(14)Aec t6c - Aec_t6c Brochure

9
 T6COMPACT 10kVA - 40kVA +

Transcript of (14)Aec t6c - Aec_t6c Brochure

Page 1: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 1/8

 T6COMPACT10kVA - 40kVA

+

Page 2: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 2/8

 T6COMPACT+10kVA - 40kVA

2| AEC|  T6 COMPACT+

In actuality, most power failures are not from an angry deity, but from altogether more benign sources.

 The reality is that your computer suite is more vulnerable from the contractor down the road with his big yellow JCB, or from

the site electrician who has forgotten which breaker does what, in the jumbled up, spaghetti wired power distribution panel. Or

what about one of the most common causes of a PC computer crash, the cleaner pulling the plug to use the vacuum cleaner,

yes, it really happens!

Many have the genuinely misguided opinion that a UPS is there essentially to protect against a power failure, and it’s true that

such a failure can be a disaster for any IT installation. But in reality the electrical threats are much wider and more subtle than

most can imagine, here are some threats explained, and how the T6 Compact+ can protect your system.

 A “brown out” happens when the voltage to your network

drops to a point whereby by it can cause a server or PC to

simply stop working. The effect is the same as a full power

failure, but may only last a second or two, or maybe even

less. To illustrate, how often have you experienced your

lights dim, just briefly? 90% of the time this is because of 

a voltage drop, or “brown out”. The T6 Compact+ is

designed to deal with this subtle threat, offering your

servers a fully regulated and clean supply regardless of the

input voltage, and it will even record the event so that you

can investigate at a later time.

> Brown Outs

 The T6 Compact+ is designed to protect against the many electrical threats which

stalk our heavily computerised infrastructure. Most individuals simply think of 

power failures in the context of lightening strikes or some other so called “act of 

God”; however these opinions are very far from the truth.

Page 3: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 3/8

  T6 COMPACT+| AEC|3

habit of locking or freezing a computer program, an irritation

we have all experienced. There is a bigger danger that larger

spikes can easily damage a power supply, hence many

quality servers have two. The T6 Compact+ incorporates

high energy absorbing filters that will mitigate this threat,

offering your network a clean and regulated supply.

> Spikes

> Installation Simplicity

Spikes are very short bursts of high voltage and high

energy; these are often caused by the stopping and

starting of motors or compressors, typically air

conditioning or chilling units. Smaller but equally

disruptive spikes can be caused by laser printers or

other similar machines. These spikes have a nasty

 A 15kVA T6 Compact+ weighs in at only 90Kg (no

batteries), even it’s bigger brother the T6+ 40kVA

weighs in at a meagre 141Kg. The weight advantage

proves to be very useful when having to use lifts to

site the UPS, as raised floors generally don’t have to

be reinforced and the whole siting procedure is

made safer because of integrated wheels and easy

manoeuvrability.

 Add to these features convenient cable access and

battery installation, and its easy to see why we call

the T6 Compact, the T6 Compact “+”.

“Performance,

compactness and

reliability for criticalapplications”

Page 4: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 4/8

4| AEC|  T6 COMPACT+

> Reduced Power Consumption

When running in its normal On-Line mode the T6 Compact+

can offer an AC/AC efficiency of 92%, this increases to 98%

in DC to AC mode. Achieving a high DC to AC efficiency

means that the batteries can run for longer, thus your

network runs for longer.

Should “Green Mode” be selected then AC to AC efficiency

increases to approximately 98%, In “Green Mode” the T6Compact+ acts as a Line-Interactive device, so that in the

event that the mains fail, the load will be supported within

less than 2 m/s by the battery. Note: when in On-Line mode

there is no time delay between mains fail and battery on.

 The T6 Compact+ is available from 10kVA to 30kVA in three

to single phase and from 10kVA to 40kVA three to three

phase. The technology of the T6 Compact+ series is true

double conversion. With Double conversion technology, the

load is run 100% of the time by a continuously rated

inverter, with the output voltage and frequency being

regulated, cleaned and constantly monitored. Added to the

inverter section are additional output filters which remove

any other electrical noise, even in bypass mode.

> Configurations

  The T6 Compact+ offers ultimate protection for data

networks, CCTV and other essential applications, thanks to

its cutting edge modular design. Every T6 Compact+ is

packed with communications options and optional

operating modes. Normal mode is as a double conversion

UPS, alternatively the T6 Compact+ can be configured to

run as a line-Interactive system (green mode), further

reducing energy costs or as a frequency converter, again

all programmable.

Page 5: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 5/8

 T6 COMPACT +| AEC|5

Should the batteries get warmer the T6 Compact+ will

adjust its charging regime to reduce voltage. Any life

threatening battery problems will automatically be raised as

an alarm, giving an opportunity to remedy the problem.

