1756 Series Io Modules
-
Upload
ivam-alvarado -
Category
Documents
-
view
237 -
download
0
Transcript of 1756 Series Io Modules
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 1/158
Technical Data
1756 ControlLogix I/O Modules
Catalog Numbers 1756 series
The ControlLogix architecture provides a wide range of input and outputmodules to span many applications, from high-speed digital to process control.
The ControlLogix architecture uses Producer-Consumer technology, whichallows input information and output status to be shared among multipleControlLogix controllers.
Each ControlLogix I/O module mounts in a ControlLogix chassis andrequires either a removable terminal block (RTB) or a 1492 interface module(IFM) to connect all field-side wiring. RTBs and IFMs are not included with
the I/O modules. They must be ordered separately.
Topic Page
Available 1756 I/O Modules page 2Environmental Specifications - 1756 I/O Modules page 3Digital I/O Modules page 3Analog I/O Modules page 5Specialty I/O Modules page 6Module Specifications page 7ControlLogix I/O Accessories page 156
ControlLogixControllers
Input ModulesOutput Modules
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 2/158
2 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Available 1756 I/O ModulesI/O Type Catalog Number
AC digital 1756-IA8D1756-IA161756-IA16I1756-IA321756-IM16I1756-IN16
page 7page 9page 11page 13page 57page 59
1756-OA81756-OA8D1756-OA8E1756-OA161756-OA16I1756-ON8
page 76page 79page 82page 85page 88page 130
DC digital 1756-IB161756-IB16D1756-IB16I1756-IB16ISOE1756-IC161756-IG161756-IH16I
1756-IH16ISOE1756-IV161756-IV32
page 15page 17page 19page 21page 26page 50page 53
page 55page 71page 73
1756-OB81756-OB8EI1756-OB8I1756-OB16D1756-OB16E1756-OB16I1756-OB16IS
1756-OB321756-OC81756-OG161756-OH8I1756-OV16E1756-OV32E
page 91page 93page 96page 98page 101page 103page 105
page 107page 109page 125page 128page 133page 136
Contact 1756-OW16I page 139 1756-OX8I page 142Analog 1756-IF6CIS
1756-IF6I1756-IF81756-IF16
1756-IF4FXOF2F1756-IR6I1756-IT6I1756-IT6I2
page 28page 32page 36page 43
page 47page 61page 65page 68
1756-OF41756-OF6CI1756-OF6VI1756-OF8
page 111page 114page 117page 119
HART interface 1756-IF8H page 40 1756-OF8H page 122Specialty 1756-CFM
1756-HSCpage 145page 149
1756-PLS page 152
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 3/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 4/158
4 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Module Type Features
1756 digital AC input modules • Change of state: Software configurable
• Timestamp of inputs: ±200μs• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
1756 digital AC output modules • Scheduled outputs: Synchronization within 16.7 seconds maximum, referenCoordinated System Time
• Fault states per point: Hold last state, on or off (off is default)• States in Program mode per point: Hold last state, on or off (off is default)• Fusing:
− 1756-OA8D, 1756-OA8E: Electronically fused per point− 1756-OA16: Mechanically fused/group, 3.15 A @ 250V AC slow blow,
interruption current, Littelfuse p/n H2153.15− All other modules: Not protected. A fused IFM is recommended to prote
(see publication 1492-2.12)• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
1756 digital DC input modules • Reverse polarity protection: All modules except 1756-IG16 module• Change of state: Software configurable• Timestamp of inputs:
− ±100μs for sequence of events modules− ±200μs for all other modules
• Module keying: Electronic, software configurable
• RTB Keying: User-defined mechanical
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 5/158Publication 1756-TD002A-EN-E - May 2009 5
1756 ControlLogix I/O Modu
Analog I/O Modules The 1756 digital I/O modules support these features:
1756 digital DC output modules • Scheduled outputs: Synchronization within 16.7 seconds maximum, referencCoordinated System Time
• Fault states per point: Hold last state, on or off (off is default)• States in Program mode per point: Hold last state, on or off (off is default)• Fusing:
− 1756-OB8EI, 1756-OB16D, 1756-OB16E, 1756-OV16E, 1756-OV32E: fused per point
− All other modules. Not protected. A fused IFM is recommended to protec(see publication 1492-2.12)
• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
1756 digital contact modules • Scheduled outputs: Synchronization within 16.7 seconds maximum, referencCoordinated System Time
• Configurable fault states per point: Hold last state, on or off (off is default)• Configurable states in Program mode per point: Hold last state, on or off (off• Fusing: Not protected. A fused IFM is recommended to protect outputs (See
publication 1492-2.12)• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
Module Type Features
Module Type Features
1756 analog input modules • On-board data alarming• Scaling to engineering units• Real-time channel sampling• Data Format: Integer mode (left justified, 2s complement) IEEE 32-bit float• Module conversion method: Sigma-Delta
1756 analog output modules • Data format: Integer mode (left justified, 2s complement) IEEE 32-bit floati• Module conversion method: R-Ladder DAC, monotonicity with no missing • Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 6/158
6 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Specialty I/O Modules These specialty modules are available:
1756 high-speed analog combination module • Data format: Integer mode (left justified, 2s complement) IEEE 32-bit floati• Input conversion method: Successive approximation• Output conversion method: R-Ladder DAC, monotonicity with no missing c• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
1756 analog RTD and thermocouple modules • Data Format: Integer mode (left justified, 2s complement) IEEE 32-bit float• Module conversion method: Sigma-Delta• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
1756 analog modules with HART interface • Data format: Integer mode (left justified, 2s complement), Floating point IE• Input conversion method: Successive approximation• Output conversion method: R-Ladder DAC, monotonicity with no missing c• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
Module Type Features
Module Type Features
1756-CFM configurable flow meter module The 1756-CFM module provides Totalizer mode for metering applicatfrequency measurements for speed or rate control applications, on two channelconnected to flowmeters.• Totalizer fill and prover• High-resolution 100 kHz max• Frequency 0.0005 Hz resolution• Reverse polarity protection: Outputs only• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical
1756-HSC high-speed counter module The 1756-HSC module provides four high-speed, output-switching, on-module uses pulses for counting and frequency.• Counter: 1 MHz max• Rate Measurement: 500 kHz max• Encoder: 250 kHz max• Debounce filter: 70 Hz max• Module keying: Electronic, software configurable• RTB keying: User-defined mechanical keying
1756-PLS programmable limit switch module The 1756-PLS module supports enhanced packaging applications.• Requires three contiguous slots in chassis• RTB keying: User-defined mechanical
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 7/158Publication 1756-TD002A-EN-E - May 2009 7
1756 ControlLogix I/O Modu
1756-IA8DControlLogix AC (79...132V) diagnostic input module
Diagnostics - 1756-IA8D
Technical Specifications - 1756-IA8D
+5V
12
34
56
78
910
1112
1314
1516
1718
1920
47 kΩ, 1/2W,5% Resistor
47 kΩ, 1/2W
5% Resistor
Not UsedL2-0
L2-0
L2-0
L2-0
L2-1
L2-1
L2-1
L2-1
L2-1
L1-0 Loss of Field PowerIN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
L1-1 Loss of Field Power
Daisy Chain toOther RTBs
Group0
Group 0
Group1Group 1
L2
L1
1756-IA8D
ControlLogixBackplane Interface
ControlLogixBackplane Interface
Display
Simplified Schematic
Input
DisplayOpen Wire
GND
GND
+5V
Attribute 1756-IA8D
Open wire Off-state leakage current 1.5 mA min
Loss of power Transition range 46…85V AC
Timestamp of diagnostics ±1 ms
Attribute 1756-IA8D
Inputs 8 diagnostic (4 points/group)
Voltage category 120V AC
Operating voltage range 79…132V AC,47…63 Hz
Digital filter, off to on 1 or 2 msInput delay, off to on 10 ms + filter
Digital filter, on to off 9 or 18 ms
Input delay, on to off 8 ms + filter
Current draw @ 5.1V 100 mA
Current draw @ 24V 3 mA
Power dissipation, max 4.5 W @ 60 °C
Thermal dissipation 15.35 BTU/hr
AC INPUT
ST
FLT
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
OK
DIAGNOSTIC
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 8/158
8 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IA8D
Off-state voltage, max 20V
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 74V AC
On-state current, max 16 mA @ 132V ACInrush current, max 250 mA
Input impedance, max 8.25 kΩ @ 132V AC, 60 Hz
Cyclic update time 200μs...750 ms
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA8D
Certification (1) 1756-IA8D
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 9/158Publication 1756-TD002A-EN-E - May 2009 9
1756 ControlLogix I/O Modu
1756-IA16ControlLogix AC (79...132V) input module
Technical Specifications - 1756-IA16
12
34
56
78
910
1112
1314
1516
1718
1920
L2 L1
DaisyChain toOtherRTBs
1756-IA16
Group 0
Group 0
Group 1Group 1
IN-1
IN-3
IN-5
IN-7
L2-0
IN-9
IN-11
IN-13
IN-15
L2-1
IN-0
IN-2
IN-4
IN-6
L2-0
IN-8
IN-10
IN-12
IN-14
L2-1
Simplified Schematic
ControlLogixBackplaneInterface
Display
+5V
L2-0
IN-O
GND
Attribute 1756-IA16
Inputs 16 (8 points/group)
Voltage category 120V AC
Operating voltage range 74…132V AC,47…63 Hz
Digital filter, off to on 1 or 2 ms
Input delay, off to on 10 ms + filter
Digital filter, on to off 9 or 18 ms
Input delay, on to off 8 ms + filter
Current draw @ 5.1V 105 mA
Current draw @ 24V 2 mA
Power dissipation, max 5.8 W @ 60 °C
Thermal dissipation 18.41 BTU/hr
Off-state voltage, max 20V
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 74V AC
On-state current, max 13 mA @ 132V AC
AC INPUT
ST
FLT
0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7
OK
DIAGNOSTIC
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 10/158
10 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IA16
Inrush current, max 250 mA peak (decaying to <37% in 22 ms, withactivation)
Input impedance, max 10.15 kΩ @ 132V AC, 60 Hz
Cyclic update time 100μs...750 msIsolation voltage 250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size0.324...2.08 mm
2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA16
Certification (1) 1756-IA16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 11/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 12/158
12 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IA16I
Input impedance, max 8.8 kΩ @ 132V AC, 60Hz
Cyclic update time 100μs...750 ms
Isolation voltage 250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA16I
Certification (1) 1756-IA16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 13/158Publication 1756-TD002A-EN-E - May 2009 13
1756 ControlLogix I/O Modu
1756-IA32ControlLogix AC (74...132V) input module
Technical Specifications - 1756-IA32
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
IN-0IN-2IN-4IN-6IN-8IN-10IN-12IN-14
IN-16IN-18IN-20IN-22IN-24IN-26IN-28IN-30L2-1
L2-0
IN-1IN-3IN-5IN-7IN-9
IN-11IN-13IN-15L2-0
IN-17IN-19IN-21IN-23IN-25IN-27IN-29IN-31L2-1
L1
L2
Daisy Chainto Other RTBs
1puorG1puorG
0puorG0puorG
1756-IA32Simplified Schematic
ControlLogixBackplaneInterface
Display
+5V
L2-0
IN-O
GND
Attribute 1756-IA32Inputs 32 diagnostic (4 points/group)
Voltage category 120V AC
Operating voltage range 74…132V AC,47…63 Hz
Digital filter, off to on 1 or 2 ms
Input delay, off to on 10 ms + filter
Digital filter, on to off 9 or 18 ms
Input delay, on to off 8 ms + filter
Current draw @ 5.1V 165 mA
Current draw @ 24V 2 mA
Power dissipation, max 6.1 W @ 60 °CThermal dissipation 20.8 BTU/hr
Off-state voltage, max 20V
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 74V AC
On-state current, max 15 mA @ 132V AC
Inrush current, max 390 mA
Input impedance, max 14.0 kΩ @ 132V AC, 60 Hz
AC INPUT
OK
ST 0 1 2 3 4 5 6 7
ST 8 9 1
0 21 3 4 51 1 1 11
ST 6 718 09 1 2 3
1 2 2 221 1
ST 4 526 87 9 0 1
2 2 2 332 2
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 14/158
14 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IA32
Cyclic update time 200μs...750 ms
Isolation voltage 250V continuousI/O group to group, I/O to system
Removable terminal block housing 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IA32
Certification (1) 1756-IA32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 15/158Publication 1756-TD002A-EN-E - May 2009 15
1756 ControlLogix I/O Modu
1756-IB16ControlLogix DC (10...31.2V) input module
Technical Specifications - 1756-IB16
1756-IB16
IN-9
IN-11
IN-13
IN-15
GND-1
IN-1
IN-3
IN-5
IN-7
GND-0
IN-8
IN-10
IN-12
IN14
GND-1
IN-0
IN-2
IN-4
IN-6
GND-0
?
??
??
??
?
?
??
??
??
??
Daisy Chainto OtherRTBs
Group 0
Group 0
Group 1Group 1
DC COM
- +
ControlLogixBackplaneInterface
Simplified Schematic
Display
GND
GND-0
IN-0+5V
Attribute 1756-IB16
Inputs 16 (8 points/group)
Voltage category 12/24V DC sink
Operating voltage range 10...31.2V DC
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 1 ms + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 2 ms + filter
Current draw @ 5.1V 100 mA
Current draw @ 24V 2 mA
Power dissipation, max 5.1 W @ 60 °C
Thermal dissipation 17.39 BTU/hr
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10V DC
On-state current, max 10 mA @ 31.2V DC
DC INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 1112131415
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 16/158
16 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IB16
Inrush current, max 250 mA peak (decaying to < 37% in 22 ms, withactivation)
Input impedance, max 3.12 kΩ @ 31.2V DC
Cyclic update time 100μs...750 msIsolation voltage 250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size0.324...2.08 mm
2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16
Certification (1) 1756-IB16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 17/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 18/158
18 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IB16D
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10V DC
On-state current, max 13 mA @ 30V DC
Inrush current, max 250 mAInput impedance, max 2.31 kΩ @ 30V DC
Cyclic update time 200μs...750 ms
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16D
Certifications (1) 1756-IB16D
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 19/158Publication 1756-TD002A-EN-E - May 2009 19
1756 ControlLogix I/O Modu
1756-IB16IControlLogix DC (10...30V) isolated input module
Technical Specifications 1756-IB16I
1 2
3 4
5 6
7 8
01 9
21 11
41 31
61 51
81 71
02 91
22 12
42 32
62 52
82 72
03 92
23 13
43 33
63 53
(+)(+)
+–
+–
Non isolatedwWir in g
Isolated Wir in g
Daisy Chain to Other RTBs
1756-IB16I
GND-0GND-1
GND-2GND-3
GND-8
GND-4
GND-5
GND-6
GND-7
Not Used
GND-9
GND-10
GND-11
GND-12
GND-13GND-14
GND-15
GND-15
IN-0IN-1
IN-2IN-3
IN-8
IN-4
IN-5
IN-6
IN-7
Not Used
IN-9
IN-10IN-11
IN-12
IN-13IN-14
IN-15
Not Used
DC-5 (-)
DC(-)
Jumper Bar (Cut to Length)
DC-6 (-)DC-5 (+)DC-6 (+)
DC(+)
DC-0 (+)
DC-1 (+)
DC-0 (-)
DC-1 (-)
Sour ce In pu t Wir in g
Sin k In pu t Wir in g
ControlLogixBackplaneInterface
Simplified Schematic
Display
GND-0
GND
IN-0+5V
Attribute 1756-IB16I
Inputs 16 individually isolated
Voltage category 12/24V DC sink/source
Operating voltage range 10...30V DC
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 1 ms + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 4 ms + filter
Current draw @ 5.1V 100 mA
Current draw @ 24V 3 mAPower dissipation, max 5 W @ 60 °C
Thermal dissipation 17.05 BTU/hr
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10 V DC
On-state current, max 10 mA @ 30V DC
Inrush current, max 250 mA peak (decaying to < 37% in 22 ms, withactivation)
DC INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 101112 13 14 15
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 20/158
20 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IB16I
Input impedance, max 3 kΩ @ 30V DC
Cyclic update time 100μs...750 ms
Isolation voltage 250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16I
Certification (1) 1756-IB16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 21/158Publication 1756-TD002A-EN-E - May 2009 21
1756 ControlLogix I/O Modu
1756-IB16ISOEControlLogix DC (10...55V) sequence of events input module
Technical Specifications - 1756-IB16ISOE
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non isolatedWir in g
Isolated Wir in g
Daisy Chain to Other RTBs
DC (-)
Jumper Bar(Cut to Length)
)+(6-CD)-(6-CD
DC (+)
DC-0 (+)DC-1 (+)
DC-0 (-)
DC-5 (-)
IN-0IN-1IN-2IN-3
IN-8
IN-4IN-5IN-6IN-7
Not Used
IN-9IN-10IN-11IN-12IN-13IN-14IN-15Not Used
GND-0GND-1GND-2GND-3
GND-8
GND-4GND-5GND-6GND-7
Not Used
GND-9GND-10GND-11GND-12GND-13GND-14GND-15GND-15
DC-5 (+)
Sin k In pu t Wir in g
Sour ce In pu t Wir in gSour ce In pu t Wir in g
Sin k In pu t Wir in g
1756-IB16ISOE
ControlLogixBackplaneInterface
Simplified Schematic
Display
GND-0
IN-0
Electronic CurrentLimit Circuit
+5V
Attribute 1756-IB16ISOE(1)
Inputs 16 individually isolated, sequence of events
Voltage category 24/48V DC sink/sourceOperating voltage range 10...55V DC
Digital filter, off to on 0…50 ms
Input delay, off to on Hardware delay (10 μs nominal/20 μ s max)+ Firmware scan (up to 25μs)+ Input filter time (user selectable time: 0ms...50ms)+ ASIC delay (175μs - FIFO/625μs - Coordinated SystemTime per point)
Input delay, on to off Hardware delay (25 μs nominal/50 μ s max)+ Firmware scan (up to 25μs)+ Input filter time (user selectable time: 0ms...50ms)+ ASIC delay (175μs - FIFO/625μs - Coordinated SystemTime per point)
Current draw @ 5.1V 320 mA§
Current draw @ 24V 2 mA
Power dissipation, max 5.5 W @ 60 °C
Thermal dissipation 17.22 BTU/hr
Off-state voltage, max 5V
Off-state current, max 1.5 mA
On-state current, min 2.0 mA @ 9V DC
On-state current, max 5.1 mA @ 48…55V DC
SOE INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 22/158
22 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IB16ISOE
Input impedance, max 10.8 kΩ @ 55V DC
Cyclic update time 250μs...750 ms
Isolation voltage 250V continuous, inputs to system
125V continuous, channel to channelRemovable terminal block 1756-TBCH
1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mmin.) insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-Smodule to coordinate system time.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB16ISOE(1)
Certification (1) 1756-IB16ISOE
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 23/158Publication 1756-TD002A-EN-E - May 2009 23
1756 ControlLogix I/O Modu
1756-IB32ControlLogix DC (10...31.2V) input module
Diagnostics - 1756-IB32
Technical Specifications - 1756-IB32
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+–
Daisy Chainto Other RTBs
DC COM
0puorG0puorG
1puorG1puorG
1756-IB32
IN-1IN-3IN-5IN-7
GND-0
IN-9IN-11IN-13IN-15
GND-1
IN-17IN-19IN-21IN-23IN-25IN-27IN-29IN-31
IN-0IN-2IN-4IN-6
GND-0
IN-8IN-10IN-12IN-14
GND-1
IN-16IN-18IN-20IN-22IN-24IN-26IN-28IN-30
ControlLogixBackplaneInterface
Simplified Schematic
Display
GND-0
GND
IN-0+5V
Attribute 1756-IB32
Change of state Software configurable
Timestamp of diagnostics ±200μs
Attribute 1756-IB32
Inputs 32 (16 points/group)
Voltage category 12/24V DC sinkOperating voltage range 10...31.2V DC
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 380μs + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 420μs + filter
Current draw @ 5.1V 120 mA
Current draw @ 24V 2 mA
DC INPUT
O
K
ST 0 1 2 3 4 5 6 7
ST 8 9 1
0 21 3 4 51 1 1 11
ST 6 718 09 1 2 3
1 2 2 221 1
ST 4 526 87 9 0 1
2 2 2 332 2
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 24/158
24 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Power dissipation, max 6.2 W @ 60 °C
Thermal dissipation 21.1 BTU/hr @ 60 °C
Off-state voltage, max 5V
Off-state current, max 1.5 mAOn-state current, min 2 mA
On-state current, max 5.5 mA
Inrush current, max 250 mA (decaying to < 37% in 22 ms, without ac
Input impedance, max 5.67 kΩ @ 31.2V DC
Cyclic update time 100μs...750 ms
Isolation voltage 250V (continuous), Reinforced Insulation Type bInput group to system250V (continuous), Basic insulation type between Ingroup to Input groupRoutine tested at 1900V AC for 2 s, between Input gto Input group and Input group to system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module Location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1 - on signal ports(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IB32
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 25/158Publication 1756-TD002A-EN-E - May 2009 25
1756 ControlLogix I/O Modu
Certifications - 1756-IB32
Certification (1) 1756-IB32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 26/158
26 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-IC16ControlLogix DC (30...60V) input module
Technical Specifications - 1756-IC16
12
34
56
78
910
1112
1314
1516
1718
1920
+–Daisy Chain toOther RTBs
1756-IC16
Group 0Group 0
Group 1Group 1
IN-1
IN-3
IN-5
IN-7
GND-0
IN-9
IN-11
IN-13
IN-15
GND-1
IN-0
IN-2
IN-4
IN-6
GND-0
IN-8
IN-10
IN-11
IN-14
GND-1
DC COM
Simplified Schematic
GND-0
IN-0
ControlLogixBackplaneInterface
Display
GND
+5V
Attribute 1756-IC16
Inputs 16 (8 points/group)
Voltage category 48V DC sink
Operating voltage range 30...55V DC @ 60 °C30...60V DC @ 55 °C
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 1 ms + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 4 ms + filter
Current draw @ 5.1V 100 mA
Current draw @ 24V 3 mA
Power dissipation, max 5.2 W @ 60 °C
Thermal dissipation 17.73 BTU/hr
Off-state voltage, max 10V
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 30V DC
DC INPUT
S T 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 27/158Publication 1756-TD002A-EN-E - May 2009 27
1756 ControlLogix I/O Modu
Certifications - 1756-IC16
On-state current, max 7 mA @ 60V DC
Inrush current, max 250 mA
Input impedance, max 8.57 kΩ @ 60V DC
Cyclic update time 200μs...750 msIsolation voltage 250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IC16
Certification (1) 1756-IC16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 28/158
28 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-IF6CISControlLogix sourcing current loop analog input module
+
–
12
34
56
78
910
1112
1314
1516
1718
1920
VOUT-1
IN-1/I
RTN-1
VOUT-3
IN-3/I
RTN-3
Not Used
VOUT-5
IN-5/I
RTN-5
VOUT-0
IN-0/I
RTN-0
VOUT-2
IN-2/I
RTN-2
Not Used
VOUT-4
IN-4/I
RTN-4
2-wireTransmitter
Shield Ground
i
1756-IF6CIS 2-wire Tran smitte r Conn ected to the Mod u le a n d theModu le Providin g 24V DC Loop Power
+–
12
34
56
78
910
1112
1314
1516
1718
1920
VOUT-1
IN-1/I
RTN-1
VOUT-3
IN-3/I
RTN-3
Not Used
VOUT-5
IN-5/I
RTN-5
VOUT-0
IN-0/I
RTN-0
VOUT-2
IN-2/I
RTN-2
Not Used
VOUT-4
IN-4/I
RTN-4
2-wireTransmitter24V DC
Shield Ground
1756-IF6CIS 2-wire Tran smitte r Conn ected to the Mod u le a n d anExtern al, User -provided Powe r Su pply Providin g 24V DC Loop Power
• Do not connect more than two wires to any single terminal.• Place additional loop devices (e.g. strip chart recorders) at
either A location in the current loop.
