    ProcessLogixFunction BlockParameters

    1757 Series

    Reference Manual

  • 8/10/2019 1757-rm811_-en-p

    2/282

  • 8/10/2019 1757-rm811_-en-p

    3/282

    Important User Information Because of the variety of uses for the products described in thispublication, those responsible for the application and use of theseproducts must satisfy themselves that all necessary steps have beentaken to assure that each application and use meets all performanceand safety requirements, including any applicable laws, regulations,codes and standards. In no event will Allen-Bradley be responsible

    or liable for indirect or consequential damage resulting from the useor application of these products.

    Any illustrations, charts, sample programs, and layout examplesshown in this publication are intended solely for purposes ofexample. Since there are many variables and requirements associated

    with any particular installation, Allen-Bradley does not assumeresponsibility or liability (to include intellectual property liability) foractual use based upon the examples shown in this publication.

    Allen-Bradley publication SGI-1.1, Safety Guidelines for theApplication, Installation and Maintenance of Solid-State Control

    (available from your local Allen-Bradley office), describes someimportant differences between solid-state equipment andelectromechanical devices that should be taken into consideration

    when applying products such as those described in this publication.

    Reproduction of the contents of this copyrighted publication, inwhole or part, without written permission of Rockwell Automation, isprohibited.

    Throughout this publication, notes may be used to make you awareof safety considerations. The following annotations and theiraccompanying statements help you to identify a potential hazard,avoid a potential hazard, and recognize the consequences of a

    potential hazard:

    Allen-Bradley is a trademark of Rockwell Automation

    WARNING

    !

    Identifies information about practices orcircumstances that can cause an explosion in ahazardous environment, which may lead to personalinjury or death, property damage, or economic loss.

    ATTENTION

    !

    Identifies information about practices orcircumstances that can lead to personal injury or

    death, property damage, or economic loss.

    IMPORTANTIdentifies information that is critical for successfulapplication and understanding of the product.

  • 8/10/2019 1757-rm811_-en-p

    4/282

    Rockwell AutomationSupport

    Rockwell Automation offers support services worldwide, with over 75sales/support offices, 512 authorized distributors, and 260 authorizedsystems integrators located throughout the United States alone, plusRockwell Automation representatives in every major country in the

    world.

    Local Product Support

    Contact your local Rockwell Automation representative for:

    sales and order support

    product technical training

    warranty support

    support service agreements

    Technical Product Assistance

    If you need to contact Rockwell Automation for technical assistance,first call your local Rockwell Automation representative, then:

    Post-sales Technical Support, 440.646.5800

    Web Links, http://www.ab.com

    Your Questions or Comments on this Manual

    If you find a problem with this manual, please notify us of it on theHow Are We Doing? form at the back of this manual.

  • 8/10/2019 1757-rm811_-en-p

    5/282

    v Publication 1757-RM811A-EN-P - May 2002

    Table of Contents

    Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . iiiRockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . iv

    Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . ivTechnical Product Assistance . . . . . . . . . . . . . . . . . . . . . iv

    Your Questions or Comments on this Manual . . . . . . . . . iv

    Preface Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viiParameter Attriubutes. . . . . . . . . . . . . . . . . . . . . . . . . . . vii

    Function Block Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    Appendix A

    Display Elements Appendix Group Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . A-1Detail Display Elements. . . . . . . . . . . . . . . . . . . . . . . . . . . A-3

    Appendix B

    Allen-Bradley Interface Appendix Array Channel Block Configuration forAllen-Bradley Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

    About Allen-Bradley Interface. . . . . . . . . . . . . . . . . . . . B-1AUXDATA Parameter Configuration . . . . . . . . . . . . . . . B-1AUXDATA[6] Parameter Setting Details . . . . . . . . . . . . . B-3DEVADDR Parameter Configuration . . . . . . . . . . . . . . . B-5STARTINDEX and Number of Elements Parameter. . . . . B-6Report by Exception Requirements . . . . . . . . . . . . . . . . B-7Performance Considerations . . . . . . . . . . . . . . . . . . . . . B-8

    Array Channel Block Execution State . . . . . . . . . . . . . B-10

    Write processing considerations . . . . . . . . . . . . . . . . . B-11Diagnostic procedures and data configuration. . . . . . . B-11Time-Out gate configuration. . . . . . . . . . . . . . . . . . . . B-14Status and error checking. . . . . . . . . . . . . . . . . . . . . . B-15Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-15Special FTA to KE/KF cabling considerations . . . . . . . B-17FTA direct to PLC-5 RS-232 Port cable considerations: . B-18Reference Specifications. . . . . . . . . . . . . . . . . . . . . . . B-19

    Appendix C

    MODBUS Interface Appendix Array Channel Block Configuration for

    Generic MODBUS Interface. . . . . . . . . . . . . . . . . . . . . . . . C-1About Generic Modbus Interface . . . . . . . . . . . . . . . . . C-1AUXDATA Parameter Configuration . . . . . . . . . . . . . . . C-1STARTINDEX and Number of Elements Parameter. . . . . C-2Modbus loopback diagnostic . . . . . . . . . . . . . . . . . . . . C-4Performance Considerations . . . . . . . . . . . . . . . . . . . . . C-4

    Array Channel Block Execution State . . . . . . . . . . . . . . C-6Write Processing Considerations. . . . . . . . . . . . . . . . . . C-6Status and Error Checking . . . . . . . . . . . . . . . . . . . . . . C-7

  • 8/10/2019 1757-rm811_-en-p

    6/282

    Publication 1757-RM811A-EN-P - May 2002

    vi

    Error Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-7Special Modbus Slave FTA Implementation . . . . . . . . . . C-9Reference Specifications. . . . . . . . . . . . . . . . . . . . . . . C-10

  • 8/10/2019 1757-rm811_-en-p

    7/282

  • 8/10/2019 1757-rm811_-en-p

    8/282

    Publication 1757-RM811A-EN-P - May 2002

    Preface viii

    Data Type

    Multiple data types are supported in ProcessLogix. See Table P.2for alisting and description of these data types.

    Table P.2 Supported Parameter Data Types

    Boolean Enumeration

    32-Bit Real Number Connection

    64-Bit Real Number Output Connection

    16-Bit Integer Input Connector

    32-Bit Integer Structure

    Constant Integer Float

    8-Bit Unsigned Integer Float64/Real64

    16-Bit Unsigned Integer String

    32-Bit Unsigned Integer TIME

    BlockId(1)/ Entity ID

    (1) BlockId - A BlockId parameter value is text describing a block s name. Example BlockId values are

    SCM3.Step7and SCM7.

    Self-Defining Enumeration(2)

    (2) Self-Defining Enumeration (SDEnum) - This data type is just like an Enumeration, except the enumeration

    members are user-defined. Parameter A being an SDEnum of B means that B (String data type) defines the

    enumeration members for A (SDEnum data type).

    TIP The numerical suffixes - 16, 32, and 64 - indicate thenumber of memory bits used to store the value;

    Real32 is commonly called single-precision, andReal64 is double-precision. The difference in theIntegers is just the supported range of values.

  • 8/10/2019 1757-rm811_-en-p

    9/282

    Publication 1757-RM811A-EN-P - May 2002

    Preface ix

    Access Lock

    The ProcessLogix system supports six access levels. Each parameterincludes an Access Lock attribute that defines what access level a

    program or operator must have in order to change the value of theparameter. See Table P.3for lists of these access levels and to see therelationship between the access lock and the access level.

    Table P.3 Supported Parameter Access Lock Levels

    AccessLock

    Access Level

    Operator Supervisor Engineer Program ContinuousControl

    ApplicationsDeveloper

    Operator X X X X X X

    Supervisor X X X X X

    Engineer X X X X

    ViewOnly

    ApplicationsDeveloperOnly

    X

    Engineer/ApplicationsDeveloper

    X X

    Program X X X

    Other

    FunctionBlock

    X X

    Control X

    Engineer Only X

  • 8/10/2019 1757-rm811_-en-p

    10/282

    Publication 1757-RM811A-EN-P - May 2002

    Preface x

    Residence

    Parameters in ProcessLogix control strategies may reside in severalplaces. See Table P.4for a listing and definition of the valid

    residences.Table P.4 Parameter Residences

    Residence Description

    CEE(Control ExecutionEnvironment)

    Supports execution of a set of function blocks for solving controlapplications. It runs in the Hybrid Controller as a software layerbuilt on top of the control software infrastructure.

    SR(System Repository)

    The file where all ProcessLogix server point data is stored.

    ProcessLogix Server ProcessLogix server:Parameters resident at the server control how data for the point isaccessed or viewed by the operator, using the ProcessLogix Station

    software.

    TIP All ProcessLogix parameters have attributes and/orvalues stored within the Engineering Repository. Inaddition, parameters of loaded blocks are stored inone or more locations. These Repositories are theProcessLogix Run Time Repositories; SR, CEE andserver. Location within one or more of the Run TimeRepositories is described by the residency parameter

    attribute.

  • 8/10/2019 1757-rm811_-en-p

    11/282

    Function Block Parameters

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

    ABORTALM.FL SCM Abort Alarm Flag Boolean Off (0)On (1)

    Off (0) No View Only CEE No ABORABORSTAT

    ABORTALM.PR SCM Abort State AlarmPriority - Specifiesthe alarm priority forthe Abort alarm

    EnumerationALPRIOR

    None (0)Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer/ApplicationDeveloper

    CEE No ABORABOR

    ABORTALM.SV SCM Abort State AlarmSeverity - Specifiesthe alarm severityfor the Abort alarm.

    16-Bit Integer 0 to 15 0 Yes Engineer CEE No ABORABOR

    ABORTLOCK SCM Abort CommandAccess Lock

    EnumerationCSCOACCLOCK

    Operator (0)Engineer (1)View Only (2)OtherFB (3)

    Engineer(1)

    Yes Engineer CEE No COM

    ACCDEV.FL [1..4] Totalizer, PulseInput Totalizer

    AccumulatorDeviation Flag -Indicates when anaccumulatordeviation trip point(ACCDEV.TP [1-4])has been reached.There is one flag pertrip point.

    Boolean Off (0):ACCDEV.TP [n]is less than orequal toACCTV PVOn (1):ACCDEV.TP [n]is greater thanor equal toACCTV PV

    Off (0) No View Only CEE No ACCDACCT

  • 8/10/2019 1757-rm811_-en-p

    12/282

    ACCDEV.TP [1..4] Totalizer AccumulatorDeviation Trip Point -Used to determinewhen theaccumulated value(PV) is getting "near"the target value

    (ACCTV). Trip pointvalues areexpressed asdeviations from thetarget value.

    64-Bit RealNumber

    NaN, orgreater thanor equal to0.0.

    NaN Yes Engineer CEE No ACCDACCT

    Pulse InputTotalizer

    AccumulatorDeviation Trip Point -Used to determinewhen theaccumulated value(PV) is getting nearthe target value(ACCTV). Trip pointvalues areexpressed asdeviations from the

    target value.

