15 KW two-phase CO2 cooling Parts StatusApril 03, 2012

Slides: R.Becker

Page 2: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Missing and/or Unsized components:

Plant Core:1) Flow Meter after pump: New to the P&I! Optimass 3000? (Andrea Paola confirmed?)2) Pump Interface: ¾” NPT-VCR Found & LEWA custom (design in hand 2940 Eu extra)

3) Damper: 1-Gallon+ size ok –need to find (Swagelok has only ½” NPT)

4) Heat exchanger: SWEP B17: Multiple port model received & implemented 5) “Brine” Valve: Tube size =1 ½” Rotarex inquiry will be sent6) 1” Filter : Resolved7) Cold box: Inquiry to be launched this week8) Fittings: Lyon & Andrea to verify. Swagelok appears to offer all that is needed?9) Temp sensor: Jumo (CERN standard) Ok as drawn by Lyon.

Under investigation: non-invasive temp sensor that is exchangable (also Jumo) inquiry for weldable sleeve made

9) Pressure sensor: DRUCK, Groby PTX 7517-3257 (same as Cryolab & as drawn in Model)10) Burst disks: 96bar? Inquiry to Fike & Ramsayer to be launched11) Pulse damper electrical heater: Watlow –in work12) Built in thermocouple at pulse damper heater: Watlow in work

Manifolds:13) Flow meter: 3 leads investigated. 1 requires 6 months lead time, the last we should order now to test

14) Cold box: (feed-throughs needed –then inquiry launched)

Page 3: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Heat Exchanger SWEP B17

Contact: Bjorn Felgenhauer +49 170 798 [email protected]

Max port size: 16mm IDWith Double ports

Port dimensions

Model received

Page 4: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Filters:

Swagelok:T-Filter: Metric: 12m

Barton Firtop Engineering Ltd: 1” strainer

Page 5: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Temp probe tip

Liquid CO2 to measure

JUMO 00529338

JUMO Dtrans T100

22-12 mmreduction

12mm Tee

71?

OD 12?

Can either the weld diameter be changed to

12 Or

The tip lengthened to 71mm

Base Line is what Lyon has modeled, but Investigating a Non-invasive temp sensor (Allows replacement without draining CO2)

Page 6: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Burst Disk Choices:

Standard Swageloc VCR ½”, 90 Bar ±10%, 100 SF/pc (see offer O-37996-12)

VCR “washer”

Plug:

Offer from Fike (Swagelok)(15/03/2012 Mr. Ruby at Fike.de)

They have designed an 88Bar +/-10% disk for us (including housing):

168 SF/pc 40 pc

Samuel Ruby Projektingenieur Fike Deutschland Tel. +49 (621) 321 6715 Fax +49 (621) 321 6750 Innstrasse 34; 68199 Mannheim, Deutschland www.fike.de

André Ramseyer AGIndustriestrasse 32CH-3175 FlamattFon +41 31 744 00 20Fax +41 31 741 25 55

[email protected]

Page 7: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Contact: [email protected] INSTRUMENT COMPANY217 STERNER MILL ROADTREVOSE, PA [email protected]

Thermal Instrument Company100 Bar, -40 deg C, ~1-24 g/s liquid CO2 flow, 3000 G Field

Accuracy: 0.5% of Full Scale or 2% of reading - whichever is better Repeatability: Better than 0.2% of reading

Response Time: Liquids less than 1/2 second, Gases 1 to 2 seconds typical (4 to 8 seconds worst case) Pressure Drop: Negligible - completely unobstructed straight thru flow path Flow Element: Construction meets NEMA 4, 7 & 9 explosion proof requirements Flow Wetted Parts: 316 S.S. standard, also many exotic metals and coatings available to suit requirements

Operating Principle: The Model 600-9/9500 operates using a constant temperature system that employs two RTD sensors: one for sensing temperature, and one for sensing flow. The flow sensor is heated to a precise temperature above that of the fluid passing by. The fluid conducts heat off the sensor in direct proportion to the mass flow rate. The temperature sensor is used to set the heat on the flow sensor and correct changes in the fluid temperature. Thermal Instrument's thermal mass flowmeters consist of one piece; a flow element with a bridge controller, signal conditioner with power supply, flow signal, A/D converter, linearizing network, 4-20 MA DC, flow output, operational flow display, and totalizer.

Theo Investigating!

$3,270.00 eachOPTION: Flow Rate and Total Display add…….$240.00

Remote 9500 Electronics add………...$240.00

½” Tube Model 600-9LT/ 316 SS/ ½” VCR/ Integral 9500 Electronics/ 4-20mA Output/ 110VAC

Calibration: Liquid CO2Line Size: ½” TubeFlow Range: 1 – 24 grams/second Temperature: -40°C Pressure: 100 Bar

Delivery: 4 – 6 weeksF.O.B.: Trevose PA

Page 8: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Contact: [email protected] Innovative Sensor Technology IST AGIndustriestrasse 2, 9630 Wattwil, SwitzerlandPhone: +41 71 987 73 73 | Fax: +41 71 987 73 [email protected]

Flow Sens100 Bar, -40 deg C, ~1-24 g/s liquid CO2 flow, 3000 G Field

5-6 months delivery as a commercial 100 bar 12mm pipe etc it is in development. Price??