• If separate power sources are used, do not exceed thespecified isolation voltage.
• Do not connect more than two wires to any single terminal.• Place additional loop devices (such as strip chart recorders) at
either A location in the current loop.
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 29/158Publication 1756-TD002A-EN-E - May 2009 29
1756 ControlLogix I/O Modu
Technical Specifications - 1756-IF6CIS
+
–
12
34
56
78
910
1112
1314
1516
1718
1920
VOUT-1
IN-1/I
RTN-1
VOUT-3
IN-3/I
RTN-3
Not Used
VOUT-5
IN-5/I
RTN-5
VOUT-0
IN-0/I
RTN-0
VOUT-2
IN-2/I
RTN-2
Not Used
VOUT-4
IN-4/I
RTN-4
4-wireTransmitter
24V DC
Shield Ground
+
–
1756-IF6CIS 4-wire Tran smitte r Conn ected to the Mod u le a n d an
Extern al, User-provided Powe r Su pply Providin g 24V DC Loop Power
• If separate power sources are used, do not exceed the specifiedisolation voltage.
• Do not connect more than two wires to any single terminal.• Place additional loop devices (such as strip chart recorders) at
either A location in the current loop.
Input Signal to User Count Conversion - 1756-IF6CIS
Range Low Signal and User Counts High Signal and User Counts
0…20 mA 0 mA-32768 counts
21.09376 mA32767 counts
Attribute 1756-IF6CISInputs 6 individually isolated current sourcing
Input range 0…21 mA
Resolution 16 bits0.34μA/bit
Current draw @ 5.1V 250 mA
Current draw @ 24V 275 mA
Power dissipation, max 5.1 W @ 60 °C
Thermal dissipation 17.4 BTU/hr
ANALOG INPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 30/158
30 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Input impedance 215Ω, approx
Open circuit detection time Zero reading within 5 s
Overvoltage protection, max 30V AC/DC with PTC and sense resistor
Normal mode noise rejection 60 dB @ 60 Hz(1)
Common mode noise rejection 120 dB @ 60 Hz100 dB @ 50 Hz
Channel bandwidth 3…262 Hz (-3 dB)(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy 25 °C Better than 0.1% of range
Calibration interval 12 months
Offset drift 200μA/°C
Gain drift with temperature 17 ppm/°C, 35 ppm/°C max0.36μA/°C, 0.74μA/°C max
Module error 0.2% of range
Module input scan time, min 25 ms min – floating point10 ms min – integer
Isolation voltage 250V continuousTested at 1900V DC for 60 s, channel to channelTested at 3250V DC for 60 s, channels to system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6
in.) insulation(2)
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF6CIS
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 31/158Publication 1756-TD002A-EN-E - May 2009 31
1756 ControlLogix I/O Modu
Certifications - 1756-IF6CIS
Certification (1) 1756-IF6CIS
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 32/158
32 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-IF6IControlLogix isolated voltage/current analog input module
12
34
56
78
910
1112
1314
1516
1718
1920
+–
i
A
A
2-wireTransmitter
IN-1/V
IN-1/I
RET-1
IN-3/V
IN-3/I
RET-3
Not Used
IN-5/V
IN-5/I
RET-5
IN-0/V
IN-0/I
RET-0
IN-2/V
IN-2/I
RET-2
Not Used
IN-4/V
IN-4/I
RET-4
1756-IF6I Curr en t 2-wire
+
–
12
34
56
78
910
1112
1314
1516
1718
1920
iA
A
IN-1/V
IN-1/I
RET-1
IN-3/V
IN-3/I
RET-3
Not Used
IN-5/V
IN-5/I
RET-5
IN-0/V
IN-0/I
RET-0
IN-2/V
IN-2/I
RET-2
Not Used
IN-4/V
IN-4/I
RET-4
Shield Ground
4-wireTransmitter
1756-IF6I Curr en t 4-wire
• Place additional loop devices (such as strip chart recorders) ateither A location.
• Place additional loop devices (such as strip chart recorders) ateither A location.
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 33/158Publication 1756-TD002A-EN-E - May 2009 33
1756 ControlLogix I/O Modu
+
–
12
34
56
78
910
1112
1314
1516
1718
1920
DeviceExternalPower
1756-IF6I VoltageVoltage Input
Shield Ground
User AnalogInput Device
IN-1/V
IN-1/I
RET-1
IN-3/V
IN-3/I
RET-3
Not Used
IN-5/V
IN-5/I
RET-5
IN-0/V
IN-0/I
RET-0
IN-2/V
IN-2/I
RET-2
Not Used
IN-4/V
IN-4/I
RET-4
• Do not connect more than 2 wires to any single terminal.
Input Signal to User Count Conversion - 1756-IF6I
Range Low Signal and User Counts High Signal and User Counts
±10V -10.54688V-32768 counts
10.54688V32767 counts
0…10V 0V-32768 counts
10.54688V32767 counts
0…5V 0V-32768 counts
5.27344V32767 counts
0…20 mA 0 mA-32768 counts
21.09376V32767 counts
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 34/158
34 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Technical Specifications - 1756-IF6I
Attribute 1756-IF6I
Inputs 6 individually isolated
Input range ±10.5V0…10.5V0…5.25V0…21 mA
Resolution 16 bits10.5V: 343μV/bit0…10.5V: 171μV/bit0…5.25V: 86μV/bit0…21 mA: 0.34μA/bit
Current draw @ 5.1V 250 mA
Current draw @ 24V 100 mA
Power dissipation, max Voltage: 3.7 WCurrent: 4.3 W
Thermal dissipation Voltage: 12.62 BTU/hrCurrent: 14.32 BTU/hr
Input impedance Voltage: > 10 MΩCurrent: 249 Ω
Open circuit detection time Positive full scale reading within 5 s
Overvoltage protection, max Voltage: 120V AC/DCCurrent: 8V AC/DC (with on-board current resistor)
Normal mode noise rejection 60 dB @ 60 Hz(1)
Common mode noise rejection 120 dB @ 60 Hz100 dB @ 50 Hz
Channel bandwidth 15 Hz (-3 dB)(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy 25 °C Better than 0.1% of range
Calibration interval 6 months
Offset drift 2μV/°C
Gain drift with temperature Voltage: 35 ppm/°C, 80 ppm/°C maxCurrent: 45 ppm/°C, 90 ppm/°C max
Module error 0.54% of range
Module input scan time, min 25 ms min – floating point10 ms min – integer(1)
Isolation voltage 250V continuousTested at 1700V DC for 1 s, channel to channel, chanto system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
Wire category 2(3)
ANALOG INPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 35/158Publication 1756-TD002A-EN-E - May 2009 35
1756 ControlLogix I/O Modu
Certifications - 1756-IF6I
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF6I
Certification (1) 1756-IF6I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 36/158
36 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-IF8ControlLogix voltage/current analog input module
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
i
i
1756-IF8 Differen tial Curr en t
A
A
ShieldGround
Channel 0
Channel 3
JumperW ires
2-wireTransmitter
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
Not Used
Not UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot Used
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
Not Used
Not UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot Used
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+
–
+
–
1756-IF8 Differen tial Voltage
Shield Ground
Channel 0
Channel 3
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
Not Used
Not UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot Used
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
Not Used
Not UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot Used
Shield Ground
• Use this table when wiring your module in differential mode.
• All terminals marked RTN are connected internally.• A 249-current loop resistor is located between IN-x and i RTN-x
terminals.• If multiple (+) or multiple (-) terminals are tied together, connect
that tie point to a RTN terminal to maintain the module’s
accuracy.• Place additional loop devices (such as strip chart recorders) at
the A location in the current loop.• Do not connect more than two wires to any single terminal.
IMPORTANT: When operating in 2 channel, High Speed mode, only usechannels 0 and 2.
This channel Uses these terminals
Channel 0 IN-0 (+), IN-1 (-), i RTN-0
Channel 1 IN-2 (+), IN-3 (-), i RTN-2
Channel 2 IN-4 (+), IN-5 (-), i RTN-4
Channel 3 IN-6 (+), IN-7 (-), i RTN-6
• Use this table when wiring your module in differential mo
• All terminals marked RTN are connected internally.• If multiple (+) or multiple (-) terminals are tied together, c
that tie point to a RTN terminal to maintain the module’saccuracy.
• Terminals marked RTN or iRTN are not used for different
voltage wiring.• Do not connect more than two wires to any single termina
IMPORTANT: When operating in 2 channel, High Speed mode, onlchannels 0 and 2.
This channel Uses these terminalsChannel 0 IN-0 (+), IN-1 (-)
Channel 1 IN-2 (+), IN-3 (-)
Channel 2 IN-4 (+), IN-5 (-)
Channel 3 IN-6 (+), IN-7 (-)
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 37/158Publication 1756-TD002A-EN-E - May 2009 37
1756 ControlLogix I/O Modu
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
27282930
3132
3334
3536
i
i
A
Shield Ground
Channel 0
Channel 5
JumperW ires
2-wireTransmitter
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
Not Used
Not UsedNot UsedNot UsedNot Used
Not UsedNot UsedNot UsedNot Used
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
Not Used
Not UsedNot UsedNot UsedNot Used
Not UsedNot UsedNot UsedNot Used
1756-IF8 Sin gle-e n ded Curr en t
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+
–
+
–
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
Not Used
Not UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot Used
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
Not Used
Not UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot Used
Shield Ground
Channel 0
Channel 1
Shield Ground
1756-IF8 Sin gle-e n ded Voltage
• All terminals marked RTN are connected internally.• For current applications, all terminals marked iRTN must be
wired to terminals marked RTN.• A -49 current loop resistor is located between IN-x and i RTN-x
terminals.• Place additional loop devices (such as strip chart recorders) at
the A location in the current loop.• Do not connect more than two wires to any single terminal.
• All terminals marked RTN are connected internally.• Terminals marked iRTN are not used for single-ended volt
wiring.• Do not connect more than two wires to any single termina
Input Signal to User Count Conversion - 1756-IF8
Range Low Signal and User Counts High Signal and User Counts
±10V -10.25V
-32768 counts
10.25V
32767 counts0…10V 0V
-32768 counts10.25V32767 counts
0…5V 0V-32768 counts
5.125V32767 counts
0…20 mA 0 mA-32768 counts
20.58V32767 counts
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 38/158
38 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Technical Specifications - 1756-IF8
Attribute 1756-IF8
Inputs 8 single-ended4 differential2 high-speed differential
Input range ±10.25V0...10.25V0...5.125V0…20.5 mA
Resolution ±10.25V: 320μV/cnt (15 bits plus sign bipolar)0…10.25V: 160μV/cnt (16 bits)0…5.125V: 80μ /V cnt (16 bits)0…20.5mA: 0.32μA/cnt (16 bits)
Current draw @ 5.1V 150 mA
Current draw @ 24V 40 mA
Power dissipation, max Voltage: 1.73 WCurrent: 2.33 W
Thermal dissipation Voltage: 5.88 BTU/hrCurrent: 7.92 BTU/hr
Input impedance Voltage: >1 MΩCurrent: 249Ω
Open circuit detection time Differential voltage: Positive full scale reading Single-ended/diff. current: Negative full scale readinwithin 5 sSingle-ended voltage: Even numbered channels go tpositive full scale reading within 5 s, odd numberedchannels go to negative full scale reading within 5 s
Overvoltage protection, max Voltage: 30V DCCurrent: 8V DC
Normal mode noise rejection >80 dB @ 50/60 Hz(1)
Common mode noise rejection >100 dB @ 50/60 Hz
Calibrated accuracy 25 °C Voltage: Better than 0.05% of rangeCurrent: Better than 0.15% of range
Calibration interval 12 months
Offset drift 45μV/°C
Gain drift with temperature Voltage: 15 ppm/°CCurrent: 20 ppm/°C
Module error Voltage: 0.1% of rangeCurrent: 0.3% of range
Module input scan time, min 8 pt single-ended (floating point): 16…488 ms4 pt differential (floating point): 8…244 ms2 pt differential (floating point): 5…122 m(1)
Isolation voltage Tested at 2500V DC for 1 s, field-side to system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
ANALOG INPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 39/158Publication 1756-TD002A-EN-E - May 2009 39
1756 ControlLogix I/O Modu
Certifications - 1756-IF8
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF8
Certification (1) 1756-IF8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 40/158
40 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-IF8HControlLogix voltage/current analog input module with HART protocol
Technical Specifications - 1756-IF8H
RTN
IN4+
IN4-
IN5+
IN5-
RTN
IN6+
IN6-
IN7+
IN7-
IN0+
IN0-
IN1+
IN1-
IN2+
IN2-
IN3+
IN3-
IRTN-0
NC
IRTN-1
NC
IRTN-2
NC
IRTN-3
NC
RTN
IRTN-4
NC
IRTN-5
NC
RTN
IRTN-6
NC
IRTN-7
NC
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
2-wire Current Input2WireXMTR
+-
24V DCPowerSupply
+-
24VDCPowerSupply
4-wire Current Input
4WireXMTR
+ +
- -
+ -
1756-IF8H Curr en t
RTN
IN4+
IN4-
IN5+
IN5-
RTN
IN6+
IN6-
IN7+
IN7-
IN0+IN0-
IN1+
IN1-
IN2+
IN2-
IN3+
IN3-
I RTN-0NC
I RTN-1
NC
I RTN-2
NC
I RTN-3
NC
RTN
I RTN-4
NC
I RTN-5
NC
RTN
I RTN-6
NC
I RTN-7
NC
24
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
13
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
+V
- V
Voltage Input1756-IF8H Voltage
Input Signal to User Count Conversion - 1756-IF8H
Range Low Signal and User Counts High Signal and User Counts
±10V -10.25V-32768 counts
10.25V32767 counts
0…10V 0V-32768 counts
10.25V32767 counts
0…5V 0V-32768 counts
5.125V32767 counts
0…20 mA 0 mA-32768 counts
20.58V32767 counts
Attribute 1756-IF8H
Inputs 8 differential voltage or current
Input range ±10V0...5V1…5V0...10V0…20 mA4…20 mA
Resolution 16…21 bits
Current draw @ 5V 300 mA
Current draw @ 24V 70 mA
Power dissipation, max Voltage: 3.21 WCurrent: 4.01 W
Thermal dissipation Voltage: 11.0 BTU/hrCurrent: 13.7 BTU/hr
ANALOG OUTPUT
CAL
OK
HART
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 41/158Publication 1756-TD002A-EN-E - May 2009 41
1756 ControlLogix I/O Modu
Input impedance > 1 MΩ voltage250Ω current
Open circuit detection time Positive full scale reading within 5 s
Overvoltage protection, max Voltage: 30V DCCurrent: 8V DC
Normal mode noise rejection > 80 dB @ 50/60 Hz
Common mode noise rejection > 100 dB @ 50/60 Hz
Calibrated accuracy Voltage: Better than 0.05% of rangeCurrent: Better than 0.15% of range
Calibration interval 12 months
Offset drift 90μV/°C
Gain drift with temperature Voltage: 10 ppm/°CCurrent: 20 ppm/°C
Module error Voltage: 0.1% of rangeCurrent: 0.3% of range
Module input scan time, min 18...488 ms (filter dependent)
Module HART scan time Typically 1 s per HART channel enabled. Estimall 8 channels have HART enabledPass through messages, handheld communicators,secondary masters, communication errors, orconfiguration changes can significantly increase theupdate time
Isolation voltage 50 V (continuous), Basic Insulation TypeTested at 1500V AC for 60 s, I/O to backplane
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.25...2.5 mm2 (22…14 AWG) stranded, 1.2 mm (3/64in.) insulation(1)
Wire category 2 - on signal ports(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF8H
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 42/158
42 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IF8H
Certification (1) 1756-IF8H
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 43/158Publication 1756-TD002A-EN-E - May 2009 43
1756 ControlLogix I/O Modu
1756-IF16ControlLogix voltage/current analog input module
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
ShieldGround
Channel 0
Channel 3
JumperW ires
i
i
A
2-wireTransmitter A
1756-IF16 Differen tial Curr en t
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
IN-15
IN-8IN-9IN-10IN-11RTNIN-12IN-13IN-14
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
i RTN-15
i RTN-8i RTN-9i RTN-10i RTN-11RTNi RTN-12i RTN-13i RTN-14
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+
–
+
–
Shield Ground
Channel 0
Channel 3
1756-IF16 Differen tial Voltage
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
IN-15
IN-8IN-9IN-10IN-11
RTNIN-12IN-13IN-14
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
i RTN-15
i RTN-8i RTN-9i RTN-10i RTN-11
RTNi RTN-12i RTN-13i RTN-14
Shield Ground
• Use this table when wiring your module in differential mode.