    Real NaN orgreater-thanor equal to 0.0

    NaN Yes Engineer CEE No >ACCACCT

    Flag, NumericFLAGARRAY,NUMERICARRAY,TEXTARRAYSIFLAGARRCH,SINUMARRCH,SITEXTARRCH

    Access Lock -Specifies who canchange the Flagfunction blocksstate (using PV andPVFL), and who canchange the Numericfunction blocksvalue (PV).

    EnumerationACCLOCK

    Operator (0)Engineer (1)OtherFB (2)

    Operator(0)

    Yes Engineer CEE No NumeFlag oFLAGPVFL [1..12NUMonly: SI Ch[1..64STR [

    ACCTV Totalizer Accumulator TargetValue - Specifies thetarget value of theaccumulator.

    64-Bit RealNumber

    NaN, orgreater-thanor equal-to 0.

    0 Yes Operator CEE No PV, AACCDACCD

    Pulse InputTotalizer

    Accumulator TargetValue Specifiesthe target value ofthe accumulator.

    64-Bit RealNumber

    NaN, orgreater-thanor equal-tozero

    0 Yes Operator CEE No PV, AACCDACCD

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    13/282

    ACCTVFL Totalizer Accumulated-Target-Value Reached Flag- The "targetreached" flag for theTotalizer functionblock. It indicates ifthe present variable

    (PV) has reached thetarget value[ACCTV].

    Boolean Off (PV is lessthan ACCTV)On (PV isgreater thanor equal toACCTV)

    No View Only CEE No PV, A

    Pulse InputTotalizer

    Accumulated-Target-Value Reached Flag- The "targetreached" flag for theTotalizer functionblock. It indicates ifthe present variable(PV) has reached thetarget value(ACCTV).

    Boolean Off (0): PV isless-thanACCTVOn (1) PV isgreater-thanor equal-toACCTV

    No View Only CEE No PV, A

    ACTIVEFL Step Step Active Flag Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    ACTIVEHANDLR[1..8]

    SCM Active Handler TypeFlag

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No ACTIVR,ACTIVRN,ACTIVE, AC[1..10ACTIV[1..10ACTIV[1..10

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    14/282

    ACTIVELOC.HANDLER

    SCM Active HandlerName

    BlockId NullString

    No View Only CEE No ACTIVRN

    ACTIVELOC.HANDLERN

    SCM Active HandlerName

    32-Bit Integer NullString

    No View Only CEE No ACTIVR

    ACTIVELOC.HNDTYPE

    SCM Active Handler Type 32-Bit Integer 0 to 8 0 No View Only CEE No TYPE

    ACTIVELOC.STEP [1..10]

    SCM Active Step Name BlockId NullString

    No View Only CEE No ACTIV[1..10

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    15/282

    ACTIVELOC.STEPN [1..10]

    SCM Active Step Name 32-Bit Integer Null String No View Only CEE No ACTIV[1..10

    ACTIVELOC.TIME [1..10]

    SCM Active Step Time 32-Bit Integer 0 to2147483647

    0 No View Only CEE No PERIOSTEP

    ACTRAMPRATE[1..NUMPROFILES][1..NUMRAMPSOAK]

    RampSoak Actual Ramp Rate (inEUs per min) - Thereis one ramp rate perRamp/Soak pair ofeach profile.

    Real NaN No View Only CEE No Ramp

    ACTSOAKTIME[1..NUMPROFILES][1..NUMRAMPSOAK]

    RampSoak Actual Soak Time (inMinutes) - There isone soak time perRamp/Soak pair.

    Real 0.0 to 120.0 0.0 No View Only CEE No NUMNUM[1..NACTR[1..N[1..N, ACT[1..N[1..N, ACT[1..NACTS[1..N

    ACTSOAKVAL[1..NUMPROFILES]

    [1..NUMRAMPSOAK]

    RampSoak Actual Soak Value -There is one soakvalue per

    Ramp/Soak pair.

    Real NaN No View Only CEE No NUMNUM[1..N

    ACTS[1..N[1..N, ACT[1..N[1..N, ACT[1..NACTS[1..N

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    16/282

    ACTSTARTOP[1..NUMPROFILES]

    RampSoak Actual StartingOutput Value

    Real 0 ViewOnly

    No CEE No NUMNUM[1..NACTS[1..N[1..N, ACT

    [1..N[1..N, ACT[1..N[NUMACTS[1..N

    ACTSTARTSEG[1..NUMPROFILES]

    RampSoak Actual StartingSegment ID

    Real 0 ViewOnly

    No CEE No NUMNUM[1..NACTS[1..N[1..N, ACT[1..N[1..N

    , ACT[1..N[1..N, ACT[1..N

    ACTVTNTIME Step Activation Time Integer No View Only CEE

    ADVDEVALM.DB PID, PIDFF, PosProp Advisory DeviationAlarm Deadband

    64-Bit RealNumber

    0.0 to 100.0 ifalarmdeadbandunits(ADVDEVALM.DBU) arePercentGreater-thanor equal-to 0.0if alarmdeadbandunits(ADVDEVALM.DBU) areEngineeringUnits

    0.0 Yes Operator CEE No ADVD

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    17/282

    ADVDEVALM.DBU

    PID, PIDFF, PosProp Advisory DeviationAlarm DeadbandUnits - Indicates ifADVDEVALM.DB isin Percent orEngineering Units.

    EnumerationALMDBU

    Percent (0)EU(1)

    Percent(0)

    Yes Engineer CEE No ADVD

    ADVDEVALM.FL PID, PIDFF, PosProp Advisory DeviationAlarm Flag -Indicates if anadvisory alarm hasbeen detected

    Boolean Off (0) (not inAdvisoryDeviationalarm)On (1) (inAdvisoryDeviationalarmcondition)

    Off (0) No View Only CEE No

    ADVDEVALM.PR PID, PIDFF, PosProp Advisory DeviationAlarm Priority -Defines the priorityof an advisorydeviation alarm.

    EnumerationALPRIOR

    None (0)Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer CEE No

    ADVDEVALM.SV PID, PIDFF, PosProp Advisory DeviationAlarm Severity

    16-Bit Integer 0 to 255 0 Yes Engineer CEE No

    ADVDEVALM.TM PID, PIDFF, PosProp Advisory DeviationAlarm Filter Time (inseconds) Thepurpose of thisvariable is to preventinput spikes fromcausing alarms.

    DeltaTime 0 to 60 0 Yes CEE No ADVDEVALM.TP

    If ADequawill bsoon deviathe tr

    ADVDEVALM.TP PID, PIDFF, PosProp Advisory DeviationAlarm Trip Point (inEngineering Units) -An alarm will begenerated when thedifference betweenthe process variable(PV) and Advisory

    Setpoint value(ADVSP) exceeds thevalue in thisvariable.

    64-Bit RealNumber

    NaN, orgreater-thanor equal-tozero.

    NaN Yes Operator CEE No PV, A

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    18/282

    ADVDEVOPT PID, PIDFF, PosProp Advisory DeviationOption - Indicates ifadvisory deviationalarming isrequested.

    EnumerationENBSTATE

    Enable (0):Advisorydeviationalarming isrequestedDisable (1):Advisory

    deviationalarming isnot requested

    Enable (0) Yes Engineer CEE No

    ADVS PID, PIDFF, PosProp Advisory SetpointValue (inEngineering Units)

    64-Bit RealNumber

    SPLOLM toSPHILM

    0 Yes Operator CEE No ADVS

    ADVSPP PID, PIDFF, PosProp Advisory SetpointValue (in Percent)

    64-Bit RealNumber

    No View Only CEE No ADVS

    ALARM nooN ALARM output value Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    ALIAS [ ].AL SCM The base nestedparameter for alias.

    Structure No ApplicationDeveloper

    CEE No NUM

    ALIAS [ ].STATU SCM Internal parameter

    for system use only.ALIAS [ ].VALUE SCM Internal parameter

    for system use only.

    ALIASBLKTYP [ ] SCM Block type of thealiases defined inthe Alias Table.

    16-Bit Integer(Template ID)

    Yes ApplicationDeveloper

    ERDB No NUM

    Alias Tableparameter

    Block type of thealias. Sized byNUMALIASES.

    Integer(TEMPLATEID)

    ApplicationDeveloper

    ERDB

    ALIASDATATYP []

    SCM Internal parameterfor system use only.

    Alias Tableparameter

    Internal parameterfor system use only.

    ALIASOPT SCM Alias Table Option -Defines whether ornot an Alias Tablewill be configured inthe SCM.

    Boolean False (0)True (1)

    False (0) Yes ApplicationDeveloper

    ERDB No If ALIconfigall thparambe exSCM form.

    ALIASPRMTYP [ ] SCM Parameter type ofthe aliases definedin the Alias Table.

    16-Bit Integer(Param ID)

    Yes ApplicationDeveloper

    ERDB No NUM

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    19/282

    ALIASREF [ ] [ ] SCM Internal parameterfor system use only.

    ALIASSRC [ ] [ ] SCM Internal parameterfor system use only.

    ALMDB DataAcq,All RegCtl Blocksexcept Fanout:AutoMan, OvrdSel,PID, PIDFF, PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Overall Deadbandfor all analog alarms

    64-Bit RealNumber

    0.00 Yes Engineer/ApplicationDeveloper

    CEE No ADVDDEVHDEVLOPHIOPLOPVHHPVHIAPVLLAPVLO

    ALMDBU DataAcq,All RegCtl Blocksexcept Fanout:AutoMan, OvrdSel,PID, PIDFF, PosProp,PulseCount,PulseLength,

    RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Overall Deadbandunit for all analogalarms

    EnumerationALMDBU

    Percent (0)EngineeringUnits (1)

    Percent(0)

    Yes ApplicationDeveloper

    CEE No ADVDDEVHDEVLOPHIOPLOPVHHPVHIA

    PVLLAPVLO

    ALMENBSTATE CM, SCM, IOM,CEE, CPM, RM

    Alarm Enable State -Defines the alarmreporting functionthat is to be used,when an alarmcondition is detectedby the functionblock, or one of itscomponents.

    Boolean Off (0)On (1)

    On (1) Yes OperatorRM only:Requests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    CEE No INAL

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    20/282

  • 8/10/2019 1757-rm811_-en-p

    21/282

    ARWOP All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,PulseLength,RampSoak,

    RemCas, RatioBias,RegCalc, andSwitch.

    Output Anti-ResetWindup Status -Applies to functionblocks with, at most,one output (OP)connection.Contains the windup

    status of the OPvariable.

    EnumerationARWNET

    Normal (0):OP is free tomove in eitherdirection.Hi (1):OP is free tomove in the

    lowerdirection.Lo (2):OP is free tomove in thehigherdirection.HiLo (3):OP cannotmove in anydirection.

    Normal(0)

    No View Only CEE No ARW

    ARWOP [1..8] Fanout Output Anti-ResetWindup Status -Applies to functionblocks with multipleoutput

    (OP)connections.Contains the windupstatus of each OPvariable.

    EnumerationARWNET

    Normal:Free to movein eitherdirection.Hi:

    Free to movein the lowerdirection.Lo:Free to movein the higherdirection.HiLo:Cannot movein anydirection.

    Normal No View Only CEE No ARW

    ASACONNSTS All IOM FunctionBlocks exceptSerial InterfaceIOM forTroubleshootingonly.Refer toASACONNSTS[0..7] for SerialInterface IOM.

