in thiscase the localswitchcontrollingsuchequipmentmaybeleftintheoffposition.Whereelectronicdevicescannotbedisconnected,testonlybetweenlivesandearth.
3.Jointogetherallliveconductorsofthesupplyandtestbetweenthisjoinandearth.Alternatively,testbetweeneachliveconductorandearthinturn.
4.Testbetweenlineandneutral.Forthreephasesystems,jointogetherall linesandtestbetweenthisjoinandneutral.
5. Then test between each of the lines.Alternatively, test between each of the liveconductorsinturn.Installationsincorporatingtwo-waylightingsystemsshouldbetested twice with the two-way switches in alternative positions. Note: all cpcsshouldbeconnectedtotheearthingarrangement(earthbar)duringthistest.
![Page 54: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/54.jpg)
Table5.1givesthetestvoltagesandminimumvaluesofinsulationresistanceforELVandLVsystems.
If a value of less than 2 MΩ is recorded it may indicate a situation where a fault isdeveloping,butasyetstillcomplieswiththeminimumpermissiblevalue.Inthiscaseeachcircuitshouldbetestedseparatelyinordertolocatetheproblem.
InthecaseofSELV,PELVandelectricalseparation,Table5.1appliestotheirowncircuitconductors. When they are with other circuits the insulation resistance between theirconductorsandthoseoftheothercircuitsshouldbebasedonthehighestvoltagepresent.ForFELVcircuitsthetest
Table5.1InsulationResistanceTestRequirements
System TestVoltage MinimumInsulationResistanceSELVandPELV 250Vd.c. 0.5MQLVupto500V 500Vd.c. 1.0MQOver500V 1000Vd.c. 1.0MQ
voltageandtheminimumvalueifinsulationisthesameasthatforLVcircuitsupto500V(i.e.500Vd.c.and1MΩ).
Wheresurgeprotectivedevicesexist,theyshouldbedisconnected.Ifthisisnotpracticablethe test voltage may be reduced to 250 V d.c. but the minimum value of insulationresistanceremainsat1MΩ.
![Page 55: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/55.jpg)
Example5.1
An installationcomprising sixcircuitshas individual insulation resistancesof2.5, 8, 200,200,200and200MΩ,andsothetotalinsulationresistancewillbe:
=0.4+0.125+0.005+0.005+0.005=0.545
Thisisclearlygreaterthanthe1.0MΩminimumbutlessthan2MΩ.Hadthisvalue(1.83)beenmeasuredfirst,thecircuitswouldneedtohavebeeninvestigatedtoidentifytheone/sthatweresuspect.
NoteIt is important that a test for cpc Continuity is conducted before an insulationresistance (IR) test. If a cpcwas broken, and an IR test between line and cpcwascarried out first, the resultwould be satisfactory, even if therewas an L-cpc faultbeyond the break.A subsequent cpc continuity testwould reveal the break,whichwouldberectified,leavinganL-cpcfaultundetected!!
Questions
1.Whatisthepurposeofaninsulationresistancetest?2.Whatinstrumentshouldbeused?3.Whydocapacitors,neons,etc.needtobedisconnected?4.Whydoitemsofelectronicequipmentneedtobedisconnected?5.Whatactionshouldbetakenregardingswitchesandprotectivedevices?6.Whatisthetestvoltageandminimumvalueofinsulationresistancefora25
VFELVcircuit?7.Whattestvoltageandminimumvalueofinsulationresistanceareappropriate
forcircuitsincorporatingsurgeprotectivedevices?8.Belowwhatvalueofoverallinsulationresistancewouldaninstallationneed
tobeinvestigatedcircuitbycircuit?9. Why may a large installation give a pessimistically low overall insulation
resistancevalue?
![Page 56: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/56.jpg)
10.Whatwouldbethetotal insulationresistanceofaninstallationcomprisingcircuitswiththefollowingvalues:3MΩ,12MΩ,100MΩand150MΩ?
Answers
1.Toensurethatconductorinsulationhasnotdeterioratedorbeendamagedtoanextentthatexcessiveleakagecurrentscanflow.
2.Aninsulationresistancetester.3.Toavoidmisleadingtestresults4.Toavoiddamagetosuchequipment.5.AllswitchesON,allfusesIN,allcircuitbreakersON.6.500Vd.c.;lMΩ.7.250Vd.c.;lMΩ.8.2MΩ.9.Becausetherearealargenumberofcircuitsallinparallel.10.2.3MΩ.
![Page 57: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/57.jpg)
CHAPTER6SpecialTests
Thenext two tests are special in that they arenot often required in the general type ofinstallation.Theyalsorequirespecialtestequipment.Inconsequence,therequirementsforthesetestswillonlybebrieflyoutlinedinthisshortchapter.
![Page 58: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/58.jpg)
ProtectionbyBarriersorEnclosures
If,onsite,basicprotectionisprovidedbyfabricatinganenclosureorerectingabarrier,itmustbeshownthattheenclosurecanprovideadegreeofprotectionofatleastIPXXBorIP2Xor,whererequired,atleastIPXXDorIP4X.
AnenclosurehavingadegreeofprotectionIP2Xcanwithstandtheingressofsolidobjectsexceeding 12mmdiameter and fingers, IPXXB is protection against finger contact only.IP4Xgivesprotectionagainstsolidobjectsandwiresexceeding1mmindiameter,IPXXDprotectsagainstwiresexceeding1mmindiameteronly.
ThetestforIPXXBorIP2Xisconductedwitha‘standardtestfinger’whichissuppliedatatestvoltagenot less than40Vd.c.andnotmore than50Vd.c.Oneendof the finger isconnectedinserieswithalampandlivepartsintheenclosure.Whentheendofthefingeris introduced into the enclosure, provided the lampdoesnot light then the protection issatisfactory(Figure6.1).
ThetestforIPXXDorIP4Xisconductedwitharigid1mmdiameterwirewithitsendcutatrightangles.Protectionisaffordedifthewiredoesnotentertheenclosure.
![Page 59: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/59.jpg)
ProtectionbyNon-ConductingLocation
This is a rare location and demands specialist equipment to measure the insulationresistance between insulated floors andwalls at various points.Appendix 13 ofBS 7671outlinesthetestsrequired.
FIGURE6.1BSfingertest.
![Page 60: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/60.jpg)
CHAPTER7TestingPolarity(Low-ResistanceOhmmeter)
Importantterms/topicscoveredinthischapter:
EdisonscrewlampholdersRadialsocketoutletcircuitsSupplypolarity
Bytheendofthischapterthereadershould:
knowtheinstrumenttobeused,knowwhyBSEN60238,E14andE27lampholdersareexemptfrompolaritytesting, know why ring final circuit polarity is not usually carried out during polarity
testing,knowhowtocheckforline—cpcreversalsonradialsocketoutletcircuits,knowwhatlivepolaritytestshouldbeconducted.
Thissimpletest,oftenoverlooked,isjustasimportantasalltheothers,andmanyseriousinjuries and electrocutions could have been prevented if only polarity checks had beencarriedout.
Therequirementsare:
1.Allfusesandsinglepoleswitchesandprotectivedevicesareinthelineconductor.2. The centre contact of an Edison screw type lampholder is connected to the line
conductor (except E14 and 27 types to BS EN 60238, as these have threads ofinsulatingmaterialandthelampmustbefullyinsertedbeforeLandNcontactsaremade).
3.Allsocketoutletsandsimilaraccessoriesarecorrectlywired.
Although polarity is towards the end of the recommended test sequence, itwould seemsensible,onlightingcircuits,forexample,toconductthistestatthesametimeasthatforcontinuityofcpcs(Figure7.1).
As discussed earlier, polarity on ring final circuit conductors is achieved simply byconducting the ring circuit test. For radial socket outlet circuits, however, this is a littlemoredifficult.Thecontinuityofthecpcwillhavealreadybeenprovedbylinkinglineandcpcandmeasuringbetweenthesameterminalsateachsocket.Whilstaline—cpcreversalwould not have shown, a line—neutral reversal would, as there would have been noreadingat thesocket inquestion.Thiswouldhavebeenremedied,andsoonly line—cpcreversalsneedtobechecked.Thiscanbedonebylinkingtogethercpcandneutralatthe
![Page 61: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/61.jpg)
origin and testing between the same terminals at each socket. A line—cpc reversal willresultinnoreadingatthesocketinquestion.
Forlightingcircuits,thetestisthesameastheR1+R2test,sopolarityischeckedthen.Thesameappliestotheradialsocketoutletcircuitsifthesocketfrontsareopentotestattheactualcableterminations,asline—cpcreversalswillbevisible.
![Page 62: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/62.jpg)
Livepolarity
Whenthesupplyisconnected,itisimportanttocheckthattheincomingsupplyiscorrect.Thisisdoneusinganapprovedvoltageindicatorattheintakepositionorclosetoit.
FIGURE7.1Lightingcircuitpolarity.
Questions
1.Whatinstrumentisusedfortestingpolarity?2.WhyareBSEN60238E14andE27lampholdersexemptfrompolaritytesting?3.Atwhatpointinatestsequenceisthepolarityofaringfinalcircuitchecked?4.Howareline—cpcreversalsidentifiedinradialsocketoutletcircuits?5.Whereshouldlivepolaritytestsbeconducted?
Answers
1.Low-resistanceohmmeter.2.Thelampholderscrewthreadismadeofaninsulatingmaterial.3.WhentheringfinalcircuitcontinuityKitisbeingconducted.4.Bycross-connectingneutralandcpcandtestingbetweenNandcpcateach
socket.5.Atthesupplyintaketotheinstallation.
![Page 63: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/63.jpg)
CHAPTER8TestingEarthElectrodeResistance(Earth
ElectrodeResistanceTesterorLoopImpedanceTesters)
Importantterms/topicscoveredinthischapter:
EarthelectroderesistanceareaPotentialdividerCurrentandpotentialelectrodesAveragevalueofearthelectroderesistanceUseofearthfaultloopimpedancetester
Bytheendofthischapterthereadershould:
knowthetestinstrumentsthatmaybeused,understandwhatismeantbytheresistanceareaofanearthelectrode, be able to state the electrodes involvedwhen using an earth electrode resistance
tester,knowtheextentoftheresistanceareaofanelectrode,knowhowtoconductatestusinganearthelectroderesistancetester,knowwhattestmaybeconductedwhenthesystemisTTandisRCDprotected,beabletodeterminethevalueofearthelectroderesistancefromtestresults.