• All terminals marked RTN are connected internally.• A 249-current loop resistor is located between IN-x and i RTN-x
terminals.
• If multiple (+) or multiple (-) terminals are tied together, connectthat tie point to a RTN terminal to maintain the module’saccuracy.
• Place additional loop devices (such as strip chart recorders) atthe A location in the current loop.
• Do not connect more than two wires to any single terminal.IMPORTANT: When operating in 4 channel, High Speed mode, only usechannels 0, 2, 4 and 6.
This channel Uses these terminals
Channel 0 IN-0 (+), IN-1 (-), i RTN-0
Channel 1 IN-2 (+), IN-3 (-), i RTN-2
Channel 2 IN-4 (+), IN-5 (-), i RTN-4
Channel 3 IN-6 (+), IN-7 (-), i RTN-6
Channel 4 IN-8 (+), IN-9 (-), i RTN-8
Channel 5 IN-10 (+), IN-11 (-), i RTN-10
Channel 6 IN-12 (+), IN-13 (-), i RTN-12
Channel 7 IN-14 (+), IN-15 (-), i RTN-14
• Use this table when wiring your module in differential
• All terminals marked RTN are connected internally.• If multiple (+) or multiple (-) terminals are tied togethe
that tie point to a RTN terminal to maintain the module
accuracy.• Terminals marked RTN or iRTN are not used for differ
voltage wiring.• Do not connect more than two wires to any single term
IMPORTANT: When operating in 4 channel, High Speed mode, ochannels 0, 2, 4 and 6.
This channel Uses these terminals
Channel 0 IN-0 (+), IN-1 (-)
Channel 1 IN-2 (+), IN-3 (-)
Channel 2 IN-4 (+), IN-5 (-)
Channel 3 IN-6 (+), IN-7 (-)
Channel 4 IN-8 (+), IN-9 (-)
Channel 5 IN-10 (+), IN-11 (-)
Channel 6 IN-12 (+), IN-13 (-)
Channel 7 IN-14 (+), IN-15 (-)
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 44/158
44 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
27282930
3132
3334
3536
ShieldGround
JumperW ires
i
i
A
2-wireTransmitter
1756-IF16 Sin gle-en ded Curr en t
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
IN-15
IN-8IN-9IN-10IN-11
RTNIN-12IN-13IN-14
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
i RTN-15
i RTN-8i RTN-9i RTN-10i RTN-11
RTNi RTN-12i RTN-13i RTN-14
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
27282930
3132
3334
3536
+
–
+
–
ShieldGround
1756-IF16 Sin gle-e n ded Voltage
IN-0IN-1IN-2IN-3
IN-7
RTNIN-4IN-5IN-6
IN-15
IN-8IN-9IN-10IN-11
RTNIN-12IN-13IN-14
i RTN-0i RTN-1i RTN-2i RTN-3
i RTN-7
RTNi RTN-4i RTN-5i RTN-6
i RTN-15
i RTN-8i RTN-9i RTN-10i RTN-11
RTNi RTN-12i RTN-13i RTN-14
ShieldGround
• All terminals marked RTN are connected internally.• For current applications, all terminals marked iRTN must be
wired to terminals marked RTN.
• A 249-current loop resistor is located between IN-x and i RTN-x terminals.• Place additional loop devices (such as strip chart recorders) at
the A location in the current loop.• Do not connect more than two wires to any single terminal.
• All terminals marked RTN are connected internally.• Terminals marked iRTN are not used for single-ended volt
wiring.
• Do not connect more than two wires to any single termina
Input Signal to User Count Conversion - 1756-IF16
Range Low Signal and User Counts High Signal and User Counts
±10V -10.25V-32768 counts
10.25V32767 counts
0…10V 0V-32768 counts
10.25V32767 counts
0…5V 0V-32768 counts
5.125V32767 counts
0…20 mA 0 mA-32768 counts
20.58V32767 counts
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 45/158Publication 1756-TD002A-EN-E - May 2009 45
1756 ControlLogix I/O Modu
Technical Specifications - 1756-IF16
Attribute 1756-IF16
Inputs 16 single ended, 8 differential or 4 differential (highspeed)
Input range ±10.5V0…10.5V0…5.25V0…21 mA
Resolution 16 bits10.5V: 343μV/bit0…10.5V: 171μV/bit0…5.25V: 86μV/bit0…21 mA: 0.34μA/bit
Current draw @ 5.1V 250 mA
Current draw @ 24V 100 mA
Power dissipation, max Voltage: 3.7 WCurrent: 4.3 W
Thermal dissipation Voltage: 12.62 BTU/hrCurrent: 14.32 BTU/hr
Input impedance Voltage: >10 MΩCurrent: 249Ω
Open circuit detection time Positive full scale reading within 5 s
Overvoltage protection, max Voltage: 120V AC/DCCurrent: 8V AC/DC (with on-board current resistor)
Normal mode noise rejection 60 dB @ 60 Hz(1)
Common mode noise rejection 120 dB @ 60 Hz100 dB @ 50 Hz
Channel bandwidth 15 Hz (-3 dB)(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy 25 °C Better than 0.1% of rangeCalibration interval 6 months
Offset drift 2μV/°C
Gain drift with temperature Voltage: 35 ppm/°C, 80 ppm/°C maxCurrent: 45 ppm/°C, 90 ppm/°C max
Module error 0.54% of range
Module input scan time, min 25 ms min – floating point10 ms min – integer(1)
Isolation voltage 250V continuousTested at 1700V DC for 1 s, channel to channel, chanto system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
ANALOG INPUT
CAL
OK
HART
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 46/158
46 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IF16
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF16
Certification (1) 1756-IF16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 47/158Publication 1756-TD002A-EN-E - May 2009 47
1756 ControlLogix I/O Modu
1756-IF4FXOF2FControlLogix high-speed input/output analog module
Technical Specifications - 1756-IF4FXOF2F
+IN-1/V
IN-1/I-IN-1
+IN-3/V
V OUT-1
IN-3/I-IN-3
Not UsedNot Used
I OUT-1RTN-1
Not Used
+IN-0/V
IN-0/I-IN-0+IN-2/V
IN-2/I-IN-2
1756-IF4FXOF2F Curr en t
2-wireTransmitter
A
A
A
(+) (-)i
i
ShieldGround
CurrenOutputLoad
Not UsedNot UsedNot Used
Not UsedNot UsedNot Used
V OUT-0
Not UsedNot Used
I OUT-0
Not UsedNot UsedNot UsedNot UsedNot UsedNot UsedNot Used
RTN-0
24
6
81012
141618
20
22242628
303234
36
13
5
7911
131517
19
21232527
293133
35
1756-IF4FXOF2F Voltage
UserAnalogInput
Device
(+)
(-)
ShieldGround
(+)
(+)
(-)
ShieldGround
+IN-1/V
IN-1/I
-IN-1
+IN-3/V
V OUT-1
IN-3/I-IN-3
Not Used
Not Used
I OUT-1RTN-1
Not Used
+IN-0/V
IN-0/I
-IN-0+IN-2/V
IN-2/I-IN-2
Not UsedNot UsedNot Used
Not UsedNot UsedNot Used
V OUT-0
Not UsedNot Used
I OUT-0
Not UsedNot UsedNot UsedNot UsedNot Used
Not UsedNot Used
RTN-0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
A = Inline field device (such as a strip chart recorder or meter)
Attribute 1756-IF4FXOF2
Inputs 4 high-speed, sub-millisecond, differential
Outputs 2 high-speed voltage or current
Current draw at 5.1V 375 mA
Current draw at 24V 100 mA
Power dissipation, max Voltage: 4.3 WCurrent: 4.7 W
Thermal dissipation, max Voltage: 14.66 BTU/hrCurrent: 16.02 BTU/hr
Isolation voltage 250V (continuous), Basic Insulation Type
125V (continuous), Reinforced Insulation TypeType Tested at 3100V DC for 60 s, I/O to systemRoutine Tested at 2121V DC for 2 s, I/O to systemNo isolation between channels
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
ANALOG INPUT
ANALOG OUTPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 48/158
48 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 2(2)
Wire type Copper
North American temperature code T4A
IEC temperature code T4
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IF4FXOF2
1756-IF4FXOF2F Input and Output SpecificationsAttribute Inputs Outputs
Number 4 high-speed, sub-millisecond, differential 2 high-speed voltage or current
Output range ± 10.5V0…10.5V0…5.25V0…21 mA
± 10.4V0…21 mA
Resolution Approx. 14 bits across ±10V DC (21V total)±10V: 1.3 mV/bit, 14-bit effective0…10.5V: 1.3 mV/bit, 13-bit effective0…5.25V: 1.3 mV/bit, 12-bit effectiveApprox. 12 bits across 21 mA0…21 mA: 5.25μA/bit
13 bits across 21 mA = 2.8μA/bit14 bits across 21.8V = 1.3 mV/bit
Impedance Voltage: >1 MΩCurrent: 249Ω
—
Open circuit detection Positive full-scale reading within 1 s Current output only (Output must be set to >0.
Overvoltage protection Voltage: 30V DCCurrent: 8V AC/DC
24V DC
Short circuit protection — Electronically current limited to 21 mA or less
Drive capability — Voltage: >2000ΩCurrent: 0…750 Ω
Settling time — < 2 ms to 95% of final value with resistive loads
Calibrated accuracy @ 25 °C 0.05% of range immediately after calibrationBetter than 0.1% of range within calibration interval
Calibration interval 12 months
Offset drift — 50μV/° C1μA/° C
Gain drift with temperature Voltage: 25 ppm/°C maxCurrent: 35 ppm/°C max
Voltage: 25 ppm/°C maxCurrent: 50 ppm/°C max
Module error 0.2% of range Voltage: 0.2% of rangeCurrent: 0.3% of range
Module scan time 300μs min(1)
(1) 300μs min for 1756-IF4FXOF2F, Series B, firmware revision 3.x or greater. 400μs min for 1756-IF4FXOF2F, Series A, firmware revision 1.x .
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 49/158Publication 1756-TD002A-EN-E - May 2009 49
1756 ControlLogix I/O Modu
Certifications - 1756-IF4FXOF2F
Certification (1) 1756-IF4FXOF2
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 50/158
50 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-IG16ControlLogix TTL input module
Low to True Format - 1756-IG16• -0.2…0.8V = Input guaranteed to be in on-state• 0.8…2.0V = Input state not guaranteed• 2.0…5.5V = Input guaranteed to be in off-state
1
3
5
7
9
19
17
15
13
11
2
4
6
8
10
20
18
16
14
12
IN-1
IN-3
IN-5
IN-7
DC-0(+)
IN-0
IN-2
IN-4
IN-6
DC COM 0
IN-9
IN-11
IN-13
IN-15
DC-1(+)
IN-8
IN-10
IN-12
IN-14
DC COM 1
5V DC
+ DC
– DC
1756-IG16
1
3
5
7
9
19
17
15
13
11
2
4
6
8
10
20
18
16
14
12
IN-1
IN-3
IN-5
IN-7
DC-0(+)
IN-0
IN-2
IN-4
IN-6
DC COM 0
IN-9
IN-11
IN-13
IN-15
DC-1(+)
IN-8
IN-10
IN-12
IN-14
DC COM 1
Capacitor0.01µF Typical(See notes below.)
5V DC Power
DC PowerW ire
I/OW ire+
–
I/OW ire
TTL InputDevice
+
–
1756-IG16
+5 DC
IN
1.5 K
1 K 74HCT14
1.5 K
1 K
560
74HCT14560
DC COM
IN
Standard Wiring CE Compliant Wiring
Simplified Schematic
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 51/158Publication 1756-TD002A-EN-E - May 2009 51
1756 ControlLogix I/O Modu
Technical Specifications - 1756-IG16
Attribute 1756-IG16
Inputs 16 (8 points/group)
Voltage category 5V DC TTL source (Low=True)(1)
(1) TTL inputs are inverted (-0.2 to +0.8 = low voltage = True = On.) Use a NOT instruction in yourconvert to traditional True - High logic.
Operating voltage range 4.5...5.5V DC50 mV P-P ripple max
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 450μs + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 700μs + filter
Current draw @ 5.1V 110 mA
Current draw @ 24V 2 mA
Power dissipation, max 1.4 W @ 60 °C
Thermal dissipation 4.8 BTU/hr @ 60 °C
Off-state voltage, max 2V
Off-state current, max 4.1 mA
On-state current, min 3.7 mA @ 5V DC
On-state current, max 4.1 mA @ 5V DC
Input impedance, max 1.4 kΩ min1.5 kΩ typical
Cyclic update time 100μs...750 ms
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(2)
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 2(3)
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Wire type Copper
Enclosure type rating None (open-style)
DC INPUT
S T 0 1 2 3 4 5 6 7
ST 8 9 10 1112131415
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 52/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 53/158Publication 1756-TD002A-EN-E - May 2009 53
1756 ControlLogix I/O Modu
1756-IH16IControlLogix DC (90...146V) isolated input module
Technical Specifications - 1756-IH16I
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non isolated Wir in g
Isolated Wir in g
Daisy Chain to Other RTBs
1756-IH16I
DC (-)
Jumper Bar(Cut to Length)
)+(7-CD)-(7-CD
DC (+)
DC-0 (+)
DC-3 (+)
DC-0 (-)
DC-3 (-)
IN-0IN-1IN-2IN-3
IN-8
IN-4IN-5IN-6IN-7
Not Ysed
IN-9IN-10IN-11IN-12IN-13IN-14IN-15Not Used
GND-0GND-1GND-2GND-3
GND-8
GND-4GND-5GND-6GND-7
Not Used
GND-9GND-10GND-11GND-12GND-13GND-14GND-15GND-15
ControlLogixBackplaneInterface
Simplified Schematic
Display
GND-0
IN-0
GND
+5V
Attribute 1756-IH16I
Inputs 16 individually isolatedVoltage category 125V DC sink/source
Operating voltage range 90...146V DC(1)
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 2 ms + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 6 ms + filter
Current draw @ 5.1V 125 mA
Current draw @ 24V 3 mA
Power dissipation, max 5 W @ 60 °C
Thermal dissipation 17.05 BTU/hrOff-state voltage, max 20V DC
Off-state current, max 0.8 mA
On-state current, min 1 mA @ 90V DC
On-state current, max 3 mA @ 146V DC
Inrush current, max 250 mA
Input impedance, max 48.67 kΩ @ 146V DC
Cyclic update time 200μs...750 ms
DC INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 1112131415
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 54/158
54 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IH16I
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBCH
1756-TBS6HSlot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open-style)(1) 90...146V DC @ 50°C,12 channels on90...132V DC @ 55°C, 14 channels on90...125V DC @ 60°C, 16 channels on90...146V DC @ 30°C, 16 channels on.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IH16I
Certification (1) 1756-IH16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 55/158Publication 1756-TD002A-EN-E - May 2009 55
1756 ControlLogix I/O Modu
1756-IH16ISOEControlLogix DC (90...140V) sequence of events input module
Technical Specifications - 1756-IH16ISOE
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non isolatedWir in g
Isolated Wir in g
Daisy Chain to Other RTBs
DC (-)
Jumper Bar(Cut to Length)
)+(6-CD)-(6-CD
DC (+)
DC-0 (+)DC-1 (+)
DC-0 (-)
DC-5 (-)
IN-0IN-1IN-2IN-3
IN-8
IN-4IN-5IN-6IN-7
Not Used
IN-9IN-10IN-11IN-12IN-13IN-14IN-15
Not Used
GND-0GND-1GND-2GND-3
GND-8
GND-4GND-5GND-6GND-7
Not Used
GND-9GND-10GND-11GND-12GND-13GND-14GND-15
GND-15
DC-5 (+)
Sin k In pu t Wir in g
Sour ce In pu t Wir in gSour ce In pu t Wir in g
Sin k In pu t Wir in g
1756-IH16ISOESimplified Schematic
ControlLogixBackplaneInterface
IN-0
GND-0
Display
+5V
Attribute 1756-IH16ISOE(1)
Inputs 16 individually isolated, sequence of events
Voltage category 125V DC sink/source
Operating voltage range 90...140V DC
Digital filter, off to on 0…50 ms
Input delay, off to on 20μs
Digital filter, on to off 0...50 ms
Input delay, on to off 75μs
Current draw @ 5.1V 275 mA§
Current draw @ 24V 2 mA
Power dissipation, max 5.5 W @ 60 °C
Thermal dissipation 17.22 BTU/hr
Off-state voltage, max 20V
Off-state current, max 0.3 mAOn-state current, min 1.15 mA @ 90V DC
On-state current, max 1.85 mA @ 140V DC
Input impedance, max 74.8 kΩ
Cyclic update time 200μs...750 ms
Isolation voltage 250V continuous, channel to channel, channels tosystem
Removable terminal block 1756-TBCH1756-TBS6H
SOE INPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 56/158
56 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IH16ISOE
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) If you use 1756-IB16ISOE or 1756-IH16ISOE modules in a remote rack, you must use a 1756-Smodule to coordinate system time.