    ASA ConnectionStatus

    32-Bit Integer 0x0 to 0x8000 No View Only CEE No

    ASACONNSTS[0..7]

    Serial InterfaceIOM

    ASA ConnectionStatus

    32-Bit Integer 0x0 to 0x8000 No View Only CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    22/282

    ASAERRCODE All IOM FunctionBlocks exceptSerial InterfaceIOM To be usedfor Troubleshootingonly.Refer to

    ASAERRCODE [0..7]for Serial InterfaceIOM.

    ASA Error Code 32-Bit Integer No View Only CEE No ASAE

    ASAERRCODE[0..7]

    Serial InterfaceIOM

    ASA Error Code 32-Bit Integer No View Only CEE No ASAE

    ASAERRINFO All IOM FunctionBlocks exceptSerial InterfaceIOM forTroubleshootingonly.Refer toASAERRINFO [0..7]for Serial InterfaceIOM.

    ASA ErrorInformation

    32-Bit Integer No View Only CEE No ASAE

    ASAERRINFO[0..7]

    Serial InterfaceIOM

    ASA ErrorInformation

    32-Bit Integer No View Only CEE No ASAE

    ASTEPID DevCtl,All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Active step handle inSequential ControlModule (SCM)Control Request(CONTROLREQ).

    32-Bit Integer 1 to 1023 0 No View Only CEE No CONTSCM

    AUTOSYNCCMD RM Auto

    SynchronizationCommand

    Enumeration Never (0)

    Always (1)Conditional (2)

    Never (0) No Operator

    Requests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    23/282

  • 8/10/2019 1757-rm811_-en-p

    24/282

  • 8/10/2019 1757-rm811_-en-p

    25/282

    AVRAWSTS Pulse Input IOC,Pulse Input w/ FastCutoff IOC

    Bad RawAccumulated ValueStatus.

    Enumeration Bad (0)Uncertn (1)Normal (2)Manual (3)

    No View Only CEE No AVRA

    AVSTS Pulse Input IOC,Pulse Input w/ FastCutoff IOC

    Bad AccumulatedValue Status

    Enumeration Bad (0)Uncertn (1)Normal (2)Manual (3)

    Off No View Only CEE No AV

    B[1..6] RegCalc Individual bias foreach input X[1]through X[6].

    Real 0.0 Yes Operator CEE No X[1..6

    BACKCALCCONN All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,

    PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Secondary Datastructure associatedwith RegulatoryControl Block

    output(s). ContainsCalculated Value(CV) limits,initialization, anddata windup status,etc.. BACKCALCINis associated withthe secondary block,and therefore isrelated to thenumber of outputsused on the primaryblock. ConnectingBACKCALCIN to itsBACKCALCOUTpartneris requiredin order to establishthe initializationpath between thetwo blocks.

    Structure No ApplicationDeveloper

    CEE Yes BACKBACKBACK

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    26/282

    BACKCALCIN All RegCtl Blocksexcept Fanout:AutoMan, OvrdSel,PID, PIDFF, PosProp,PulseCount,PulseLength,RampSoak,

    RemCas, RatioBias,RegCalc, andSwitch.

    Secondary Datastructure associatedwith RegulatoryControl Blockoutput(s). ContainsCalculated Value(CV) limits,

    initialization, anddata windup status,etc.. BACKCALCINis associated withthe secondary block,and therefore isrelated to thenumber of outputsused on the primaryblock. ConnectingBACKCALCIN to itsBACKCALCOUTpartneris requiredin order to establishthe initializationpath between thetwo blocks.

    Structure No View Only CEE Yes BACKBACKBACK

    BACKCALCIN[1..3]

    DevCtl BackCalc Record -Secondary Datastructure associatedwith Device ControlBlock output(s). Thisstructure containsstatus informationfrom the DigitalOutput Channel(DOC) block.BACKCALCIN isassociated with thesecondary block, andtherefore is relatedto the number ofoutputs used on the

    primary block.ConnectingBACKCALCIN to itsBACKCALCOUTpartneris requiredin order to establishthe initializationpath between thetwo blocks.

    Structure No View Only CEE Yes BACK

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    27/282

  • 8/10/2019 1757-rm811_-en-p

    28/282

    BACKCALCOUT[1..4]

    OvrdSel Secondary Datastructure associatedwith RegulatoryControl blockinput(s). ContainsCalculated Value(CV) limits,

    initialization, anddata windup status,etc. BACKCALCOUTis associated withthe primary block,and therefore isrelated to thenumber of inputsused on thesecondary block.ConnectingBACKCALCIN to itsBACKCALCOUTpartneris requiredin order to establishthe initializationpath between the

    two blocks.

    Structure No View Only CEE No BACK

    BACKCALCOUT[1..8]

    Switch Secondary Datastructure associatedwith RegulatoryControl blockinput(s). ContainsCalculated Value(CV) limits,initialization, anddata windup status,etc. BACKCALCOUTis associated withthe primary block,and therefore isrelated to thenumber of inputs

    used on thesecondary block.ConnectingBACKCALCIN to itsBACKCALCOUTpartneris requiredin order to establishthe initializationpath between thetwo blocks.

    Structure No View Only CEE No BACK

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    29/282

    BACKLASHL PosProp,PidPosProp

    Backlash Lowercompensation ofactuator (inseconds).

    Real 0.0 to 60.0seconds

    0.0seconds

    Yes Supervisor CEE No

    BACKLASHR PosProp,PidPosProp

    Backlash RaiseCompensation ofactuator (inseconds).

    Real 0.0 to 60.0seconds

    0.0seconds

    Yes Supervisor CEE No

    BADCAL AIC, AOC Bad CalibrationIndicator On a perchannel basis, thisparameter indicatesif calibration is bador missing.

    Boolean Ok (0)BadCalibration (1)

    Ok (0) No View Only CEE No CALB

    BADCAL[0..numChans-1]

    AIM, AOM Bad CalibrationIndicator On a perchannel basis, thisparameter indicatesif calibration is bador missing.

    Boolean Ok (0)BadCalibration (1)

    Ok (0) No View Only CEE No CALB

    BADCODE All IO Channels,SIFLAGARRCH,SINUMARRCH,SITEXTARRCH

    Reason for BadStates

    Integer 0 No View Only CEE

    BADCTLALM.FL All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Bad Control AlarmFlag

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No BADCBADCBADC

    BADCTLALM.PR All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Bad Control AlarmPriority Definesthe priority of a BadControl alarm.

    EnumerationALPRIOR None (0)Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer CEE No BADCLM.FSV

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    30/282

    BADCTLALM.SV All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,PulseLength,RampSoak,

    RemCas, RatioBias,RegCalc, andSwitch.

    Bad Control AlarmSeverity

    16-Bit Integer 0 to 255 0 Yes Engineer CEE No BADCBADCBADC

    BADCTLFL Automan, OvrdSel,and Switch.

    Bad Control Flag Indicates if a BadControl conditionexists.

    Boolean Off (0): BadControlcondition doesnot exist.On (1): BadControlconditionexists.

    Off (0) No View Only CEE No BADCBADCBADC

    BADCTLOPT AutoMan, OvrdSel,Switch.

    Bad Control Option Indicates what to dowhen CalculatedVariable (CV) is NaN(i.e., BADCTLFL =On).

    EnumerationBADCTLOPT

    No_Shed (0):ShedHold (1):ShedLow (2):ShedHigh (3):ShedSafe (4):

    No_Shed(0)

    Yes Engineer CEE No BADCMODOP

    BADINPTOPT[1..8]

    OvrdSel, Switch Bad Input Option -Indicates if badinputs (NaN) shouldbe included in theinput selectionprocess.

    EnumerationBADINPTOPT

    IgnoreBad (0):Ignore badinputs.IncludeBad(1): Includebad inputs.

    IncludeBad (1)

    Yes Engineer /ApplicationDeveloper

    CEE No

    BADPV DIC Indicates the DigitalInput processvariable (PV) status.

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    BADPVALM.FL DataAcq, DevCtl Bad PV Alarm Flag Boolean Off (0)On (1)

    Off (0) No View Only CEE No BADPBADPHIALHIALM

    HIALBADPVALM.PR DataAcq, DevCtl Bad PV Alarm

    PriorityEnumerationALMPR

    None (0)Journal (1)Low (2)High (3)Urgent (4)

    DataAcqonly: Low(2)DevCtlonly:None (0)

    Yes Engineer CEE No DataABADPBADPPVSTDevCBADPBADPNUM

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    31/282

    BADPVALM.SV DataAcq, DevCtl Bad PV AlarmSeverity

    16-Bit Integer 0 to 15 0 Yes Engineer CEE No DevCBADPBADPNUMDataABADPBADP

    PVSTBADPVFL SIFLAGARRCH,

    SINUMARRCH,SITEXTARRCH

    Bad PV Flag Flagthat indicates thatan error responsewas received for thelast request sent bythis request block.Note that this flag isset to TRUE for bothlocal errors(communicationerrors thatprevented therequest from beingsent out on thenetwork, for

    example) andremote errors (thetarget device couldnot process therequest and so sentan explicit failurestatus). For alarmingon errors, connectthe ERRFL to a FlagBlock and configurethe Flag Block tosend an Alarm whenERRFL is TRUE.

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No ERRF

    BADSO Pulse Input w/ FastCutoff IOC

    Bad Input State FlagWhen On, thisparameter indicatesthe current value ofOutput State (SO) isdoes not necessarilyreflect the value ofthe modulesterminal screws..

    Boolean Off (0): Currentvalue ofOutput State(SO) is valid.On (1): Currentvalue ofOutput State(SO) is invalid.

    Off (0) No View Only CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    32/282

    BADSO[6..7] Pulse Input IOM Bad Input State FlagWhen On, thisparameter indicatesthe current value ofOutput State (SO) isdoes not necessarilyreflect the value of

    the modulesterminal screws..

    Boolean Off (0): Currentvalue ofOutput State(SO) is valid.On (1): Currentvalue ofOutput State

    (SO) is invalid.

    Off (0) No View Only CEE No

    BASEPERIOD CEE Base Period for theCEE function block inmilliseconds (ms).

    Integer 5 ms (0)50ms (1)

    50 ms (1) ApplicationDeveloper

    CEE

    BATTERYNOTOK CPM Battery Not Okay -When On, indicatesCPM Battery iseither in a lowvoltage condition,not connected, ornot present.

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    BECMPRICMD RM Become PrimaryCommand

    Boolean True (0)False (1)

    True (0) No Operator.Requests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    BFF PIDFF Feedforward InputBias

    Real 0 Operator CEE SIFL,

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    33/282

    BOOLVALUEOFF TypeConvert Used to convertBoolean values toEnumeration.

    EnumerationTCGENERICENUM

    Enum0 toEnum63

    Enum0 Yes Engineer CEE No BOOL

    BOOLVALUEON TypeConvert Used to convertBoolean values toEnumeration.

    EnumerationTCGENERICENUM

    Enum0 toEnum63

    Enum1 Yes Engineer CEE No BOOL

    BREVISION RM Boot Revision.Identifies the minorrevision of the RMboot code.

