Furnace Safeguard Supervisory System K.C. Yadav, AVP, Noida Technical Training Centre

description

FSSS

Transcript of 17318757-FSSS

  • Furnace Safeguard Supervisory System

    K.C. Yadav, AVP,Noida Technical Training Centre

  • 2 of 27confidential

    Learning Agenda Objective of FSSS Inter facing of field equipments and

    instrumentation Operational features of FSSS Role of FSSS in starting/shutdown Role of FSSS in maintaining the

    design prescribed values of the parameters

  • 3 of 27confidential

    It must be recognized that no amount of written instruction can replace intelligent thinking and reasoning on the part of boiler operators, especially when coping with unforeseen operating conditions. It is operators responsibility to become thoroughly familiar, not only with immediate steam generating equipment but also with all pertinent control equipment. Satisfactory performance and safety depend to a great extent on proper functioning of controls and auxiliary equipment.

  • 4 of 27confidential

    PurposeThe FSSS is designed to ensure the execution of safe, orderly operating sequence in the start up and shutdown of fuel firing equipment and to prevent errors of omission and commission in following such a safe operating procedure.

  • 5 of 27confidential

    Purpose Furnace purge supervision. Secondary air damper modulation, on/off control

    and supervision. Light oil on-off control and supervision. Heavy oil on-off control and supervision. Pulveriser and feeder on-off control and

    supervision. Flame scanner intelligence and checking. Overall boiler flame failure protection. Boiler trip protection.

  • 6 of 27confidential

    Purpose Prevent any fuel firing unless a satisfactory furnace

    purge sequence has first been completed. Prevent start-up of individual fuel firing equipment

    unless certain permissive, interlocks have been satisfied.

    Monitor and control proper component sequencing during start-up and shut-down of fuel firing equipment.

    Subject continued operation of fuel firing equipment to ascertain safety interlocks remaining satisfied.

  • 7 of 27confidential

    Purpose Provide component status feedback to the

    operator and, in some cases, to the unit control system and / or to the data logger.

    Provide flame supervision when fuel firing equipment is in service and effect an Elevation Fuel Trip or Master Fuel Trip upon certain condition of unacceptable firing / load combination.

    Effect a Master Fuel Trip upon certain adverse Unit operating conditions.

  • 8 of 27confidential

    Subsystem of FSSS Purge Permissive (s) HOTV Open/Close Interlocks HORV Open/Close Interlocks Oil Guns Start/Stop Cycle Boiler Protection Logics

  • 9 of 27confidential

    Subsystem of FSSS (Cont.) PA Fan Interlocks Coal Mill Start/Stop Interlocks Coal Feeder Start/Stop Interlocks Scanner Air Fans Seal Air Fans Secondary Air Damper Interlocks

  • 10 of 27confidential

    Purge Permissives All HFO Nozzle Valves Closed HFO Trip Valve closed No Boiler Trip From MFR A & B All Pulverizers Off. All Feeders Off All Flame Scanners Sense No Flame Both PA fans Off

  • 11 of 27confidential

    Purge Permissives (Cont.) All Auxiliary Air Dampers Modulating and

    furnace to wind box P OK All Hot Air Gates Closed Air Flow > 30 % Mode Permit Proven (Air Flow < 40% Burner Tilt Horizontal) Drum Level Satisfactory FSSS AC / DC Power Available.

  • 12 of 27confidential

    HOTV InterlocksTo Open HOTV : Permissives

    SET I No. Boiler Trip persisting HFO Header temperature satisfactory >950 C HFO supply pressure > 15 Kg / cm2 All HONVs closed No close / Trip command Open PB depressed

  • 13 of 27confidential

    HOTV InterlocksTo Open HOTV : Permissives

    SET II All HONVs closed MFT acted HORV open Open PB depressed

  • 14 of 27confidential

    HOTV Interlocks

    1. HOTV closes automatically under the following conditions:

    Any HONV not closed AND

    a) HFO pressure low < 3 Kg/cm2 ORb) Atomizing steam pressure low < 3.5 Kg/cm2 OR

    c) HFO Header Temperature Lo-Lo for > 2 secs. < 95 0C

    2. Any HONV not closed and MFT acted

    3. Loss of critical power > 2 Seconds

    4. HOTV can be closed manually

  • 15 of 27confidential

    HORV Interlocks HORV can be opened by pressing the OPEN Push

    button (PB) from Console if All the HONV s are

    closed.