Inmanyruralareas, thesupplysystemisTTandhencerelianceisplacedonthegeneralmassofearthforareturnpathunderearthfaultconditions.Connectiontoearthismadebyanelectrode,usuallyoftherodtype,andpreferablyinstalledasshowninFigure8.1.
Inordertodeterminetheresistanceoftheearthreturnpath,itisnecessarytomeasuretheresistance that the electrode haswith earth. If wewere tomake suchmeasurements atincreasinglylongerdistancesfromtheelectrode,wewouldnoticeanincreaseinresistanceofuptoabout2.5-3mfromtherod,afterwhichnofurtherincreaseinresistancewouldbenoticed(Figure8.2).
![Page 64: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/64.jpg)
FIGURE8.1Earthelectrodeinstallation.
Themaximumresistancerecordedistheelectroderesistanceandtheareathatextendsto2.5-3mbeyondtheelectrodeisknownastheearthelectroderesistancearea.
There are twomethodsofmaking themeasurement, oneusingaproprietary instrumentandtheotherusingaloopimpedancetester.
![Page 65: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/65.jpg)
Method1:ProtectionbyOvercurrentDevice
Thismethodisbasedontheprincipleofthepotentialdivider(Figure8.3).
ByvaryingthepositionoftheslidertheresistanceatanypointmaybecalculatedfromR=V/I.
The earth electrode resistance test is conducted in a similar fashion with the earthreplacingtheresistanceandapotentialelectrodereplacingtheslider(Figure8.4).InFigure8.4,theearthingconductortotheelectrodeundertestistemporarilydisconnected.
FIGURE8.2Earthelectroderesistancearea.
FIGURE8.3Potentialdivider.
![Page 66: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/66.jpg)
FIGURE8.4Earthelectroderesistancetest.
Themethodoftestisasfollows:
1.Placethecurrentelectrode(C2)awayfromtheelectrodeundertest,approximately10timesitslength(i.e.30mfora3mrod).
2.Placethepotentialelectrodemidway.3.Connecttestinstrumentasshown.4.Recordresistancevalue.5.Movethepotentialelectrodeapproximately6meithersideofthemidposition,and
recordthesetworeadings.6.Takeanaverageofthesethreereadings(thisistheearthelectroderesistance).
For TT systems the result of this test will indicate compliance if the product of theelectroderesistanceandtheoperatingcurrentoftheovercurrentdevicedoesnotexceed50V.Clearlythiswillnotbeachievedwhenelectroderesistancesarehighandhencewillbemoreappropriateforelectrodesusedforearthconnectionsfortransformersandgeneratorswherethevaluesneedtobeverysmall.GenerallyspeakingthevaluesobtainedwillresultintheneedforRCDprotection.
![Page 67: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/67.jpg)
Method2:ProtectionbyaResidualCurrentDevice
In this case, anearth fault loop impedance test is carriedoutbetween the incoming lineterminalandtheelectrode(astandardtestforZe).
ThevalueobtainedisaddedtothecpcresistanceoftheprotectedcircuitsandthisvalueismultipliedbytheoperatingcurrentoftheRCD.Theresultingvalueshouldnotexceed50V.If it does, then Method 1 should be used to check the actual value of the electroderesistance.
Questions
1.Whatinstrumentsmaybeusedforearthelectroderesistancetesting?2.Whatistheextentoftheresistanceareaofanearthelectrode?3. For a 4 m electrode under test, at what distance away should the current
electrodebeplaced?4.Where should a potential electrode be initially placedwhen conducting an
earthelectroderesistancetest?5.Wherearethealternativepositionsforthepotentialelectrode?6.Whatwould be the resistance of an earth electrode if the test results gave
valuesof127Ω,129Ωand122Ω?7.What test may be performedwhen the system is TT and protected by an
RCD?
Answers
1.Earthelectroderesistancetesterorearthfaultloopimpedancetester.2.Approximately2.5mradiusfromtheelectrode.3.40mminimum.4.Centrallybetweentheelectrodeundertestandthecurrentelectrode.5.6meithersideofthepotentialelectrode’sinitialposition.6.126Ω.7.Anearthfaultloopimpedancetest.
![Page 68: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/68.jpg)
CHAPTER9TestingEarthFaultLoopImpedanceTester
Importantterms/topicscoveredinthischapter:
EarthfaultlooppathComparisonofresultswithmaximumvaluesTheruleofthumbRCDandcboperationCalculationofloopimpedanceExternalearthfaultloopimpedance
Bytheendofthischapterthereadershould:
knowwhatinstrumentisrequired,beconversantwiththevariousearthfaultlooppaths,knowthetestprocedure,knowhowtoadjustmaximumvaluesforcomparisonwithtestvalues,knowtoovercometheproblemsofRCDorcboperationduringthetest,beawareoftherequirementsfortestingexternalearthfaultloopimpedance.
This is very important but, sadly, poorly understood. So let us remind ourselves of thecomponentpartsoftheearthfaultlooppath(Figure9.1).Startingatthepointoffault:
1.Thecpc.2.Theearthingconductorandmainearthingterminal.3.Thereturnpathvia theearthforTTsystems,andthemetallicreturnpath in the
caseofTN-SorTN-C-Ssystems. Inthe lattercasethemetallicreturn is thePENconductor.
4.Theearthedneutralofthesupplytransformer.5.Thetransformerwinding.6.Thelineconductorbacktothepointoffault.
![Page 69: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/69.jpg)
FIGURE9.1Earthfaultlooppath.
Overcurrentprotectivedevicesmust,underearthfaultconditions,disconnectfastenoughtoreduce theriskofelectricshock.This isachieved if theactualvalueof theearthfaultloopimpedancedoesnotexceedthetabulatedmaximumvaluesgivenintherelevantpartsoftheIETRegulations.
Thepurposeofthetest,therefore,istodeterminetheactualvalueoftheloopimpedance(Zs),forcomparisonwiththosemaximumvalues,anditisconductedasfollows:
1.Ensurethatallmainequipotentialbondingisinplace.2.ConnectthetestinstrumenteitherbyitsBS1363plug,orthe‘flyingleads’,tothe
line,neutral andearth terminalsat the remoteendof the circuitunder test. (If aneutralisnotavailable,e.g.inthecaseofathree-phasemotor,connecttheneutralprobetoearth.)
3.Presstotestandrecordthevalueindicated.
Itmustbeunderstoodthatthisinstrumentreadingisnotvalidfordirectcomparisonwiththetabulatedmaximumvalues,asaccountmustbetakenoftheambienttemperatureatthetimeoftestandthemaximumconductoroperatingtemperature,bothofwhichwillhaveaneffectonconductorresistance.Hence,the(R1+R2)couldbegreateratthetimeoffaultthanatthetimeoftest.
So, ourmeasured value ofZsmust be corrected to allow for these possible increases intemperature occurring at a later date. This requires actually measuring the ambienttemperatureandapplyingfactorsinaformula.
ClearlythismethodofcorrectingZsistimeconsumingandunlikelytobecommonlyused.Hence,aruleofthumbmethodmaybeappliedwhichsimplyrequiresthatthemeasuredvalue ofZs does not exceed 0.8 of the appropriate tabulatedmaximum value. Table 9.1gives the 0.8 values of tabulated loop impedance for direct comparison with measured
![Page 70: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/70.jpg)
values.
Ineffect,aloopimpedancetestplacesaline/earthfaultontheinstallation,andifanRCDispresentitmaynotbepossibletoconductthetestasitwillkeeptrippingout.Unlesstheinstrument can compensate for this, thevalueofZswill have tobe calculatedusing themeasuredvaluesofZeand(R1+R2)andthe0.8ruleapplied.Remember,Zs=Ze+(R1+R2).
![Page 71: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/71.jpg)
ExternalLoopImpedanceZe
ThevalueofZe ismeasuredat theoriginof the installationon the supply sidewith themeans of earthing disconnected, to avoid parallel paths. Do not conduct this test if theinstallationcannotbeisolated.
ImportantNoteNeverbypassanRCDinorder toconduct this test.Also,as this testcreatesahighcurrent,somelowerratedcbsmayoperateonoverload.Donotreplacewithahigherratedbreakerfortestpurposes;usethecalculationmethod.
Table3.5CorrectedMaximumZsValuesforComparisonwithMeasuredValues
![Page 72: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/72.jpg)
![Page 73: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/73.jpg)
Questions
1.Whatinstrumentisusedforearthfaultloopimpedancetesting?2.WhichearthingsystemincludesaPENconductor?3.Beforetesting,whatactionshouldbetakenregardingequipotentialbonding?4.Whyisthe0.8ruleapplied?5. Isameasuredvalueof loopimpedanceof1.2Ωsatisfactoryif thetabulated
maximumvalueis1.44Ω?6. How may a value for loop impedance Zs be obtained if an RCD or a cb
operateswhenthetestisconducted?7.What action is required regarding the earthing conductor of an installation
beforeconductingatestforexternalloopimpedanceZe?8.Why is the action inQ7 above required andwhat othermeasuremust be
taken?
![Page 74: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/74.jpg)
Answers
1.Anearthfaultloopimpedancetester.2.TN-C-S.3.Ensureitisconnected.4.Tocompensateforincreasedambientandconductoroperatingtemperature.5.No,asthecorrectedmaximumwouldbe0.8×1.44=1.15Ω.6.CalculationfromZs=Ze+(R1+R2).7.Itmustbedisconnected.8.Toavoidparallelpaths.Thesupplytotheinstallationmustbeisolated.