    8-BitUnsignedInteger

    0 to 255 0 No View OnlyRequests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    BVERSION RM Boot Version.

    Identifies the majorrevision of the RMboot code.

    8-Bit

    UnsignedInteger

    0 to 255 0 No View Only

    Requests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    BYPASS DevCtl Permissive andInterlock Bypass

    Boolean Off (0)On (1)

    Off (0) Yes Operator CEE No BYPPNUMOP, P

    BYPPERM DevCtl Override andPermissive BypassPermit

    Boolean Off (0)On (1) Off (0) Yes Engineer CEE No BYPAPI[0..

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    34/282

    C [1..8] Auxcalc Results of up toeight calculatorexpressions.

    64-Bit RealNumber

    NaN No View Only CEE No CSTS

    RegCalc Expression result foreach user inputexpressionEXPR[1..8]

    Real NaN No View Only CEE No CSTS

    C[1..10].BYPPERM

    Transition Conditional ForcePermit

    Boolean Off (0)On (1)

    Off (0) Yes Engineer CEE No C [1..[1..10

    C [1..10].BYPREQ Transition Conditional ForceRequest

    EnumerationCSCOBYPREQ

    ToOff (0)ToOn (1)None (2)

    None (2) No Operator CEE No C [1..[1..10

    C[1..10].CONFIGCODE

    Transition ConditionConfiguration Code

    EnumerationCSCOCONFIGCODECOND

    See below None (0) No View Only CEE No

    C[1..10].CONFIGDESC

    Transition ConditionalConfigurationDescriptor

    String None No View Only CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

    Range

    None (0)Ok (1)UnknownError (2)ImplictConv (3)LossOfPrecsn (4)UnexpctEnd (5)UnexpctComma (6)ColonWoQMark (7)FctNotMltArg (8)ClosParenExp (9)OperandExp (10)MissingArg (11)OperatorExp (12)ColonExp (13)TypeMismatch (14)TypeNotSupp (15)SyntaxError (16)ExprTooCmplx (17)NotEPcodeMe (18)

    NotEDataStak (19)UnsuppFeatur (20)

    ExprTooLong (21)DivideByZero (22)UnknownToken (23)UnexpTokenOS (24)UnknownFunc (25)UnexpOCExpr2 (26)UnexpOCExpr3 (27)ZeroArgument (28)UnexpToken (29)InvalResult (30)InvalTokenTb (31)IntegerExp (32)DoubleExp (33)MissedImpl (34)UnicodeConv (35)ConstExprRem (36)DuplExprRem (37)ExtUse38 (38)ExtUse39 (39)

    ExtUse40 (40)ExtUse41 (41)

    ExtUse42 (42)ExtUse43 (43)ExtUse44 (44)ExtUse45 (45)ExtUse46 (46)ExtUse47 (47)ExtUse48 (48)ExtUse49 (49)ExtUse50 (50)UnSupConType (51)UnExpClsParn (52)CantAssRVal (53)UnExpArrOpen (54)ArrClsExpect (55)ArrOpnExpect (56)ArrIndxError (57)StringExpect (58)InvalidRefer (59)TooManyConns (60)

    CantConvInpt (61)

  • 8/10/2019 1757-rm811_-en-p

    35/282

    C[1..10].CONFIGSTS

    Transition ConditionConfiguration Status

    EnumerationCSCOCONFIG

    Ok (0)Information (1)Warning (2)SevereWarn(3)Fail (4)Error (5)

    SevereError(6)

    Ok (0) No View Only CEE No C[1..10C[1..10

    C [1..10].DESC Transition ConditionDescription

    String Maximumstring lengthis 23characters.

    NullString

    Yes ApplicationDeveloper

    SR No

    C [1..10].EXECCODE

    Transition Condition ExecutionCode

    EnumerationCSCOEXECCODE

    None (0)ConfigError (1)ExprEvalFail(2)StoreFailed (3)CommError (4)StoreWarning(5)InternalErr (6)CtrlReqErr (7)DataTypeErr(8)StorePending(9)

    None (0) No View Only CEE No

    C [1..10].EXECDESC

    Transition Condition ExecutionCode Descriptor

    String None No View Only CEE No

    C [1..10].EXECSTS

    Transition Condition ExecutionStatus

    EnumerationSCSCOEXECSTS

    Ok (0)Bypass (1)Info (2)Warning (3)Fail (4)Error (5)OkPaused (6)BypassPaused(7)

    InfoPaused (8)WarnPaused(9)FailPaused(10)ErrorPaused(11)

    Ok (0) No View Only CEE No C [1..C [1..

    C [1..10].EXPR Transition Condition Expression String Length: 255characters.

    NullString

    Yes ApplicationDeveloper

    SR No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    36/282

    C [1..10].EXPRPCODE

    Transition Internal parameterfor system use only.

    C [1..10].FL Transition Condition StatusFlag

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    C [1..10].GATEASGN

    Transition Internal parameterfor system use only.

    C [1..10].INVOKFL Transition Invoke TransitionCondition InvokeFlag

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No C [1..

    C1 Totalizer, PulseInput Totalizer,Deadtime

    Engineering Unitsscaling factor for thecalculation ofDELAYTIME orTotalizer ProcessVariable (PV).

    64-Bit RealNumber

    Any RealNumber, NaNis not allowed.

    1.0 Yes Deadtime:EngineerTotalizer,Pulse InputTotalizer:Operator

    CEE No DELA

    Pulse Input IOC,Pulse Input w/ FastCutoff IOC

    Engineering Unitsscale factor(dimensionless) For example, a factor

    to convert gallons tobarrels.

    64-Bit RealNumber

    Any RealNumber, NaNis not allowed.

    1.0 Yes View Only CEE No C2, A

    C1[0..7] Pulse Input IOM Engineering Unitsscale factor(dimensionless)forexample, a factor toconvert gallons tobarrels.

    64-Bit RealNumber

    3.4 e 38 to3.4 e 38

    1.0 Yes ApplicationDeveloper

    CEE No C2, A

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    37/282

  • 8/10/2019 1757-rm811_-en-p

    38/282

    CASREQFL PID, PIDFF, PosPropRemCas, RatioBias

    Cascade RequestFlag - If set, meansthe function blockwas in cascade, thenshed mode due toinput timeout, andwill return to

    cascade as soon asit fetches a goodinput.

    Boolean Off (0)On (1): Modewas shed dueto timeout;waiting toreturn tocascade

    mode.

    Off (0) No OtherFunctionBlock

    CEE No MOD

    CATNUMBER All IOM FunctionBlocks

    Catalog Number 32-Bit Integer Seebelow

    Yes ApplicationDeveloper

    CEE No

    CCLCNT CPM Number of LoadedControl ComponentLibraries (CCLs) inthe ControlProcessor Module(CPM).

    16-Bit Integer No View Only CEE No CCLN

    CCLINFO CPM Control ComponentLibrary (CCL)managementinformation.

    String (OneDimensionalArray)

    0 to 49 NullString

    No View Only CEE CCLC

    CCLLOADSTAT CPM Control ComponentLibrary (CCL) loadstatus.

    16-Bit Integer None 0 No View Only CEE No

    CCLNAME CPM List of loadedlibraries.

    String (OneDimensionalArray)

    0 to 40 NullString

    No View Only CPM No CCLC

    CCLPACKET CPM Library LoadParameter

    Engineer CEE

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

    Default

    1756-IF6I: 11756-IF16: 61756-IA16: 51756-IB32: 121756-IB16I: 61756-IA16I: 51756-IM16I: 6

    1756-IA8D: 1

    1756-IB16D: 21756-IR6I: 21756-IT6I: 5TC- MUX021: 01756-OF6CI: 41756-OF6VI: 31756-OF8: 9

    1756-OA16: 7

    1756-OB32: 171756-OB16I: 71756-OA16I: 71756-OA8D: 41756-OB16D: 41757-PIM: 8

  • 8/10/2019 1757-rm811_-en-p

    39/282

    CEECOMMAND CEE, CPM Control ExecutionEnvironmentCommand

    EnumerationCEECOMMAND

    Idle (0)Run (1)None (2)

    None (2) No Supervisor orEngineerwhan an Idlecommand isstored toCEECOMMAND and the

    CEE is in theRun state.Supervisor,Engineer orOperatorwhen aCEECOMMAND of Run isstored andthe CEE is inIdle.

    CEE No CEES

    CEESTATE CEE, CM, SCM,IOM, CPM

    Control ExecutionEnvironment State -Gives current stateof CEE.

    EnumerationCEESTATE

    Idle(0)Run(1)Failed(2)NotLoaded(3)

    Idle(0) No View Only CEE No CEECEXECPCMS

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    40/282

    CHANINUSE[0..31]

    RM, SerialInterface IOM

    Channel In Use Indicates whetherthe Channel iscurrently being used(a value of On) or not(a value of Off).

    Boolean Off (0)On (1)

    Off (0) No View OnlyRM only:Requests toread or storeto any RMparametermust come

    from theSupervisoryplatform.

    CEE No CHAN

    CHANSTS[0..31] RM, SerialInterface IOM

    Channel Status Provides a status foreach channel of themodule.

    Enumeration NotUsed(0)Ok(1)Bad(2)

    NotUsed(0)

    No View OnlyRM only:Requests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    CEE No CHANERRF

    CHANTEXT IOM Channel In Use Indicates whetherthe Channel iscurrently being used(a value of On) or not(a value of Off).

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    CIPNAME RSPNUMARRAYRSPFLAGARRAYRSPTEXTARRAY

    CIP Tag Name String Maximum of40 characters

    Blank(no name)

    Yes ApplicationDeveloper

    CEE

    CJDISABLE AIM, RM Cold JunctionDisable Appearsas a configurationcheckbox that whenenabled allowsCJOFFSET to beconfigured.

    Boolean Off (0)On (1)

    Off (0) Yes ApplicationDeveloperRM only:Requests toread or storeto any RMparametermust comefrom the

    Supervisoryplatform.

    CEE No CJOF

    CJOFFSET AIC Cold Junction Offset- Offset to be addedto cold junctiontemperature as acorrection factor.

    64-Bit RealNumber

    -5 to +5degrees (C orF)

    0.0 No View Only Not Loaded No CJDISCALB

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    41/282

    CJOFFSET[0..numChans-1]

    AIM Cold Junction Offset- Offset to be addedto cold junctiontemperature as acorrection factor.

    64-Bit RealNumber

    -5 to +5degrees (C orF)

    0.0 Yes ApplicationDeveloper

    CEE(1756-IF16not loaded)

    No CJDISCALBs-1] (A

    CLKADJUST RM Local clockadjustment

    Enumeration Standard (0)Daylight (1)

    Standard(0)

    No View OnlyRequests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    CLKTIME RM Clock time, asreported by theRedundancyModule.

    TIME No View OnlyRequests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    CLKZONE RM Time zone 16-BitUnsignedInteger

    No View OnlyRequests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    CLROPREQFL DevCtl Clear RequestedOutput Value(OPREQ) Flag

    Boolean Off (0)On (1)

    Off (0) No OtherFunctionBlock

    CEE No GOPROPTY

    CMDATTR Totalizer, Pulse

    Input Totalizer

    Totalizer Command

    Attribute - Specifieswho may store tothe COMMANDparameter, (i.e., theoperator, anotherfunction block, oruser program).