Page 9: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Andrea Investigating (coreolis)

Optimass 3000 For large flow in Plant100 Bar, -40 deg C, ~1-24 g/s liquid CO2 flow, 3000 G Field

Andrea Investigating this one (coreolis)1 pce 8.722,50 CHF pce

Conditions de serviceDébits maximum01 20 kg/h / 0,733 lb/min03 130 kg/h / 4,766 lb/min04 450 kg/h / 16,5 lb/minTempérature ambianteVersion compacte avec convertisseur enaluminium-40...+60 °C/-40…+140 °FPlage de température étendue : 65°C / 149°F pour certaines options E/S.Pour plus d'informations, contacter le fabricant.Version compacte avec convertisseur enacier inoxydable-40...+55°C / -40…+130°FVersions à distance -40...+65°C / -40…+149°FTempérature de serviceAcier inoxydable/Hastelloy® -40…+150°C / -40…+302°FPression nominale à 20°C / 68°FTube de mesureAcier inoxydable/Hastelloy® -1…150 barg / -14,5…2 175 psigEnveloppe extérieureHomologation DESP CRN -1…30 barg / -14,5…435 psigPour des pressions de service >30 barg / 435 psig, un disque de sécurité estobligatoirePropriétés des fluidesÉtat physique admissible Liquides, gazContenu gazeux admissible (volume) Contacter le fabricant pour plus d'informations.Contenu solide admissible (volume) Contacter le fabricant pour plus d'informations.Classe de protection (selon EN 60529) IP 67, NEMA 4X

Page 10: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

1400

1400

800 (+ 2x100)

Cold Box Dimennions for the Primary system

Latchable, removable doors with refrigerator seals

Thalheimer Kuehlunghttp://www.thalheimer-kuehlung.de/

Contact: Herr [email protected]+49 7961 / 56770

Bulkhead connector attachment & feed-through pattern to be finalized –then inquiry can be sent.

Page 11: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Manifold Status: redesign in work & will have progress & box dimensions by next meeting. (barring “part searching” or valve testing tasks interferes)

1000

1600

700 (+ 2x120)

120 (100 door, 20 seal)

Current box dimensions

Page 12: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

LEWA Visit key pointsFrom LEWA: Marc Geiselhart, [email protected], +41 61 717 9400, Fax: +41 61 717 9401, Mobile: +41 79 825 39 69 Stephan Dueblin, [email protected], +41 61 717 9400, Fax: +41 61 717 9401. Mobile: +41 79 126 8040

Attendees CERN: Jerome, Paola, Bart, Hans, Joao, Robert, (remote: Nick)

LEWA LDE1/MR510S/44 mm pump LEWA quotation: LL1-6329 rev1 (247598) was reviewed in detail going through the offer point-by-point.

Pump Cold-head:1) Older 500 series head chosen in our case due to long experience, and larger teflon membrane, allowing for better flexing under cold

conditions2) Positive pressure is needed for CO2 before starting the pump

3) Double membrane with lubrication and mesh separator allows membrane leak detection. LEWA requires a lubricant to “stick” the membranes together. LEWA will send us a list of lubricants for the membrane4) Check valve selected is the largest stainless steel ball and seat available (hard-hard valve). Other valve types are inferior in terms of back-leakage. The ball requires a preload/spring to achieve frequencies of above 180 strokes/min (the ball/mass’s natural frequency)5) 15mm dia check valve inlet (our pump)

6) Standard DIN flange connections. We send LEWA our VCR fitting @ they can weld (-or we do this)7) Orifice / pressure reduction needed with pulsation damper. LEWA may have a leaflet entailing calculations to size damper and reduction

Crank-case8) Weak point of pump: -the small end bearing of the piston rod wears out first!9) Adjusting flow: a) Stroke adjustment level range from 1-7, b) frequency adjustment regulation from 1-7. Rule of thumb: adjust stroke to 50% then adjust frequency to what is required10) Oil compressibility in hydraulic system: 0.4%11) The Pump in the offer is sized for all cases meeting our requirements (90 Bar, -40 degC etc) and can be run full time all year-round in any condition.12) For LEWA pumps in general: pistons larger than 25mm dia have piston rings

Motor & General13) Our pump is sized with 5.7 KW Nominal operation14) Lead time is 18 weeks due to custom manufactured cold head units + Connecting tube

15) After order tender 3-4weeks delay for a CAD model16) Prices in general for LEWA pumps: 1/3 Drive unit, 2/3 Pump head price -changes with multiple pump heads! 17) Tentative pricing for us: 1 pump + design work at full price. Multiple orders get a reduction, so ordering the remaining 2 units there will be slight savings as design is complete and manufacturing of 2 simultaneously will be more efficient 18) LEWA supplies filters for their pumps: We need a typical 0.3mm strainer mesh size –inquiring now for our 1” return line filter/strainer

To be resolved before ordering: Understanding all flows..1) Cryo lab test results2) Understand flow distribution behavior: Capillary sizing & overflow sizing optimization (Joao & Paola? Willi) By when?3) Main bypass flow (with overflow regulation this is adjustable –so if large range is known this shouldn’t be a big issue)

Page 13: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Example of a cold Remote-head LEWA Pump

Page 14: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

1.3m

Liquid membrane pump

200-300

??

Critical Dimensions Needed:

Dia: ~250

300-400 mm

Damper sizing paper available

15/03/2012 update

Page 15: 15 KW two-phase CO2 cooling Parts Status April 03, 2012 Slides: R.Becker.

Additional LEWA info 15/03/2012:

Pressure drop of spring design valves? Spring design valves are available with pressure drops of 0.1 to 1.6bar.Usually we use this types for liquids with high viscosity. Possible Diaphragm liquids:For the space between the two layers of the sandwich diaphragm there several possible liquids.Depending on the temperature range and the reactivity/contamination requirements of the fluid the lubricant will be selected. MineraloilPolyglycoloilSiliconoilDemi waterVegetable oilChlorine fluor carbon Possible pump connections :Flange according to DIN /EN or ANSI (Size according to the valve size)Threat connections ISO G 1/2" or G 3/4" Thread connections ANSI ½ NPT or ¾ NPT

For our pump this part is on the pump chassis and not on the remote head