(14)Aec t6c - Aec_t6c Brochure
-
Upload
anonymous-3uvyzis -
Category
Documents
-
view
224 -
download
0
Transcript of (14)Aec t6c - Aec_t6c Brochure
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 1/8
T6COMPACT10kVA - 40kVA
+
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 2/8
T6COMPACT+10kVA - 40kVA
2| AEC| T6 COMPACT+
In actuality, most power failures are not from an angry deity, but from altogether more benign sources.
The reality is that your computer suite is more vulnerable from the contractor down the road with his big yellow JCB, or from
the site electrician who has forgotten which breaker does what, in the jumbled up, spaghetti wired power distribution panel. Or
what about one of the most common causes of a PC computer crash, the cleaner pulling the plug to use the vacuum cleaner,
yes, it really happens!
Many have the genuinely misguided opinion that a UPS is there essentially to protect against a power failure, and it’s true that
such a failure can be a disaster for any IT installation. But in reality the electrical threats are much wider and more subtle than
most can imagine, here are some threats explained, and how the T6 Compact+ can protect your system.
A “brown out” happens when the voltage to your network
drops to a point whereby by it can cause a server or PC to
simply stop working. The effect is the same as a full power
failure, but may only last a second or two, or maybe even
less. To illustrate, how often have you experienced your
lights dim, just briefly? 90% of the time this is because of
a voltage drop, or “brown out”. The T6 Compact+ is
designed to deal with this subtle threat, offering your
servers a fully regulated and clean supply regardless of the
input voltage, and it will even record the event so that you
can investigate at a later time.
> Brown Outs
The T6 Compact+ is designed to protect against the many electrical threats which
stalk our heavily computerised infrastructure. Most individuals simply think of
power failures in the context of lightening strikes or some other so called “act of
God”; however these opinions are very far from the truth.
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 3/8
T6 COMPACT+| AEC|3
habit of locking or freezing a computer program, an irritation
we have all experienced. There is a bigger danger that larger
spikes can easily damage a power supply, hence many
quality servers have two. The T6 Compact+ incorporates
high energy absorbing filters that will mitigate this threat,
offering your network a clean and regulated supply.
> Spikes
> Installation Simplicity
Spikes are very short bursts of high voltage and high
energy; these are often caused by the stopping and
starting of motors or compressors, typically air
conditioning or chilling units. Smaller but equally
disruptive spikes can be caused by laser printers or
other similar machines. These spikes have a nasty
A 15kVA T6 Compact+ weighs in at only 90Kg (no
batteries), even it’s bigger brother the T6+ 40kVA
weighs in at a meagre 141Kg. The weight advantage
proves to be very useful when having to use lifts to
site the UPS, as raised floors generally don’t have to
be reinforced and the whole siting procedure is
made safer because of integrated wheels and easy
manoeuvrability.
Add to these features convenient cable access and
battery installation, and its easy to see why we call
the T6 Compact, the T6 Compact “+”.
“Performance,
compactness and
reliability for criticalapplications”
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 4/8
4| AEC| T6 COMPACT+
> Reduced Power Consumption
When running in its normal On-Line mode the T6 Compact+
can offer an AC/AC efficiency of 92%, this increases to 98%
in DC to AC mode. Achieving a high DC to AC efficiency
means that the batteries can run for longer, thus your
network runs for longer.
Should “Green Mode” be selected then AC to AC efficiency
increases to approximately 98%, In “Green Mode” the T6Compact+ acts as a Line-Interactive device, so that in the
event that the mains fail, the load will be supported within
less than 2 m/s by the battery. Note: when in On-Line mode
there is no time delay between mains fail and battery on.
The T6 Compact+ is available from 10kVA to 30kVA in three
to single phase and from 10kVA to 40kVA three to three
phase. The technology of the T6 Compact+ series is true
double conversion. With Double conversion technology, the
load is run 100% of the time by a continuously rated
inverter, with the output voltage and frequency being
regulated, cleaned and constantly monitored. Added to the
inverter section are additional output filters which remove
any other electrical noise, even in bypass mode.
> Configurations
The T6 Compact+ offers ultimate protection for data
networks, CCTV and other essential applications, thanks to
its cutting edge modular design. Every T6 Compact+ is
packed with communications options and optional
operating modes. Normal mode is as a double conversion
UPS, alternatively the T6 Compact+ can be configured to
run as a line-Interactive system (green mode), further
reducing energy costs or as a frequency converter, again
all programmable.
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 5/8
T6 COMPACT +| AEC|5
Should the batteries get warmer the T6 Compact+ will
adjust its charging regime to reduce voltage. Any life
threatening battery problems will automatically be raised as
an alarm, giving an opportunity to remedy the problem.
> Mains Friendly
The T6 Compact+ is a transformerless UPS with an IGBT
input and output all controlled by DSP technology (Digital
Signal Processor). Again here we have acronyms, IGBT,
DSP, but how do these affect you, the user? The
combination of Isolated Gate Bipolar Transistors and Digital
Signal Possessing, allows the T6 Compact+ to have an
almost negligible effect on the mains supply, in that less than
five percent harmonic distortion is generated. The benefit of
this important feature is that a generator can be down sized
by as much as 50%, the user, will more than likely fall
outside any financial penalty bands that many EEC
countries are considering for mains pollution.