(2)Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IH16ISOE(1)
Certification (1) 1756-IH16ISOE
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 57/158Publication 1756-TD002A-EN-E - May 2009 57
1756 ControlLogix I/O Modu
1756-IM16IControlLogix AC (159...265V) input module
Technical Specifications - 1756-IM16I
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non isolated Wir in g
Isolated Wi r in g
Daisy Chain to Other RTBs
L2-0
1756-IM16I
L2-0L2-1L2-2L2-3
L2-8
L2-4L2-5L2-6L2-7
Not Used
L2-9L2-10L2-11L2-12L2-13L2-14
L2-15L2-15
IN-0IN-1IN-2IN-3
IN-8
IN-4IN-5IN-6IN-7
Not Used
IN-9IN-10IN-11IN-12IN-13IN-14
IN-15Not Used
L2-2
L2-4
L2
L1
L1-0
L1-2
L1-4
Jumper Bar(Cut to Length)
ControlLogixBackplaneInterface
Simplified Schematic
Display
+5V
L2-0
IN-O
GND
Attribute 1756-IM16IInputs 16 individually isolated
Voltage category 240V AC
Operating voltage range 159…265V AC,47…63 Hz(1)
Digital filter, off to on 1 or 2 ms
Input delay, off to on 10 ms + filter
Digital filter, on to off 9 or 18 ms
Input delay, on to off 8 ms + filter
Current draw @ 5.1V 100 mA
Current draw @ 24V 3 mA
Power dissipation, max 5.8 W @ 60 °C
Thermal dissipation 19.78 BTU/hr
Off-state voltage, max 40V
Off-state current, max 2.5 mA
On-state current, min 5 mA @ 159V AC, 60 Hz
On-state current, max 13 mA @ 265V AC, 60 Hz
Inrush current, max 250 mA
Input impedance, max 20.38 kΩ @ 265V AC, 60 Hz
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 1213 14 15
OK
AC INPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 58/158
58 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IM16I
Cyclic update time 200μs...750 ms
Isolation voltage 265V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
Wire category 1(3)
Wire type CopperEnclosure type rating None (open-style)
(1) 159…265V AC, 47…63Hz @ 30°C all channels on159…265V AC, 47…63Hz @ 40°C 8 points on159…253V AC, 47…63Hz @ 45°C all channels on159…242V AC, 47…63Hz @ 60°C all channels on.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IM16I
Certification (1) 1756-IM16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 59/158Publication 1756-TD002A-EN-E - May 2009 59
1756 ControlLogix I/O Modu
1756-IN16ControlLogix AC (10...30V) input module
Technical Specifications - 1756-IN16
12
34
56
78
910
1112
1314
1516
1718
1920
Daisy Chain toOther RTBs
1756-IN16
Group 0Group 0
Group 1Group 1
IN-1
IN-3
IN-5
IN-7
L2-0
IN-9
IN-11
IN-13
IN-15
L2-1
IN-0
IN-2
IN-4
IN-6
L2-0
IN-8
IN-10
IN-12
IN-14
L2-1
L2
L1
ControlLogixBackplaneInterface
Simplified Schematic
Display
+5V
L2-0
IN-O
GND
Attribute 1756-IN16
Inputs 16 (8 points/group)
Voltage category 24V AC
Operating voltage range 10…30V AC,47…63 Hz
Digital filter, off to on 1 or 2 ms
Input delay, off to on 10 ms + filter
Digital filter, on to off 9 or 18 ms
Input delay, on to off 8 ms + filter
Current draw @ 5.1V 100 mA
Current draw @ 24V 2 mAPower dissipation, max 5.1 W @ 60 °C
Thermal dissipation 17.39 BTU/hr
Off-state voltage, max 5V
Off-state current, max 2.75 mA
On-state current, min 5 mA @ 10V AC, 60 Hz
On-state current, max 1.2 mA @ 30V AC, 60 Hz
Inrush current, max 250 mA
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 1213 14 15
OK
AC INPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 60/158
60 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IN16
Input impedance, max 2.5 kΩ @ 30V AC, 60 Hz
Cyclic update time 200μs...750 ms
Isolation voltage 250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IN16
Certification (1) 1756-IN16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 61/158Publication 1756-TD002A-EN-E - May 2009 61
1756 ControlLogix I/O Modu
1756-IR6IControlLogix temperature sensing analog input module
12
34
56
78
910
1112
1314
1516
1718
1920
1756-IR6I3-wi re RTD
3-wire RTD
Shield Ground
IN-1/A
IN-1/B
RTN-1/C
IN-3/A
IN-3/B
RTN-3/C
Not used
IN-5/A
IN-5/B
RTN-5/C
IN-0/A
IN-0/B
RTN-0/C
IN-2/A
IN-2/B
RTN-2/C
Not used
IN-4/A
IN-4/B
RTN-4/C
Do not connect more than two wires to any single terminal.
IMPORTANT: For 2-wire resistor applications including calibration, make sure IN-x /B and
RTN-x
/C are shorted together as shown.
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 62/158
62 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
12
34
56
78
910
1112
1314
1516
1718
1920
1756-IR6I 4-wire RTD
4-wire RTD
Shield Ground
IN-1/A
IN-1/B
RTN-1/C
IN-3/A
IN-3/B
RTN-3/C
Not used
IN-5/A
IN-5/B
RTN-5/C
IN-0/A
IN-0/B
RTN-0/C
IN-2/A
IN-2/B
RTN-2/C
Not used
IN-4/A
IN-4/B
RTN-4/C
• Do not connect more than two wires to any single terminal.• Wiring is exactly the same as the 3-wire RTD with one wire left open.
Input Signal to User Count Conversion - 1756-IR6I
Range Low Signal and User Counts High Signal and User Counts
1...487Ω 0.859068653Ω-32768 counts
507.862Ω32767 counts
2...1000Ω 2Ω-32768 counts
1016.502Ω32767 counts
4...2000Ω 4Ω-32768 counts
2033.780Ω32767 counts
8...4020Ω 8Ω-32768 counts
4068.392Ω32767 counts
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 63/158Publication 1756-TD002A-EN-E - May 2009 63
1756 ControlLogix I/O Modu
Technical Specifications - 1756-IR6I
Attribute 1756-IR6I
Inputs 6 individually isolated RTD
Input range 1…487Ω2…1000Ω4…2000 Ω8…4020Ω
Resolution 16 bits1…487Ω: 7.7 mΩ /bit2…1000Ω:15 mΩ /bit4…2000Ω:30 mΩ /bit8…4020Ω:60 mΩ /bit
Sensors supported 100, 200, 500, 1000Ω Platinum, alpha=385100, 200, 500, 1000Ω Platinum, alpha=3916120Ω Nickel, alpha=672100, 120, 200, 500Ω Nickel, alpha=61810Ω Copper
Current draw @ 5.1V 250 mA
Current draw @ 24V 125 mA
Power dissipation, max 4.3 W
Thermal dissipation 14.66 BTU/hr
Open circuit detection time Negative full scale reading within 5 s with anycombination of lost wires, except input terminal A alIf input terminal A is lost by itself, the module reads positive full scale reading within 5 s
Overvoltage protection, max 24V AC/DC
Normal mode noise rejection 60 dB at 60 Hz(1)
Common mode noise rejection 120 dB @ 60 Hz100 dB @ 50 Hz
Channel bandwidth 15 Hz(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy @ 25 °C Better than 0.1% of range
Calibration interval 6 months
Offset drift 10 MΩ /°C
Gain drift with temperature 50 ppm/°C, 90 ppm/°C max
Module error 0.54% of range
Module scan time 25 ms min floating point (ohms)50 ms min floating point (temperature)10 ms min integer (ohms)(1)
Isolation voltage 250V continuousTested at 1700V DC for 1 s, channel to channel, chanto system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
ANALOG INPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 64/158
64 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IR6I
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
Wire category 2(3)
Wire type CopperEnclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IR6I
Certification (1) 1756-IR6I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 65/158Publication 1756-TD002A-EN-E - May 2009 65
1756 ControlLogix I/O Modu
1756-IT6IControlLogix temperature sensing analog input module
12
34
56
78
910
1112
1314
1516
1718
1920
+
–
ColdJ un ctio n Sen sor
Thermocouple
W ire
IN-0
Not Used
RTN-0
IN-2
Not Used
RTN-2
Not Used
IN-4
Not Used
RTN-4
1756-IT6I
IN-0
Not Used
RTN-1
IN-3
CJC+
RTN-3
CJC-
IN-5
Not Used
RTN-5
Lug
• Do not connect more than two wires to any single terminal.• One CJC, part number 94238301, is shipped with the module. A
replacement can be ordered as RP-94238301.
Input Signal to User Count Conversion - 1756-IT6I
Range Low Signal and User Counts High Signal and User Counts
-12...30 mV -15.80323 mV-32768 counts
31.396 mV32767 counts
-12...78 mV -15.15836 mV-32768 counts
79.241 mV32767 counts
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 66/158
66 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Technical Specifications - 1756-IT6I
Attribute 1756-IT6I
Inputs 6 individually isolated thermocouple1 CJC
Input range -12…78 mV-12…30 mV
Resolution 16 bits-12...78 mV: 1.4μV/bit-12...30 mV: 0.7μV/bit
Thermocouples B, E, J, K, R, S, T, N, C
Current draw @ 5.1V 250 mA
Current draw @ 24V 125 mA
Power dissipation, max 4.3 W
Thermal dissipation 14.66 BTU/hr
Input impedance >10 MΩ
Open circuit detection time Positive full scale reading within 2 sOvervoltage protection, max 120V AC/DC
Normal mode noise rejection 60 dB at 60 Hz(1)
Common mode noise rejection 120 dB @ 60 Hz100 dB @ 50 Hz
Channel bandwidth 15 Hz (-3 dB)(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy @ 25 °C Better than 0.1% of range
Calibration interval 6 months
Local CJC sensor accuracy ±0.3…±3.2 °C, depending on channel
Remote CJC sensor accuracy ±0.3 °COffset drift 0.5μV/°C
Gain drift with temperature 65 ppm/°C, 80 ppm/°C max
Module error 0.5% of range
Module scan time 25 ms min floating point (millivolt)50 ms min floating point (temperature)10 ms min integer (millivolt)(1)
Isolation voltage 250V continuousTested at 1700V DC for 1 s, channel to channel, chanto system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
ANALOG INPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 67/158Publication 1756-TD002A-EN-E - May 2009 67
1756 ControlLogix I/O Modu
Certifications - 1756-IT6I
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IT6I
Certification (1) 1756-IF4FXOF2
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 68/158
68 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-IT6I2ControlLogix enhanced thermocouple analog input module
Technical Specifications - 1756-IT6I2
?
Cold JunctionSensor
Thermocouple
W ire
Not Used
CJC–
RTN-0
RTN-1
RTN-
RTN-3
RTN-
RTN-5
CJC–
Not used
Spade Lug
Not Used
CJC+
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
CJC+
Not used
W ire Spade Lug
1756-IT6I Cold Jun ction Sen so r
• Do not connect more than two wires to any single terminal.• Two CJCs, part number 94286501, are shipped with the module.
Replacements can be ordered as RP-94286501.
Input Signal to User Count Conversion - 1756-IT6I2
Range Low Signal and User Counts High Signal and User Counts
-12...30 mV -15.80323 mV-32768 counts
31.396 mV32767 counts
-12...78 mV -15.15836 mV-32768 counts
79.241 mV32767 counts
Attribute 1756-IT6I2
Inputs 6 individually isolated thermocouple2 CJC
Input range -12…78 mV (1.4μV per bit)-12…30 mV (0.7μV per bit – high resolution range)
Resolution 16 bits-12...78 mV: 1.4μV/bit-12...30 mV: 0.7μV/bit
Analog Input
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 69/158Publication 1756-TD002A-EN-E - May 2009 69
1756 ControlLogix I/O Modu
Thermocouples B, E, J, K, R, S, T, N, C, D, L (TXK/XK)
Current draw @ 5.1V 200 mA
Current draw @ 24V 150 mA
Power dissipation, max 4.6 WThermal dissipation 15.7 BTU/hr
Open circuit detection time Positive full scale reading within 2 s
Overvoltage protection, max 120V AC/DC
Normal mode noise rejection 60 dB at 60 Hz(1)
Common mode noise rejection 160 dB min, tested at 600V AC/60 Hz applied wΩ differential resistance
Channel bandwidth 15 Hz(1)
Settling time <80 ms to 5% of full scale(1)
Calibrated accuracy @ 25 °C Better than 0.1% of range
Calibration interval 12 monthsLocal CJC sensor accuracy ±0.3 °C
Remote CJC sensor accuracy ±0.3 °C
Offset drift 0.5μV/°C
Gain drift with temperature 15 ppm/°C, 25 ppm/°C max1.4μV/°C, 2.3μV/°C max, -12…78 mV0.6μV/°C, 1.1μV/°C max, -12…30 mV
Module error 0.15% of range
Module scan time 25 ms min floating point (millivolt)50 ms min floating point (temperature)10 ms min integer (millivolt)(1)
Isolation voltage 250V (continuous), Reinforced Insulation Type, usystem, tested at 3250V DC for 60 s250V (continuous), Reinforced Insulation Type, grougroup, tested at 1900V DC for 60 s
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.25...2.5 mm2 (22…14 AWG) stranded, 1.2 mm (3/64in.) insulation(2)
Wire category 2(3)
Wire type Copper
Enclosure type rating None (open-style)
(1) Notch filter dependent.
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IT6I2
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 70/158
70 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IT6I2
Certification (1) 1756-IT6I2
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
TÜV TÜV Certified for Functional Safety: up to and including SIL 2
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 71/158Publication 1756-TD002A-EN-E - May 2009 71
1756 ControlLogix I/O Modu
1756-IV16ControlLogix DC (10...30V) sourcing input module
Technical Specifications - 1756-IV16
1756-IV16
12
34
56
78
910
1112
1314
1516
1718
1920
–+
Daisy Chain to Other RTBs
Group 0Group 0
Group 1Group 1
DC COM
IN-0
IN-2
IN-4
IN-6
DC-0 +
IN-8
IN-10
IN-12
IN-14
DC-1 +
IN-1
IN-3
IN-5
IN-7
DC-0 +
IN-9
IN-11
IN-13
IN-15
DC-1 +
ControlLogixBackplaneInterface
Simplified Schematic
Display
GND
IN-0
DC-0++5V
Attribute 1756-IV16
Inputs 16 (8 points/group)
Voltage category 12/24V DC source
Operating voltage range 10...30V DC
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 1 ms + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 2 ms + filter
Current draw @ 5.1V 110 mA
Current draw @ 24V 2 mA
Power dissipation, max 5.41 W @ 60 °C
Thermal dissipation 18.47 BTU/hr
Off-state voltage, max 5V DC
Off-state current, max 1.5 mA
On-state current, min 2 mA @ 10V DC
On-state current, max 10 mA @ 30V DC
Inrush current, max 250 mA
DC INPUT
ST 0 1 2 3 4 5 6 7ST 8 9 10 1112131415
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 72/158
72 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-IV16
Input impedance, max 3.2 kΩ @ 30V DC
Cyclic update time 100μs...750 ms
Isolation voltage 250V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block housing 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IV16
Certification (1) 1756-IV16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 73/158Publication 1756-TD002A-EN-E - May 2009 73
1756 ControlLogix I/O Modu
1756-IV32ControlLogix DC (10...30V) sourcing input module
Diagnostics - 1756-IV32
Technical Specifications - 1756-IV32
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+ –
DaisyChain toOtherRTBs
DC COM
0puorG0puorG
1puorG1puorG
1756-IV32
IN-1IN-3IN-5IN-7
DC-0 (+)
IN-9IN-11IN-13IN-15
DC-1 (+)
IN-17IN-19
IN-21IN-23IN-25
IN-27IN-29IN-31
IN-0IN-2IN-4IN-6
DC-0 (+)
IN-8IN-10IN-12IN-14
DC-1 (+)
IN-16IN-18IN-20IN-22IN-24
IN-26IN-28IN-30
JumperW ire
ControlLogixBackplaneInterface
Simplified Schematic
Display
IN-0 GND
DC-0++5V
Attribute 1756-IV32
Change of state Software configurable
Timestamp of diagnostics ±200μs
Attribute 1756-IV32
Inputs 32 (16 points/group)
Voltage category 12/24V DC sourceOperating voltage range 10...30V DC
Digital filter, off to on 0, 1, or 2 ms
Input delay, off to on 1 ms + filter
Digital filter, on to off 0, 1, 2, 9, or 18 ms
Input delay, on to off 2 ms + filter
Current draw @ 5.1V 120 mA
Current draw @ 24V 2 mA
DC INPUT
OK
ST 0 1 2 3 4 5 6 7
ST 8 9 10 21 3 4 5
1 1 1 11
ST 6 7 18 09 1 2 31 2 2 221 1
ST 4 526 87 9 0 1
2 2 2 332 2
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 74/158
74 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Power dissipation, max 4.1 W @ 60 °C
Thermal dissipation 14 BTU/hr @ 60 °C
Off-state voltage, max 5V
Off-state current, max 1.5 mAOn-state current, min 2 mA
On-state current, max 3.5 mA
Inrush current, max 250 mA (decaying to <37% in 22 ms, without ac
Input impedance, max 8.6 kΩ @ 30V DC
Cyclic update time 100μs...750 ms
Isolation voltage 250V (continuous), Reinforced Insulation Type bInput group to system250V (continuous), Basic insulation type between Ingroup to Input groupRoutine tested at 1900V AC for 2 s, between Input grto Input group and Input group to system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module Location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1 - on signal ports(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-IV32
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 75/158Publication 1756-TD002A-EN-E - May 2009 75
1756 ControlLogix I/O Modu
Certifications - 1756-IV32
Certification (1) 1756-IV32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 76/158
76 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OA8ControlLogix AC (74...265V) output module
Technical Specifications - 1756-OA8
12
34
56
78
910
1112
1314
1516
1718
1920
Daisy Chain toOther RTBs
Group 0Group 0
Group 1Group 1
L2
1756-OA8
L1-0
L1-0
L1-0
L1-0
L1-1
L1-1
L1-1
L1-1
L1-0
L1-1
OUT-0
OUT-1
OUT-2
OUT-3
OUT-4
OUT-5
OUT-6
OUT-7
Not used
Not Used
L1
ControlLogix Backplane Interface
Surge Current Chart
C u r r e n t
Display
Simplified Schematic
OUT-0
Time
Surge
+5V L1-0
20 A
2 A
0 43 ms
Attribute 1756-OA8
Outputs 8 (4 points/group)
Voltage category 120/240V AC
Operating voltage range 79…265V AC47…63 Hz
Output delay, off to on 9.3 ms @ 60 Hz11 ms @ 50 Hz
Output delay, on to off 9.3 ms @ 60 Hz11 ms @ 50 Hz
Current draw @ 5.1V 200 mACurrent draw @ 24V 2 mA
Power dissipation, max 5.1 W @ 60 °C
Thermal dissipation, max 17.39 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 1.5V peak @ 2 A6V peak @ <50 mA
Current per point, max 2 A @ 60 °C (linear derating)
Current per module, max 5 A @ 30 °C (linear derating)4 A @ 60 °C (linear derating)
S T 0 1 2 3 4 5 6 7 O
K
AC OUTPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 77/158Publication 1756-TD002A-EN-E - May 2009 77
1756 ControlLogix I/O Modu
Surge current per point 20 A for 43 ms per point, repeatable every 2 s @
Load current, min 10 mA per point
