1783-in007_-en- p january 2010

32
Installation Instructions EtherNet/IP Copper Tap Catalog Number 1783-ETAP Topic Page Important User Information 2 North American Hazardous Location Approval 3 European Hazardous Location Approval 4 Environment and Enclosure 5 Preventing Electrostatic Discharge 6 About the 1783-ETAP EtherNet/IP Tap 6 Install the Tap 9 Use the Web Interface 21 Specifications 25 Additional Resources 29

Transcript of 1783-in007_-en- p january 2010

Installation Instructions

EtherNet/IP Copper Tap

Catalog Number 1783-ETAPTopic Page

Important User Information North American Hazardous Location Approval European Hazardous Location Approval Environment and Enclosure Preventing Electrostatic Discharge About the 1783-ETAP EtherNet/IP Tap Install the Tap Use the Web Interface Specifications Additional Resources

2 3 4 5 6 6 9 21 25 29

2 EtherNet/IP Copper Tap

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.WARNING

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.

IMPORTANT

ATTENTION

SHOCK HAZARD

Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be on or inside the equipment, for example a drive or motor, to alert people that surfaces may reach dangerous temperatures.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 3

North American Hazardous Location ApprovalThe following information applies when operating this equipment in hazardous locations.Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Informations sur lutilisation de cet quipement en environnements dangereux.Les produits marqus CL I, DIV 2, GP A, B, C, D ne conviennent qu' une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livr avec des marquages sur sa plaque d'identification qui indiquent le code de temprature pour les environnements dangereux. Lorsque plusieurs produits sont combins dans un systme, le code de temprature le plus dfavorable (code de temprature le plus faible) peut tre utilis pour dterminer le code de temprature global du systme. Les combinaisons d'quipements dans le systme sont sujettes inspection par les autorits locales qualifies au moment de l'installation. AVERTISSEMENT

WARNING

EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. Substitution of components may impair suitability for Class I, Division 2. If this product contains batteries, they must be changed only in an area known to be nonhazardous.

RISQUE DEXPLOSION Couper le courant ou s'assurer que l'environnement est class non dangereux avant de dbrancher l'quipement. Couper le courant ou s'assurer que l'environnement est class non dangereux avant de dbrancher les connecteurs. Fixer tous les connecteurs externes relis cet quipement l'aide de vis, loquets coulissants, connecteurs filets ou autres moyens fournis avec ce produit. La substitution de composants peut rendre cet quipement inadapt une utilisation en environnement de Classe I, Division 2. S'assurer que l'environnement est class non dangereux avant de changer les piles.

WARNING

An electrical arc can occur: if you connect or disconnect the communication cable with power applied to this device or any device on the network. if you connect or disconnect wiring while the field-side power is on. These actions could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Publication 1783-IN007B-EN-P - January 2010

4 EtherNet/IP Copper Tap

European Hazardous Location ApprovalATTENTION

European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking): This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.

WARNING

This equipment must be installed in an enclosure providing at least IP54protection when applied in Zone 2 environments.

This equipment shall be used within its specified ratings defined byRockwell Automation:.

Provision shall be made to prevent the rated voltage from being exceededby transient disturbances of more than 40% when applied in Zone 2 environments. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product. Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.ATTENTION

This equipment is not resistant to sunlight or other sources of UV radiation.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 5

Environment and EnclosureATTENTION

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see: Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for additional installation requirements. NEMA Standards 250, and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures.

Publication 1783-IN007B-EN-P - January 2010

6 EtherNet/IP Copper Tap

Preventing Electrostatic DischargeATTENTION

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. Use a static-safe workstation, if available. Store the equipment in appropriate static-safe packaging when not in use.

About the 1783-ETAP EtherNet/IP TapThe 1783-ETAP EtherNet/IP tap provides EtherNet/IP connectivity. Use the tap to support linear, star, and device-level ring (DLR) topologies. The tap is configured by default to support linear, star, and ring (as non-supervisor ring node) topologies.IMPORTANT

When setting up a DLR, follow the steps in the Use the Tap in a Device-level Ring (DLR) Network section on page 16 to avoid adversely impacting your network.