    HORV closes automatically when any HONV is not

    closed OR by pressing close PB.

  • 16 of 27confidential

    s

    s

    s

    s

    s

    s

    HFO PUMP-1

    HFO PUMP-2

    HFO PUMP-3

    HFO HTR-1

    HFO HTR-2

    HFO HTR-3

    FROM HFO DAY TANK

    FROM AUXILIARY STEAM HEADERHFO Supply Scheme

    TO BOILERFRONT

    TO HFO DAY TANK

  • 17 of 27confidential

    M

    FT

    FT

    AB ELEVATION

    CD ELEVATION

    EF ELEVATION

    HOFCVHOTV

    HORV

    SHORTRECIRCULATION

    HFO SUPPLY

    LINE

    HFO RETURN

    LINE

    HFO Scheme At Boiler Front

  • 18 of 27confidential

    OIL GUN

    ATOMISINGSTEAM VALVE

    HFO NOZZLEVALVE SCAVENGE

    VALVE

    AB ELEVATION

    CD ELEVATION

    EF ELEVATION

    Oil Gun Connection

    Atomizing Steam Scheme

  • 19 of 27confidential

    Pair Firing Mode (Start Up) Pair firing mode is selected when no feeder is in

    service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)

    When pair 1-3 start push button is pressed;A 30 second counting period is started A 70 second counting period is started

    Oil Gun No-1 advances from retracted position if, it is engaged, corresponding scavenge valve is closed, atomizing steam and HFO isolation valves are open.

  • 20 of 27confidential

    Pair Firing Mode (Start Up) HEA igniter advances. Atomizing steam valve opens. Igniter starts sparking. HFO Nozzle valve for corner 1 opens HFO catches fire and flame indication comes. After 25 seconds igniter retracts. When the 30 second counting period expires

    command will go to corner 3 and same events will take place.

    Corner 2-4 can also be placed exactly in the same manner.

  • 21 of 27confidential

    Elevation Firing Mode (Start Up) Elevation firing mode is selected when any feeder is

    proven. Oil elevation is placed in service when Pair 1-3 or Pair 2-4

    start Push Button is pressed. In elevation firing mode also the oil guns are proven on pair basis.

    First command goes for placing Pair 1-3 into service and Pair 1-3 is placed into service exactly in the same way as in the pair mode.

  • 22 of 27confidential

    Elevation Firing Mode (Start Up) First start command goes to corner-1 then after 30 second

    start command goes to corner-3. After the start command has gone to corner 3, a 30 second

    counting period is started. When 30 seconds counting period expires then start command goes for corner 2-4 and corner 2-4 are placed into service exactly in the same manner as in the pair mode.

  • 23 of 27confidential

    PAIR FIRING MODE (SHUT DOWN) Pair firing mode is selected when no feeder

    is in service. Pairs are made for the opposite corners. (Pair 1-3 and Pair 2-4)

    When pair 1-3 stop push button is pressed the following events take placeA 30 second counting period is startedA 340 second counting period is started

    Oil Gun No-1 HFO nozzle valve closes. Scavenge and atomizing steam valve opens. HEA igniter advances and spark remains for

    15 seconds.

  • 24 of 27confidential

    Pair Firing Mode (Shut Down) When atomizing steam valve is proven fully open,

    a 5 minutes counting period starts. When 5 minutes counting period expires scavenge

    valve and atomizing steam valve closes and further closing command goes HFO nozzle valves to reinsure that they are fully closed.

    Oil Gun corner no-1 retracts to its home position. When the 30 second counting period expires stop

    command will go to corner 3 and same events will take place.

    Corner 2-4 can be shut-down exactly in the same manner.