    Enumeration

    CMDATTR

    Operator (0)

    OtherFB (1)

    Operator

    (0)

    Yes Operator CEE No COM

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    42/282

    CMDDISALM.FL DevCtl Command DisagreeAlarm Flag

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No CMDCMDCMD2], GONUMNUMOPFIN

    CMDDISALM.PR DevCtl Command DisagreeAlarm Priority

    EnumerationALPRIOR

    None (0)Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer CEE No CMDCMDCMD2], NUNUM

    CMDDISALM.SV DevCtl Command DisagreeAlarm Severity

    16-Bit Integer 0 to 255 0 Yes Engineer CEE No CMDCMDCMD2], NUNUM

    CMDDISALM.TM[0..2]

    DevCtl Command DisagreeFeedback Times -The wait time foreach state, beforeCommand Disagree

    Alarm becomesactive.

    32-Bit Integer 0 to 1000seconds

    0 seconds Yes Engineer CEE No CMDCMDCMDNUMNUM

    NUM

    CMDEXEC SCM Sequential ControlModule (SCM)Execution Command

    EnumerationCSCOEXECC

    None (0)Resume (1)CheckConfig(2)

    None (0) No View Only CEE No COM

    CMDFALALM.FL DevCtl Command Fail AlarmFlag

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No CMDCMDCMD2], GONUMNUMOPFIN

    CMDFALALM.PR DevCtl Command Fail AlarmPriority

    EnumerationALPRIOR

    None (0)Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer CEE No CMDCMDCMD2], NUNUM

    CMDFALALM.SV DevCtl Command Fail AlarmSeverity

    16-Bit Integer 0 to 255 0 Yes Engineer CEE No CMDCMDCMD2], NUNUM

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    43/282

  • 8/10/2019 1757-rm811_-en-p

    44/282

    COMMAND(cont)

    REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY

    Method thatspecifies the type ofcommunication thatthis block isconfigured toperform.

    Enumeration See b elow PLC5TypRead

    Yes ApplicationDeveloper

    CEE No

    CONFIGCODE SCM, Handler,RegCalc, Step,Transition

    Configuration Code EnumerationCSCOCONFIGCODE

    See below None (0) No View Only CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

    Range

    PLC5TypRead Used if this block is to read data from a PLC-5 or aCL5550 using the PLC-5 Typed Read Command.

    PLC5TypWrite Used if this block is to write data from a PLC-5 or aCL5550 using the PLC-5 Typed write Command.

    CIPRead Used to read data from a CL5550

    CIPWrite Used to write data from a CL5550.

    Range

    None (0)UnknownError (1)InternalErr (2)

    ILLOwnHandle (3)ILLHndlrHndl (4)NextHNotNull (5)ILLNNextTrns (6)ConnInvObjs (7)InvNextType (8)NotImplNxTyp (9)ILLExcConds (10)ILLConds (11)ILLOutputs (12)IncObjects (13)ILLNOutputs (14)ILLNConds (15)

    ILLGateLogic (16)IncGateLogic (17)NullGateUsed (18)

    OvlpGateInps (19)SkipGateInps (20)ILLInvkTObj (21)ILLInvkTCnfg (22)ILLHndlrType (23)ILLHndlrSel (24)HndlrInstMis (25)ILLExcCProp (26)IncOpProp (27)IncCondProp (28)IncInvkTProp (29)IncPropagtn (30)LostObjects (31)

    ActIgnored (32)EditIgnored (33)TooFewCond (34)

    MaxTmLtMinT (35)NegativeTime (36)EnbHdUnavail (37)DisHdUnavail (38)EditNotPermt (39)IntGateError (40)UserNullHnd (41)UserEditHnd (42)ILLObjAsHnd (43)NonEditLostO (44)NonOptGatLog (45)RefusedConn (46)ILLMultRef (47)

    ConfHndErr (48)CnfHndSurWrn (49)ConfHndWarn (50)

    ConfHndInfo (51)ConfUnknCnfSt (52)Spare53 (53)Spare54 (54)Spare55 (55)Spare56 (56)Spare57 (57)Spare58 (58)Spare59 (59)Spare60 (60)Spare61 (61)

  • 8/10/2019 1757-rm811_-en-p

    45/282

    CONFIGCODE[1..8]

    Auxcalc Configuration Code EnumerationAUXCALCCONFIGCODE

    See below None (0) No Engineer/ApplicationDeveloper

    CEE No

    CONFIGDESC Handler, RegCalc,SCM, Step,Transition

    ConfigurationDescriptor

    String Maximum of39 characters.

    None No View Only CEE No

    CONFIGDESC[1..8]

    Auxcalc ConfigurationDescriptor

    String Maximum of39 characters.

    None No View Only CEE No

    CONFIGSTS Handler, RegCalc,SCM, Step,Transition

    Configuration Status EnumerationAUXCALCCONFIGSTS,CSCOCONFIG

    Ok (0)Information (1)Warning (2)SevereWarning (3)Fail (4)Error (5)SevereError(6)

    Ok (0) No View Only CEE No

    CONFIGSTS[1..8] Auxcalc Configuration Status EnumerationAUXCALCCONFIGSTS,

    CSCOCONFIG

    Ok (0)Information (1)Warning (2)

    SevereWarning (3)Fail (4)Error (5)SevereError(6)

    Ok (0) No View Only CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

    Range

    None (0)Ok (1)UnknownError (2)ImplicitConv (3)LossOfPrecsn (4)UnexpctEnd (5)UnexpctComm (6)ColonWoQMar (7)FctNotMltArg (8)ClosParenExp (9)OperandExp (10)MissingArg (11)OperatorExp (12)ColonExp (13)TypeMismatch (14)TypeNotSupp (15)

    SyntaxError (16)ExprTooCmplx (17)NotEPcodeMe (18)NotEDataStak (19)UnsuppFeatur (20)ExprTooLong (21)DivideByZero (22)UnknownToken (23)UnexpTokenO (24)UnknownFunc (25)UnexpOCExpr2 (26)UnexpOCExpr3 (27)ZeroArgument (28)UnexpToken (29)InvalResult (30)InvalTokenTb (31)

    IntegerExp (32)DoubleExp (33)MissedImpl (34)UnicodeConv (35)ConstExprRem (36)DuplExprRem (37)ExtUse38 (38)ExtUse39 (39)ExtUse40 (40)ExtUse41 (41)ExtUse42 (42)ExtUse43 (43)ExtUse44 (44)ExtUse45 (45)ExtUse46 (46)ExtUse47 (47)

    ExtUse48 (48)ExtUse49 (49)ExtUse50 (50)UnSupConTyp (51)UnExpClsParn (52)CantAssRVal (53)UnExpArrOpen (54)ArrClsExpect (55)ArrOpnExpect (56)ArrIndxError (57)StringExpect (58)InvalidRefer (59)TooManyConn (60)CantConvInpt (61)

  • 8/10/2019 1757-rm811_-en-p

    46/282

    CONFIGURED RM RM ConfigurationStatus. Value ofUSER indicates themodule has beenconfigured to dosomething differentthan the

    out-of-the-boxdefault.

    Enumeration Factory (0)User (1)

    Factory (0) No View OnlyRequests toread or storeto any RMparametermust comefrom the

    Supervisoryplatform.

    Not Loaded No

    CONFIRM[0..15] Message Confirmation Boolean Off (0)On (1)

    Off (0) No Operator CEE No

    CONFIRMED[0..15]

    Message Confirmed Boolean Off (0)On (1)

    View Only CEE No

    CONNLISTSIZE CM Integer 0 View Only No

    CONTROLLOCK SCM Control Access Lock EnumerationCSCOACCLOCK

    Operator (0)Engineer (1)View Only (2)OtherFB (3)

    Operator(0)

    Yes Engineer CEE No MOD

    CONTROLREQ DevCtlAll RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Sequential ControlModule (SCM)Control Request

    Structure No OtherFunctionBlock

    CEE No GOPRMODOPTYSCMSCM

    COS DIC Change of State. Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    COS[0..NumChans-1]

    DIM Change of State. Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    CPMCOMMAND[0..numChans-1]

    CPM This block willreplacePCMCOMMAND ina later release.

    CPMSTATE CPM This block willreplace PCMSTATEat a later release.

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    47/282

  • 8/10/2019 1757-rm811_-en-p

    48/282

    CRCYCLEOVRN[0..40]

    CEE Current Hour CycleOverruns.

    16-Bit RealNumber

    0 to 32767 0 No View Only CEE No LSCY

    CSRC [1..10][1..6] Transition Internal parameterfor system use only.

    CSTS[1..8] AuxCalc Expression S tatuses EnumerationPVSTS

    Bad (0)Uncertn (1)Normal (2)Manual (3)

    Bad (0) No View Only CEE No

    RegCalc Expression resultstatus for eachresult C [1] through C[8].

    EnumerationPVSTS

    Bad to Manual(0 to 3)

    Bad (0) No View Only CEE No C [1..

    CTLACTN PID, PIDFF Control Action - Theoutput direction of aPID function block(direct or reverse).

    EnumerationCTLACTN

    Direct (0)Reverse (1)

    Reverse(1)

    Yes Engineer CEE No

    CTLEQN PID, PIDFF, OvrdSel,Switch.

    Control EquationType

    EnumerationCTLEQN

    EqA (0)EqB (1)EqC (2)EqD (3)EqE (4)EqF (5)EqG (6)

    EqA (0) Yes Engineer /ApplicationDeveloper

    CEE No

    CTLINIT All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,

    PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Control InitializationRequest Flag - Usedto request one-shot

    initialization of aRegulatory Controlblock. May bewritten to by a userprogram or anotherfunction.

    Boolean Off (0)On (1)

    Off (0) No OtherFunctionBlock

    CEE No

    CURPROFILEID RampSoak Current Profile ID Integer 1 to 10 1 Operator No CEE No CURS

    CURSEGID RampSoak Current Segment ID. Integer 1 to 60 No Operator CEE No CURP

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    49/282

    CURSEGTYP RampSoak Current SegmentType (Ramp or Soak).

    Enumeration Ramp (0)Soak (1)

    Ramp (0) No View Only CEE No

    CUTOFF.LM Totalizer, PulseInput Totalizer,Deadtime

    Zero-Flow CutoffLimit in EngineeringUnits - Allows theuser to specify acutoff limit suchthat, when the valueof the RATE fallsbelow this limit, PVremains constant (noaccumulation).

    64-Bit RealNumber

    NaN, orgreater-thanor equal-to0.0.

    Deadtime: NaNTotalizer,PulseInputTotalizer:0.0

    Yes Totalizer,Pulse InputTotalizer:EngineerDeadtime:Supervisor

    CEE No

    CV All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Calculated Value -The result(calculated value) ofthe function blocks.The value may be inPercent orEngineering Units,depending on thefunction block.

    64-Bit RealNumber

    NaN No OtherFunctionBlock

    CEE No

    CV[1..8] Fanout Calculated Variablefor function blockswith MultipleOutputs - The result(calculated value) ofthe function block.There is one CV foreach output.