> Battery Management
To off-set the unavoidable process of battery decay, the T6
Compact+ incorporates a battery management system
which is calibrated in accordance with almost any battery
manufacturers’ specifications. If at some future point you
want to use an alternative brand of battery other than the
original it’s no problem, after a small adjustment the T6
Compact+ will accommodate your desired brand.
A great friend of current ripple and equally destructive is
temperature, the hotter a battery gets the less it performs.
Battery temperature within the T6 Compact+ is carefully
monitored, with the data being passed back to the charger.
> Serviceability
MTTR (Mean Time to Repair) can mean a lot more than just four letters when
responsible for the efficient running of an IT network or production plant. A low
MTTR is what all serious users need, in fact demand! This requirement is no
problem for the T6 Compact+, which offers features that dramatically reduce
service or repair times. Even before an engineer arrives on site, a problem can be
diagnosed via the LCD screen or through a software interface. All circuit boards are
housed within drawer like modules and are accessed via the front of the UPS, so
removal and replacement of a drawer can be done in less than ten minutes.
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 6/8
> Standard Properties
• Hi Level diagnostics via LCD screen or lap top.
• Input power factor correction .99pf
• Low audible noise.
• Back feed protection
• Green Mode.
• Modular Construction
• High speed temperature compensated
battery charge
• Light weight and compact.
• Front access
• Made in EEC
6| AEC| T6 COMPACT+
> Efficiency
DSP, IGBT, Tri Core technology, all add up to an efficient
UPS, and efficiency equates to saving substantial amounts
of money. Achieving >92% in On-Line mode, this is typically
7% to 8% better than a conventional UPS, in real terms you
could be saving 2.8KW per hour on a 40kVA installation.
Imagine a 2.5KW electric fire running in your office day in
day out, this is the potential saving you could make with the
help of the T6 Compact+!
Because the T6 Compact+ runs efficiently, generating less
heat, the air conditioning system can be down rated on an
almost pro-rata basis, again savings are made, another big
PLUS for the T6 Compact+.
> Blade Server Compatibility
The T6 Compact+ will work with almost any type of load
accepting power factors of either .9 leading or .9 lagging
(many other manufactures standard is .8pf).
This makes it ideally suited for applications with Blade
Servers, or other devices where a leading power factor can
offer a serious challenge, a challenge not all UPS can meet.
> Optional Accessories
• Parallel capacity/
redundancy
• Isolation transformer
• External bypass
• External batterycabinets
• Battery switch box
• Battery thermal probe
• Transformers/
autotransformers for
voltage adaption
“ The T6 Compact+ runs so
efficiently, the air conditioningcan be down rated”
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 7/8
T6 COMPACT+| AEC|7
T6COMPACT+ TECHNICAL SPECIFICATIONS
POWER - KVA 10 kVA 15 kVA 20 kVA 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Capacity (kVA/kW) 10/8 15/12 20/16 10/8 15/12 20/16 30/24 20/16
Dimensions WxHxD (mm) 450x1200x650
Weight (kg) w/o battery 90 100 100 90 100 100 141 141
with battery 250 260 260 250 260 260
Input/output connection Hardwired (dual input) Hardwired (optional dual input)
Battery Internal or external, 360 cells External, 360 cells
INPUT
Nominal voltage 220/380, 230/400, 240/415 Vac three phase
Voltage range -20%, +10% from nominal
Frequency 50/60 Hz (45–65 Hz)
Power factor 0,99
Current distortion (THDi) 3%
OUTPUT
Nominal voltage 220, 230, 240 Vac single phase 220/380, 230/400, 240/415 Vac three phase
Frequency 50/60 Hz
Voltage regulation ±1% static; ± 2% dynamic 100% load change, <10 ms recovery time
PF acceptable without de-rating Lagging to 0.9 leading
Overload capacity 101–125% for 10 min (on-line); 126–150% for 1 min (on-line);
500% for 1 cycle (bypass)
Efficiency >92%
EPS (Eco-mode) >98%
Options Parallel capacity/redundancy; isolation transformer; external bypass; external battery cabinets,
battery switch box; battery thermal probe; transformers/ autotransformers for voltage adaptation;
USER INTERFACE
Front panel Graphical LCD display, mimic with LED’s and keyboard
Standard communication ports RS232 serial port, USB port, Emergency Power Off input, battery switch monitoring portOptional Web/SNMP, ModBus, relay, modem cards; remote panel; monitoring, managing and shutdown software
ENVIRONMENTAL
Operating temperature 0°C – +40°C
Storage temperature -10°C – +70°C
Altitude <1000 m
Audible noise at 1 meter (dBA) <60
STANDARDS & CERTIFICATION
Marking CE
Safety IEC EN 62040-1
EMC IEC EN 62040-2
Test and Performance IEC EN 62040-3
Quality ISO9001 :2000
The data and text contained within this brochure are for general information only and can not be deemed as definitive, specifications can change without notice.
8/3/2019 (14)Aec t6c - Aec_t6c Brochure
http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 8/8
AEC UK
Systems House
Eckington Business Park
Rotherside RoadEckington
Sheffield. S21 4HL
Tel: 0044 01246 431431
Fax: 0044 01246 431444
Email: [email protected]
Web: www.aeceuro.co.uk