  • 25 of 27confidential

    Elevation Firing Mode (Shutdown) Elevation firing mode is selected when any feeder is proven. By pressing stop push-button of Pair 1-3 or Pair 2-4 the

    following events will take place. Corner 1-3 will be shut-down in the similar way as in the pair

    mode. When stop command has gone to corner 3, a 30 second

    counting period is started. When 30 seconds counting period expires then stop

    command goes for corner 2-4 and corner 2-4 are shut-down exactly in the same manner as in the pair mod

  • 26 of 27confidential

    Boiler Trip Conditions Both FD Fans Off All ID Fans Off Inadequate Water Wall Circulation Loss Of Reheater Protection Deaerator level Lo-Lo ( -2134 mm 2 / 3 logic) All Boiler Feed Pumps Off Drum Level High-High (> + 250 mm, delay of 10 seconds) Drum Level Lo-Lo (< - 375 mm, delay 10 seconds) Elevation Power Failure For > 2 seconds. Furnace Pressure High-High (> + 325 mmWCl, 2 / 3 logic)

  • 27 of 27confidential

    Boiler Trip Conditions Furnace Pressure Lo-Lo (< -250 mmWC, 2 / 3 logic) Loss Of All Fuel Unit Flame Failure Loss Of Critical Power For > 2 seconds Loss Of 220 V DC For > 2 seconds Loss Of ACS Power > 2 seconds Simulated Trip Air Flow < 30 % Both Emergency Push Buttons Pressed.

  • 28 of 27confidential

    Boiler TripWhen the boiler trips the following events takes place

    Boiler trip red lamp comes on. MFT A & B trip lamp comes on and reset lamp goes off. Cause of trip memory can not be reset till the furnace

    purge is completed. F D Fans Control is transferred to manual. I D fans vane position is transferred to manual. Pulverizers are tripped. Coal feeders are tripped. P A fans are tripped.

  • 29 of 27confidential

    Boiler Trip (Cont.)When the boiler trips .

    Cold air dampers opens 100 %. HFO trip valve closes. All HFO Nozzle valves closes. Upper and Lower Fuel air damper opens. Auxiliary air damper opens and control is transferred to

    manual. Loss of all fuel trip protection disarms. S/H and R/H spray block valves S-82 & R-31 closes and

    can not be opened unless furnace purge is completed. Turbine Trips

  • 30 of 27confidential

    Inadequate Water Wall Circulation

    1.Boiler load > 60 % and less than two pumps or

    pump on and differential pressure < 10 psi.

    2.Boiler load < 60 % and no BCW pump on or

    pump on and differential pressure < 10 psi.

  • 31 of 27confidential

    Reheat Protection1. Turbine trip or generator circuit breaker open and hp/lp

    bypass opening < 2 %.

    2. Turbine working (hp & ip cvs opening > 2 % and load

    shedding relay operated and hp/lp bypass opening < 2 %.

    3. Turbine not working and boiler working and hp/lp bypass

    opening < 2 %.

  • 32 of 27confidential

    Loss of all fuel armingSET

    RESETMFT 5 SEC

    Any elevation Nozzle valve proven

    All feeders off 2 SEC

    All HFO Nozzle valve closed

    All feeders off

    HOTV NOT OPEN2 SEC

    All HFO Elevation Trip

    Loss of all fuel trip

    Loss of All Fuel Trip

  • 33 of 27confidential

    Flame Failure Trip

    Elevation AB No Flame Vote

    Elevation BC No Flame Vote

    Elevation DE No Flame Vote

    Elevation FG No Flame Vote

    Elevation GH No Flame Vote

    Any Feeder Proven 2 Sec

    Flame Failure

    Trip

  • 34 of 27confidential

    Flame Failure Vote Logics

    Feeder A Off2 Sec

    Feeder B Off

    Elevation AB Any HFO Nozzle Valve Not Closed

    Elevation AB 2/4 Nozzle Valve Not Proven

    Elevation AB Scanners No Flame

    Feeder C Off

    2 Sec

    2 Sec

    Elevation BC Scanners No Flame

    Elevation AB No Flame Vote

    Elevation BC No Flame Vote

    Elevation DE No Flame VoteFeeder D Off

    Feeder E Off

    Elevation DE Scanners No Flame

  • 35 of 27confidential

    FEEDER H OFF

    ELEVATION GH ANY HFO NOZZLE VALVE NOT CLOSED

    ELEVATION GH 2/4 NOZZLE VALVE NOT PROVEN

    2 SEC

    ELEVATION GH NO FLAME VOTE

    ELEVATION FG NO FLAME VOTE

    Flame Failure Vote Logics

    FEEDER F OFF

    FEEDER G OFF

    ELEVATION FG SCANNERS NO FLAME

    ELEVATION GH SCANNERS NO FLAME

  • 36 of 27confidential

    Mill Interlocks Start Permissive (s):Mill starts after the ON push button is pressed if following conditions are fulfilled.Pulveriser Ready available signal will be available if following conditions are fulfilled M.D.V. is open (all four) Mill outlet temp < 93 0 C Feeder local switch in Remote