Commutating voltage 4V/μs for loads > 50 mA
0.2V/μs for loads < 50 mA(1)
Isolation voltage 265V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Inhibit voltage, max Zero crossing 60V peak
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)
insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added across the output and L2. The purpose of to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a higher dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will d
(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waat fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattene
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OA8
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 78/158
78 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OA8
Certification (1) 1756-OA8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 79/158Publication 1756-TD002A-EN-E - May 2009 79
1756 ControlLogix I/O Modu
1756-OA8DControlLogix AC (74...132V) diagnostic output module
Diagnostics - 1756-OA8D
Technical Specifications - 1756-OA8D
12
34
56
78
910
1112
1314
1516
1718
1920
DaisyChain toOtherRTBs
Daisy Chain toOther RTBs
Group 0Group 0
Group 1Group 1
L2
1756-OA8D
Not Used
L1-0
L1-0
L1-0
L1-1
L1-1
L1-1
L1-1
L1-0
L1-1
L2-0
OUT-0
OUT-1
OUT-2
OUT-4
OUT-5
OUT-6
OUT-7
OUT-3
L2-1
L1
ControlLogixBackplaneInterface
Diagnostic Control Block withOpto and Transformer Isolation
Surge Current Chart
Continuous @ 30° C C u r r e n
t
Display
Simplified Schematic
OUT
L1
Continuous @ 60° C
Time
Surge @ 30° C
Surge @ 60° C
Loss of Field Power
ShortVerify/No Load
VACGATE
L2
500 mA0 43 ms
1 A
5 A
8 A
Attribute 1756-OA8D
Short trip, min 12 A for 500μs
No load Off-state detection only
Output verification On-state detection only
Pulse test Configurable maximum width and max time delay zero cross
Field power loss (zero cross) Detects at 25V peak min (firmware phase lock
Time stamp of diagnostics ±1 ms
Attribute 1756-OA8D
Outputs 8 diagnostic, electronic fusing (4 points/group)
Voltage category 120V AC
Operating voltage range 74…132V AC47…63 Hz
Output delay, off to on 9.3 ms @ 60 Hz11 ms @ 50 Hz
DIAGNOSTIC
S T 0 1 2 3 4 5 6 7 OK
AC OUTPUT
F LT 0 1 2 3 4 5 6 7
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 80/158
80 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Output delay, on to off 9.3 ms @ 60 Hz11 ms @ 50 Hz
Current draw @ 5.1V 175 mA
Current draw @ 24V 250 mAPower dissipation, max 5.3 W @ 60 °C
Thermal dissipation, max 18.0 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 2.5V peak @ 0.5 A3V peak @ 1 A
Current per point, max 1 A @ 30 °C (linear derating)0.5 A @ 60 °C (linear derating)
Current per module, max 8 A @ 30 °C (linear derating)4 A @ 60 °C (linear derating)
Surge current per point 8 A for 43 ms per point, repeatable every 2 s @ 5 A for 43 ms per point, repeatable every 1 s @ 60 °C
Load current, min 10 mA per point
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Inhibit voltage, max Zero crossing 25V peak
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OA8D
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 81/158Publication 1756-TD002A-EN-E - May 2009 81
1756 ControlLogix I/O Modu
Certifications - 1756-OA8D
Certification (1) 1756-OA8D
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 82/158
82 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OA8EControlLogix AC (74...132V) electronically-fused output module
Diagnostics - 1756-OA8E
Technical Specifications - 1756-OA8E
12
34
56
78
910
1112
1314
1516
1718
1920
Daisy Chain toOther RTBs
Group 0Group 0
Group 1Group 1
L2
1756-OA8E
Not Used
L1-0
L1-0
L1-0
L1-1
L1-1
L1-1
L1-1
L1-0
L1-1
L2-0
OUT-0
OUT-1
OUT-2
OUT-4
OUT-5
OUT-6
OUT-7
OUT-3
L2-1
DaisyChain toOtherRTBs
L1
ControlLogixBackplaneInterface
Opto and Transformer Isolation
Surge Current Chart
Display
Simplified Schematic
OUT
L1
Time
Surge
Loss of Field Power
Short
VACGATE
0 43 ms
C u r r e n t
20 A
2 A
L2
Attribute 1756-OA8E
Short trip, min >20 A for 100 ms
Field power loss (zero cross) Detects at 25V peak min (firmware phase lock
Time stamp of diagnostics ±1 ms
Attribute 1756-OA8E
Outputs 8 electronic fusing (4 points/group)Voltage category 120V AC
Operating voltage range 74…132V AC47…63 Hz
Output delay, off to on 9.3 ms @ 60 Hz11 ms @ 50 Hz
Output delay, on to off 9.3 ms @ 60 Hz11 ms @ 50 Hz
Current draw @ 5.1V 200 mA
Current draw @ 24V 250 mA
ST 0 1 2 3 4 5 6 7
FUSE0 1 2 3 4 5 6 7OK
AC OUTPUT
ELECTRONICALLY FUSED
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 83/158Publication 1756-TD002A-EN-E - May 2009 83
1756 ControlLogix I/O Modu
Power dissipation, max 5.5 W @ 60 °C
Thermal dissipation, max 18.76 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 4V peak @ 2 ACurrent per point, max 2 A @ 60 °C
Current per module, max 8 A @ 30 °C (linear derating)4 A @ 60 °C (linear derating)
Surge current per point 20 A for 43 ms per point, repeatable every 2 s @
Load current, min 10 mA per point
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Inhibit voltage, max Zero crossing 25V peak
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OA8E
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 84/158
84 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OA8E
Certification (1) 1756-OA8E
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 85/158Publication 1756-TD002A-EN-E - May 2009 85
1756 ControlLogix I/O Modu
1756-OA16ControlLogix AC (74...265V) output module
Diagnostics - 1756-OA16
Technical Specifications - 1756-OA16
L1
12
34
56
78
910
1112
1314
1516
1718
1920
L1 L2
Daisy Chainto OtherRTBs
1756-OA16
Group 0
Group 0
Group 1 Group 1
OUT-1
OUT-3
OUT-5
OUT-7
OUT-9
OUT-11
OUT-13
OUT-15
L1-0
L1-1
OUT-0
OUT-2
OUT-4
OUT-6
OUT-8
OUT-10
OUT-12
OUT-14
L2-0
L2-1
ControlLogix Backplane Interface
ControlLogixBackplaneInterface
(Fused per Group)
Simplified Schematic
Per Group
Surge Current Chart
Per Group
Surge
Display
L1-0
OUT-0
C u r r e n
t
Time
500 mA0 43 ms
2 A5 A
20 A
+5V
Attribute 1756-OA16
Time stamp of diagnostics ±1 ms
Fuse blown 1 fuse and indicator/group
Attribute 1756-OA16
Outputs 16 mechanically fused/group (8 points/group)
Voltage category 120/240V AC
Operating voltage range 74…265V AC47…63 Hz
Output delay, off to on 9.3 ms @ 60 Hz11 ms @ 50 Hz
Output delay, on to off 9.3 ms @ 60 Hz11 ms @ 50 Hz
AC OUTPUT
S T 0 1 2 3 4 5 6 7
ST 8 9 10111213 14 15
O
K
FUSE
FUSE
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 86/158
86 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Current draw @ 5.1V 400 mA
Current draw @ 24V 2 mA
Power dissipation, max 6.5 W @ 60 °C
Thermal dissipation, max 22.17 BTU/hrOff-state leakage current, max 3 mA per point
On-state voltage drop, max 1.5V @ 0.5 A5.7V @ load current < 50 mA
Current per point, max 0.5 A @ 60 °C
Current per module, max 4 A @ 60 °C
Surge current per point 5 A for 43 ms per point, repeatable every 2 s @
Load current, min 10 mA per point
Commutating voltage 4V/μs for loads > 50 mA0.2V/μs for loads < 50 mA(1)
Isolation voltage 265V continuous
Tested at 2546V DC for 1 s, I/O group to group, I/O system
Inhibit voltage, max Zero crossing 60V peak
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6
in.) insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added AC ross the output and L2. The purpose is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a highdv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will (P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC wavfault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened s
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OA16
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 87/158Publication 1756-TD002A-EN-E - May 2009 87
1756 ControlLogix I/O Modu
Certifications - 1756-OA16
Certification (1) 1756-OA16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 88/158
88 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OA16IControlLogix AC (74...265V) isolated output module
Technical Specifications - 1756-OA16I
1 2
3 4
5 6
7 8
01 9
21 11
41 31
61 51
81 71
02 91
22 12
42 32
62 52
82 72
03 92
23 13
43 33
63 53
Non isolated Wirin g
Isolated Wi r in g
Daisy Chain to Other RTBs
L1-0
1756-OA16I
L1-0L1-1L1-2L1-3
L1-8
L1-4L1-5L1-6L1-7
Not Used
L1-9L1-10L1-11L1-12
L1-13L1-14L1-15L1-15
OUT-0OUT-1OUT-2OUT-3
OUT-8
OUT-4OUT-5OUT-6OUT-7
Not Used
OUT-9OUT-10OUT-11OUT-12
OUT-13OUT-14OUT-15Not Used
L1-2
L1-4
L1
L2
L2-0
L2-2
L2-4
Jumper Bar (Cut to Length)
ControlLogix Backplane Interface
Surge Current Chart
Continuous @ 30°C
Display
Simplified Schematic
OUT-0
L1-0
Continuous @ 60°C
C u r r e n
t
Time
1 A
0 43 ms
2 A
20 A
+5V
Attribute 1756-OA16I
Outputs 16 individually isolated
Voltage category 120/240V AC
Operating voltage range 74…265V AC47…63 Hz
Output delay, off to on 9.3 ms @ 60 Hz11 ms @ 50 Hz
Output delay, on to off 9.3 ms @ 60 Hz11 ms @ 50 Hz
Current draw @ 5.1V 300 mA
Current draw @ 24V 2.5 mA
Power dissipation, max 5.5 W @ 60 °C
Thermal dissipation, max 18.76 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 1.5V peak @ 2 A6V peak @ load current < 50 mA
Current per point, max 2 A @ 30 °C (linear derating)1 A @ 60 °C (linear derating)
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 1415
O
K
AC OUTPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 89/158Publication 1756-TD002A-EN-E - May 2009 89
1756 ControlLogix I/O Modu
Current per module, max 5 A @ 30 °C (linear derating)4 A @ 60 °C (linear derating)
Surge current per point 20 A for 43 ms per point, repeatable every 2 s @
Load current, min 10 mA per pointCommutating voltage 4V/μs for loads > 50 mA
0.2V/μs for loads < 50 mA(1)
Isolation voltage 265V continuousTested at 2546V DC for 1 s, channel to channel, I/O system
Inhibit voltage, max Zero crossing 60V peak
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added AC ross the output and L2. The purpose is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a highdv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will d(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC wavfault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattened s
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OA16I
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 90/158
90 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OA16I
Certification (1) 1756-OA16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 91/158Publication 1756-TD002A-EN-E - May 2009 91
1756 ControlLogix I/O Modu
1756-OB8ControlLogix DC (10...30V) output module
Technical Specifications - 1756-OB8
12
34
56
78
910
1112
1314
1516
1718
1920
+ –
Group 0Group 0
Group 1Group 1
Daisy Chain toOther RTBs
Daisy Chain toOther RTBs
DC COM
1756-OB8
DC-0 (+)
DC-0 (+)
DC-0 (+)
DC-0 (+)
DC-1 (+)
DC-1 (+)
DC-1 (+)
DC-1 (+)
RTN OUT-0
RTN OUT-1
OUT-0
OUT-1
OUT-2
OUT-3
OUT-4
OUT-5
OUT-6
OUT-7
RTN OUT-0
RTN OUT-1
RTNOUT-0
OUT-0
DC-0(+)
ControlLogix Backplane Interface
Display
Continuous @ 60oC
Surge Current Chart
Simplified Schematic
Surge
+5V
C u r r e n
t
Time0 10 ms
2 A
4 A
Attribute 1756-OB8
Outputs 8 electronically fused, individually isolated
Voltage category 12/24V DC source
Operating voltage range 10...30V DC
Output delay, off to on 1 ms
Output delay, on to off 2 ms
Current draw @ 5.1V 250 mA
Current draw @ 24V 2 mAPower dissipation, max 4.7 W @ 60 °C
Thermal dissipation, max 16.03 BTU/hr
Off-state leakage current, max 1 mA per point
On-state voltage drop, max 1.2V DC @ 2A
Current per point, max 2 A @ 60 °C
Current per module, max 16 A @ 55 °C (linear derating)10 A @ 60 °C
Surge current per point 4 A for 10 ms per point, repeatable every 2 s
DC OUTPUT
S T 0 1 2 3 4 5 6 7 O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 92/158
92 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OB8
Load current, min 3 mA per point
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type CopperEnclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB8
Certification (1) 1756-OB8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 93/158Publication 1756-TD002A-EN-E - May 2009 93
1756 ControlLogix I/O Modu
1756-OB8EIControlLogix DC (10...30V) electronically-fused, isolated output module
Diagnostics - 1756-OB8EI
Technical Specifications - 1756-OB8EI
1 2
3 4
5 6
7 8
01 9
21 11
41 31
61 51
81 71
02 91
22 12
42 32
62 52
82 72
03 9223 13
43 33
63 53
+
+
-
-
+ –
DC-0 (+)RTN OUT-0
DC-1 (+)RTN OUT-1
DC-4 (+)
DC-2 (+)RTN OUT-2
DC-3 (+)RTN OUT-3
Not Used
RTN OUT-4DC-5 (+)
RTN OUT-5DC-6 (+)
RTN OUT-6
DC-7 (+)RTN OUT-7Not Used
OUT-0OUT-0OUT-1OUT-1
OUT-4
OUT-2OUT-2OUT-3OUT-3
Not Used
OUT-4OUT-5OUT-5OUT-6OUT-6
OUT-7OUT-7Not Used
DC COM
Isolated Wirin g
1756-OB8EI
Daisy Chain toOther RTBs
Non isolated Wirin g
Daisy Chain toOther RTBs
Continuous @ 60oC
ControlLogix BackplaneInterface
Display OutputDevice
OUT-0
RTNOUT-0
DC-0(+)
OUT-0
Surge Current Chart
Simplified Schematic
Surge
+5V
C u r r e n
t
Time0 10 ms
2 A
4 A
Attribute 1756-OB8EI
Short trip > 4.5 A for 500μs max (output on, then short)> 4.5 A for 1.5 ms max (output on into short)
Timestamp of diagnostics ±1 ms
Attribute 1756-OB8EI
Outputs 8 individually isolated
Voltage category 12/24V DC source
Operating voltage range 10...30V DC
Output delay, off to on 1 ms
Output delay, on to off 2 ms
Current draw @ 5.1V 165 mA
Current draw @ 24V 2 mA
DC OUTPUT
S T 0 1 2 3 4 5 6 7 O
K FUSE
ELECTRONICALLY FUSED
0 1 2 3 4 5 6 7
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 94/158
94 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Power dissipation, max 4.6W A @ 60 °C
Thermal dissipation, max 15.70 BTU/hr
Off-state leakage current, max 0.5 mA per point
On-state voltage drop, max 0.5V DC @ 2 ACurrent per point, max 2 A @ 60 °C
Current per module, max 16 A @ 60 °C
Surge current per point 4 A for 10 ms each, repeatable every 1 s @ 60 °
Load current, min 2 mA
Isolation voltage 250V user to backplane, Reinforced Insulation Ty250V channel to channel, Basic Insulation TypeTested to withstand 1900V DC for 2 s user to backplTested to withstand 1900V DC for 2 s channel to cha
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slotChassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.25...2.5 mm2 (22…14 AWG) stranded, 1.2 mm (3/64in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1)
Maximum wire size requires extended housing, cat. no. 1756-TBE.(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB8EI
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 95/158Publication 1756-TD002A-EN-E - May 2009 95
1756 ControlLogix I/O Modu
Certifications - 1756-OB8EI
Certification (1) 1756-OB8EI
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 96/158
96 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OB8IControlLogix DC (10...30V) isolated output module
Technical Specifications - 1756-OB8I
DC-0 (+) RTN OUT-0 DC-1 (+) RTN OUT-1 DC-2 (+) RTN OUT-2 DC-3 (+) RTN OUT-3 DC-4 (+) RTN OUT-4 DC-5 (+) RTN OUT-5 DC-6 (+) RTN OUT-6 DC-7 (+) RTN OUT-7
Not Used Not Used
OUT-0 OUT-0 OUT-1 OUT-1 OUT-2 OUT-2 OUT-3 OUT-3 OUT-4 OUT-4 OUT-5 OUT-5 OUT-6 OUT-6 OUT-7 OUT-7 Not Used Not Used
2468101214161820222426283032
3436
135791113151719212325272931
3335
DaisyChain toOtherRTBs
DaisyChain toOtherRTBs
1756-OBI
Isolated Wir in g
Non isolated Wir in g
Continuous @ 60oC
ControlLogix BackplaneInterface
Display OutputDevice
OUT-0
RTNOUT-0
DC-0(+)
OUT-0
Surge Current Chart
Simplified Schematic
Surge
+5V
C u r r e n
t
Time0 10 ms
2 A
4 A
Attribute 1756-OB8I
Outputs 8 individually isolated
Voltage category 12/24V DC source
Operating voltage range 10...30V DC
Output delay, off to on 1 ms
Output delay, on to off 2 ms
Current draw @ 5.1V 165 mA
Current draw @ 24V 2 mA
Power dissipation, max 4.6W A @ 60 °C
Thermal dissipation, max 15.70 BTU/hrOff-state leakage current, max 0.5 mA per point
On-state voltage drop, max 0.5V DC @ 2 A
Current per point, max 2 A @ 60 °C
Current per module, max 16 A @ 60 °C
Surge current per point 4 A for 10 ms each, repeatable every 1 s @ 60 °
Load current, min 2 mA
DC OUTPUT
ST 0 1 2 3 4 5 6 7 OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 97/158Publication 1756-TD002A-EN-E - May 2009 97
1756 ControlLogix I/O Modu
Certifications - 1756-OB8I
Isolation voltage 250V user to backplane, Reinforced Insulation Ty250V channel to channel, Basic Insulation TypeTested to withstand 1900V DC for 2 s user to backplTested to withstand 1900V DC for 2 s channel to cha
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.25...2.5 mm2 (22…14 AWG) stranded, 1.2 mm (3/64in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB8I
Certification (1) 1756-OB8I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 98/158
98 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OB16DControlLogix DC (19.2...30V) diagnostic output module
Diagnostics - 1756-OB16D
Technical Specifications - 1756-OB16D
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+ –
Daisy Chainto Other RTBs
DC COM
0puorG0puorG
1puorG1puorG
1756-OB16D
+DC-0+DC-0+DC-0+DC-0
+DC-1
+DC-0+DC-0+DC-0GND-0
Not Used
+DC-1+DC-1
+DC-1+DC-1+DC-1
+DC-1GND-1GND-1
OUT-0OUT-1OUT-2OUT-3
OUT-8
OUT-4OUT-5OUT-6OUT-7
Not Used
OUT-9OUT-10OUT-11OUT-12OUT-13
OUT-14OUT-15Not Used
Daisy Chain to Other RTBs
ControlLogixBackplaneInterface Display
+5VShort CircuitDetectOptoisolation
+5V
+ DC
OUT
RTNOutput Verify/No Load
Surge Current Chart
Continuous @ 30° C
Simplified schematic