![Page 75: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/75.jpg)
CHAPTER10AdditionalProtection(RCDTester)
Importantterms/topicscoveredbythischapter:
RCD/RCBOtestrequirementsUsesforRCDs/RCBOsDeterminationofRCD/RCBOrating
Bytheendofthischapterthereadershould:
knowwhatinstrumentshouldbeused,knowthetestrequirementsforvarioustypesofRCD/RCBO,knowtheinstrumentsettingsrequired,beabletoidentifywhereRCDs/RCBOsarerequired,knowhowtodeterminetheratingofRCDs/RCBOs.
![Page 76: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/76.jpg)
RCD/RCBOOperation
WhereRCDsandRCBOsareusedasadditionalprotectionagainstshock,itisessentialthattheyoperatewithinsetparameters.TheRCDtestersusedaredesignedtodojustthis,andthebasictestsrequiredareasfollows(Table10.1):
Note
AloopimpedancetestmustbeconductedbeforetheRCDtestashighvaluesofloopimpedanceortheabsenceofanearthpathcouldresultindangerousvoltages appearing between exposed and extraneous conductive parts andpersons should be told not to touch metalwork whilst the test is beingconducted.MostRCDtestershave the facility to test, separately, eachhalf cycleof thesupply and so each test should bedone at 0° and 180°.Thehighest readingshouldberecorded.
1.SetthetestinstrumenttotheratingoftheRCD.2.Setthetestinstrumenttohalf-ratedtrip(1/2IΔn).3.OperatetheinstrumentandtheRCDshouldnottrip.4.Settheinstrumenttodeliverthefull-ratedtrippingcurrentoftheRCD(IΔn).5.OperatetheinstrumentandtheRCDshouldtripoutintherequiredtime.6.A30mARCDorless,operatingat5×IΔn,shouldtripin40ms.
Table10.1RCD/RCBOTestRequirements
RCDType Half-Rated Full-RatedTripCurrentBS4239andBS7288sockets Notrip <200ms
BS4239withtimedelay Notrip 1/2timedelay+200mstotimedelay+200ms
BSEN61009orBSEN61009RCBO Notrip <300msAsabovebutTypeSwithtimedelay Notrip 130ms≤l≤500ms
NoteThislasttestisnotrequiredforRCDsratedover30mA.
ThereseemstobeapopularmisconceptionregardingtheratingsandusesofRCDsinthattheyarethepanaceaforallelectricalillsandtheonlyusefulratingis30mA!
First, RCDs are not fail-safe devices; they are electromechanical in operation and can
![Page 77: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/77.jpg)
malfunction.Second,generalpurposeRCDsaremanufacturedinratingsfrom5to500mAandhavemanyuses.Theacceptedlethallevelofshockcurrentis50mAandhenceRCDsratedat30mAorlesswouldbeappropriateforusewhereshockisanincreasedrisk.ThefollowinglistindicatestheresidualcurrentratingsandusesofRCDsasstatedinBS7671.
![Page 78: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/78.jpg)
RequirementsforRCDProtection
30mA
Allsocketoutletsratedatnotmorethan20Aandforunsupervisedgeneraluse.Mobileequipmentratedatnotmorethan32Aforuseoutdoors.Allcircuitsinabath/showerroom.PreferredforallcircuitsinaTTsystem. All cables installed less than 50 mm from the surface of a wall or partition in
prescribedzonesandnotprotectedbyanyothermethod,andalsoatanydepthiftheconstructionofthewallorpartitionincludesmetallicparts.
Inzones0,1and2ofswimmingpoollocations.Allcircuitsinalocationcontainingsaunas,etc.Socketoutletfinalcircuitsnotexceeding32Ainagriculturallocations.CircuitssupplyingClassIIequipmentinrestrictiveconductivelocations.Eachsocketoutletincaravanparksandmarinasandfinalcircuitforhouseboats.Allsocketoutletcircuitsratednotmorethan32Aforshowstands,etc. All socket outlet circuits rated notmore than 32A for construction sites (where
reducedlowvoltage,etc.isnotused).Allsocketoutletssupplyingequipmentoutsidemobileortransportableunits.Allcircuitsincaravans.Allcircuitsincircuses,etc.AcircuitsupplyingClassIIheatingequipmentforfloorandceilingheatingsystems.
100mA
Socketoutletfinalcircuitsofratingexceeding32Ainagriculturallocations.
300mA
Attheoriginofatemporarysupplytocircuses,etc.Wherethereisariskoffireduetostorageofcombustiblematerials.Allcircuits(exceptsocketoutlets)inagriculturallocations.
500mA
Any circuit supplying one ormore socket outlets of rating exceeding 32A, on a
![Page 79: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/79.jpg)
constructionsite.
Where loop impedance values cannot be met, RCDs of an appropriate rating can beinstalled.Theirratingcanbedeterminedfrom
whereIΔnistheratedoperatingcurrentofthedevice,50isthetouchvoltage,andZsisthemeasuredloopimpedance.
Questions
1.WhattestinstrumentisrequiredforRCD/RCBOtesting?2.What is themaximumoperating time foraBSEN61008RCDat full rated
current?3.What is themaximumoperatingtimefora30mARCDwhentestedat150
mA?4.WhatmaximumratingofRCDshouldbeusedfora63Asocketoutletona
constructionsite?5.WhatratingofRCDisrequiredforacaravaninstallation?6.Whatwould be the requiredmaximum rating of an RCDwhere the earth
faultloopimpedancewas167Ω?
Answers
1.AnRCDtester.2.300ms.3.40ms.4.500mA.5.30mA.6.300mA.
![Page 80: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/80.jpg)
CHAPTER11ProspectiveFaultCurrent(PFC/PSCCTester)
There is a requirement to determine the prospective fault current at the origin of aninstallation and at relevant points throughout.At the origin thismay be ascertained byenquiryormeasurement,whereasatotherpointsmeasurementistheonlyoption.
WherethelowestratedprotectivedeviceintheinstallationhasabreakingcapacityhigherthanthePFCattheorigin,thenmeasurementatotherpointsisnotneeded.
The purpose of this test is to verify that the breaking capacity of a protective device issuitablefortheprospectivefaultcurrentatthepointthatitisinstalled.
Aprotectivedevicewithabreakingcapacityof,say,3kAinstalledinadistributionboardwherethePFCis6kAcouldresultinseriousdamageand/orfireintheeventofafault.
BSEN60898circuitbreakershave twovaluesofbreakingcapacity, theservicerating IcsandthefaultratingIcn.TheIcnratingismarkedonthedevice,e.g. ;atthisvalueoffaultcurrentthebreakerwilloperatebutmaynotbeusableafterwards.
PFCisagenerictermandcanbeeitherprospectiveshort-circuitcurrent,PSCC(betweenlinesorlineandneutral)orprospectiveearthfaultcurrent,PEFC(betweenlineandearth).Both should bemeasured and the highest value recorded, although there is no harm inrecordingboth.
Thetestersaredesignedforsingle-phaseuse,sowhereavalueofPSCCisrequiredforathree-phase system itmaybedeterminedbymultiplying the single phase by 2, ormoreaccurately1.732.
![Page 81: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/81.jpg)
CHAPTER12CheckofPhaseSequence(PhaseSequence
Indicator)For three-phase systems it is important to have knowledge of the phase rotation of thesupplyandatvariouspointswithinaninstallation.ItisconventionforthisrotationtobenormallyBrown,Black,Grey, or L1, L2, L3. The direction of three-phasemotors can bereversed simply by reversing any two phases. In consequence the correct sequence isessentialtoensuretherightrotation.
Parallelingoftwothree-phasegeneratorsorofageneratortothethree-phasepublicsupplysystemrequirestheirphasesequencestobesynchronized.
The instrument is simply a small three-phasemotorwith a dial that indicates inwhichdirectionthesupplyisrotating(Figure12.1).
FIGURE12.1Phasesequenceindicator.
![Page 82: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/82.jpg)
CHAPTER13FunctionalTesting
AllRCDshaveabuilt-intestfacilityintheformofatestbutton.Operatingthistestfacilitycreatesanartificialout-of-balanceconditionthatcausesthedevicetotrip.Thisonlychecksthemechanicsof the trippingoperation; it doesnot check the conditionof the electricalinstallationandhenceisnotasubstituteforthetestsdiscussedinChapter10.
Thereshouldbeanotice inaprominentpositionatornear theoriginof the installationwherethedeviceislocatedindicatingthatthetestbuttonshouldbeoperatedquarterly.Fortemporary installations it is recommended that this operation be carried out at moreregularintervals.
All other items of equipment such as switchgear, controlgear interlocks, etc. must bechecked to ensure that they are correctlymounted and adjusted, and that they functioncorrectly.
This could involve the operation of, for example, two-way switching, dimmer switches,timers,thermostats,mainisolators,circuitbreakers,etc.
![Page 83: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/83.jpg)
CHAPTER14VoltageDrop(ApprovedVoltmeter)
Theremay be a requirement to determine the voltage at the terminals of equipment toensure that items of electrical equipment will function correctly and safely. As themaximum volt drop will occur when the circuit is at full load and at maximum cableoperating temperature it would be unlikely that an accurate instrument measurementwouldbeachievable.Hencethecalculationmethodisused.
ThisissimplybasedongoodoldOhm’slaw:V=I×R.
Allweneedisthelengthandcsaofthecable/conductorsorameasuredvalueofresistanceandthefullloadcurrent.
![Page 84: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/84.jpg)
Example14.1
Amotorwithafullloadcurrentof10Aisfedfroma230Vsupplybya70°Cthermoplasticcableof total resistance (L+N)0.222Ωmeasuredat20°C.What is theexpectedvoltagedropandisitacceptable?
VoltdropV=I×R=10×0.222×1.2=2.66V(the1.2factorconvertsthe20°Cresistancetowhatitwouldbeat70°C).Thisisacceptable,asthemaximumis11.5V.
Alternativelywe could use the length, the csa and the tabulated resistance inmΩ/m at20°C.
In theexampleabove the lengthwouldhavebeen15mandthesingleconductorcsa2.5mm2whichhasaresistanceof7.41mΩat20°C.