    64-Bit RealNumber

    NaN Yes OtherFunctionBlock

    CEE No

    CVEUHI All RegCtl Blocksexcept Fanout:AutoMan, OvrdSel,PID, PIDFF, PosProp,PulseCount,PulseLength,RampSoak,RemCas, RatioBias,

    RegCalc, andSwitch.

    Calculated Variable(CV) High Range (inEngineering Units) -This valuecorresponds to100% of full-scalevalue.

    64-Bit RealNumber

    Greater-thanor equal-toCVEULO

    100.0 Yes Engineer CEE No CVEU

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    50/282

  • 8/10/2019 1757-rm811_-en-p

    51/282

    CVORFBSRC RegCalc Calculated Variableunder overridefeedback conditions(CVORFB) sourceselector.

    EnumerationREGCALCSELECTOR

    X1 to C8STS(0 - 27)

    X1 (0) Yes Engineer CEE No

    CVSRC RegCalc Calculated Variable(CV) output sourceselector.

    EnumerationREGCALCSELECTOR

    X1 to C8STS(0 - 27)

    X1 (0) Yes Engineer CEE No

    CYCLEOPT[1..NUMPROFILES]

    RampSoak Cycle Option. Integer Single (0)RoundRob (1)Cyclic (2)

    RoundRob(1)

    Engineer CEE

    CYCLETIME PosProp,PidPosProp

    Cycle time forcommanding raise orlower pulses (inseconds).

    Real 0.020 to1000.0

    10.0 Yes Supervisor CEE No

    D1 Deadtime Bias for thecalculation ofDELAYTIME.

    Real Number 0.0 Yes Supervisor CEE No DELA

    D2 Deadtime Bias for the P2 input. Real Number 0.0 Yes Supervisor CEE No

    DATATYPE RSPNUMARRAY DataType forPCCC/CIP Access.The type of data thatcan be read from orwritten to by aremote device.

    Enumeration 32-Bit RealNumber,8-Bit SignedInteger,16-Bit SignedInteger,32-Bit SignedInteger,

    32-BitRealNumber

    Yes ApplicationDeveloper

    CEE No

    DEADBAND GE, GT, LE, LT Deadband ValueDefines the value ofthe deadband forComparisonFunctions.

    64-Bit Real Greater-thanor equal-to 0.

    0.005 Yes Engineer CEE No

    DEADBAND1 EQ, NE Deadband Value #1Defines the valueof the (inner)

    deadband.

    64-Bit Real Greater-thanor equal-to 0.Less-than or

    equal-toDEADBAND2

    0.005 Yes Engineer CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    52/282

    DEADBAND2 EQ, NE Deadband Value #2Defines the valueof the (outer)deadband.

    64-Bit Real Greater-thanor equal-toDEADBAND1

    0.01 Yes Engineer CEE No

    DEBUG All IO Channels,SIFLAGARRCH,SINUMARRCH,SITEXTARRCH.

    Spare for debuginformation

    Integer 0 View Only CEE

    DELAYTABLE[1..60]

    Deadtime Delay Table. Real Number No ViewOnly CEE No NUM

    DELAYTIME 2oo3, Delay,MVote, Ondelay,Offdelay, Watchdog

    Delay in seconds Integer 0-8000seconds

    Delay,Ondelay,Offdelay,Watchdog:2 seconds2oo3,MVote:5 seconds

    Yes Engineer CEE No

    Deadtime Delay Time (inMinutes) If fixed

    delay is configured,it is a fixed time,specified by theuser; for variabledelay, it is aParameter time,calculated by thefunction block.

    Real Number Greater-thanor equal-to 0.0

    minutes.

    0.0 FixedDelay:

    YesVariableDelay: No

    Fixed Delay:Engineer

    VariableDelay:ViewOnly

    CEE No DELA

    DELAYTYPE Deadtime Delay Type Enumerationof DELAYTYPE

    Fixed (0)Variable (1)

    Fixed (0) Yes Engineer CEE No

    DELCV PID, PIDFF Incremental Changein CalculatedVariable (CV) , inPercent.

    64-Bit Real NaN No ViewOnly CEE No

    DELTATIME Totalizer Delta Time Real 0 View Only

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    53/282

    DESC Applies to all blockswith alarmingcapability exceptTimer.Also includes Flagand Messageblocks.

    Block Descriptor -Used to specifydescriptive text forthe function block.Appears on bothdetail and groupdisplays.

    String Length: 24charactersExceptions:40 charactersfor Step,Transition,and Handler.

    23 charactersfor DevCtl.

    Nullstring

    Yes ApplicationDeveloper

    SR No KEYW

    DEV PID, PIDFF, PosProp Deviation - Thedifference betweenthe Process Variable(PV) and Set Point(SP).

    64-Bit Real NaN No ViewOnly CEE No PV, S

    DEVADDR SIFLAGARRCH,SINUMARRCH,SITEXTARRCH.

    Serial Link DeviceAddress Identifiesa device on theserial link connectedto the FTA.

    32-Bit Integer 0 Yes ApplicationDeveloper

    CEE No

    DEVHIALM.DB PID, PIDFF, PosPropand RampSoak

    Deviation HighAlarm Deadband

    64-Bit Real 0.0 to 100.0, ifalarmdeadband

    units(DEVHIALM.DBU) are inPercent.Greater-thanor equal to0.0, if alarmdeadbandunits(DEVHIALM.DBU) areEngineeringUnits (EUs).

    0.0 Yes Engineer/ApplicationDeveloper

    CEE No PV, SDEVHDEVH

    DEVHDEVHDEVHDEVH

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    54/282

    DEVHIALM.DBU PID, PIDFF, PosPropand RampSoak

    Deviation HighAlarm DeadbandUnits - Indicates ifDEVHIALM.DB is inPercent orEngineering Units.

    EnumerationALMDBU

    Percent (0)EU (1)

    Percent(0)

    Yes ApplicationDeveloper

    CEE No PV, SDEVHDEVHDEVHDEVHDEVHDEVH

    DEVHIALM.FL PID, PIDFF, PosPropand RampSoak Deviation HighAlarm Flag -Indicates ifDEVHIALM.TP hasbeen exceeded.

    Boolean Off (0):DEVHIALM.TPhas not beenexceeded (i.e.,no DeviationHigh alarm).On (1):DEVHIALM.TPhas beenexceeded.

    Off (0) No ViewOnly CEE No PV, SDEVHDEVHDEVHDEVHDEVHDEVH

    DEVHIALM.PR PID, PIDFF, PosPropand RampSoak

    Deviation HighAlarm Priority -Defines the priorityof a Deviation Highalarm.

    EnumerationALPRIOR

    None (0)Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer CEE No PV, SDEVHDEVHDEVHDEVHDEVHDEVH

    DEVHIALM.SV PID, PIDFF, PosPropand RampSoak

    Deviation HighAlarm Severity

    16-Bit Integer 0 to 15 0 Yes Engineer CEE No PV, SDEVHDEVHDEVHDEVHDEVHDEVH

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    55/282

  • 8/10/2019 1757-rm811_-en-p

    56/282

    DEVLOALM.DB PID, PIDFF, PosPropand RampSoak

    Deviation Low AlarmDeadband

    64-Bit RealNumber

    to 100.0 ifalarmdeadbandunits(DEVLOALM.DBU) arePercent

    Greater-thanor equal to 0.0if alarmdeadbandunits(DEVLOALM.DBU) areEngineeringUnits (EUs).

    0.0 Yes Engineer/ApplicationDeveloper

    CEE No DEVL

    DEVLOALM.DBU PID, PIDFF, PosPropand RampSoak Deviation Low AlarmDeadband Units - p -Indicates ifDEVLOALM.DB is inPercent orEngineering Units.

    EnumerationALMDBU Percent (0)EU (1) Percent(0) No ApplicationDeveloper CEE No DEVL

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    57/282

    DEVLOALM.FL PID, PIDFF, PosProp,RampSoak

    Deviation Low AlarmFlag Indicates ifDEVLOALM.TP hasbeen exceeded.

    Boolean Off (0):DEVLOALM.TPhas not beenexceeded,;i.e., noDeviation Lowalarm.

    On (1):DEVLOALM.TPhas beenexceeded.

    Off (0) No ViewOnly CEE No

    DEVLOALM.PR PID, PIDFF, PosPropand RampSoak

    Deviation Low AlarmPriority - Defines thepriority of aDeviation Lowalarm.

    EnumerationALPRIOR

    None (0)Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer CEE No

    DEVLOALM.SV PID, PIDFF, PosPropand RampSoak

    Deviation Low AlarmSeverity

    16-Bit Integer 0 to 15 0 Yes Engineer CEE No DEVLDEVL

    DEVLOALM.TM PID, PIDFF, PosPropand RampSoak

    Deviation Low AlarmFilter Time (inSeconds) - Thepurpose of this

    variable is to preventinput spikes fromcausing alarms. Analarm will only begenerated if thedeviation isconsistently belowthe low deviationtrip point for morethan DEVLOALM.TMseconds.

    32-BitUnsignedInteger

    0 to 60 0 Yes Engineer CEE No DEVL

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    58/282

    DEVLOALM.TP PID, PIDFF, PosPropand RampSoak

    Deviation Low AlarmTrip Point (inEngineering Units) -Defines the lowerlimit for thedeviation.

    64-Bit RealNumber

    NaN, or 0.0 to[PVEUHI -PVEULO]

    NaN Yes Engineer CEE No SP, PVPVEU

    DHCHANNEL REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY:when using PCCCand COMMAND iseither:PLC5TypRead orPLC5TypWriteand the target is onDH+. Thisparameter isenabled only whenDHFL is True.

    The DH+ channel thetarget node islocated on. This canbe one of twochannels A or B.Unlike ControlNet,the two DH+channels are notused merely forredundant cabling.

    Enumeration A,B A Yes ApplicationDeveloper

    CEE No

    DHDESTLINK REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY:when using PCCCand COMMAND iseither:PLC5TypRead orPLC5TypWriteand the target is onDH+. Thisparameter isenabled only whenDHFL is True.

    Destination Link forthe DH+ route. Thisparameter is usedonly when usingDH+ RemoteMessaging, andshould be zero whenusing DH+ LocalMessaging.

    32-Bit Integer 0 to 199 0 Yes ApplicationDeveloper

    CEE No

    DHFL REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY:when using PCCCand COMMAND iseither PLC5TypReador PLC5TypWrite

    This flag is TRUEwhen the targetdevice is on DH+. Inthis case, the PATHis the path to theDHRIO module andadditional pathinformation isrequired to get fromthe DHRIO moduleto the target device.

    Boolean Off(0)On(1)

    Off(0) Yes ApplicationDeveloper

    CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    59/282

    DHNODE REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY:when using PCCC.I.e., when theCOMMAND is oneof the following:

    PLC5TypRead PLC5TypWriteAnd the target is onDH+. Thisparameter isenabled only whenDHFL is True.

    Node number of thetarget node on theDH+ network. Thisparameter has avalue from 0 to 77octal.