Continuous @ 60° C
Surge
+5V
C u r r e n
t
Time0 10 ms
2 A
4 A
Attribute 1756-OB16D
Short trip 8 A for 180 ms10 A for 120 ms
No load Off-state detection only
Output verification On-state detection only
Pulse test Configurable maximum pulse width
Time stamp of diagnostics ±1 ms
Attribute 1756-OB16D
Outputs 16 diagnostic (8 points/group)
Voltage category 24V DC source
Operating voltage range 19.2...30V DC
Output delay, off to on 1 ms
Output delay, on to off 5 ms
S T 0 1 2 3 4 5 6 7
F LT 0 1 2 3 4 5 6 7
DIAGNOSTIC
ST 8 9 10111213 14 15
FLT 8 9 10 1112131415
DC OUTPUT
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 99/158Publication 1756-TD002A-EN-E - May 2009 99
1756 ControlLogix I/O Modu
Current draw @ 5.1V 250 mA
Current draw @ 24V 140 mA
Power dissipation, max 3.3 W @ 60 °C
Thermal dissipation, max 11.25 BTU/hrOff-state leakage current per point, max 1 mA per point
On-state voltage drop, max 1.2V DC @ 2A
Current per point, max 2 A @ 30 °C (linear derating)1 A @ 60 °C (linear derating)
Current per module, max 8 A @ 30 °C (linear derating)4 A @ 60 °C (linear derating)
Surge current per point 4 A for 10 ms per point, repeatable every 1 s
Load current, min 3 mA per point
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type CopperSlot width None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB16D
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 100/158
100 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OB16D
Certification (1) 1756-OB16D
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 101/158Publication 1756-TD002A-EN-E - May 2009 101
1756 ControlLogix I/O Modu
1756-OB16EControlLogix DC (10...31.2V) electronically-fused output module
Technical Specifications - 1756-OB16E
12
34
56
78
910
1112
1314
1516
1718
1920
+ –
Daisy Chain toOther RTBs
Group 0Group 0
Group 1Group 1
DC COM
OUT-1
OUT-3
OUT-5
OUT-7
OUT-9
OUT-11
OUT-13
OUT-15
DC-0(+)
DC-1(+)
OUT-0
OUT-2
OUT-4
OUT-6
OUT-8
OUT-10
OUT-12
OUT-14
RTN OUT-0
RTN OUT-1
1756-OB16E
ControlLogixBackplaneInterface
ElectronicFuse Circuitry
Continuous @ 60oC
Display Optoisolation
RTNOUT-0
OUT-0
DC-0(+)
Surge Current Chart
Simplified Schematic
Surge
C u r r e n
t
Time0 10 ms
1 A
2 A
Attribute 1756-OB16E
Outputs 16 electronically fused (8 points/group)
Voltage category 12/24V DC source
Operating voltage range 10...31.2V DC
Output delay, off to on 1 ms
Output delay, on to off 1 ms
Current draw @ 5.1V 250 mA
Current draw @ 24V 2 mA
Power dissipation, max 4.1 W @ 60 °C
Thermal dissipation, max 13.98 BTU/hrOff-state leakage current per point, max 1 mA per point
On-state voltage drop, max 400 mV DC @ 1 A
Current per point, max 1 A @ 60 °C
Current per module, max 8 A @ 60 °C
Surge current per point 2 A for 10 ms per point, repeatable every 2 s @
Load current, min 3 mA per point
DC OUTPUT
S T 0 1 2 3 4 5 6 7
ST 8 9 10 11 1213 14 15
OK
FUSE
FUSE
ELECTRONICALLY FUSED
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 102/158
102 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OB16E
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBNH
1756-TBSHSlot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Slot width None (open-style)(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB16E
Certification (1) 1756-OB16E
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 103/158Publication 1756-TD002A-EN-E - May 2009 103
1756 ControlLogix I/O Modu
1756-OB16IControlLogix DC (10...30V) isolated output module
Technical Specifications - 1756-OB16I
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+ –
Non isolatedWir in g
Isolated Wir in g
Daisy Chain to Other RTBs
1756-OB16I
DC-0 (+)DC-1 (+)
DC-2 (+)DC-3 (+)
DC-8 (+)
DC-4 (+)
DC-5 (+)
DC-6 (+)
DC-7 (+)
Not Used
DC-9 (+)
DC-10 (+)
DC-11 (+)
DC-12 (+)
DC-13 (+)
DC-14 (+)DC-15 (+)
DC-15 (+)
OUT-0OUT-1
OUT-2OUT-3
OUT-8
OUT-4
OUT-5
OUT-6
OUT-7
Not Used
OUT-9
OUT-10
OUT-11
OUT-12
OUT-13
OUT-14OUT-15
Not Used
DC-0 (+)
DC(+)
Jumper Bar(Cut to Length)
DC-2 (+)
DC-6 (+)
Sin kin g Ou tpu t Wir in g
Non isolatedSour cin gOu tpu t
Wir in g
Isolated Sour cin gOu tpu t Wir in g
DC-0 (-)
DC-2 (-)
DC-6 (-)
DC(-)
ControlLogix Backplane Interface
Continuous @ 60oC
Display
Surge Current Chart
Simplified Schematic
Surge
Continuous @ 30oC
OUT-0
DC-0(+)
C u r r e n
t
Time0 10 ms
2 A
4 A
+5V
Attribute 1756-OB16I
Outputs 16 individually isolated
Voltage category 12/24V DC sink/source
Operating voltage range 10...30V DC
Output delay, off to on 1 ms
Output delay, on to off 2 ms
Current draw @ 5.1V 350 mA
Current draw @ 24V 2.5 mA
Power dissipation, max 3.6 W @ 60 °CThermal dissipation, max 12.28 BTU/hr
Off-state leakage current per point, max 0.5 mA per point
On-state voltage drop, max 1.2V DC @ 2 A
Current per point, max 2 A @ 30 °C1 A @ 60 °C
Current per module, max 8 A @ 30 °C4 A @ 60 °C
Surge current per point 4 A for 10 ms per point, repeatable every 2 s
Load current, min 1 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 1415
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 104/158
104 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OB16I
Isolation voltage 250V continuousTested at 2546V DC for 1 s, channel to channel, I/O system
Removable terminal block 1756-TBCH
1756-TBS6HSlot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Slot width None (open-style)(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB16I
Certification (1) 1756-OB16I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 105/158Publication 1756-TD002A-EN-E - May 2009 105
1756 ControlLogix I/O Modu
1756-OB16ISControlLogix DC (10...30V) scheduled, isolated output module
Technical Specifications - 1756-OB16IS
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+ –
Non isolated Wir in g
Isolated Wi r in g
Daisy Chain to Other RTBs
1756-OB16IS
DC-0 (+)DC-1 (+)DC-2 (+)DC-3 (+)
DC-8 (+)
DC-4 (+)DC-5 (+)DC-6 (+)DC-7 (+)
Not Used
DC-9 (+)DC-10 (+)DC-11 (+)DC-12 (+)DC-13 (+)DC-14 (+)
DC-15 (+)DC-15 (+)
OUT-0OUT-1OUT-2OUT-3
OUT-8
OUT-4OUT-5OUT-6OUT-7
Not Used
OUT-9OUT-10OUT-11OUT-12OUT-13OUT-14
OUT-15Not Used
DC-0 (+)
DC(+)
Jumper Bar(Cut to Length)
DC-2 (+)
DC-6 (+)Sin kin g Ou tpu t Wir in g
Non isolatedSour ci n g
Ou tpu t Wir in g
Isolated So ur ci n gOu tpu t Wir in g
DC-0 (-)
DC-2 (-)
DC-6 (-)
DC(-)
ControlLogix Backplane Interface
Continuous @ 60o C
Display
Surge Current Chart
Simplified Schematic
Surge
Continuous @ 30oC
OUT-0
DC-0(+)
C u r r e n
t
Time0 10 ms
2 A
4 A
+5V
Attribute 1756-OB16IS
Outputs 16 individually isolated, 8 scheduled
Voltage category 12/24V DC sink/source
Operating voltage range 10...30V DC
Output delay, off to on 1 ms
Output delay, on to off 2 ms
Current draw @ 5.1V 350 mA
Current draw @ 24V 2.5 mA
Power dissipation, max 3.6 W @ 60 °C
Thermal dissipation, max 12.28 BTU/hrOff-state leakage current per point, max 0.5 mA per point
On-state voltage drop, max 1.2V DC @ 2 A
Current per point, max 2 A @ 30 °C1 A @ 60 °C
Current per module, max 8 A @ 30 °C4 A @ 60 °C
Surge current per point 4 A for 10 ms per point, repeatable every 2 s
Load current, min 1 mA per point
DC OUTPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 1213 1415
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 106/158
106 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OB16IS
Isolation voltage 250V continuousTested at 2546V DC for 1 s, channel to channel, I/O system
Removable terminal block 1756-TBCH
1756-TBS6HSlot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Slot width None (open-style)(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB16IS
Certification (1) 1756-OB16IS
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1)When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 107/158Publication 1756-TD002A-EN-E - May 2009 107
1756 ControlLogix I/O Modu
1756-OB32ControlLogix DC (10...31.2V) output module
Technical Specifications - 1756-OB32
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
27282930
3132
3334
3536
+ _
Daisy Chainto OtherRTBs
Group 0
Group 1
Group 0
Group 1
DC COM
OUT-1OUT-3OUT-5OUT-7OUT-9OUT-11OUT-13OUT-15DC-0(+)
DC-1(+)
OUT-0OUT-2OUT-4OUT-6OUT-8OUT-10OUT-12OUT-14RTN OUT-0
RTN OUT-1
OUT-17OUT-19OUT-21OUT-23
OUT-25OUT-27OUT-29OUT-31
OUT-16OUT-18OUT-20OUT-22
OUT-24OUT-26OUT-28OUT-30
1756-OB32
Continuous @ 60oC
+5V
RTN OUT-0
OUT-0
DC-0(+
ControlLogix Backplane Interface
Display
Surge Current Chart
Simplified Schematic
Surge
C u r r e n
t
Time0 10 ms
0.5 A
1 A
Attribute 1756-OB32
Outputs 32 (16 points/group)
Voltage category 12/24V DC source
Operating voltage range 10...31.2V DC
Output delay, off to on 1 ms
Output delay, on to off 1 ms
Current draw @ 5.1V 300 mA
Current draw @ 24V 2 mA
Power dissipation, max 4.8 W @ 60 °C
Thermal dissipation, max 16.37 BTU/hrOff-state leakage current per point, max 0.5 mA per point
On-state voltage drop, max 200 mV DC @ 0.5 A
Current per point, max 0.5 A @ 50 °C (linear derating)0.35 A @ 60 °C
Current per module, max 16 A @ 50 °C (linear derating)10 A @ 60 °C
Surge current per point 1 A for 10 ms per point, repeatable every 2 s @
Load current, min 3 mA per point
DC OUTPUT
OK
ST 0 1 2 3 4 5 6 7
ST 8 9 1
0 21 3 4 51 1 1 11
ST 6 718 09 1 2 3
1 2 2 221 1
ST 4 526 87 9 0 1
2 2 2 332 2
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 108/158
108 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OB32
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBCH
1756-TBS6HSlot width 1
Module Location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1751756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)Certifications‡ c-UL-us, CE, CSA, C-Tick, FM, ATEX
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OB32
Certification (1) 1756-OB32
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 109/158Publication 1756-TD002A-EN-E - May 2009 109
1756 ControlLogix I/O Modu
1756-OC8ControlLogix DC (30...60V) output module
Technical Specifications - 1756-OC8
12
34
56
78
910
1112
1314
1516
1718
1920
+ –
Group 0
Group 1
Daisy Chain to Other RTBs
Daisy Chain toOther RTBs
1756-OC8
Group 0
Group 1
DC-0 (+)
DC-0 (+)
DC-0 (+)
DC-0 (+)
DC-1(+)
DC-1(+)
DC-1(+)
DC-1(+)
RTN OUT-0
RTN OUT-1
OUT-0
OUT-1
OUT-2
OUT-3
OUT-4
OUT-5
OUT-6
OUT-7
RTN OUT-0
RTN OUT-1
DC COM
Continuous @ 60oC
+5V
RTN OUT-0
OUT-0
DC-0(+
ControlLogix Backplane Interface
Display
Surge Current Chart
Simplified Schematic
Surge
C u r r e n
t
Time0 10 ms
2 A
4 A
Attribute 1756-OC8
Outputs 8 (4 points/group)
Voltage category 48V DC source
Operating voltage range 30...60V DC
Output delay, off to on 1 ms
Output delay, on to off 2 ms
Current draw @ 5.1V 165 mA
Current draw @ 24V 2 mA
Power dissipation, max 4.9 W @ 60 °CThermal dissipation, max 16.71 BTU/hr
Off-state leakage current, max 1 mA per point
On-state voltage drop, max 2V DC @ 2 A
Current per point, max 2 A @ 60 °C
Current per module, max 8 A @ 60 °C
Surge current per point 4 A for 10 ms per point, repeatable every 1 s @
Load current, min 2 mA per point
DC OUTPUT
S T 0 1 2 3 4 5 6 7 O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 110/158
110 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OC8
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBNH
1756-TBSHSlot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)(1) Maximum wire size requires extended housing, cat. no. 1756-TBE. Maximum wire size requirehousing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OC8
Certification (1) 1756-OC8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 111/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 112/158
112 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Current draw @ 24V 120 mA
Power dissipation, max 3.25 W, 4 channel current
Thermal dissipation 10.91 BTU/hr
Open circuit detection Current output only (Output must be set to >0.1 Overvoltage protection 24V DC
Short circuit protection Electronically current limited to 21mA or less
Drive capability Voltage: >2000ΩCurrent: 0…750Ω
Settling time <2 ms to 95% of final value with resistive loads
Calibrated accuracy 4…21 mA, -10.4…10.4V: Better than 0.05% of r25 °C
Calibration interval 12 months
Offset drift 50μV/ °C100 nA/°C
Gain drift with temperature Voltage: 25 ppm/°C, 520μV/°CCurrent: 50 ppm/°C, 1050μA/°C
Module error Voltage: 0.15% of rangeCurrent: 0.3% of range
Module scan time 12 ms floating point8 ms integer
Isolation voltage Tested at 2550V DC for 1 s, I/O to system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 2(2)
Wire type Copper
Enclosure type rating None (open-style)
Certifications‡ c-UL-us, CE, CSA, C-Tick, FM, ATEX
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OF4
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 113/158Publication 1756-TD002A-EN-E - May 2009 113
1756 ControlLogix I/O Modu
Certifications - 1756-OF4
Certification (1) 1756-OF4
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 114/158
114 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OF6CIControlLogix current loop output analog module
Technical Specifications - 1756-OF6CI
12
34
56
78
910
1112
1314
1516
1718
1920
iOUT-1
ALT-1
RTN-1
OUT-3
RTN-3
Not Used
OUT-5
ALT-5
ALT-3
RTN-5
OUT-0
ALT-0
RTN-0
OUT-2
RTN-2
Not Used
OUT-4
ALT-4
ALT-2
RTN-4
User AnalogOutput Device
ShieldGround
1756-OF6CI 0...550 Ω
12
34
56
78
910
1112
1314
1516
1718
1920
iOUT-1
ALT-1
RTN-1
OUT-3
RTN-3
Not Used
OUT-5
ALT-5
ALT-3
RTN-5
OUT-0
ALT-0
RTN-0
OUT-2
RTN-2
Not Used
OUT-4
ALT-4
ALT-2
RTN-4
User AnalogOutput Device
Shield Ground
1756-OF6CI 551...1000 Ω
• Place additional devices anywhere in the loop.
• Do not connect more than two wires to any single terminal.
• Place additional devices anywhere in the loop.
• Do not connect more than two wires to any single termina
Input Signal to User Count Conversion - 1756-OF6CI
Range Low Signal and User Counts High Signal and User Counts
0...20 mA 0 mA-32768 counts
21.074 mA32767 counts
Attribute 1756-OF6CI
Outputs 6 individually isolated
Output range 0…21 mA
Resolution 13 bits across 21 mA (2.7μA)
Current draw @ 5.1V 250 mA for 0...550 W loads terminated on OUTRTNs(Total backplane power in this range 6.7 W)250 mA for 551...1000 W loads terminated on OUTsALTs(Total backplane power in this range 8.5 W)
ANALOG OUTPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 115/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 116/158
116 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OF6CI
Certification (1) 1756-OF6CI
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 117/158Publication 1756-TD002A-EN-E - May 2009 117
1756 ControlLogix I/O Modu
1756-OF6VIControlLogix voltage loop output analog module
Technical Specifications - 1756-OF6VI
12
34
56
78
910
1112
1314
1516
1718
1920
+
–
Shield Ground
1756-OF6VI
OUT-1
Not Used
RTN-1
OUT-3
RTN-3
Not Used
OUT-5
Not Used
Not Used
RTN-5
OUT-0
Not Used
RTN-0
OUT-2
RTN-2
Not Used
OUT-4
Not Used
Not Used
RTN-4
User AnalogOutput Device
• Place additional devices anywhere in the loop.• Do not connect more than two wires to any single terminal.
Input Signal to User Count Conversion - 1756-OF6V
Range Low Signal and User Counts High Signal and User Counts
±10V -10.517V-32768 counts
10.517V32767 counts
Attribute 1756-OF6VI
Outputs 6 individually isolated
Output range ± 10.5V
Resolution 14 bits across 21V (1.3 mV)(13 bits across 10.5V +sign bit)
Current draw @ 5.1V 250 mA
Current draw @ 24V 175 mA
Power dissipation, max 4.85 W
Thermal dissipation 16.54 BTU/hr
Output impedance <1Ω
Open circuit detection None
Overvoltage protection 24V DC
Short circuit protection Electronically current limited
Drive capability > 1000Ω loads, 10 mA
ANALOG OUTPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 118/158
118 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OF6VI
Settling time < 2 ms to 95% of final value with resistive loads
Calibrated accuracy 4…21 mA: Better than 0.1% of range @ 25 °C
Calibration interval 6 months
Offset drift 60μV/ °CGain drift with temperature 50 ppm/°C, 80 ppm/°C max
Module error 0.5% of range
Module scan time 25 ms floating point10 ms integer
Isolation voltage 250V continuousTested at 1700V DC for 1 s, channel to channel, I/O system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-APower supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,
1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 2(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OF6VI
Certification (1) 1756-OF6VI
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 119/158Publication 1756-TD002A-EN-E - May 2009 119
1756 ControlLogix I/O Modu
1756-OF8ControlLogix voltage/current output analog module
Technical Specifications - 1756-OF8
12
34
56
78
910
1112
1314
1516
1718
1920
Shield Ground
i
CurrentOutputLoad
1756-OF8 Curr en t
VOUT-4
IOUT-4
RTN
VOUT-5
VOUT-6
IOUT-6
RTNVOUT-7
IOUT-5
IOUT-7
VOUT-0
IOUT-0
RTN
VOUT-1
VOUT-2
IOUT-2
RTNVOUT-3
IOUT-1
IOUT-3
A
12
34
56
78
910
1112
1314
1516
1718
1920
+
–
Shield Ground
1756-OF8 Voltage
VOUT-4
IOUT-4
RTN
VOUT-5
VOUT-6
IOUT-6
RTN
VOUT-7
IOUT-5
IOUT-7
VOUT-0
IOUT-0
RTN
VOUT-1
VOUT-2
IOUT-2
RTN
VOUT-3
IOUT-1
IOUT-3
• Place additional loop devices (such as strip chart recorders) atthe A location noted above.
• Do not connect more than two wires to any single terminal.
• All terminals marked RTN are connected internally.
• Do not connect more than two wires to any single terminal.• All terminals marked RTN are connected internally.