Table14.1MaximumPermissibleVoltageDrop
LVLighting3% LVPower5%Single-phase230V 6.9V 11.5VThree-phase400V 12V 20V
![Page 85: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/85.jpg)
CHAPTER15PeriodicInspection
Importantterms/topicscoveredinthischapter:
CircumstancesrequiringperiodicinspectionandtestingGeneralreasonsforperiodicinspectionandtestingConditionstobeinvestigatedDocumentationtobecompletedGeneralareasofnon-compliancethatmayberevealed
Bytheendofthischapterthereadershould:
knowwhyperiodicinspectionandtestingisrequired,knowwhatgeneralconditionswithinaninstallationneedinvestigation,knowwhatdocumentationneedstobecompleted,knowwhatactionisrequiredifthereisinsufficientinformation/drawings,etc.,understandtheextenttowhichdismantlingandsamplingshouldtakeplace, be aware of the conditions that may permit an installation to be exempt from
periodicinspectionandtesting.
![Page 86: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/86.jpg)
PeriodicInspectionandTesting
This is the province of the experienced inspectorwho has not only the knowledge andtechnical expertise to competently carry out the testing process but who is also fullyconversantwithcorrectelectricalinstallationpractices.
The purpose of the periodic inspection and testing is to establish whether or not theinstallation is in a satisfactory condition for continued use. This is achieved by relevantinspectionandappropriatetesting.Themostimportanttestistheloopimpedancetest,asthiswillestablishifdisconnectiontimesarebeingmet.
Therearemanyinstanceswheretestingisnotrequired.Forexample,themainpurposeofconductingaringcircuitcontinuitytestistoestablishifthereareinterconnectionsinthering.Thus,iftherearerecordsofthetestresultsfrompreviousinspectionsandtherehasbeen nowork carried out on the circuit, then it is impossible for an interconnection tohappenonitsown!Hencetheringcircuittestisawasteoftime.
Infact,evenR1+R2testscanbeavoidedastheZstestswillshowthecontinuityofcpcs.Theonlyothertestwhichshouldbecarriedoutisinsulationresistance,astheremayhavebeensomedeteriorationsincethelastinspection.
Clearly,iftherearenoprevioustestresults,morecomprehensivetestingwillberequired.
In any case the inspector should conduct a walk round to establish the extent of anysamplingofthecircuitstobeinspected.Thissamplingmaybereducedorincreasedastheinspectionproceeds,dependingonthefindings.
It should also be noted that in its true sense, Periodic Inspection and Testing does notincludefaultfindingasthisistimeconsumingandfinanciallyprohibitive.Remember,thepurposeistoreportontheconditionoftheinstallation,nottorectifyit.
![Page 87: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/87.jpg)
CircumstancesWhichRequireaPeriodicInspectionandTest
Testandinspectionisdue;insurance,mortgage,licensingreasons;changeofuse;changeofownership; after additions or alterations; after damage; change of loading; to assesscompliancewithcurrentregulations.
![Page 88: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/88.jpg)
GeneralReasonsforaPeriodicInspectionandTest
1.Toensurethesafetyofpersonsandlivestock.2.Toensureprotectionofpropertyfromfireandheat.3.Toensurethattheinstallationisnotdamagedsoastoimpairsafety.4. To ensure that the installation is not defective and complies with the current
regulations.
![Page 89: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/89.jpg)
GeneralAreasofInvestigation
Safety,Ageing,Damage,Corrosion,Overloading,Wearand tear,External influencesandSuitability(asanaidememoiretheauthorcallsthishisSADCOWESlist!).
![Page 90: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/90.jpg)
DocumentationtoBeCompleted
Anelectricalinstallationconditionreport(EICR),ascheduleoftestresultsandascheduleofinspections.
![Page 91: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/91.jpg)
SequenceofTests
Thereisnorequiredsequence.However,thesequenceforanInitialVerificationispreferredifpossible.
Periodic inspection and testing could be such a simple and straightforward process.Nevertheless,itusuallytendstobecomplicatedandfrustrating.
On the domestic scene, I doubt if any house owner actually decides to have a regularinspection,thecommentbeing,‘IfitworksitmustbeOK’.Itisusuallyonlywhenthereisa change of ownership that themortgage companies insist on an electrical survey. Theworstcasesare,however,inindustryandcommerce.
Periodic inspections are often requested by clients, reluctantly, to satisfy insurers or animpendingvisitbytheHSE.Eventhenitisusuallythecasethat‘youcan’tturnthatoff’or‘whycan’tyoujusttestthisbitandthenissueacertificateforthewholelot’.
Under the rare circumstances that an inspection and test is genuinely requested due toresponsibleconcernsforthesafetyofstaff,etc.,itisdifficulttoconvincetheclientthat,asthere are no drawings, or information about the installation, and that no switchgear islabelled,etc.,youaregoingtobeonsiteforaconsiderabletimeandataconsiderablecost.
When there are no drawings or items of information, especially on a large installation,theremaybeadegreeofexploratoryworktobecarriedoutinordertoensuresafetywhilstinspectingandtesting.Ifitisfeltthatitmaybeunsafetocontinuewiththeinspectionandtest, then drawings and information must be produced in order to avoid contraveningSection6oftheHealthandSafetyatWorkAct.
However, let us assume (in ourwildest dreams) that, aswith an Initial Verification, theoriginal installation was erected in accordance with the Wiring Regulations, and anyalterations and/or additions have been faithfully recorded and all the originaldocumentation/diagrams/charts,etc.arereadilyavailable!
Aperiodicinspectionandtestunderthesecircumstancesshouldberelativelyeasy,aslittledismantling of the installation will be necessary, and the bulk of the work will beinspection.
Inspection shouldbecarriedoutwith the supplydisconnectedas itmaybenecessary togainaccesstowiringinenclosures,etc.,andhencewithlargeinstallationsitwillprobablyneed considerable liaisonwith the client to arrange convenient times for interruptionofsuppliestovariouspartsoftheinstallation.
This is also the case when testing protective conductors, as these must never bedisconnectedunless thesupplycanbe isolated. It isparticularly important in thecaseofmainprotectivebondingconductorswhichneedtobedisconnectedinordertomeasureZe.
![Page 92: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/92.jpg)
Ingeneralaninspectionshouldreveal:
1.Anyaspectsoftheinstallationthatmayimpairthesafetyofpersonsandlivestockagainsttheeffectsofelectricshockandburns.
2.Thattherearenoinstallationdefectsthatcouldgiverisetoheatandfire,andhencedamageproperty.
3.Thattheinstallationisnotdamagedordeterioratedsoastoimpairsafety.4.Thatanydefectsornon-compliancewiththeRegulations,whichmaygiveriseto
danger,areidentified.
Aswasmentionedearlier,dismantlingshouldbekepttoaminimumasthisprocessmaycreatefaults.Henceacertainamountofsamplingwillberequired.
Theamountofsamplingwouldneedtobecommensuratewiththenumberofdefectsbeingfound.
It should be noted that if an installation is effectively supervised in normal use, thenperiodicinspectionandtestingcanbereplacedbyregularmaintenancebyskilledpersons.This would only apply to, say, factory installations where there are permanentmaintenancestaff.
Questions
1. State few circumstances that would result in the need for a periodicinspection.
2.Statethreeinstallationconditionsthatmayneedinvestigation.3.Statethethreeitemsofdocumentationthatwillneedtisbe-completed.4. When may exploratory work be required before commencing a periodic
inspectionandtestofalargeinstallation?5.Whyshoulddismantlingbekepttoaminimum?6. When may periodic inspection and testing be replaced by routine
maintenance?
Answers
1.Anytwo,fromduedata,mortgage,insurance,etc.,2.AnythreefromSADCOWESlist.3.Periodic/conditionreport.4.Wherethereisalackofinformation/drawings,etc.,anditmaybeunsafeto
continuewithoutthem.
![Page 93: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/93.jpg)
5.Toavoidcausingdamageandcreatingfaults.6.When the installation isundereffective supervisionand themaintenance is
carriedoutbyskilledpersons.
![Page 94: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/94.jpg)
CHAPTER16Certification
Havingcompletedalltheinspectionchecksandcarriedoutalltherelevanttests,itremainsto document all this information. This is done on Electrical Installation Certificates,Electrical Installation Condition Reports, schedules, test results, Minor ElectricalInstallationWorksCertificates and any other documentation youwish to append to theforegoing.ExamplesofsuchdocumentationareshowninBS7671andthe IETGuidanceNote3oninspectionandtesting.
Thisdocumentationisvitallyimportant.Ithastobecorrectandsignedorauthenticatedbyacompetentperson.ElectricalInstallationCertificatesandElectricalInstallationConditionReportsmustbeaccompaniedbyascheduleoftestresultsandascheduleofinspectionsforthemtobevalid.ItshouldbenotedthatbothElectricalInstallationCertificatesandMinorElectrical InstallationWorksCertificates should be signed or otherwise authenticated bycompetentpersonsinrespectofthedesign,theconstructionandtheinspectionandtestingoftheinstallation.TheElectricalInstallationConditionReportissignedbytheinspector.
(For larger installations theremay bemore than one designer, hence the certificate hasspace for twosignatures, i.e.designer1anddesigner2.) Itcouldbe,ofcourse, that foraverysmallcompany,onepersonsignsallthreeparts.Whateverthecase,theoriginalmustbegiventothepersonorderingthework,andaduplicateretainedbythecontractor.
One important aspect of an EIC is the recommended interval between inspections. Thisshould be evaluated by the designer andwill depend on the type of installation and itsusage. In some cases the time interval ismandatory, especiallywhere environments aresubject to use by the public. The IET Guidance Note 3 give recommended maximumfrequenciesbetweeninspections.
An Electrical Installation Condition Report is very similar in part to an ElectricalInstallationCertificateinrespectofdetailsoftheinstallation,i.e.maximumdemand,typeofearthingsystem,Ze,etc.Therestoftheformdealswiththeextentandlimitationsoftheinspectionandtest,recommendations,andasummaryoftheinstallation.Therecordoftheextentandlimitationsoftheinspectionisveryimportant.Itmustbeagreedwiththeclientorotherthirdpartyexactlywhatpartsoftheinstallationwillbecoveredbythereportandthosethatwillnot.Theintervaluntilthenexttestisdeterminedbytheinspector.