Refer to the EtherNet/IP Ring Topology Application Guide, publication ENET-AP005, for information on setting up EtherNet/IP network topologies.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 7

2 1

10 9 8

3

7 6 A B 5 Item 1 Description DIP switches Refer to Set the DIP Switches on page 17. Top view Side view DC connector Bottom view Item 6 Description Ports for connection to linear or ring network A: Port 1 B: Port 2 Front view MAC ID label Device port on front panel Status indicators 4

2 3 4 5

7 8 9 10

Publication 1783-IN007B-EN-P - January 2010

8 EtherNet/IP Copper Tap By default, the individual ports on the tap auto-negotiate link speeds (10 Mbps or 100 Mbps) and duplex (full or half).IMPORTANT

The device you connect to a tap should have its Ethernet port configured to match the taps speed and duplex settings. Failure to make the speed and duplex settings of directly connected devices match may result in higher error rates, or loss of network connectivity.

Software RequirementsYou must have the following versions of software.Software RSLinx Classic RSLogix 5000 Version 2.56 or later 17.01 or laterIf you are using version 17.01, you need version 2.x of the add-on profile. Download it from http://www.rockwellautomation.com/support/downloads.html.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 9

Install the TapFollow these procedures to install the tap.WARNING

For hazardous location applications, use the supplied Phoenix MSTB 2.5/2-ST-5.08 power terminal block.

IMPORTANT

When mounting the tap, allow a minimum clearance between product and adjacent equipment of 2.54 cm (1 in.) on all sides.

DIN Rail MountingTo install the tap on a DIN rail, proceed as follows. 1. Mount your DIN rail. 2. Use a flat-bladed screwdriver to open the latch at the bottom of the tap. 3. Hook the latch over the DIN rail while holding the latch open with your screwdriver. 4. Remove the screwdriver and push the latch to close.

Publication 1783-IN007B-EN-P - January 2010

10 EtherNet/IP Copper Tap The top figure shows using a screwdriver to open the latch so that you can remove the tap from the DIN rail. The bottom figure shows the latch at the bottom of the tap in the open position.

Panel MountingTo panel mount a tap, proceed as follows. 1. Use the tap as a template and mark pilot holes on your panel. 2. Drill the pilot holes for M4 or #8 screws.

Wire the TapWARNING

An electrical arc can occur: if you connect or disconnect the communication cable with power applied to this module or any device on the network. if you connect or disconnect wiring while the field-side power is on. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 11To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV). To comply with UL restrictions, this equipment must be powered from a source compliant with Class 2 or Limited Voltage/Current.

ATTENTION

Provide DC power to the tap by using the DC connector at the bottom of the tap.WARNING

For hazardous location applications, use the supplied Phoenix MSTB 2.5/2-ST-5.08 power terminal block.

ATTENTION

Do not wire more than two conductors on any single terminal.

1

2 3

Item 1 2 3

Description Tap bottom DC- (0V DC) terminal DC+ (24V DC nom.) terminal

Publication 1783-IN007B-EN-P - January 2010

12 EtherNet/IP Copper Tap

Grounding ConsiderationsThis product is intended to be mounted to a well-grounded mounting surface such as a metal pane or DIN rail.ATTENTION

This product is grounded through the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure the DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.

Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional information.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 13

Connect the Copper Ethernet PortsFollow these steps to connect the copper Ethernet ports on the tap. 1. Locate the copper Ethernet RJ45 ports on the front and bottom of the tap, as shown in the figure.

1

2

Item 1 2

Description Device port on tap front panel Ports on tap bottom for connection to the linear or ring network

2. Connect one end of an Ethernet cable to the front panel port used as a device port. 3. Connect the other end of the Ethernet cable to the appropriate device in your network.

Publication 1783-IN007B-EN-P - January 2010

14 EtherNet/IP Copper Tap 4. Connect one end of an Ethernet cable to a port at the bottom of the tap and connect the other end of the Ethernet cable to the linear or ring network, repeating with the other port at the bottom of the tap, if used by your network.IMPORTANT

When setting up a DLR, follow the steps in the Use the Tap in a Device-level Ring (DLR) Network section on page 16 to avoid adversely impacting your network.

Download the Tap Add-on Profile (AOP) [RSLogix 5000 Software Version 17.01 Only]If you are using RSLogix 5000 software, version 17.01, you need version 2.x of the AOP. Follow these steps to download the AOP. 1. Locate the tap AOP at http://www.rockwellautomation.com/support/downloads.htmlIMPORTANT

You need a Rockwell Automation MySupport account to download the AOP. If you do not have one, follow the steps on the MySupport website to obtain an account.