  • 37 of 27confidential

    Mill Interlocks Pulverizer start permit (if Nozzle tilt Horizontal & air

    flow < 40 %) OR Any feeder proven & NO MFT Tramp iron valve open

    Cold air gate open Feeder inlet gate open Lub oil level & temp. adequate Lub oil pressure not low for more than 300 sec No Mill trip existing

  • 38 of 27confidential

    Mill InterlocksP.A. permit available.

    (i) Hot P.A. duct Pressure. not low (< 625 mmWCl)(ii) P.A. duct pr. not lo-lo ( > 500 mmWCl AND (iii) Both FD s ON and both PA fans ON or (Any PA fan ON and any FD Fan ON and > 4 mills not ON)

    No Auto pulverizer unsuccessful start Seal air Header to mill under bowl DP satisfactory > 8" WCl Mill not ON Pulverizer Ignition permit available.

  • 39 of 27confidential

    Mill Interlocks FOR Mill A AB elevation 3/4 HONVs open

    OR Boiler load > 30 % and Feeder - B speed > 50 % ( > 30 T/hr.)For Mill B AB elevation proven 3/4 HONVs open

    OR Boiler load > 30 % and Feeder A or Feeder C proven.

  • 40 of 27confidential

    Mill InterlocksFor Mill C CD elevation proven OR

    AB oil elevation and feeder B proven OR

    Boiler load > 30 % & either feeder B or Feeder D proven

    For Mill D CD elevation proven OR

    Boiler load > 30 % and either feeder C or feeder E proven.

    For Mill E,F,G & H identical logic

  • 41 of 27confidential

    Pulveriser Trip Conditions Auto / manual mode selected to manual & stop PB

    depressed. Pulv. start command given & not ON for > 2 Secs. Loss of Elevation OR Unit Power for > 2 Secs Pulv ON & seal air / under DP Low > 1 min < 5wc Pulv ON and lub oil pump OFF > 10 sec. Pulv ON and lub oil pr. low > 10 secs. < 1.76 Kg/cm2 Ignition permit required (> 180 secs) & ignition permit

    lost (i.e. within 180 sec of feeder start)

  • 42 of 27confidential

    Pulveriser Trip Conditions Any of the MDV is not fully open Hot PA duct. pr. Lo < 625 mm of WCL (delay 5 sec) Hot PA duct. pr. Lo - Lo = < 525mm WC (instantaneous) MFT PA / FD Fan trip

    a) If both PA Fans & both FD fans running & any PA or any FD Fan trips then mills start tripping from top elevations with 2 secs time delay till 4 mills are available.b) If both PA / FD fans trip then all mills will trip.

  • 43 of 27confidential

    Pulverizer Seal Air Valves Interlocks Valve opens when Pulverizer start command is given

    OR Mill is ON Valve closes when Pulverizer is OFF

    Hot Air Gate Interlocks Hot air gate (HAG) opens when Pulverizer is ON AND

    Hot air gate open P.B. depressed or auto HAG open command is there

    AND NO HAG close command.

  • 44 of 27confidential

    Hot air gate closes when1. Loss of power > 2 secs2. Pulverizer off

    3. Pulverizer outlet temp > 93 0 C

    4. Close P.B. depressed5. Feeder Trips.(Delay 40 sec) 6. Auto pulverizer unsuccessful start 7. Auto pulverizer run feeder speed to minimum

  • 45 of 27confidential

    Feeder Start Permissive (s) Pulveriser Ready is available Feeder speed demand at minimum Pulveriser manual mode Pulveriser ignition permit available No feeder stop command No MFT Pulveriser ON

  • 46 of 27confidential

    Feeder Trip Condition Ignition energy removed within 180 seconds of

    feeder start Feeder in manual mode & stop PB depressed Auto Pulverizer Feeder stop command Pulverizer OFF MFT No coal on belt Discharge plugged

  • 47 of 27confidential

    SADCThe secondary air dampers located in wind box apportions the total secondary air between various elevations. How this air is proportioned, depends on which fuel is being burnt, the number of elevations in service and the firing rate at each elevation.The function of Secondary Air Damper Control System (SADC) is to proportion the total secondary air around the firing elevation as per the criteria spelt above. In fact the SADC system is a combination of both analog and digital system, as the amount of fuel fired and the no. of firing elevations decide the damper position.