Withregardtothescheduleoftestresults,testvaluesshouldberecordedunadjusted,anycompensationfortemperature,etc.beingmadeafterthetestingiscompleted.
AnyalterationsoradditionstoaninstallationwillbesubjecttotheissueofanElectricalInstallationCertificate,exceptwheretheadditionis,say,asinglepointaddedtoanexistingcircuit,whentheworkissubjecttotheissueofanMEIWC.
![Page 95: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/95.jpg)
Summary:
1. The additionof points to existing circuits requires aMinorElectrical InstallationWorksCertificate.
2.AnewinstallationoranadditionoralterationthatcomprisesnewcircuitsrequiresanElectricalInstallationCertificate.
3.AnexistinginstallationrequiresanElectricalInstallationConditionReport.
NotePoints(2)and(3)mustbeaccompaniedbyascheduleoftestresultsandascheduleofinspections.
Astheclient/customeristoreceivetheoriginalsofanycertification,itisimportantthatallrelevantdetails are completed correctly.This ensures that future inspectors are awareoftheinstallationdetailsandtestresultswhichmayindicateaslowprogressivedeteriorationinsomeoralloftheinstallation.
Thesecertificates,etc.couldalsoformpartofa‘seller’spack’whenaclientwishestosellaproperty.
ThefollowingisageneralguidetocompletingthenecessarydocumentationandshouldbereadinconjunctionwiththeexamplesgiveninBS7671andtheIETGuidanceNote3.
![Page 96: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/96.jpg)
ElectricalInstallationCertificate
1.Detailsofclient:Name:Fullname.Address:Fulladdressandpostcode.Description:Domestic,industrial,commercial.Extent:Whatworkhasbeencarriedout (e.g. fullrewire,newshowercircuit,etc.).Tickrelevantbox.
2.Designer/constructor/tester:Detailsofeachorcouldbeoneperson.Note: Departures are not faults, they are systems/equipment, etc. that are notdetailedinBS7671butmaybeperfectlysatisfactory.
3.Nexttest:Whenthenexttestshouldbecarriedoutanddecidedbythedesigner.
4.Supplycharacteristicsandearthingarrangements:Earthingsystem:Tickrelevantbox(TT,TN-S,etc.).Liveconductors:Tickrelevantboxes.Nominalvoltage:Obtainfromsupplier,butusually230Vsingle-phaseUandU0but400VUand230U0forthree-phase.Frequency:Fromsupplierbutusually50Hz.PFC:Fromsupplierormeasured.Supplierusuallygives16kA.Ze:Fromsupplierormeasurement.Supplierusuallygives0.8VforTN-S;0.35VforTN-C-Sand21VforTTsystems.Mainfuse:UsuallyBS1361,ratingdependsonmaximumdemand.
5.Particularsofinstallation:Meansofearthing:Tick‘supplier’sfacility’forTNsystems,‘earthelectrode’forTTsystems.Maximumdemand:Valuewithoutdiversity.Earthelectrode:MeasuredvalueorN/A.Earthingandbonding:Conductors:Actualsizesandmaterial,usuallycopper.Main switch or circuit breaker (could be separate units or part of a consumercontrolunit):BSnumber;Rating,currentandvoltage;Location;‘notaddress’;thatis,whereitislocatedinthebuilding;Fuseratingifinaswitch-fuse,elseN/A;RCDdetailsonlyifusedasamainswitch.
6.Commentsonexistinginstallation:Write down any defects found in other parts of the installationwhichmay havebeenrevealedduringanadditionoranalteration.
7.Schedules:Indicate the number of test and inspection ‘schedules that will accompany this
![Page 97: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/97.jpg)
certificate’.
![Page 98: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/98.jpg)
ElectricalInstallationConditionReport
1.Detailsofclient:Name:Fullname(couldbealandlord,etc.).Address:Fulladdressandpostcode(maybedifferenttotheinstallationaddress).Purpose:Forexample,duedate;changeofowner/tenant;changeofuse,etc.
2.Detailsofinstallation:Occupier:Couldbetheclientoratenant.Installation:Couldbethewholeorpart(givedetails).Address:Fullandpostcode.Description:Tickrelevantbox.Age:Ifnotknown,sayso,oreducatedguess.Alterations:Tickrelevantboxandinsertagewhereknown.Lastinspection:Insertdateor‘notknown’.Records:Tickrelevantbox.
3.Extentandlimitations:Full details of what is being tested (extent) and what is not (limitations). If notenoughspaceonformaddextrasheets.
4.Nextinspection:Filledinbyinspectorandsigned,etc.underdeclaration.
5.Supplydetails:AsperanElectricalInstallationCertificate.
6.Observations:Tickrelevantbox,ifworkisrequired,recorddetailsandenterrelevantcode(C1,C2,C3andF1)inspaceonright-handside.
7.Summary:Comment on overall condition. Only the identification of a code C1 or C2 willrequireaninstallationtobeclassifiedasbeingUNSATISFACTORY.
8.Schedules:Attachcompletedschedulesofinspectionsandtestresults.
![Page 99: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/99.jpg)
ObservationCodes
C1Dangerpresent,immediateremedialactionrequired.Thisisusedwherethereis,forexample,anexposedlivepartthatcanbetouched.Itsissuggestedthatifpracticable,thisberectifiedondiscoverybut,ifnot,thentheownermustbeinformedinwritingasamatterofurgency.
C2Potentiallydangerous,urgentremedialactionrequired.This would be the case, say, wheremain protective bondingwas not present. Itwouldonlybecomedangerousiftherewasafaulttoearthandapersonhappenedtobesimultaneouslytouchingaccessibleexposedandextraneousconductiveparts.
C3Improvementrecommended.This would be used, for example, if there was a label missing for non-standardcolours.Itisanomissionbutitdoesnotmaketheinstallationunsafefortheuser.
F1Furtherinvestigationneededwithoutdelay.Thiswouldbe thecasewhenacodeC1orC2defect is suspectedbutbecauseofextentandlimitationsthecircuit/sinquestioncannotbeaccessed.
![Page 100: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/100.jpg)
MinorElectricalInstallationWorksCertificate
Onlytobeusedwhensimpleadditionsoralterationsaremade,notwhenanewcircuitisadded.
1.Description:Fulldescriptionofwork.Address:Fulladdress.Date:Datewhenworkwascarriedout.Departures: These are not faults, they are systems/equipment, etc. that are notdetailedinBS7671butmaybeperfectlysatisfactory(thisisusuallyN/A).
2.Installationdetails:Earthing:Tickrelevantbox.Methodoffaultprotection:99%ofthetimethiswillbeautomaticdisconnectionofsupply.Protectivedevice:Entertypeandrating.Forexample,BSEN60898CBtypeB,20A.Comments:Noteanydefects/faults/omissionsinotherpartsoftheinstallationseenwhileconductingtheminorworks.
3.Tests:Earthcontinuity:MeasuredandthentickinboxifOK.Insulationresistance:Standardtestsandresults.EFLI(Zs):Standardtestsandresults.Polarity:StandardtestsandthentickinboxifOK.RCD:Standardtests,recordoperatingcurrentandtime.
4.DeclarationName,address,signature,etc.
![Page 101: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/101.jpg)
ContentsofaTypicalScheduleofTestResults
1.Contractor: Fullnameoftester.2.Date: Dateoftest3.Signature: Signatureoftester.
4.Vulnerableequipment:Dimmers,electronictimers,CHcontrollers,etc.(i.e.anythingelectronic).
5.Address:Full,orifinalargeinstallation,thelocationofaparticularDB.
6.Zeatorigin: Measuredvalue.
7.RFC:RecordthehighestvaluethatisPEFCorPSCC(shouldbethesameforTN-C-S).
8.Confirmationofsupplypolarityandphasesequence:
Tickbox.
9.Instruments:Recordserialnumbersofeachinstrument,oronenumberforacompositeinstrument.
10.CircuitDescription: Detailsofcircuit,e.g.firstfloorlights.11.kVAratingofprotection: Takenfromdevice.
12.Typeandrating:Forexample,BSEN60898CBtypeB,32A,orBS8840A,etc.
13.Referencemethod: EnterA’,B’,‘C,‘100’,etc.14.Wiringconductors: Sizeofliveandcpc,e.g.2.5mm2/1.5mm2.15.Testresults: Enterallmeasuredresults,notcorrectedvalues.
![Page 102: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/102.jpg)
ScheduleofInspections(asperBS7671)
ForEICsdonotleaveboxesuncompleted:N/Ainaboxifitisnotrelevant;inaboxifithas been inspected and is OK. For EICRs, the same as the EIC except when defects,omissions,etc.arefound,thenenteroneoftheappropriatecodesC1,C2,C3,orF1.