2. Click on the desired file to download it. 3. Enter your RSLogix 5000 software serial number and click Qualify for Update. 4. Download and extract the zipped files to a temporary directory. 5. Shut down any instances of RSLogix 5000 that are currently running. 6. In the temporary directory, double-click the MPSetup.exe file and follow the onscreen instructions to install the AOP.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 15

Download the EDS FileFollow these steps to download the EDS file for the tap. 1. Obtain the EDS file from http://www.rockwellautomation.com/resources/eds/. 2. In the Network field, Select the EtherNet/IP network. 3. In the Device Type field, select Communication Adapter. 4. In the Bulletin/catalog number field, enter 1783-ETAP. 5. Click Search. 6. Click Download to download the EDS file for the tap. 7. Save the file to an appropriate location on your computer. 8. Use your configuration software to register the downloaded file. a. If you are using RSLinx Classic software, use the EDS Hardware Installation Tool. b. Click Start>All Programs>Rockwell Software>RSLinx>Tools.

Publication 1783-IN007B-EN-P - January 2010

16 EtherNet/IP Copper Tap

Use the Tap in a Device-level Ring (DLR) NetworkFollow these steps to configure the tap as a ring supervisor in a DLR network.IMPORTANT

If using a tap for a linear network or as a non-supervisor in a ring, you do not need to configure the tap.

1. Follow the procedures outlined in the online help that accompanies RSLinx Classic or RSLogix 5000 software to enable the ring supervisor function with this software.IMPORTANT

Make sure at least one ring supervisor is present before connecting thelast link of a device-level ring network and physically closing the ring.

Do not connect nodes that do not support a device-level ring asmembers of the ring.

DIP Switch 3 lets you enable the ring supervisor by using the settingspresent in the tap non-volatile storage (NVS). Refer to Set the DIP Switches on page 17.

2. Refer to the EtherNet/IP Ring Topology Application Guide, publication ENET-AP005 for information on setting up EtherNet/IP network topologies.

Set the IP AddressConfigure the IP address in one of these ways: Use the default out-of-the-box IP address of 169.254.1.1 by connecting to your computer. Configure the DIP switches at the top of the tap to use either a DHCP server or a BOOTP server.TIP

After connecting with the out-of-box IP address or an address obtained by using a DHCP server or a BOOTP server, the RSLinx Classic or RSLogix 5000 software may be used to configure a static IP address that can be stored in non-volatile memory.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 17

Set the DIP SwitchesFollow this procedure to set the DIP switches. 1. Move the switches to the desired position and cycle power to the tap.IMPORTANT

The switch settings take effect only at power up. The tap's behavior will not be modified by switch changes until the tap is power cycled.

2. Refer to the illustration and table for DIP switch settings.Off On Switch 3 Switch 2 Switch 1

Switch 1Off

2Off

3Off

Power-up/Reset Behaviors

Use Internet Protocol settings configured by software (stored in tap non-volatile storage [NVS] or factory default IP address of 169.254.1.1.). Default. Use settings configured by software to enable ring supervisor and other ring configuration parameters stored in the taps NVS. Use Internet Protocol settings configured by software (stored in tap non-volatile storage [NVS] or factory default IP address of 169.254.1.1.). Enables the ring supervisor capability, and all other supervisor settings, using the settings present in the taps NVS.(1)

On

Publication 1783-IN007B-EN-P - January 2010

18 EtherNet/IP Copper TapSwitch 1On

2Off

3Off

Power-up/Reset Behaviors

Use BOOTP to acquire the Internet Protocol settings. Default. Use settings configured by software to enable ring supervisor and other ring configuration parameters stored in the taps NVS. Use BOOTP to acquire the Internet Protocol settings. Enables the ring supervisor capability, and all other supervisor settings, using the settings present in the taps NVS.(1)

On

Off

On

Off

Use DHCP to acquire the Internet Protocol settings. Default. Use settings configured by software to enable ring supervisor and other ring configuration parameters stored in the taps NVS. Use DHCP to acquire the Internet Protocol settings. Enables the ring supervisor capability, and all other supervisor settings, using the settings present in the taps NVS.(1)