Input Signal to User Count Conversion - 1756-OF8
Range Low Signal and User Counts High Signal and User Counts
0...20 mA 0 mA-32768 counts
21.2916 mA32767 counts
±10V -10.4336V-32768 counts
10.4336V32767 counts
Attribute 1756-OF8
Outputs 8 voltage or current
Output range ± 10.4V0…21 mA
Resolution 15 bits across 21 mA - 650 nA/bit15 bits across 10.4V - 320μV/bit
Current draw @ 5.1V 150 mA
ANALOG OUTPUT
CAL
OK
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 120/158
120 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Current draw @ 24V 210 mA
Power dissipation, max 4.92 W, 4 channel current
Thermal dissipation 16.78 BTU/hr
Open circuit detection Current output only (Output must be set to >0.1 Overvoltage protection 24V DC
Short circuit protection Electronically current limited to 21 mA or less
Drive capability Voltage: > 2000Ω Current: 0…750Ω
Settling time < 2 ms to 95% of final value with resistive loads
Calibrated accuracy 4…21 mA, -10.4…10.4V: Better than 0.05% of r25 °C
Calibration interval 12 months
Offset drift 50μV/°C100 nA/°C1μA/°C
Gain drift with temperature Voltage: 25 ppm/°C maxCurrent: 50 ppm/°C max
Module error Voltage: 0.15% of rangeCurrent: 0.3% of range
Module scan time 12 ms min floating point8 ms min integer
Isolation voltage Tested at 2550V DC for 1 s, I/O to system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 2(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OF8
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 121/158Publication 1756-TD002A-EN-E - May 2009 121
1756 ControlLogix I/O Modu
Certifications - 1756-OF8
Certification (1) 1756-OF8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 122/158
122 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OF8HControlLogix voltage/current output analog module with HART protocol
Technical Specifications - 1756-OF8H
1756-OF8H
Input Signal to User Count Conversion - 1756-OF8
Range Low Signal and User Counts High Signal and User Counts
0...20 mA 0 mA-32768 counts
21.2916 mA32767 counts
±10V -10.4336V-32768 counts
10.4336V32767 counts
Attribute 1756-OF8H
Outputs 8 voltage or current
Output range ±10.4V0…20 mA4…20 mA
Resolution 15…16 bits
Current draw @ 5V 200 mA
Current draw @ 24V 230 mA
Power dissipation, max 4.92 W, 8 channel current
Thermal dissipation 16.78 BTU/hr
Output impedance Voltage: >2 kΩ @ 10.4VCurrent: 50…750Ω drive
Open circuit detection time Current output only (output must be set to < 0.1
Overvoltage protection, max ±24V DC
Drive capability Voltage: > 2000Ω @ 10.4VCurrent: 50…750Ω with short circuit survival current
Load reactance Voltage: 1μFCurrent: 10μH
ANALOG OUTPUT
CAL
OK
HART
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 123/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 124/158
124 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OF8H
Certification (1) 1756-OF8H
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 125/158Publication 1756-TD002A-EN-E - May 2009 125
1756 ControlLogix I/O Modu
1756-OG16ControlLogix TTL output module
Low to True Format - 1756-OG16• 0…0.4V DC = Output guaranteed to be in on-state• 0.4…4.5V DC = Output state not guaranteed• 4.5…5.5V DC = Output guaranteed to be in off-state
1
3
5
7
9
19
17
15
13
11
2
4
6
8
10
20
18
16
14
12
OUT-1
OUT-3
OUT-5
OUT-7
DC-0(+)
OUT-0
OUT-2
OUT-4
OUT-6
DC COM 0
OUT-9
OUT-11
OUT-13
OUT-15
DC-1(+)
OUT-8
OUT-10
OUT-12
OUT-14
DC COM 1
– DC
+ DC
+5V DC
1756-OG16
1
3
5
7
9
19
17
15
13
11
2
4
6
8
10
20
18
16
14
12
OUT-1
OUT-3
OUT-5
OUT-7
DC-0(+)
OUT-0
OUT-2
OUT-4
OUT-6
DC COM 0
OUT-9
OUT-11
OUT-13OUT-15
DC-1(+)
OUT-8
OUT-10
OUT-12OUT-14
DC COM 1
Capacitor
0.01 µF Typical(See notes below.)
DC PowerW ire
I/OW ire
5V DCPower
+
–
+
–TTLOutputDevice
1756-OG16
DC COM
OUT
74AC14
OUT
+5 DC
74AC14
Standard Wiring CE Compliant Wiring
Simplified Schematic
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 126/158
126 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Technical Specifications - 1756-OG16
Attribute 1756-OG16
Outputs 16 (8 points/group)
Voltage category 5V DC TTL(1)
(1) TTL outputs are inverted (0 to +0.4V dc = low voltage = True = On.) Use a NOT instruction in yconvert to traditional True - High logic.
Operating voltage range 4.5...5.5V DC source50 mV P-P ripple max
Output delay, off to on 450μs
Output delay, on to off 700μs
Current draw @ 5.1V 210 mA
Current draw @ 24V 2 mA
Power dissipation, max 1.5 W @ 60 °C
Thermal dissipation, max 5.2 BTU/hr @ 60 °C
Off-state leakage current per point, max 0.1 mA per point
On-state voltage drop, max 0.4V DC
Current per point, max 24 mA @ 60 °C
Current per module, max 384 mA @ 60 °C
Load current, min 0.15 mA per point
Isolation voltage 250V continuous, I/O group to group, I/O to syst
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(2)
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 2(3)
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Wire type Copper
Slot width None (open-style)
DC OUTPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 1213 14 15
O
K
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 127/158Publication 1756-TD002A-EN-E - May 2009 127
1756 ControlLogix I/O Modu
Certifications - 1756-OG16
Certification (1) 1756-OG16
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1)When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 128/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 129/158Publication 1756-TD002A-EN-E - May 2009 129
1756 ControlLogix I/O Modu
Certifications - 1756-OH8I
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O channel to channel, I/system
Removable terminal block 1756-TBCH
1756-TBS6HSlot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OH8I
Certification (1) 1756-OH8I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 130/158
130 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-ON8ControlLogix AC (10...30V) output module
Technical Specifications - 1756-ON8
12
34
56
78
910
1112
1314
1516
1718
1920
Daisy Chain to Other RTBs
Group 0Group 0
Group 1Group 1
1756-ON8
L1-0
L1-0
L1-0
L1-0
L1-1
L1-1
L1-1
L1-1
L1-0
L1-1
OUT-0
OUT-1
OUT-2
OUT-3
OUT-4
OUT-5
OUT-6
OUT-7
Not Used
Not Used
L1
L2
ControlLogix Backplane Interface
OUT-0
L1-0
Display
Surge Current Chart
Simplified Schematic
Surge
+5V
C u r r e n t
Time0 43 ms
2 A
20 A
Attribute 1756-ON8
Outputs 8 (4 points/group)
Voltage category 24V AC
Operating voltage range 10…30V AC, current >50 mA, 47…63Hz16…30V AC, current <50 mA, 47…63Hz
Output delay, off to on 9.3 ms @ 60 Hz11 ms @ 50 Hz
Output delay, on to off 9.3 ms @ 60 Hz11 ms @ 50 Hz
Current draw @ 5.1V 200 mACurrent draw @ 24V 2 mA
Power dissipation, max 5.1 W @ 60 °C
Thermal dissipation, max 17.39 BTU/hr
Off-state leakage current, max 3 mA per point
On-state voltage drop, max 1.5V peak @ 2 A6V peak @ < 50 mA
Current per point, max 2 A @ 60 °C
S T 0 1 2 3 4 5 6 7 O
K
AC OUTPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 131/158Publication 1756-TD002A-EN-E - May 2009 131
1756 ControlLogix I/O Modu
Current per module, max 5 A @ 30 °C4 A @ 60 °C (linear derating)
Surge current per point 20 A for 43 ms per point, repeatable every 2 s @
Load current, min 10 mA per pointCommutating voltage 4V/μs for loads > 50 mA
0.2V/μs for loads < 50 mA(1)
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(2)
Wire category 1(3)
Wire type Copper
Enclosure type rating None (open style)
(1) The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/ms for loThe commutating dv/dt rating of the module for loads 50…500 mA (OUTPUT to L2) is 4V/ms maxcommutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on. If the commutating exceeded in the 10…50 mA range, a resistor may be added AC ross the output and L2. The purpose is to increase the total output current to 50 mA (I=V/R). At 50 mA and above, the module has a high
dv/dt rating. When adding a resistor for the output to L2, be sure it is rated for the power that it will d(P=(V**2)/R). If the commutating dv/dt rating is exceeded in the 50…500 mA range, the L1 AC waat fault. Be sure the waveform is a good sinusoid, void of any anomalies such as distorted or flattene
(2) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(3) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-ON8
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 132/158
132 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-ON8
Certification (1) 1756-ON8
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 133/158Publication 1756-TD002A-EN-E - May 2009 133
1756 ControlLogix I/O Modu
1756-OV16EControlLogix DC (10...30V) electronically-fused, sinking output module
Diagnostics - 1756-OV16E
Technical Specifications - 1756-OV16E
12
34
56
78
910
1112
1314
1516
1718
1920
+ –
Group 0Group 0
Group 1Group 1
DC COM
1756-OV16E
OUT-1
OUT-3
OUT-5
OUT-7
OUT-9
OUT-11
OUT-13
OUT-15
DC-0(+)
DC-1(+)
OUT-0
OUT-2
OUT-4
OUT-6
OUT-8
OUT-10
OUT-12
OUT-14
RTN OUT-0
RTN OUT-1
Daisy Chain to Other RTBs Daisy Chain to Other RTBs
ControlLogixBackplaneInterface
ElectronicFuse Circuitry
Continuous @ 60o C
Display Optoisolation
RTNOUT-0
OUT-0
DC-0(+)
Surge Current Chart
Simplified Schematic
Surge
C u r r e n
t
Time0 10 ms
1 A
2 A
Attribute 1756-OV16E
Short trip 5 A for 20 ms @ 24V DC (output on, then short)5 A for 20 ms @ 24V DC (output on into short)
Time stamp of diagnostics ±1 ms
Attribute 1756-OV16E
Outputs 16 electronically fused (8 points/group)
Voltage category 12/24V DC sink
Operating voltage range 10...30V DC
Output delay, off to on 1 ms
Output delay, on to off 1 ms
Current draw @ 5.1V 210 mA
Current draw @ 24V 2 mA
DC OUTPUTST 0 1 2 3 4 5 6 7
ST 8 9 101112131415
OK
FUSE
FUSE
ELECTRONICALLYFUSED
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 134/158
134 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Power dissipation, max 6.72 W @ 60 °C
Thermal dissipation, max 22.94 BTU/hr
Off-state leakage current per point, max 1 mA per point
On-state voltage drop, max 700 mV DC @ 1 ACurrent per point, max 1 A @ 60 °C
Current per module, max 8 A @ 60 °C
Surge current per point 2 A for 10 ms per Point, repeatable every 2 s @
Load current, min 2 mA per point
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Copper
Slot width None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OV16E
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 135/158Publication 1756-TD002A-EN-E - May 2009 135
1756 ControlLogix I/O Modu
Certifications - 1756-OV16E
Certification (1) 1756-OV16E
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 136/158
136 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OV32EControlLogix DC (10...30V) electronically-fused, sinking output module
Diagnostics - 1756-OV32E
Technical Specifications - 1756-OV32E
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
+ _
Daisy Chain toOther RTBs
Daisy Chain toOther RTBs
Group 0
Group 1
Group 0
Group 1
DC COM
OUT-1OUT-3OUT-5OUT-7OUT-9OUT-11OUT-13OUT-15DC-0(+)
DC-1(+)
OUT-0OUT-2OUT-4OUT-6OUT-8OUT-10OUT-12OUT-14RTN OUT-0
RTN OUT-1
OUT-17OUT-19OUT-21OUT-23
OUT-25OUT-27OUT-29OUT-31
OUT-16OUT-18OUT-20OUT-22
OUT-24OUT-26OUT-28OUT-30
1756-OV32E
ControlLogixBackplaneInterface
ElectronicFuse Circuitry
Continuous @ 60oC
Display Optoisolation
RTNOUT-0
OUT-0
DC-0(+)
Surge Current Chart
Simplified Schematic
Surge
C u r r e n
t
Time0 10 ms
1 A
2 A
Attribute 1756-OV32E
Short trip 5 A for 20 ms @ 24V DC (output on then short)5 A for 20 ms @ 24V DC (output into short)
Time stamp of diagnostics ±1 ms
Attribute 1756-OV32E
Outputs 32 electronically fused (16 points/group)Voltage category 12/24V DC sink
Operating voltage range 10...30V DC
Output delay, off to on 300μs
Output delay, on to off 1 ms
Current draw @ 5.1V 390 mA
Current draw @ 24V 2 mA
Power dissipation, max 5.88 W @ 60 °C
OK
ST 0 1 2 3 4 5 6 7
ST 8 9 10 21 3 4 51 1 1 11
ST 6 718 09 1 2 3
1 2 2 221 1
ST 4 526 87 9 0 1
2 2 2 332 2
DC OUTPUT
ELECTRONIC FUSING
F
0
F1
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 137/158Publication 1756-TD002A-EN-E - May 2009 137
1756 ControlLogix I/O Modu
Thermal dissipation, max 20.1 BTU/hr
Off-state leakage current per point, max 1 mA per point
On-state voltage drop, max 350 mV DC @ 0.5 A
Current per point, max 0.5 A @ 50 °C (linear derating)0.35 A @ 60 °C
Current per module, max 16 A @ 50 °C (linear derating)10 A @ 60 °C
Surge current per point 2 A for 10 ms per point, repeatable every 2 s @
Load current, min 2 mA per output
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module Location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 17561756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OV32E
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 138/158
138 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OV32E
Certification (1) 1756-OV32E
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1)When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 139/158Publication 1756-TD002A-EN-E - May 2009 139
1756 ControlLogix I/O Modu
1756-OW16IControlLogix AC (10...265V) DC (5...150V) isolated contact module
Technical Specifications - 1756-OW16I
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non isolated Wir in g
Isolated Wi r in g
Daisy Chainto Other RTBs
1756-OW16I
L1-0L1-1L1-2L1-3
L1-8
L1-4L1-5L1-6L1-7
L1-9L1-10L1-11L1-12L1-13
L1-14L1-15
Not Used
OUT-0OUT-1 N.O.OUT-2 N.O.OUT-3 N.O.
OUT-8 N.O.
OUT-4 N.O.OUT-5 N.O.OUT-6 N.O.OUT-7 N.O.
Not Used
OUT-9 N.O.OUT-10 N.O.OUT-11 N.O.OUT-12 N.O.OUT-13 N.O.
OUT-14 N.O.OUT-15 N.ONot UsedL1
Jumper Bar(Cut to Length)
DC-4 (-)
L2
L1-15
L2-0
DC-4 (+)
L1-0
L1-2 L2-2
ControlLogixBackplaneInterface
Display
OUT
L1+24V
Simplified Schematic
Attribute 1756-OW16I
Outputs 16 N.O. individually isolated
Operating voltage range 5...150V DC10...265V AC
Load dependent output voltage range 5…30V DC @ 2 A resistive48V DC @ 0.5 A resistive125V DC @ 0.25 A resistive125V AC @ 2 A resistive240V AC @ 2 A resistive
Resistive output current rating (at rated power) 2 A @ 5…30V DC0.5 A @ 48V DC0.25 A @ 125V DC2 A @ 125/240V AC
Inductive output current rating (at rated power) 2 A steady state @ 5…30V DC
0.5 A steady state @ 48V DC0.25 A steady state @ 125V DC2 A steady state, 15 A make @ 125V AC2 A steady state, 15 A make @ 240 V AC
Power rating (steady state), max 250 W for 125V AC resistive output480 W for 240V AC resistive output60 W for 30V DC resistive output24 W for 48V DC resistive output31 W for 125V DC resistive output250VA for 125V AC inductive output480VA for 240V AC inductive output60VA for 30V DC inductive output24VA for 48V DC inductive output31VA for 125V DC inductive output
S T 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O
K
RELAY OUTPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 140/158
140 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Output delay, off to on 13 ms
Output delay, on to off 13 ms
Current draw @ 5.1V 150 mA
Current draw @ 24V 150 mAPower dissipation, max 4.5 W @ 60 °C
Thermal dissipation, max 15.35 BTU/hr
Off-state leakage current per point, max 1.5 mA per point
Initial contact resistance, max 30 MΩ
Switching frequency, max 1 operation/3 s (0.3 Hz at rated load)
Bounce time, mean 1.2 ms
Expected contact life 300 K cycles resistive100 K cycles inductive
Isolation voltage 265V continuousTested at 2546V DC for 1 s, channel to channel, I/O system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,1756-PB75/B, 1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/6in.) insulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OW16I
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 141/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 142/158
142 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-OX8IControlLogix AC (10...265V) DC (5...150V) isolated contact module
Technical Specifications - 1756-OX8I
1234
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Non isolated Wir in g
Isolated Wi r in g
Daisy Chain to Other RTBs
1756-OX8I
L1-0L1-0L1-1L1-1
L1-4
L1-2L1-2L1-3L1-3
L1-4L1-5L1-5L1-6L1-6L1-7
L1-7
Not Used
OUT-0 N.C.OUT-0 N.O.OUT-1 N.C.OUT-1 N.O.
OUT-4 N.C.
OUT-2 N.C.OUT-2 N.O.OUT-3 N.C.OUT-3 N.O.
Not Used
OUT-4 N.O.OUT-5 N.C.OUT-5 N.O.OUT-6 N.C.OUT-6 N.O.OUT-7 N.C.
OUT-7 N.ONot UsedL1
Jumper Bar (Cut to Length)(Part number 97739201)
DC-2 (-)
L2
L1-7
L2-0
DC-2 (+)
L1-0
ControlLogixBackplaneInterface
+24V
Display
L1-0
OUT-0 N.C.
OUT-0 N.O.
Simplified Schematic
Attribute 1756-OX8I
Outputs 8 N.O.8 N.C. individually isolated (2 points/group)
Operating voltage range 5...150V DC10...265V AC @ 47…63
Load dependent output voltage range 5…30V DC @ 2 A resistive48V DC @ 0.5 A resistive125V DC @ 0.25 A resistive125V AC @ 2 A resistive240V AC @ 2 A resistive
Resistive output current rating (at rated power) 2 A @ 5…30V DC0.5 A @ 48V DC0.25 A @ 125V DC2 A @ 125/240V AC
Inductive output current rating (at rated power) 2 A steady state @ 5…30V DC0.5 A steady state @ 48V DC0.25 A steady state @ 125V DC2 A steady state, 15 A make @ 125V AC2 A steady state, 15 A make @ 240 V AC
Power rating (steady state), max 250 W for 125V AC resistive output480 W for 240V AC resistive output60 W for 30V DC resistive output24 W for 48V DC resistive output31 W for 125V DC resistive output250VA for 125V AC inductive output480VA for 240V AC inductive output60VA for 30V DC inductive output24VA for 48V DC inductive output31VA for 125V DC inductive output
Output delay, off to on 13 ms
Output delay, on to off 13 ms
S T 0 1 2 3 4 5 6 7 O
K
RELAY OUTPUT
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 143/158Publication 1756-TD002A-EN-E - May 2009 143
1756 ControlLogix I/O Modu
Current draw @ 5.1V 100 mA
Current draw @ 24V 100 mA
Power dissipation, max 3.1 W @ 60 °C
Thermal dissipation, max 10.57 BTU/hrOff-state leakage current per point, max 0 mA
Initial contact resistance, max 100 MΩ @ 6V 1 A
Switching frequency, max 1 operation/3 s (0.3 Hz at rated load)
Bounce time, mean 1.2 ms
Expected contact life 300 K cycles resistive100 K cycles inductive
Isolation voltage 265V continuousTested at 2546V DC for 1 s, channel to channel, I/O to sy
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 ininsulation(1)
Wire category 1(2)
Wire type Copper
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Attribute 1756-OX8I
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 144/158
144 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-OX8I
Certification (1) 1756-OX8I
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 145/158Publication 1756-TD002A-EN-E - May 2009 145
1756 ControlLogix I/O Modu
1756-CFMControlLogix configurable flow meter module
ShieldGround
InputDevice
1756-CFM Stan dar d Magn etic Picku p
Z0 12-24V DC
Z0 5V DC
Z0 Return
CustomerVCC
F0
F0 Return
Not Used
Not Used
Output 0
CustomerVCC
Z1 12-24V DC
Z1 5V DC
Z1 RET
Not Used
CustomerCommon
Not Used
Output 1
F1
F1 Return
12
34
56
78
910
1112
1314
1516
1718
1920CustomerCommon
+
–
1756-CFM Stan da rd Ou tpu t
12
34
56
78
910
1112
1314
1516
1718
1920
Load
+
–
Z0 12-24V DC
Z0 5V DC
Z0 Return
CustomerVCC
F0
F0 Return
Not Used
Not Used
Output 0
CustomerVCC
Z1 12-24V DC
Z1 5V DC
Z1 RET
Not Used
CustomerCommon
Not Used
Output 1
F1
F1 Return
CustomerCommon Load
+
–+
–
• This wiring diagram can be used in applications with 50 mV(magnetic pickup), 1.3V (TTL), or 4V (preamp level) thresholds.You must use RSLogix 5000 software to choose the appropriatethreshold level for your specific application.