![Page 103: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/103.jpg)
APPENDIX12394SamplePaper
![Page 104: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/104.jpg)
![Page 105: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/105.jpg)
SectionA
1.
a. For the initial verification of a new installation, list six items ofinformationregardingtheincomingsupplyandthreeitemsregardingtheinstallationthatshouldbemadeavailabletotheInspector.(9marks)
b. StatethethreereasonsfortheissueofanElectricalInstallationCertificate.(3marks)
c. State the documentation that must accompany an Electrical InstallationCertificate.(2marks)
d. State the Statutory document that relates to Inspection and Testing. (1mark)
2.
a. StatefourmethodsofprovidingBasicProtectiononly.(4marks)b. StatetwomethodsofprovidingbothBasicandFaultProtection.(2marks)c. Give an example of Electrical Separation in a domestic installation. (1
mark)d. StatetheIPcodesapplicabletoanaccessiblehorizontaltopsurfaceofan
enclosure.(2marks)e. State the conditions that would allow ‘routing of cables in prescribed
zones’tobeusedastheonlymethodofprotectionwherecablesareburiedlessthan50mmfromthesurfaceofawall.(3marks)
f. Statethethreeteststhatrequiretheuseofalow-resistanceohmmeter.(3marks)
3.
a. Explain,withregardtoringfinalcircuitcontinuity
i. why,whenLsandNshavebeencrossconnected,thereadingsateachsocketmayvaryconsiderablyaroundthering;(2marks)
ii. thesignificanceofthehighestreadingwhenLandcpcaretestedateachsocket.(2marks)
b.Listthefirstfivetests,asperBS7671:2008,tobeconductedonanewlightindustrialunitwhereallcircuitsareradials.ThesupplyearthingsystemisTN-C-S.(5marks)
c.Statetwomethodsofprovidingadditionalprotection.(2marks)d.ExplainindetailwhyanRCDtestshouldnotbeconductedbeforeanearth
![Page 106: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/106.jpg)
faultloopimpedancetest.(4marks)
![Page 107: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/107.jpg)
![Page 108: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/108.jpg)
SectionB
Allquestionsinthissectionrelatetothefollowingscenario:
Avillagecricketclubhashadanewclubhousebuiltcomprisingchangingrooms,amainoffice, a loungeandbararea, aplayers’waitingandviewingarea, andmaleand femaletoiletsandshowerfacilities.
Thebuilding isa traditionalbrickand timberconstructionwith internalblockwalls.Allcables are 70°C thermoplastic flat sheathed 6242/3Y, ‘chased in’ to full plaster depth andaccessoriesare flushmounted.AllcircuitsareRCBOprotectedtoBSEN61009-1 typeB.Themainprotectivebondingtogasandwaterservices is10mm2copper.Themaximumlengthofthisbondingconductoris10m.
Thesupplyis230V50Hzsingle-phaseandtheearthingsystemisTN-C-SwithameasuredZevalueof0.23ΩandaPFCof1kA.Thedistributionfuseboardis12-waymetal-clad.
TableA1.1givescircuitdetails,TableA1.2indicatesconductorresistances.
Alltestsarecarriedoutat20°C.
TableA1.1
TableA1.2
ConductorSizemm2 ResistanceinmΩ/mat20°C1.0 18.11.5 12.12.5 7.416.0 3.08
![Page 109: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/109.jpg)
10.0 1.83
4.
a. Statethemethodusedforprotectionagainstshockforthisinstallation.(2marks)
b. Explainwhythelighting,cookerandhanddryercircuitshavebeenRCDprotected.(4marks)
c. Explaintheconsiderationstobemaderegardingtheentryofthemaintailsandearthingconductorintothedistributionboard.(5marks)
d. Determine the expected resistance R2 of the main protective bondingconductor.(4marks)
5.
a. Thekitchenringfinalcircuithasbeensecurelyisolated.Describeindetailhowaringfinalcircuitcontinuitytestwouldbecarriedout.(10marks)
b. Whatwouldbe:
i. the expected L toN resistance at each socket after correct L–Ncross-connection?(2marks)
ii. theexpectedLtocpcresistanceateachsocketaftercorrectL–cpccrossconnection?(3marks)
6.
a. Drawafullylabelleddiagramoftheearthfaultlooppathforcircuit5.(8marks)
b. Explainwhy the PEFC and the PSCC for this installationwould be thesamevalue.(2marks)
c. DeterminetheexpectedZsvaluesforcircuits1,6and9andconfirmiftheyareacceptable.(5marks)
![Page 110: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/110.jpg)
2395SamplePaper
![Page 111: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/111.jpg)
![Page 112: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/112.jpg)
SectionA
1.
a. Statethefourresponsibilitiesofaninspectorwhilstcarryingoutaperiodicinspectionandtestofaninstallation.(4)
b. Statetheactiontobetakenbyaninspectorpriortocarryingoutaperiodicinspection and test of a complex installation, where no diagrams,drawings,charts,etc.areavailable.(5)
c. List the three documents that must be completed for the periodicinspectionandtestofaninstallation.(3)
d. StateoneStatutoryand twonon-statutorypublications thatwouldapplytotheperiodicinspectionandtestofaninstallation.(3)
2.
a. State the human senses that would be used when inspecting a metalconduitsystemina30-year-oldinstallation.(2)
b. List three considerations thatwoulddetermine the frequencyofperiodicinspectionandtestingofaninstallation.(3)
c. ListthreerequirementsofH&SEGS38regardinginstrumenttestleads.(3)d. Describetheprocedureforthesafeisolationofsupplies.(7)
3.
a. State the action to be taken, giving reasons, regarding the earthingconductorduringatestofexternalearthfaultloopimpedance.(2)
b. Determine, from the following test results,whichcircuitsdonot complywiththerequirementsofBS7671(showallcalculations):
CircuitNo. MeasuredZsΩ MaximumTabulatedZsΩ1 1.37 1.752 2.15 2.733 0.68 0.874 6.0 7.285 1.72 2.186 0.5 0.54
(3)
c. Describe, indicating all test values, the procedure for carrying out aninstrumenttestona20mARCDusedforadditionalprotection.(10)
![Page 113: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/113.jpg)
![Page 114: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/114.jpg)
SectionB
A small 30-year-old dry-powder coating company is situated adjacent to an 11 kV/400V/230VDistributionNetworkOperator’ssubstation.TheearthingsystemisT.N-C-Swithanexternalearthfaultloopimpedance(Ze)of0.015andaprospectivefaultcurrent(PFC)of15kA.TheSupplyisthree-phasefourwirewith100ABS1361fusesandtheservicetailsare35mm2witha25mm2earthingconductor.
Gas andwater services are located some 30m from the electricity intake and nomainprotectivebondingconductorsarepresent.
Attheintakeposition,aTP&Ndistributionboard,housingBS88fuses,isusedtosupplyallfinalcircuitsinthefactoryarea.AnSP&NconsumerunithousingBS3036fusesislocatednexttothedistributionboardandsuppliesfinalcircuitsinasmallkitchenarea.
The wiring system throughout is 70°C thermoplastic, copper single core conductorsenclosedinmetaltrunkingandconduit.
Theprocessofdry-powdercoatingofmetalpartsinvolvestheuseofacidbaths,waterjets,atunnelovenandelectrostaticallychargedpowderspraying.
Newownershaverequestedaperiodicinspectionandtestofthewholeinstallationbeforetheycontinuewiththeproductionprocesses.
Alloriginaldocumentation,diagrams,charts,etc.havebeenlost.
Alltestingiscarriedoutatatemperatureof20°C.
TableA1.3givesresistancevaluesofcopperconductorsat20°C.
TableA1.3Conductorresistance
Conductorcsamm2 mΩ/mat20°C1.5 12.12.5 7.414.0 4.616.0 3.0810.0 1.8316.0 1.15
4.
a. State three considerations to be made by the inspector in order todeterminetheinitialamountofsamplingtobecarriedout.(3)
b. Explain the circumstances thatmay require an increase in the samplingrateabovetheinitialamountdetermined.(3)
c. Statethreecircumstanceswherecableswouldnotbeinspectedandwould,
![Page 115: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/115.jpg)
therefore, not be included in the extent and limitations section of theElectricalInstallationConditionReport.(3)
d. List,apartfromage, threegeneralareasof investigationtobeconsideredbytheinspectorcarryingouttheinspectionofthisinstallation.(3)
e. State three external influences that should be considered for thisinstallation.(3)
5.
a. Explain why the protective devices in the SP&N consumer unit do notcomplywithBS7671:2008.Indicatetheclassificationcodetoberecorded.(5)
b. State the cross-sectional area of themain protective bonding conductorsthatshouldbeinstalled,theclassificationcodetoberecordedduetotheiromission,andtheexpectedtestresistanceiftheywereinstalled.(6)
c. List, apart from socket outlets not exceeding 20 A, four situations thatrequireadditionalprotectionbyRCDs.(4)
6.
a. Describehowa test forcpccontinuity,henceobtainingavalue for (R1+R2),wouldbecarriedoutonaradialcircuitsupplyingsingle-phasespray-boothmotor.Thiscircuithasbeencorrectlyisolatedatitsorigin.(9)
b. Calculatetheexpectedvoltagedropinthemotorcircuitin(a)above,ifthemotor has a design current of 20 A and is supplied by 4 mm2 liveconductorswithameasuredlinetoneutralresistanceof0.15Ω.(6)
![Page 116: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/116.jpg)
APPENDIX22394SamplePaper(Answers)
![Page 117: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/117.jpg)
![Page 118: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/118.jpg)
SectionA
1.
a. anysixfrom:EarthingsystemNumberandtypeofliveconductorsVoltageFrequencyPFCZe
TypeandratingofsupplyprotectivedeviceAnythreefrom:Typeandcompositionofwiring,type,numberofpoints,etc.MethodoffaultprotectionIdentificationofprotectivedevices,andisolators,switches,etc.DetailsofcircuitsorequipmentvulnerabletoatypicaltestDetailsofprotectivebondingconductors
b. Newinstallation;Addition;Alterationc. Scheduleoftestresults;Scheduleofinspectionsd. EAWR
2.
a. Insulation;Barriersorenclosures;Obstacles;Placingoutofreachb. SELV;PELV;Doubleinsulation;Reinforcedinsulation(anytwo)c. Shaverpointd. IPXXDorIP4Xe. Installationmustbeunderthesupervisionofaskilledorinstructedpersonf. Continuityorprotectiveconductors;Ringcircuitcontinuity;Deadpolarity
3.
a.
i. Incorrectcross-connectionii. R1+R2forthering
b.Continuityofprotectiveconductors
i. Insulationresistanceii. Polarityiii. Earthfaultloopimpedance
![Page 119: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/119.jpg)
iv. OperationofRCDs
c.RCD;Supplementaryequipotentialbondingd.IftheRCDtestwasdonefirstandtheearthlooppathwastoohigh,afault
would have been placed on the circuit and the RCD may not operate,placingeveryoneatrisk
![Page 120: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/120.jpg)
![Page 121: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/121.jpg)
SectionB
4.
a. Automaticdisconnectionofsupplyb. These circuits only need RCD protection because the cables supplying
themarelessthan50mmfromthesurfaceofthewallsc. The tails and earthing conductor should enter theDB through the same
holetoavoidelectromagneticeffects.TheentryholeshouldbetoIPXXDorIP4Xiftopentry,IPXXBorIP2Xelsewhereandcablesprotectedagainstmechanicaldamage.
d. 10mof10mm2bondingconductor 1000
5.
a.