On

(1)

These switch settings cause the described power-up/reset behavior only for 1783-ETAP taps using firmware revision 2.x or later. If you set the switches as described here on a 1783-ETAP tap with firmware revision 1.x, the described power-up/behavior does not occur.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 19 3. Observe these guidelines on use of the DIP switches: In the out-of-box position, all three switches are in the off position. This is the software settable position. The tap will use either the default IP settings or the IP configuration last programmed with software. When the switch is pushed to the left, it is in the off (unused) position When the switch is pushed to the right, it is in the on (in use) position. To select DHCP, move the middle switch (switch 2 in the figure) to the right to the on position. To select BOOTP, move the switch closest to the tap front panel (switch 1 in the figure) to the right to the on position. To enable the Ring Supervisor function (using the DLR configuration parameters stored in NVS), move the switch closest to the tap rear panel (switch 3 in the figure) to the right to the on position. To restore factory default settings, move the middle switch (switch 2 in the figure) and the switch closest to the tap front panel (switch 1 in the figure) to the right to the unlocked (on) position. When both switch 1 and 2 are to the right, the position of switch 3 is ignored. When both the middle switch (switch 2 in the figure) and the switch closest to the tap front panel (switch 1 in the figure) are moved to the right to the unlocked (on) position, the tap resets all configuration settings to factory defaults, suspends operation, and the OK status indicator blinks red. To resume normal operation, move the switches to the desired positions and cycle power to the module. Publication 1783-IN007B-EN-P - January 2010

20 EtherNet/IP Copper Tap

Use DHCP/BOOTP ServerIf your network infrastructure does not provide DHCP/BOOT functionality, you may download our DHCP/BOOTP server software to a personal computer running the Microsoft Windows operating system. To set the network address by using the Rockwell Automation DHCP/BOOTP server, follow these steps. 1. Access the DHCP/BOOTP utility at http://www.ab.com/networks/ethernet/bootp.html. 2. Download the version 2.3.2 DHCP/BOOTP utility. 3. Extract the zipped files to a temporary directory. 4. In the temporary directory, double-click setup.exe to install the DHCP/BOOTP utility. 5. Run the utility. 6. Refer to the following chart, which describes what happens next, depending on whether DHCP/BOOTP is enabled on the tap.The tap Asks for an address from a DHCP/BOOTP server. Consult the online help available in the BOOTP/DHCP application to configure the server to provide the desired IP address for your tap. Uses the IP settings stored in nonvolatile memory.

If DHCP/BOOTP is Enabled

Not enabled

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 21

Use the Web InterfaceThe tap supports a Web interface that provides diagnostic read-only information. Follow these steps to access the Web page. 1. Connect a computer to any of the taps Ethernet ports. 2. Browse to the tap by entering the taps IP address (the out-of-the-box default is 169.254.1.1) in your Web browsers address bar.TIP

If you configure the tap with an IP address, you can also access the tap Web page from any computer connected to the network.

3. Click Enter. You see the 1783-ETAP tap page, which provides general information about the tap.

Publication 1783-IN007B-EN-P - January 2010

22 EtherNet/IP Copper Tap 4. In the left pane, click Diagnostics. You see links to these pages: Diagnostic Overview Network Settings Ethernet Statistics Ring StatisticsContains information on

This Web page Diagnostic Overview

Module resource utilization Web server read and write hits Module settings Ring status Network management features subnet mask

Network Settings

Network interface details, such as IP address & Ethernet Interface configuration method Ethernet port details

Ethernet Statistcs

Ethernet counters Ethernet port details Error informationRing supervisor, configuration, and fault details

Ring Statistics

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 23

Status Indicators

Indicator OK

Status Off Flashing green Solid green Flashing red Solid red

Description Tap is not powered. Tap is not configured. Tap is powered, configured, and operating correctly. Recoverable fault, such as duplicate IP address or flash update in progress, is detected. Unrecoverable fault detected.

Publication 1783-IN007B-EN-P - January 2010

24 EtherNet/IP Copper TapIndicator LINK1, LINK2 Status Off Description One of these conditions exists:

No link. Port administratively disabled. Port disabled because of rapid ring faultcondition, and this tap is the active ring supervisor (LINK 2).