    Enumeration 0 to 77 octal. 0 octal Yes ApplicationDeveloper

    CEE No

    DHSRCLINK REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY:when using PCCC.I.e., when theCOMMAND is oneof the following: PLC5TypRead PLC5TypWrite

    And the target is onDH+. Thisparameter isenabled only whenDHFL is True.

    Source link for theDH+ route. Thisparameter is usedonly when usingDH+ RemoteMessaging, andshould be zero whenusing DH+ LocalMessaging.

    32-Bit Integer 0 to 199 0 Yes ApplicationDeveloper

    CEE No

    DI [1..4] DevCtl Digital Input Value Boolean Off (0)On (1)

    Off (0) No ViewOnly CEE Yes, InsideInput

    DIPVGPVANUMNUMPVAU

    DIGFILTER 1797-IBN16 Digital Filter Time. Enumeration .25 ms Delay.5 ms Delay1 ms Delay2 ms Delay4 ms Delay8 ms Delay16 ms Delay32 ms Delay

    .25 msDelay

    Yes ApplicationDeveloper

    CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    60/282

    DIGFILTER[0..numChans-1]

    AIM Digital Filter (msec)This parameter isa configurable timeconstant used in afirst order lag filterwhich is used toremove noise from

    inputs.

    32-Bit Integer If [0],minimum to20100 msIf not [0],minimum to100 ms

    0(indicatesdigitalfiltering isoff)

    Yes ViewOnly -See Notes

    CEE No

    DIPVMAP [0..15] DevCtl Actual StateDefinitions.

    String Bad (0)InBet (1)State0 (4)State1 (5)State2 (6)

    Bad (0) Yes Engineer CEE No DI [1.NUMNUMPVAU

    DISCREP 2oo3, MVote Discrepancy outputvalue.

    Boolean Off (0)On (1)

    Off (0) No ViewOnly CEE No

    DISPPOS RM Display position.Identifies theChassis A vs.

    Chassis Bworkstation displayfield groups to whichthe remainder of thisobjects data shouldbe applied.

    Enumeration Undefined (0)Chassis_A (1)Chassis_B (2)

    Undefined (0)

    No ViewOnlyRequests toread or store

    to any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    DISQSECCMD RM DisqualifySecondaryCommand

    Boolean True (0)False (1)

    True (0) No OperatorRequests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    61/282

  • 8/10/2019 1757-rm811_-en-p

    62/282

    EDGEDETECT Pulse Input IOC,Pulse Input w/ FastCutoff IOC

    Input Edge Detectionspecifies whichedge of pulse to bedetected forcounting. All timing,counting andfrequency functions

    in the hardwarebegin with thetransition of thesignal (applied to thescrew terminals)from Low to High, orHigh to Low.

    Enumeration Rising Edge(0):Signaltransitionsfrom lowvoltage tohigh voltage

    will cause anOff-to-Ontransition inthe ASICfunctions ofthe module.Falling Edge(1):Signaltransitionsfrom highvoltage to lowvoltage willcause anOff-to-Ontransition inthe ASIC

    functions ofthe module.

    RisingEdge (0)

    Yes View Only CEE No

    EDGEDETECT[0..7]

    Pulse Input IOM Input Edge Detectionspecifies whichedge of pulse to bedetected forcounting.

    Enumeration Rising Edge (0)Falling Edge(1)

    RisingEdge (0)

    Yes ApplicationDeveloper

    CEE No RisinreferscrewtransvoltavoltaOff-toin theof theFallinreferscrewtransvolta

    voltaOff-toin theof the

    ELOF[0..numChans-1]

    DIM (onlyconfigurable on the8-channel, 120VAC, Diagnosticmodule)

    Enable Loss ofPower

    Boolean Off (0)On (1)

    Off (0) Yes ApplicationDeveloper

    CEE No NOFI[0..nu

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    63/282

  • 8/10/2019 1757-rm811_-en-p

    64/282

  • 8/10/2019 1757-rm811_-en-p

    65/282

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

    ERRCODE [0..31] Serial InterfaceIOM

    Detailed Error CodeProvides anindication of thestatus of the arraydata for eachChannel.

    String See below NullString

    No ViewOnly CEE No ERRF

    ERRFL SIFLAGARRCH,SINUMARRCH,

    SITEXTARRCH

    Flag that indicatesthat an error

    response wasreceived for the lastrequest sent by thisrequest block. Notethat this flag is setto TRUE for bothlocal errors andremote errors . Foralarming on errors,connect the ERRFL toa Flag Block andconfigure the FlagBlock to send anAlarm when ERRFLis TRUE.

    Boolean Off (0): data isokay

    On (1): data isinvalid

    Off (0) No ViewOnly CEE No BADPINITR

    All Exchange

    Library RequestArray functionblocks:REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY

    Flat indicating an

    error response wasreceived for the lastrequest sent by thisrequest block.

    Boolean Off(0)

    On(1)

    Off(0) No View Only CEE No

    Range

    Length: 8 charactersPossible String values:

    NO_CONF: Inital value set by SIM

    CFG_LOAD: Set by SIM when loading configuration to FTA

    ARR_INIT: Set by FTA after receiving configuration

    CONFIG: Set by SIM if it cannot load a configuration

    FTA COMM: Set by SIM if it cannot communicate with the FTA

    #ELEMNT: Set by SIM if number of elements does not match datatype (possibly also set by FTA)

  • 8/10/2019 1757-rm811_-en-p

    66/282

    ERRFL [0..31] Serial InterfaceIOM

    Overall Error Flag Indicates the validityof the array data foreach Channel; whenOff the data is Ok,and when On thedata is invalid.

    Boolean Off (0)On (1)

    Off (0) No ViewOnly CEE No ERRC

    ERRINFO REQFLAGARRAY,REQNUMARRAY,REQTEXTARRAY

    Extended ErrorStatus on the lastrequest operation.

    32-Bit Integer 0 No ViewOnly CEE No This vwhenparamand isthe laoperaan erExtenExtenStatudebuthe fa

    ERRORCODE RM Redundancy ModuleStatus Code, as itappears on the frontpanel of theRedundancyModule.

    String Maximum of 6characters

    No ViewOnlyRequests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    ERRORDBL PosProp,PidPosProp (whenPV > SP)

    Error Deadband forthe lower direction(in percent).

    Real 0.0 to 100.0% 5.0% Yes Supervisor CEE No

    ERRORDBR PosProp,PidPosProp (whenPV < SP)

    Error Deadband forthe raise direction(in percent).

    Real 0.0 to 100.0% 5.0% Yes Supervisor CEE No

    ERRORMSGIDX RM Redundancy ModuleError MessageIndex. Full error

    code, whichreferences amatching test string.

    16-BitUnsignedInteger

    0 to 65535 No ViewOnlyRequests toread or store

    to any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    67/282

  • 8/10/2019 1757-rm811_-en-p

    68/282

    EVALTRANS[1..10] [1..10]

    SCM Currently EvaluatedTransition Name

    BlockId NullString

    No ViewOnly CEE No ACTIV[1..10[1..10

    EVALTRANSN[1..10] [1..10]

    SCM Currently EvaluatedTransition Name

    32-Bit Integer NullString

    No ViewOnly CEE No ACTIV[1..10[1..10

    EVENTFL[1..NUMEVENTS]

    RampSoak RampSoak EventFlags

    Boolean Off (0)On (1)

    Off (0) No ViewOnly CEE No

    EVENTBGNTIME[1..NUMPROFILES][1..NUMEVENTS]

    RampSoak Event Start Time Real NaN, orGreater-thanor equal-to 0.0

    0.0 Yes Supervisor CEE No

    EVENTENDTIME[1..NUMPROFILES][1..NUMEVENTS]

    RampSoak Event End Time Real NaN, orGreater-thanor equal-to 0.0

    0.0 Yes Supervisor CEE No

    EVENTSEGID[1..NUMPROFILES][1..NUMEVENTS]

    RampSoak Event Segment ID Integer 0 to 100 1 Yes Supervisor CEE No

    EVERIFY[0..numChans-1]

    DOM (see Notes) Enable Output Verify Boolean Off (0)On (1)

    Off (0) Yes ApplicationDeveloper

    CEE No VERIF[0..nu

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    69/282

  • 8/10/2019 1757-rm811_-en-p

    70/282

    EXECDESC [1..8] Auxcalc Execution CodeDescriptor

    String Maximum of39 characters.

    None No ViewOnly CEE No EXECEXEC

    EXECSTATE CM, IOM, SCM Execution state ofthe block and itscomponents.

    Enumerationof EXECSTATE

    Inactive (0)Active (1)

    Inactive(0)

    No Supervisor CEE No CEES(for S

    EXECSTS SCM, Handler,Step, Transition,AuxCalc, RegCalc.

    Execution Status EnumerationCSCOEXECSTS

    Ok (0)Bypass (1)Info (2)Warning (3)Fail (4)Error (5)OkPaused (6)BypassPaused(7)InfoPaused (8)WarnPaused(9)FailPaused(10)ErrorPaused(11)

    Ok (0) No ViewOnly CEE No

    TypeConvert Execution Status Provides the overalloperation status ofthe TypeConvertfunction block.

    EnumerationTCEXECSTS

    Ok (0)Warning (1)Error (2)

    Ok (0) No ViewOnly CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    71/282

  • 8/10/2019 1757-rm811_-en-p

    72/282

    FAILSTATE[0..numChans-1]

    DOM Shed Mode Shedto Hold enabler.

    Boolean Use SafeState (0)Hold LastOutput State(1)

    Use SafeState (0)

    Yes ApplicationDeveloper

    CEE No SAFE[0..nu

    FAULTDELAY 1797-OB4D Fault DetectionDelay Time

    Enumeration 11 ms12 ms14 ms18 ms26 ms42 ms

    11 ms Yes ApplicationDeveloper

    CEE No FAULLATC

    FAULTENB [ ] 1797-OB4D Enable FaultDetection

    Boolean Off(0)On(1)

    Off(0) Yes ApplicationDeveloper

    CEE No FAULLATC

    FAULTRESET 1797-OB4D Fault Reset Boolean Off(0)On(1)

    Off(0) Yes Engineer CEE No FAULLATC

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    73/282

    FAULTVALUE[0..numChans-1]

    AOM Safe Value (inpercent) Specifiesa safe output valueto be assumed in theevent of a controllerfailure or loss ofcommunication

    between thecontroller and IOM.Note thatSHEDMODE must beenabled in order toconfigure and usethe FAULTVALUE.Note that if the IOMdevice itself fails,the output value isnot deterministic.

    64-Bit RealNumber

    50 formodulesoperatingin voltagemodeonly.-25 for

    modulesoperatingin currentmode (orcurrentandvoltagemodes).

    Yes ApplicationDeveloper

    CEE No SAFE[0..nuDOM

    FBORSTS All RegCtl Blocks:AutoMan, Fanout,OvrdSel, PID, PIDFF,PosProp,PulseCount,

    PulseLength,RampSoak,RemCas, RatioBias,RegCalc, andSwitch.