Selectalow-resistanceohmmeterCheckfordamageandbatteryconditionandcurrentcalibrationNullorzerotestleads(GS38leads)IdentifylegsofringMeasureindividualloops,r1,rnandr2Cross-connectoppositeLsandNsMeasurebetweenLandNateachsocket(shouldbethesamevalue)RepeatwithLsandcpcscrossed(highestreadingisR1+R2)Record(R1+R2)Reinstatesystem
b. i.r1andrneach soreadingateachsocket
ii. soreadingateachsocket
6.a.
![Page 122: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/122.jpg)
4marksfordiagram,4marksforlabels(halfeach)NOMARKSIFDIAGRAMINCORRECT
b.Theearthfaultcurrentandtheshort-circuitcurrenttakethesamepath,i.ethePENconductor
c.
Zs=0.23+0.1=0.33Ωok,0.8×maxis1.09Ω
Zs=0.23+0.13=0.36Ωok,0.8×maxis1.75Ω
Zs=0.23+0.58=0.81Ωok,0.8×maxis5.83Ω
![Page 123: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/123.jpg)
2395SamplePaper(Answers)
![Page 124: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/124.jpg)
![Page 125: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/125.jpg)
SectionA
1.
a. Ensuretheirownsafetyandthatofothers,etc.(1)Compareresultswithrelevantcriteria(1)ConfirmcompliancewithBS7671(1)Takeaviewoftheconditionoftheinstallation(1)(4marks)
b. Exploratorysurveytoestablishifsafetocarryoutinspectionandtestingwithoutdiagrams/drawings,etc. Ifnot,thentheclientcanberequiredtoproducethem.(5marks)
c. EICR,schedulesofinspectionsandschedulesoftestresults(3marks)d. EAWR,BS7671,GN3,On-siteguide,etc.(3marks)
2.
a. Touchandsight(2marks)b. Typeofinstallationandequipment;useofinstallation;externalinfluences;
qualityandfrequencyofmaintenance(anythree)(3marks)c. Nomorethan4mmprobetips;fingerguards;coloured;suitablyinsulated;
fused;suitablelength(anyfour)(3marks)d. Seekpermissiontoisolate(1)
Isolateandlockoff(1)Retainkey(1)SelectanapprovedvoltageindicatortoGS38(1)Proveindicatoronknownsupplywithsamevoltageassystemundertest(1)Checksystemisde-energized(1)Reprovevoltageindicator(1)(7marks)
3.
a. Disconnecttoavoidparallelpaths(2marks)
CircuitNo. MeasuredZsΩ CorrectedMaximumZsΩ1 1.37 1.75x0.8=1.42 2.15 2.73x0.8=2.183 0.68 0.87x0.8=0.74 6.0 7.28x0.8=5.825 1.72 2.18x0.8=1.746 0.5 0.54x0.8=0.43
b. Circuits4and6donotcomply(3marks)
![Page 126: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/126.jpg)
c. Ensureearthingissatisfactory(1)SelectRCDtester(1)CheckleadsaretoGS38(1)ConnectleadstoL,NandEonloadsideofRCD(1)Testat20mAonboth0°and180°(1)CheckRCDtripswithin300ms(1)Recordlongesttime(1)Repeattestat100mAonboth0°and180°(1)CheckRCDtripswithin40ms(1)Recordlongesttime(1)(10marks)
![Page 127: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/127.jpg)
![Page 128: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/128.jpg)
SectionB
4.
a. Anythreefromtheliston‘Settinginspectionandtestingsamples’GN3(3marks)
b. Ifinspectionortestingoftheoriginalsamplerevealspoorresults(3marks)c. Cables in conduit or trunking; under floors; in roof spaces; within the
buildingfabricorunderground(anythree)(3marks)d. AnyotherthreefromtheSADCOWESlist(3marks)e. Water;dust;corrosion;heat(Anythree)(3marks)
5.
a. BS3036fuseshaveaverylowbreakingcapacity(4kAmax)andthePSCCattheorigin,wherethesefusesarelocated,is15kA;henceashort-circuiton any of the circuits fed by these fuses is likely to cause seriousdamage/arcing/fireintheSP&Nconsumerunit(5marks)
b. 10mm2;C2; (6marks)c. Circuitssupplyingmobileequipmentnotexceeding32A,outdoors;Cables
inwallslessthan50mm;AllLVcircuitsinbathrooms;Circuitsinsaunas;Swimmingpools;Agriculturallocations,etc.(4marks)
6.
a. Isolate/disconnectatmotorendofcircuit(1)Selectalow-resistanceohmmeter(1)Checkforinstrumentdamage(1)Checkbatterycondition(1)CheckleadsaretoGS38(1)LinklinetocpcatDBormotor(1)Testbetweenlineandcpcatotherend(1)RecordresultReinstatesystem(1)(9marks)
b. Circuitresistance=0.15×1.2=0.18ΩMotorcurrent=20AVoltdrop=20×0.15×1.2=3.6volts(6marks)
![Page 129: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/129.jpg)
APPENDIX32394/5SampleMCQPaperandAnswers
1. InordertocomplywithBS7671,whichoneofthefollowingshouldaninspectorbe?
a. Anapprovedcontractorb. Acompetentpersonc. Aqualifiedelectriciand. Aninstructedperson
2.Whichoneofthefollowingfulfilstherequirementforsafeisolationofacircuit?
a. Switchoffandinformallpersonnelb. Switchoffanddisplaynoticesc. Lockoffanddisplaynoticesd. Lockoffandgivekeytoclient
3. Which one of the following is the correct procedure for the use of a voltageindicatorwhencarryingoutsafeisolation?
a. Checktheindicatorviaitsowntestbuttonb. Checktheindicatorontheisolatedcircuitc. Checktheindicatoronaprovingunitd. Checktheindicatorisconnectedtoearth
4.Whichoneofthefollowingisthecorrectactionforaninspectoraftercompletingthesafeisolationofacircuit?
a. Keepthekeyinatool-boxb. Handkeytotheclientc. Giveduplicatekeytoclientd. Keepkeyonperson
5.Thesupplytoanofficecomplexistobeisolatedinordertocarryoutaninspectionand test.Which one of the following is the inspector’s first step in the isolationprocess?
a. Switchoffandprovedeadb. Seekpermissiontoisolate
![Page 130: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/130.jpg)
c. Carryoutacontinuitytestd. Informtheenergysupplier
6.ApropertywhichincludesasolarPVsystemistobeinspectedandtested.Whichoneofthefollowingactionsmustbetakentoensuresafeisolation?
a. IsolatebothmainandPVsuppliesb. IsolatePVsupplyonlyc. Isolatemainsupplyonlyd. LinkoutthePVmetering
7.Whichoneofthefollowingcanonlybeconductedwiththesupplyisolated?
a. RCDtestb. Phaserotationatamotorc. Ringfinalcircuitcontinuityd. Earthfaultloopimpedance
8.WhichoneofthefollowingisthestatusofBS7671?
a. Statutoryb. Non-statutoryc. Advisoryd. Mandatory
9. Which one of the following would be the most suitable as a reference for aninspectorconductinganinspectionandtest?
a. BS7671b. GS38c. EAWRd. GN3
10.Whichoneofthefollowingdocumentsrequiresthedetailsofthemethodoffaultprotection?
a. Electricalinstallationcertificateb. Electricalinstallationconditionreportc. Minorworkscertificated. Scheduleoftestresults
11.GS38requiresthatlowvoltagetestleadsshouldbe:
![Page 131: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/131.jpg)
a. fused,havefingerguardsandnomorethan4mmexposedtipsb. fused,havefingerguardsandmorethan4mmexposedtipsc. non-fused,havefingerguardsandnomorethan4mmexposedtipsd. non-fused,havefingerguardsandnomorethan2mmexposedtips
12. Which one of the following is the instrument to be used for an insulationresistancetest?
a. Aresistancetesterb. Ahigh-readingohmmeterc. anohmmeterd. aninsulationresistancetester
13.WhichoneofthefollowingunitsisdisplayedonanRCDtester?
a. msb. Msc. mAd. MΩ
14.Thetechnicalspecificationforalow-resistanceohmmeterrequirestheinstrumenttodeliverano-loadvoltageandashort-circuitcurrent:
a. between4V–24Va.c.;notexceeding200mAb. between4V–24Vd.c.;notlessthan100mAc. between4V–24Va.c.ord.c.;notlessthan200mAd. between4V–24Va.c.ord.c.;notexceeding200mA
15. The following tests are to be conducted on an installation: i. Earth fault loopimpedance;ii.RCDoperation;iii.Continuityofprotectiveconductors;iv.insulationresistance.Whichoneofthefollowingisthecorrectsequenceforthesetests?
a. 1,2,3,4b. 3,2,1,4c. 4,3,2,1d. 3,4,1,2
16.Which one of the following tests automatically conducts a dead circuit polaritytest?
a. Insulationresistanceb. Ringfinalcircuitcontinuityc. Protectivebondingcontinuity
![Page 132: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/132.jpg)
d. RCDoperation
17.Whichoneofthefollowingtestsrequirestheinstrumentleadstobetested‘open’and‘shorted’beforetestingcommences?
a. Insulationresistanceb. Conductorcontinuityc. RCDoperationd. Polarity
18.Whichoneofthefollowinggivesdetailsofthecorrectuseofavoltageindicator?