Ring network has encountered a rare, partialnetwork fault, and this tap is the active supervisor (LINK 2). Green One of these conditions exists: A 100 Mbps (full or half duplex) link exists. The ring network is operating normally and this tap is the active supervisor (LINK 2). A 100 Mbps link exists and there is activity. One of these conditions exists: A 10 Mbps (full or half duplex) link exists.

Flashing green Solid yellow

Ring network is operating normally, and this tap isthe active supervisor (LINK 2). Flashing yellow A 10 Mbps link exists and there is activity.

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 25

SpecificationsTechnical Specifications - 1783-ETAPAttribute Enclosure type rating Current consumption, max. DC power supply voltage rating Isolation voltage 1783-ETAP None (open-style) 125 mA @ 24V DC 24V DC (20.4...27.6V DC) 30V (continuous), Basic Insulation Type, Network channels to Power and Network channels to Network channels Type tested at 1250V DC for 60 s 3W 3W Ethernet connections: RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e minimum cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702 DC Power connections: One 0.333.3 mm2 (2212 AWG) or two 0.331.3 mm2 (2216 AWG) solid or stranded copper wire(s) rated at 75 C (167 F) or greater, 1.2 mm (3/64 in.) insulation max Torque Dimensions HxWxD approx. Wiring Category(1)

Power consumption, max. Power dissipation Wire Size

0.60.8 Nm (57 lbin) on power connectors 132 x 56.7 x 35.6 mm (5.20 x 1.4 x 4.14 in.) 1 - on power ports 2 - on communications ports T5 T5

North American Temp Code IEC Temp Code(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1783-IN007B-EN-P - January 2010

26 EtherNet/IP Copper TapEnvironmental Specifications - 1783-ETAPAttribute 1783-ETAP

Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) Voltage variation IEC 61000-4-29 Vibration IEC 60068-2-6 (Test Fc, Operating) Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock): Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) Emissions CISPR 11

-2570 C (-13158 F)

-4085 C (-40185 F)

595% noncondensing

10 ms interruption on DC supply ports 5 g @ 10500 Hz 30 g

50 g

Group 1, Class A

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 27Environmental Specifications - 1783-ETAPAttribute 1783-ETAP

ESD immunity IEC 61000-4-2 Radiated RF immunity IEC 61000-4-3

6 kV contact discharges 8 kV air discharges 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz 4 kV at 5 kHz on power ports 3 kV at 5 kHz on communication ports 1 kV line-line(DM) and 2 kV line-earth(CM) on power ports 2 kV line-earth(CM) on communication ports 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz

EFT/B immunity IEC 61000-4-4 Surge transient immunity IEC 61000-4-5

Conducted RF immunity IEC 61000-4-6

Publication 1783-IN007B-EN-P - January 2010

28 EtherNet/IP Copper TapCertifications - 1783-ETAP Certification 1783-ETAP

When product is marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity

CE

EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause8, Zone A & B) C-Tick Ex Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n

EN 60079-0; General Requirements II 3 G Ex nA IIC T5XEtherNet/IP ODVA conformance tested to EtherNet/IP specifications

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 29

Additional ResourcesThese documents contain additional information concerning related Rockwell Automation products.Resource EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001 EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005 Description Provides details about how to configure your module. Provides information about using products with embedded switch technology to construct networks with linear and ring topologies. Describes how to implement services and data objects on a TCP/UDP/IP based Ethernet network. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details.

EtherNet/IP Industrial Protocol White Paper, publication ENET-WP001 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com

You can view or download publications at http://www.rockwellautomation.com/literature. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.

Publication 1783-IN007B-EN-P - January 2010

30 EtherNet/IP Copper Tap

Notes:

Publication 1783-IN007B-EN-P - January 2010

EtherNet/IP Copper Tap 31

Notes:

Publication 1783-IN007B-EN-P - January 2010

Rockwell Automation SupportRockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support.

Installation AssistanceIf you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.United States Outside United States 1.440.646.3434 Monday Friday, 8 a.m. 5 p.m. EST Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction ReturnRockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor in order to complete the return process. Please contact your local Rockwell Automation representative for the return procedure.

Outside United States

Allen-Bradley, RSLinx, RSLogix, Rockwell Automation, Rockwell Software, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1783-IN007B-EN-P - January 2010

PN-58118

Copyright 2010 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.