• If separate power sources are used, do not exceed the specified
isolation voltage.
If separate power sources are used, do not exceed the specifieisolation voltage.
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 146/158
146 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Technical Specifications - 1756-CFM
Shield rGound
InputDevice
1756-CFM Stan da rd Prover /Store Coun t
12
34
56
78
910
1112
1314
1516
1718
1920
+
–
Z0 12-24V DC
Z0 5V DC
Z0 Return
CustomerVCC
F0
F0 Return
Not Used
Not Used
Output 0
CustomerVCC
Z1 12-24V DC
Z1 5V DC
Z1 RET
Not Used
CustomerCommon
Not Used
Output 1
F1
F1 Return
CustomerCommon
12-24V DC +
–
Shield Ground
• Detectors 1 and 2 must be wired in parallel.• Customer VCC may be used to power detectors. In this case, though, the maximum curre
wiring arm must be less than 4 A.• The wiring example above shows a 12-24V DC standard prover connected to the module
5V DC standard prover, make sure the positive wire is connected to the 5V terminal (such• If separate power sources are used, do not exceed the specified isolation voltage.
Attribute 1756-CFM
Inputs 4 (2 per channel)
Inputs per channel 2 Flowmeter (F) inputs used for all modes2 Gate inputs used in Totalizer mode for prover/storecount
Outputs 2 current sourcing
Current draw at 5.1V 300 mA
Current draw at 24V 6 mA
Backplane power, total 1.7 W
Power dissipation, max 6 W @ 60 °C
Thermal dissipation, max 20.4 BTU/hr
Isolation voltage 125V continuousTested at 1700V DC, I/O group to group, I/O to syste
Removable terminal block 1756-TBNH1756-TBSH
Slot width 1
METERING
DC I/O
OK
F0
Z0
F1
Z1
O0
O1
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 147/158Publication 1756-TD002A-EN-E - May 2009 147
1756 ControlLogix I/O Modu
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C,
1756-PB75/B, 1756-PC75/B, 1756-PH75/BPower supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 2 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.)insulation(1)
Wire category 1(2)
Wire type Belden 8761 or equivalent
Enclosure type rating None (open-style)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
1756-CFM Input Specifications
Attributes Value
Inputs 4 (2 per channel)
Inputs per channel 2 Flowmeter (F) inputs used for all modes2 Gate inputs used in Totalizer mode for prover/store count
Input type IEC Type 2 (6…30 mA) @ 24V DC
Count range, max 2,147,483,647
Input frequency, max 100 kHz @ flowmeter inputs (overrange occurs at 100 kHz)
Flowmeter input voltage ±30V, selectable input thresholds of 50 mV, 1.3V and 4V:• ±30V peak unterminated open circuit voltage, magnetic pickup• TTL compatible, input voltage >1.3V DC is Logic 1 and -0.7…1.3Logic 0• 12…24V DC powered preamp output, 4V DC threshold
Flowmeter input impedance 5 kΩ ±30% resistive
Filtering (inputs F0 & F1) Firmware selectable: High-speed 100 kHz or low-pass filter fo< 70 Hz
Gate input voltage range 5V operation: 4.5…5.5V DC12/24V operation: 10…31.2V DC
Gate input on-state current, min 4 mA
Gate input on-state current, nom 15 mA
Mechanical filter debouncing (Z0& Z1 Inputs)
Software selectable
Input sampling period User Selectable
Attribute 1756-CFM
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 148/158
148 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
Certifications - 1756-CFM
1756-CFM Output Specifications
Attribute Value
Outputs 2 current sourcing
Output voltage source Customer suppliedOutput voltage range 5V operation: 4.5…5.5V DC for 3…20 mA load per point
12/24V operation: 10…31.2V DC for 40 mA…1 A load per point
Output type IEC 1A 24V DC
Output Current per point 1 A @ 10…31.2V DC20 mA @ 4.5…5.5V DC(1)
(1) All outputs can be on simultaneously without derating.
Surge current, max 2 A for 50 ms, repeatable every 2 s
Off-state leakage current, max < 300μA @ 31.2V DC
On-state voltage drop, max 0.6Ω x current
Output control Any number of outputs is assignable to any of 2 flowmeter channEach output can have 2 “turn-on” and “turn-off” preset values
Output switching time < 50μ
s turn on, <300μ
s turn offOutputs triggered by Total; all other “turn-on” and “turn-off” times
Overload current Electronic (< 4A)
Output short circuit protection Electronic (No indication of fault. Remove overload and togglon/off to restore.)
Output reverse polarity protection Yes (If wired incorrectly, module outputs may be permanently
Certification (1) 1756-CFM
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 149/158Publication 1756-TD002A-EN-E - May 2009 149
1756 ControlLogix I/O Modu
1756-HSCControlLogix high-speed counter module
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Z1 (12...24V)Z1 (5V)Z1 (RET)B1 (12...24V)B1 (5V)B1 (RET)A1 (12...24V)A1 (5V)A1 (RET)Not UsedNot UsedNot Used
Z0 (12...24V)Z0 (5V)Z0 (RET)B0 (12..24V)B0 (5V)B0 (RET)A0 (12...24V)A0 (5V)A0 (RET)Not UsedNot UsedNot Used
COMMON 0COMMON 0COMMON 0DC-0(+)
Out 2Out 3COMMON 1COMMON 1COMMON 1DC-1(+)
Out 0Out 1
Black
Black
W hiteBlack
Blue
Green Allen-BradleyBulletin 845IncrementalEncoder
Differential LineDriver Output
1756-HSC to Allen -Bradley 845 In creme n tal En code r
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
JumperBlack
Blue
W hit
Not Used
10-30V DC
PhotoswitchSeries10,000Z1 (12...24V)
Z1 (5V)Z1 (RET)B1 (12...24V)B1 (5V)
B1 (RET)A1 (12...24V)A1 (5V)A1 (RET)Not UsedNot Used
Not Used
Z0 (12...24V)
Z0 (5V)Z0 (RET)B0 (12...24V)B0 (5V)
B0 (RET)A0 (12...24V)A0 (5V)A0 (RET)Not UsedNot Used
Not Used
COMMON 0COMMON 0COMMON 0
DC-0(+)
Out 2
Out 3COMMON 1COMMON 1COMMON 1DC-1(+)
Out 0Out 1
12...24V
1756-HSC to Allen -Br adley Ser ies 10,000 Photoelectr ic Sen so r
12
34
5678
910
1112
1314
1516
1718
1920
2122
2324
2526
2728
2930
3132
3334
3536
Jumpers
Black
Blue
Allen-BradleyBulletin 8723-wire DCProximitySensor
Z1 (12...24V)Z1 (5V)
Z1 (RET)B1 (12...24V)B1 (5V)B1 (RET)A1 (12...24V)A1 (5V)A1 (RET)Not UsedNot UsedNot Used
Z0 (12...24V)Z0 (5V)
Z0 (RET)B0 (12...24V)B0 (5V)B0 (RET)A0 (12...24V)A0 (5V)A0 (RET)Not UsedNot UsedNot Used
COMMON 0COMMON 0COMMON 0
DC-0(+)
Out 2Out 3COMMON 1COMMON 1COMMON 1
DC-1(+)
Out 0Out 1
12...24V DCReturn
12...24V DC
1756-HSC to Allen -Bradley 8723-wi re DC Proximity Sen so r
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 150/158
150 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-HSC Technical Specifications
Attribute 1756-HSC
Number of counters 2
Inputs per counter 3 (A, B, Z for gate/reset)Outputs 4 (2 points/group)
Operating voltage range 5V operation: 4.5…5.5V DC12/24V operation: 10…31.2V DC
Current draw at 5.1V 300 mA
Current draw at 24V 3 mA
Backplane power, total 1.9 W
Power dissipation, max 5.6 W @ 60°C
Thermal dissipation, max 19.1 BTU/hr
Isolation voltage 125V (continuous), basic insulation type between input group to
30V (continuous), basic insulation type between input group to inpu
Routine tested at 1700V DC for 1 s, between input group to input grinput group to system
Removable terminal block 1756-TBCH1756-TBS6H
Slot width 1
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17
Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756-PB75/B, 1751756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size 0.324...2.08 mm2 (22…14 AWG) stranded, 1.2 mm (3/64 in.) insulatio(1)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 1(2)
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Wire type Copper
Enclosure type rating None (open-style)
1756-HSC Input Specifications
Attribute Value
Number of counters 2Inputs per counter 3 (A, B, Z for gate/reset)
Input frequency, max 1 MHz in counter modes (A input)500 kHz in rate measurement mode (A input)250 kHz in encoder mode (A/B inputs, X1 or X4)70 Hz with filter enabled
Count range 0…16, 777, 214
Counting frequency, max 1000 kHz
Input current, min 4 mA
Input current, nom 15 mA
A
O
K
COUNTER
B Z
O
0
DC I/O
A B Z
0 0
O
1 1 1
0 1O O2 3
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 151/158Publication 1756-TD002A-EN-E - May 2009 151
1756 ControlLogix I/O Modu
Certifications - 1756-HSC
1756-HSC Output Specifications
Attribute Value
Outputs 4 (2 per common)
Output delay, off to on 20μs typical, 50μs maxOutput delay, on to off 60μs typical, 300μs max
Off-state leakage current perpoint, max
300μA
On-state voltage drop, max 0.55V
Output current rating, per point 20 mA @ 4.5…5.5V DC1.0 A @ 10…31.2V DC
Current limit < 9 A
Surge current per point 2 A for 10 ms every 1s @ 60 °C
Load current per point, min 5V operation: 3 mA12/24V operation: 40 mA
Output control Any number of output channels is assignable to each counter cha
Each output can have 2 "turn-on" and "turn-off" preset valuesShort circuit protection Electronic (Remove overload and toggle On/Off to restore.)
Reverse polarity protection Yes (If wired incorrectly, module outputs may be permanently d
Certification (1) 1756-HSC
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
ATEX European Union 94/9/EC ATEX Directive, compliant with:EN 60079-15; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 152/158
152 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-PLSControlLogix programmable limit switch module
+
_
+
_
OUTPUT 0
OUTPUT 1
OUTPUT 2
OUTPUT 3
DC PW R 0...3
INPUT 1
INPUT 0
OUTPUT 4
OUTPUT 7
DC PWR 4...7
OUTPUT 5
OUTPUT 6
INPUT 2
INPUT 3
INPUT 4
INPUT 5
INPUT 6
INPUT 7
DC COM 4-...7
12
34
56
78
910
1112
1314
1516
1718
1920
10...30V DC
1756-PLS In pu ts - Left Side
DC COM 0...3
+
_
OUTPUT 8
OUTPUT 9
OUTPUT 10
OUTPUT 11
DC PW R 8...11
INPUT 9
INPUT 8
OUTPUT 12
OUTPUT 15
DC PW R 12...15
OUTPUT 13
OUTPUT 14
INPUT 10
INPUT 11
INPUT 12
INPUT 13
INPUT 14
INPUT 15
DC COM 12...15
12
34
56
78
910
1112
1314
1516
1718
1920
1756-PLS Ou tpu ts - Right Side
DC COM 8...11
Do Not Use
Sine +
Sine –
Cosine +
Cosine –
12
34
56
78
910
1112
1314
1516
1718
1920
Allen-Bradley Resolver846-SJDA1CG-R3-C
F (S3)
D (S1)
E (S2)
G (S4)
A (R1)
B (R2)Reference +
Reference –
Do Not UseDo Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
Do Not Use
1756-PLS Resolver
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 153/158Publication 1756-TD002A-EN-E - May 2009 153
1756 ControlLogix I/O Modu
Technical Specifications - 1756-PLS
Attribute 1756-PLS
Module configuration Left section: 2 groups of 4 outputs and 4 inputs Center section: resolver interface and I/O controlRight section: 2 groups of 4 outputs and 4 inputs eac
Current draw at 5.1V 1000 mACurrent draw at 24V 125 mA
Power dissipation, max 25.7 W @ 30 °C21.3 W @ 60 °C
Thermal dissipation, max 87.74 BTU/hr @ 30 °C72.72 BTU/hr @ 60 °C
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O system
Removable terminal block Requires 3 RTBs: 1756-TBNH or 1756-TBSH
Slot width 3
Module location Chassis-based, any slot
Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A1Power supply, standard 1756-PA72/C, 1756-PA75/B, 1756-PB72/C, 1756
1756-PC75/B, 1756-PH75/B
Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2
Wire size Center: Alpha Cable #6054C (use 3 of 4 twisted paLeft and right: 2 mm2 (22…14 AWG) stranded, 1.2 mm(3/64 in.) insulation(1)
(1) Maximum wire size requires extended housing, cat. no. 1756-TBE.
Wire category 2 - Center slot1 - Left & right slots(2)
(2) Use this conductor category information for planning conductor routing as described in the systeinstallation manual. See the Industrial Automation Wiring and Grounding Guidelines,publication 1770-4.1.
Wire type Left and right: Copper
Enclosure type rating None (open style)
OK
0OK
31 42 5 6 7
0 31 42 5 6 7
OUT
IN
PROG. LIMIT SWITCHPROG. LIMIT SWITCH
REVLOSERO/ICD
8OK
119 1210 13 14 15OUT
IN
PROG. LIMIT SWITCH
DC I/O
8 119 1210 13 14 15
Indicator for LeftS lot I/O Module
Indicator for Resolver Module Indicator for RightSlot I/O Module
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 154/158
154 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
1756-PLS Resolver Specifications
Attribute Value
Resolver location Center section
Compatible resolver Allen-Bradley resolver 846-SJxxxx-R3-x (x = customer optionsResolver interface 2V rms, reference output (differential pair)
2V rms, sine and cosine inputs (2 differential pairs)
Reference voltage 2V rms ±20%
Reference frequency 5 kHz ±20%
Digital resolution 12 bits (4096 counts from hardware)
Angular resolution 0.088 °/bit
Digital count range 0…4095 (decimal)
Maximum tracking rate ±1800 RPM
Repeatability ±0.0488% of full scale
Accuracy ±0.0976% of full scale
Isolation voltage 100% tested at 1700V DC for 1 s
1756-PLS Input Specifications
Attribute Value
Inputs 16 (2 groups of 4 per I/O section)
Voltage category 12/24V DC
Operating voltage range 10.8…31.2V DC
Input delay, off to on < 15μs @ 30 °C< 150μs @ 60 °C
Input delay, on to off < 30μs @ 30 °C< 200μs @ 60 °C
Power dissipation, inputs, max 2.8 W @ 60°C
Thermal dissipation, inputs, max 9.56 BTU/hr
Off-state voltage, max 5V DC
Off-state current, max 1.5 mA
On-state current, min 3 mA
On-state current, max 10 mA
Input impedance, max 3.3 kΩ @ 24V DC
Reverse polarity protection Yes
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O to system
1756-PLS Output Specifications
Attribute Value
Outputs 16 (2 groups of 4 per I/O section)
Voltage category 12/24V DC
Operating voltage range 10…31.2V DC
Output delay, off to on < 15μs @ 60 °C
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 155/158Publication 1756-TD002A-EN-E - May 2009 155
1756 ControlLogix I/O Modu
Certifications - 1756-PLS
Output delay, on to off < 25μs @ 60 °C
Power dissipation, outputs, max 6 W @ 30 °C
3.8 W @ 60 °CThermal dissipation, outputs, max 21.48 BTU/hr @ 30 °C
11.93 BTU/hr @ 60 °C
Off-state leakage current perpoint, max
300μA @ 60 °C
On-state voltage drop, max 0.55V DC
Current per point, max 1 A @ 30 °C(1)
Current per module, max 8 A @ 30 °C(2)
Current limit < 4A
Surge current per point 2 A for 10 ms every 1s @ 60 °C
Load current per point, min 40 mA
Output switching time Switching 1 A @ 24V DCShort circuit protection Electronic (No indication of fault. Remove load and toggle on/o
restore.)
Reverse polarity protection Yes, current limited. (If wired incorrectly, outputs may be permdisabled.)
Isolation voltage 250V continuousTested at 2546V DC for 1 s, I/O group to group, I/O to system
(1) Derate 16.7 mA/ °C above 30 °C: 0.5 A @ 60 °C.
(2) Derate 133.6 mA/ °C above 30 °C: 4 A @ 60 °C.
1756-PLS Output Specifications
Attribute Value
Certification (1) 1756-PLS
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and CanaE194810.
CSA CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous LocatiLR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:• EN 61326-1; Meas./Control/Lab., Industrial Requirements• EN 61000-6-2; Industrial Immunity• EN 61000-6-4; Industrial Emissions• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick Australian Radiocommunications Act, compliant with:AS/NZS CISPR 11; Industrial Emissions
(1) When marked. See the Product Certification link athttp://www.ab.com for Declarations of Conformity, Certificates, and other certification
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 156/158
156 Publication 1756-TD002A-EN-E - May
1756 ControlLogix I/O Modules
ControlLogix I/OAccessories
1756 Removable Terminal Blocks
Removable terminal blocks (RTBs) provide a flexible interconnection betweenyour plant wiring and 1756 I/O modules. The RTB plugs into the front of the
I/O module. The type of module determines which RTB you need. You canchoose screw-clamp or spring-clamp RTBs.
RTBs are not shipped with I/O modules. You must order them separately. Thestandard housing on the front of the wiring arm is not deep enough for 2.5mm2 (14 AWG) wiring. If you plan to use 2.5 mm 2 (14 AWG) wiring, alsoorder the extended housing.
Wiring Systems As an alternative to buying RTBs and connecting the wires yourself, you canbuy a wiring system of:
• interface modules (IFMs) that provide the output terminal blocks fordigital I/O modules. Use the pre-wired cables that match the I/O
module to the IFM.• analog interface modules (AIFMs) that provide the output terminal
blocks for analog I/O modules. Use the pre-wired cables that match theI/O module to the AIFM.
• I/O module-ready cables. One end of the cable assembly is an RTB thatplugs into the front of the I/O module. The other end has individuallycolor-coded conductors that connect to a standard terminal block.
Attribute 1756-TBNH 1756-TBSH 1756-TBCH 1756-TBS6H 1756-TBE
Description 20-position NEMAscrew-clamp removableblock
20-pin spring-clampremovable terminal blockwith standard housing
36-pin cage-clampremovable terminal blockwith standard housing
36-pin spring-clampremovable terminal blockwith standard housing
Extended depth terminalblock housing
Screw torque 0.8…1 N•m7…9 lb•in
0.4 N•m4.4 lb•in
—
Screwdriver width 8 mm (5/16 in.) max
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 157/158
8/18/2019 1756 Series Io Modules
http://slidepdf.com/reader/full/1756-series-io-modules 158/158
Rockwell AutomationSupport
Rockwell Automation provides technical information on the Web to assist you in usingits products. At http://support.rockwellautomation.com , you can find technicalmanuals, a knowledge base of FAQs, technical and application notes, sample code andlinks to software service packs, and a MySupport feature that you can customize tomake the best use of these tools.
For an additional level of technical phone support for installation, configuration, andtroubleshooting, we offer TechConnect support programs. For more information,contact your local distributor or Rockwell Automation representative, or visithttp://support.rockwellautomation.com .
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review theinformation that's contained in this manual. You can also contact a special CustomerSupport number for initial help in getting your product up and running.
New Product Satisfaction Return
United States 1.440.646.3434Monday – Friday, 8am – 5pm EST
Outside UnitedStates
Please contact your local Rockwell Automation representative technical support issues.