    Function BlockOverride Status

    EnumerationPTORST

    NotCon (0)Sel (1)NotSel (2)

    NotCon(0)

    No View Only No

    FBTYPE PID Function Block TypeIndicates type ofbase template fromwhich the functionblock was derived.

    EnumerationFBTYPES

    Null PID and all

    RegulatoryControlfunctionblocks

    DataAcqand allAuxiliaryfunctionblocks

    DigComp DisDev All Logic

    functionblocks

    All Utilityfunctionblocks

    Sco

    Null No View Only CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    74/282

    FETCHMODE All IO Channels,PWM Channel,SIFLAGARRCH,SINUMARRCH,SITEXTARRCH

    Fetch Mode - Whenthis mode is set, theIO Channel workswithout the IOMfunction block.

    Integer Off (0) No Engineer CEE No

    FF PIDFF Feed Forward Inputin Engineering Units.

    Real NaN SIFL,

    FFCONN PIDFF Feed Forward InputConnect.

    ApplicationDeveloper

    FFOPT PIDFF Feedforward Option.FFOPT indicates iffeedforward is to beadded to ormultiplied by theincremental PIDoutput.

    Integer 0 Engineer SIFL,

    FFSTS PIDFF Feed Forward InputStatus

    Integer 0 View Only

    FILENUM REQFLAGARRAY,REQNUMARRAY,

    REQTEXTARRAY

    When using PCCC(i.e., when the

    COMMAND isPLC5TypRead orPLC5TypWrite), thisparameter is thePCCC File Name andOffset in the targetdevice. This value isthe Logical ASCIISymbolic Addresswithout the LogicalASCII Identifier. Thefollowing is anexample of a validvalue for thisparameter: N7:0When using CIP (i.e.,when the

    COMMAND isCIPRead orCIPWrite), thisparameter is thename of the file inthe target device.

    String Maximum of40 characters

    NullString

    Yes ApplicationDeveloper

    CEE

    FILTERHDR[0..numChans-1]

    DIM Filter Grid Header String Maximum of20 characters

    NullString

    View Only SR

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    75/282

  • 8/10/2019 1757-rm811_-en-p

    76/282

    FREQPERIOD Pulse Input IOC,Pulse Input w/ FastCutoff IOC

    FrequencyIntegration Period Period at whichModule calculatesfrequency.

    Enumeration 25ms (0)50ms (1)100ms (2)200ms (3)500ms (4)1000ms (5)2000ms (6)

    1000ms(5)

    Yes View Only CEE No

    FREQPERIOD[0..7]

    Pulse Input IOM FrequencyIntegration Period Period at whichModule calculatesfrequency.

    Enumeration 25ms (0)50ms (1)100ms (2)200ms (3)500ms (4)1000ms (5)2000ms (6)

    1000ms(5)

    Yes ApplicationDeveloper

    CEE No

    FTAAOVRNFL Serial InterfaceIOM

    FTA A Overrun Flag Indicates whetherthe FTA currently hastoo many writes toprocess and is in anoverrun condition(value is On) or not(value is Off).

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No FTAB

    FTAASTS Serial InterfaceIOM

    FTA A Status Provides the currentstatus of the FTA.

    Enumeration FtaNotPresnt(0)TfaOk (1)FtaConfig (2)FtaSoftFail (3)

    FtaNotPresnt (0)

    No View Only CEE No FTAB

    FTABOVRNFL Serial InterfaceIOM

    FTA B Overrun Flag Indicates whetherthe FTA currently hastoo many writes toprocess and is in anoverrun condition(value is On) or not(value is Off).

    Boolean Off (0)On (1)

    Off (0) No View Only CEE No FTAA

    FTABSTS Serial InterfaceIOM

    FTA B Status Provides the currentstatus of the FTA.

    Enumeration FtaNotPresnt(0)TfaOk (1)FtaConfig (2)FtaSoftFail (3)

    FtaNotPresnt (0)

    No View Only CEE No FTAA

    G Sel, Selreal G Selector inputvalue

    Boolean Off (0)On (1)

    Off (0) Yes Engineer CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    77/282

    G [1..4].ALGID Transition Gate Algorithm IDG [1].ALGID:Secondary Gate (S)TypeG [2..4].ALGID:Primary Gate (Px)Type

    EnumerationCSCOALGID

    None (0)On (1)Off (2)Connect (3)Not (4)Or (5)Nor (6)

    And (7)Nand (8)Xor (9)

    None (0) Yes ApplicationDeveloper

    CEE No

    G[1..4].FIRSTCOND

    Transition Gate First ConditionHandle

    32-Bit Integer 0 to 10 0 No ViewOnly CEE No

    G[1..4].NUMINPTS

    Transition Gate Number ofInputs

    32-Bit Integer 0 to 10 0 Yes ApplicationDeveloper

    CEE No

    G [1..4].SO Transition Gate Status Output Boolean Off (0)On (1)

    Off (0) No View Only CEE No

    GAINHILM AutoMan, Fanout,PID, PIDFF, PosProp,RegCalc

    Gain High Limit -K,KLIN, andKMODIFEXT will beclamped to this limit.

    64-Bit RealNumber

    Any valuegreater thanGAINLOLM.

    240.00 Yes Engineer CEE No

    GAINLOLM AutoMan, Fanout,PID, PIDFF, PosProp,RegCalc

    Gain Low Limit - K,KLIN, andKMODIFEXT will beclamped to this limit

    64-Bit RealNumber Any value lessthanGAINHILM.

    0.00 Yes Engineer CEE No

    GAINOPT PID, PIDFF Gain Option.Specifies how thePID gain should becalculated.

    EnumerationGAINOPT

    Lin (0): LinearGainGap (1): GapGainNonlin (2):NonlinearGainExt (3):External Gain

    Lin (0) Yes Engineer/ApplicationDeveloper

    CEE No

    GAPHILM PID, PIDFF Gap High Limit.Used if GAINOPT =Gap (configured).

    64-Bit RealNumber

    0.00 Yes Engineer CEE No

    GAPLOLM PID, PIDFF Gap Low Limit.Used if GAINOPT =Gap (configured).

    64-Bit RealNumber

    0.00 Yes Engineer CEE No

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    78/282

    GENSTATE RM General State of theRedundancy Module

    Enumeration Undefined (0)Startup (1)Reload (2)Fault (3)Ok (4)

    Undefined (0)

    No View OnlyRequests toread or storeto any RMparametermust comefrom the

    Supervisoryplatform.

    Not Loaded No

    GENSTATEA RM RM Module GeneralState. For eachmodule in the hostchassis, generalstate of module

    Enumeration[20]

    Undefined (0)Startup (1)Reload (2)Fault (3)Ok (4)

    Undefined (0)

    No View OnlyRequests toread or storeto any RMparametermust comefrom theSupervisoryplatform.

    Not Loaded No

    GOP DevCtl Generic Output (OP) EnumerationGENSTATE

    See below. S0 (4) No OtherFunctionBlock

    CEE No GOPFMODNUMNUMOPFINSAFESAFE

    GOPFINAL DevCtl Generic Field OutputState (OPFINAL)

    EnumerationGENSTATE

    S0 (4)S1 (5)S2 (6)

    S0 (4) No ViewOnly CEE No GOP,NUMNUMOPDO[1..3]

    GOPREQ DevCtl Generic RequestedOutput Value(OPREQ)

    EnumerationGENSTATE

    Null (0)Active (2)Safe (3)S0 (4)S1 (5)S2 (6)

    Null (0) No OtherFunctionBlock

    CEE No CONTOPRENUMSCM

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

    Range

    Active (2): Not configured SafeOP for two state device (i.e., ifSafeOp = State 0, Active will set OP to state 1).

    Safe (3): The state nominated as the SafeOP state on the StateAssignment form.

    S0 (4): State zero as defined on the State Assignment form.

    S1 (5): State one as defined on the State Assignment form.

    S2 (6): State two as defined on the State Assignment form.

  • 8/10/2019 1757-rm811_-en-p

    79/282

    GOPSCADA DevCtl Generic Output forProcessLogix Serverdetail displays - Thisparameterrepresents the threeuser-defined statesso that they may be

    represented clearlyin the detaildisplays.

    EnumerationGENSTATESC

    State_0 (0)State_1 (1)State_2 (2)

    State_0(0)

    No Operator CEE No GOP,

    GPV DevCtl Generic ProcessVariable (PV)

    EnumerationGENSTATE

    Null (0)Inbet (1)S0 (4)S1 (5)S2 (6)

    Null (0) No View Only,OtherFunctionBlock (seeNotes)

    CEE No DIPVGPVANUMNUMPVAUPVSR

    GPVAUTO DevCtl Generic PVAUTO EnumerationGENSTATE

    Null (0)Inbet (1)S0 (4)S1 (5)S2 (6)

    Null (0) No View Only CEE No DIPVGPV, NUMPVAU

    HANDLER Step, Transition,Handler

    Contains the nameof the Handler towhich thatTransition or Stepbelongs.

    BlockId NullString

    No View Only CEE No NUM

    HANDLERREF Handler, Step,Transition

    Internal parameterfor system use only.

    HIALM.PR RegCtl, DevCtl,

    DataAcq, SCM,Flag

    Highest Alarm

    Priority - Indicatesthe priority of thehighest-level alarmthat currently existsfor the functionblock.

    Enumeration

    ALPRIOR

    None (0)

    Journal (1)Low (2)High (3)Urgent (4)

    None (0) No View Only CEE No HIAL

    HIAL

    Parameter Specific toBlock(s)

    Description Data Type Range Default ConfigLoad

    AccessLock

    Residence ActiveConnector

    RelaPara

  • 8/10/2019 1757-rm811_-en-p

    80/282

  • 8/10/2019 1757-rm811_-en-p

    81/282

    HIGHENG[0..numChans-1]

    AIM, AOMThis parameter isconfigurable onlyon the AIM.

    High Engineering (f) 64-Bit RealNumber

    NaN,greater-thanLOWENG

    100.0 AIM: YesAOM: No

    AIM:ApplicationDeveloperAOM: ViewOnly

    CEE No LOW[0..nu

    HIGHSIGNAL[0..numChans-1]

    AIM, AOM High Signal 64-Bit RealNumber

    SeeNotes.

    No View Only CEE No SIPTY[0..nuINPU[0..nuLOW[0..nu

    HISTDESC SCM History ParameterDescriptor

    String Maximum of63 characters.

    NullString

    Yes Engineer CEE No NUM

    HOLDALM.FL SCM Hold Alarm Flag Boolean Off (0)On (1)

    Off (0) No View Only CEE No HOLDHOLD

    HOLDALM.PR SCM Hold Alarm Priority -

    Specifies the alarmpriority for the Holdalarm.

    Enumeration

    ALMPRIOR

    None (0)

    Journal (1)Low (2)High (3)Urgent (4)

    Low (2) Yes Engineer CEE No HOLD

    HOLD

    HOLDALM.SV SCM Hold Alarm Severity- Specifies the alarmseverity for the Holdalarm.

    16-Bit Integer 0 to 15 0 Yes Engineer CEE No HOLDHOLD

    HOLDCMD RampSoak RampSoak Hold Flag Boolean Off (0)On (1)

    Off (0) No OtherFunctionBlock

    C