  • 48 of 27confidential

    The auxiliary air dampers are positioned to maintain the required wind box to furnace differential pressure according to the boiler load. In the initial periods of operation, the flame condition with reference to ignition stability, ignition point relative to fuel nozzles, overall combustion conditions in the furnace are to be studied for various wind box to furnace differential pressures and the values are to be optimized at site (the values are adjustable). Based on this, the final curve showing the relationship between the wind box to furnace differential pressure versus the boiler load is to be decided for the type of coal used.

  • 49 of 27confidential

    The auxiliary elevation dampers act as fuel (oil) air dampers when oil firing is taking place and is open to a preset position. The fuel (oil) elevation dampers are selected to be closed if there is a back up trip in that elevation and adjacent pulverizers are off and No Boiler Trip signal is present. When a HFO Elevation is started (i.e. when the associated elevation back-up trip is removed) the associated auxiliary air dampers in that elevation are set to preset position for HFO firing.

  • 50 of 27confidential

    Above 30% MCR boiler load, the auxiliary air elevation associated with the main fuel elevation in service modulate to maintain the varying DP. Those not associated with any elevation in service are closed from top to bottom. The closing signal comes from FSSS. When the unit load is increased above 30% MCR, the Aux. air dampers of elev. AA,AB, BC, CD, DE, EF & FF are closed in a timed sequence (10 sec. interval) provided the associated coal elevations are not in service and the associated oil elevations are not in service. The auxiliary air dampers are closed, starting from the top elevation, progressing towards the lowest elevation.

  • 51 of 27confidential

    All elevations of the aux. air dampers will be automatically switched to Manual control and then commanded to open 100%, if any one of the following conditions exist.

    Both FD fans are OFF. Both ID fans are OFF. Master fuel trip occurs. Loss of unit critical power . (+24V DC)

    Also the auxiliary air control loop is tripped to manual if any of the following conditions exist.

    DP transmitter deviation high. Failure of selected DP transmitter Furnace to Windbox DP very high (> 240mm WCL).

  • 52 of 27confidential

    The fuel air damper control system positions the fuel air damper in proportion to the fuel firing rate. In the initial periods of operation, the flame condition with reference to ignition stability, ignition point relative to fuel nozzles, overall combustion conditions in the furnace are to be studied for various fuel air damper positions and the values are to be optimized at site. Based on this the final curve showing the relationship between the fuel air damper positions versus the fuel feed rate is to be decided for the type of coal used.

  • 53 of 27confidential

    All elevations of fuel air dampers are commanded to open 100% when any one of the following conditions exist.

    Both FD fans are OFF. Both ID fans are OFF. Master fuel trip occurs. Loss of unit Critical Power.(+24 VDC)

  • 54 of 27confidential

    On coal fired boilers the characteristics of fuel like, Fixed Carbon, Volatile Matter and Ash composition will determine the optimum wind box to furnace differential pressures and the fuel air damper positions. Accordingly the optimized settings are to be decided as above for the coal used.

  • 55 of 27confidential

    Later, if the coal quality changes or the coal source itself is changed, it shall be necessary to once again carryout optimization studies for the new coal and revised settings are to be finalized.

  • 56 of 27confidential

  • 57 of 27confidential

    Modulation of Auxiliary Air Dampers

  • 58 of 27confidential

    Modulation of Fuel Air Dampers

  • 59 of 27confidential

    Modulation of Over Firing Air Dampers

  • 60 of 27confidential

    The two elevations of the over fire air dampers will be automatically switched to Manual control and then commanded to open 100%, if any one of the following conditions exist

    Master fuel trip occurs. Loss of unit critical power .(+24 VDC) Both FD fans are OFF. Both ID fans are OFF. WB To Furnace DP exceeds 240mm WCL.

  • 61 of 27confidential

  • 62 of 27confidential

  • Thank you