a. GN3b. BS7671c. GS38d. EAWR
19. In order to significantly reduce the risk of electric shock under ‘fault-free’conditions,itisimportantthat:
a. disconnectiontimesaremetb. basicprotectionisprovidedc. theearthingconductoris≥6.0mm2
d. a‘non-standardcolours’noticeisdisplayed
20. A test for continuity of a main protective bonding conductor requires itsdisconnectionatoneend.Thisistoeliminate:
a. theriskofshockduringthetestb. thetestleadresistancec. excessivevoltdropduringthetestd. theintroductionofparallelpaths
21.Whichoneofthefollowingwouldbetheeffectontheresistanceofacableifbothitscsaandlengthweredoubled?
a. Halvedb. Stayedthesamec. Doubledd. Quadrupled
22.Alengthof2.5mm2flatsheathedcablehasend-to-endliveconductorresistancesof0.37Ω.Whichoneofthefollowingwouldbetheapproximateresistanceofthe
![Page 133: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/133.jpg)
associated1.5mm2cpc?
a. 1.67Ωb. 1.48Ωc. 0,62Ωd. 0.19Ω
23.Whichoneofthefollowingwouldbetheoverallvalueofinsulationresistanceofaninstallationifindividualcircuitvalueswere10MΩ;
MΩ;25MΩand45MΩ?
a. 95MΩb. 23.75MΩc. 4.37MΩd. 0.23MΩ
24.Whichoneofthefollowingwouldnotberecordedonascheduleoftestresultsforaringfinalcircuitcontinuitytest?
a. r1b. rnc. LtoNateachsocketd. Ltocpcateachsocket
25.Whichoneofthefollowingwouldbetheeffectontheinsulationresistanceofacableifbothitscsaandlengthweredoubled?
a. Halvedb. Stayedthesamec. Doubledd. Quadrupled
26.WhichoneofthefollowingearthingsystemsincludesaPENconductor?
a. TTb. TN-Sc. ITd. TN-C-S
27.Whenconductinganearth electrode resistance testonagenerator electrode, anacceptable value should be the average of three readings and an instrumentaccuracyof:
![Page 134: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/134.jpg)
a. 100%b. >5%c. >2%d. ≤2%
28.Anexternalearthfaultloopimpedancetestmustbecarriedoutwiththeearthingconductor:
a. disconnectedandtheinstallationenergizedb. connectedandtheinstallationenergizedc. disconnectedandtheinstallationisolatedd. connectedandtheinstallationisolated
29. When conducting an earth fault loop impedance test on a radial circuit theearthingconductoroftheinstallationmustbe:
a. disconnectedandallprotectivebondingconductorsinplaceb. disconnectedandallprotectivebondingconductorsdisconnectedc. connectedandallprotectivebondingconductorsinplaced. connectedandallprotectivebondingconductorsdisconnected
30. Which one of the following would be the maximum value of Zs permitted toachievetherequireddisconnectiontime, foramaximummeasuredvalueofearthfaultloopimpedanceof1.15Ω?
a. 2.3Ωb. 1.92Ωc. 1.44Ωd. 0.92Ω
31. Which one of the following needs to be compensated for when comparingmeasuredvaluesofZswithmaximumtabulatedvalues?
a. Cablelengthb. Cablecsac. Changeintemperatured. Typeofprotectivedevice
32.ThevalueofZs tobe recorded for anearth fault loop impedance testona ringfinalcircuitisthevaluemeasuredatasocketoutlet:
a. nearestthedistributionboardb. thatgivesthehighestreading
![Page 135: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/135.jpg)
c. nearestthemidpointoftheringd. thatgivesthelowestreading
33. Which one of the following is the requirement for RCDs used for additionalprotection?
a. >30mAandtrippingin40msat5×IΔn
b. ≤30mAandtrippingin40msat5×IΔn
c. <30mAandtrippingin40msat5×IΔn
d. ≥30mAandtrippingin300msat5×IΔn
34.Whichoneof the following is themaximumtestcurrent required fora300mARCDinstalledforprotectionagainstfire?
a. 1500mAb. 300mAc. 100mAd. 30mA
35. Which one of the following is the rating of an RCD installed for additionalprotectionifthemaximumtestcurrentis100mA?
a. 100mAb. 30mAc. 20mAd. 10mA
36.Whenconductingaprospectivefaultcurrent testat theoriginofan installation,theearthingconductormustbe:
a. disconnectedb. linkedtotheneutralc. connectedd. excludedfromthetest
37.Aprospectivefaultcurrenttestattheoriginofathree-phaseinstallationgavethefollowingresults:PEFC–4.7kA;PSCC–5.5kA.Whichoneofthefollowingwouldberecordedonascheduleoftestresults?
a. 11kAb. 10.2kAc. 5.5kAd. 4.7kA
![Page 136: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/136.jpg)
38.ItisrecommendedthatafunctionaltestonanRCDviaitsintegraltestbutton,becarriedout:
a. annuallyb. half-yearlyc. everythreemonthsd. everyfourmonths
39.Disconnectiontimesexceedingthepermittedmaximumvaluesareadirectresultof:
a. insulationresistancevaluesapproachingtheirminimumb. poorlyconnectedmainprotectivebondingconductorsc. earthfaultloopimpedancevaluesexceedingBS7671requirementsd. earthfaultloopimpedancevaluesunacceptablylow
40.Aleakagecurrentof11mAbetweenLandEoccurringina230VcircuitwouldbetheresultofaL–Einsulationresistancevalueof:
a. 2.53MΩb. 0.02MΩc. 0.5MΩd. 1.0MΩ
![Page 137: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/137.jpg)
Answers
1b 11a 21b 31c2c 12d 22c 32b3c 13a 23c 33b4d 14c 24c 34b5b 15d 25a 35c6a 16b 26d 36c7c 17a 27d 37a8b 18c 28c 38c9d 19b 29c 39c10c 20d 30c 40b
![Page 138: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/138.jpg)
IndexPagenumbersinitalicsdenoteanillustration,boldindicatesatable
![Page 139: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/139.jpg)
A
additionalprotectionxi–xii,xv–xvi,55–8,56
additionsandalterations4,5,11,68,74
ambienttemperaturecorrection49
approvedtestlamp(voltageindicator)8,9
![Page 140: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/140.jpg)
B
barriersandenclosuresxix,35,36
basicprotectionxii,xv–xvi
BSfingertest35,36
BuildingRegulationsPartP4–5
![Page 141: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/141.jpg)
C
certification:competency5,73;documents2,5,73–6;observationcodes77
circuitbreakers13,59
City&Guilds2394course:sampleMCQpaper&answers95–103;samplepaper81–4,82–3;samplepaper(answers)89–91
City&Guilds2395course:sampleMCQpaper&answers95–103;samplepaper85–8,87;samplepaper(answers)92–4
ClassIIequipmentxvi
conductoroperatingtemperature49
conductorresistance49
continuityofprotectiveconductors17–20,18,19–20
continuityofringfinalcircuitconductors23–7,24–7,27
continuitytesters6
![Page 142: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/142.jpg)
D
dutyholdersxii,3–4
![Page 143: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/143.jpg)
E
earthelectroderesistance:earthfault loopimpedancetest44–5;electrodeinstallation42; potentialdivider42,43–4, 44;
resistancearea41–2,43;tester7
earthfaultloopimpedancetest:earthelectroderesistance44–5;earthfaultlooppath47,48;externalloopimpedanceZe
49;methodandcalculationprocess48–9,50–2
earth-freelocalequipotentialbondingxvii
Edisonscrewtypelampholder37
ElectricalInstallationCertificate(EIC)5,11,73–6,79
ElectricalInstallationConditionReport(EICR)2,5,69,73–4,76–7,79
electricalseparationxvii,xvii,xix
electricalsystemsandequipmentxii,3–4
ElectricityatWorkRegulations(EAWR)19893–4,9
electricshock:IPCodesxviii–xix;protectionmeasuresxv–xvii,xvii,xix;risklevelsxiii–xv,xiv
electricsystemsandequipment3–4
exposedconductivepartxii,xvi
extentandlimitations73–4
externalloopimpedanceZe49
extraneousconductivepartxii,xvi
![Page 144: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/144.jpg)
F
faultprotectionxi,xvi
functionaltesting63
![Page 145: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/145.jpg)
I
Icnrating59
IETwiringregulations2–3
initialverification2,11–14
inspectionschedule2,11,69,73,79
insulationresistance29–32,30,31
insulationresistancetester6
IPCodesxviii–xix,xix
![Page 146: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/146.jpg)
L
lightingcircuits20,37,38,38
LocalBuildingControlAuthority(LABC)4,5
loopimpedancetester7
low-resistance ohmmeters: protective conductors 18, 19–20, 19–20; ring final circuit conductors 23–7, 24–7, 27; test
instrument6
![Page 147: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/147.jpg)
M
meggeringseeinsulationresistance
MinorElectricalInstallationWorksCertificate(MEIWC)2,5,73–4,77–8
![Page 148: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/148.jpg)
N
non-conductinglocationxvi–xvii,35
non-statutoryregulations2–3
![Page 149: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/149.jpg)
P
periodicinspectionandtesting2,67–71
PeriodicInspectionReport(PIR)2
PFCtester8
phasesequenceindicator61,61
polarity37–8,38
potentialdivider42,43–4,44
prospectivefaultcurrent(PFC/PSCC)59
protectiveconductorsxiii
protectiveequipotentialbondingxvi
provingunit8
![Page 150: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/150.jpg)
R
radialsocketoutletcircuits38
RCDs:additionalprotectionxv–xvi;earthfaultloopimpedancetest45,49,55;operationaltest55–6,56;requirementsfor
protection56–8;testinstrument7
![Page 151: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/151.jpg)
S
SELVxv,31,31
statutoryregulationsxi,2
supplypolarity38
![Page 152: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/152.jpg)
T
testinstruments5–9,9
testresultsschedule2,11,69,73,74,78–9
testsequence:initialverification12–13;periodicinspectionandtesting67–70
![Page 153: 17th Edition IET Wiring Regulations Inspection, Testing and Certification - Brian Scaddan](https://reader034.fdocuments.net/reader034/viewer/2022042500/577c83291a28abe054b3d9f6/html5/thumbnails/153.jpg)
V
voltagedrop65,66