> Mains Friendly

 The T6 Compact+ is a transformerless UPS with an IGBT

input and output all controlled by DSP technology (Digital

Signal Processor). Again here we have acronyms, IGBT,

DSP, but how do these affect you, the user? The

combination of Isolated Gate Bipolar Transistors and Digital

Signal Possessing, allows the T6 Compact+ to have an

almost negligible effect on the mains supply, in that less than

five percent harmonic distortion is generated. The benefit of 

this important feature is that a generator can be down sized

by as much as 50%, the user, will more than likely fall

outside any financial penalty bands that many EEC

countries are considering for mains pollution.

> Battery Management

 To off-set the unavoidable process of battery decay, the T6

Compact+ incorporates a battery management system

which is calibrated in accordance with almost any battery

manufacturers’ specifications. If at some future point you

want to use an alternative brand of battery other than the

original it’s no problem, after a small adjustment the T6

Compact+ will accommodate your desired brand.

  A great friend of current ripple and equally destructive is

temperature, the hotter a battery gets the less it performs.

Battery temperature within the T6 Compact+ is carefully

monitored, with the data being passed back to the charger.

> Serviceability

MTTR (Mean Time to Repair) can mean a lot more than just four letters when

responsible for the efficient running of an IT network or production plant. A low

MTTR is what all serious users need, in fact demand! This requirement is no

problem for the T6 Compact+, which offers features that dramatically reduce

service or repair times. Even before an engineer arrives on site, a problem can be

diagnosed via the LCD screen or through a software interface. All circuit boards are

housed within drawer like modules and are accessed via the front of the UPS, so

removal and replacement of a drawer can be done in less than ten minutes.

Page 6: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 6/8

> Standard Properties

• Hi Level diagnostics via LCD screen or lap top.

• Input power factor correction .99pf 

• Low audible noise.

• Back feed protection

• Green Mode.

• Modular Construction

• High speed temperature compensated

battery charge

• Light weight and compact.

• Front access

• Made in EEC

6| AEC|  T6 COMPACT+

> Efficiency

DSP, IGBT, Tri Core technology, all add up to an efficient

UPS, and efficiency equates to saving substantial amounts

of money. Achieving >92% in On-Line mode, this is typically

7% to 8% better than a conventional UPS, in real terms you

could be saving 2.8KW per hour on a 40kVA installation.

Imagine a 2.5KW electric fire running in your office day in

day out, this is the potential saving you could make with the

help of the T6 Compact+!

Because the T6 Compact+ runs efficiently, generating less

heat, the air conditioning system can be down rated on an

almost pro-rata basis, again savings are made, another big

PLUS for the T6 Compact+.

> Blade Server Compatibility

 The T6 Compact+ will work with almost any type of load

accepting power factors of either .9 leading or .9 lagging

(many other manufactures standard is .8pf).

  This makes it ideally suited for applications with Blade

Servers, or other devices where a leading power factor can

offer a serious challenge, a challenge not all UPS can meet.

> Optional Accessories

• Parallel capacity/ 

redundancy

• Isolation transformer

• External bypass

• External batterycabinets

• Battery switch box

• Battery thermal probe

•  Transformers/ 

autotransformers for

voltage adaption

“ The T6 Compact+ runs so

efficiently, the air conditioningcan be down rated”

Page 7: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 7/8

  T6 COMPACT+| AEC|7

 T6COMPACT+ TECHNICAL SPECIFICATIONS

POWER - KVA 10 kVA 15 kVA 20 kVA 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA

Capacity (kVA/kW) 10/8 15/12 20/16 10/8 15/12 20/16 30/24 20/16

Dimensions WxHxD (mm) 450x1200x650

Weight (kg) w/o battery 90 100 100 90 100 100 141 141

with battery 250 260 260 250 260 260

Input/output connection Hardwired (dual input) Hardwired (optional dual input)

Battery Internal or external, 360 cells External, 360 cells

INPUT

Nominal voltage 220/380, 230/400, 240/415 Vac three phase

Voltage range -20%, +10% from nominal

Frequency 50/60 Hz (45–65 Hz)

Power factor 0,99

Current distortion (THDi) 3%

OUTPUT

Nominal voltage 220, 230, 240 Vac single phase 220/380, 230/400, 240/415 Vac three phase

Frequency 50/60 Hz

Voltage regulation ±1% static; ± 2% dynamic 100% load change, <10 ms recovery time

PF acceptable without de-rating Lagging to 0.9 leading

Overload capacity 101–125% for 10 min (on-line); 126–150% for 1 min (on-line);

500% for 1 cycle (bypass)

Efficiency >92%

EPS (Eco-mode) >98%

Options Parallel capacity/redundancy; isolation transformer; external bypass; external battery cabinets,

battery switch box; battery thermal probe; transformers/ autotransformers for voltage adaptation;

USER INTERFACE

Front panel Graphical LCD display, mimic with LED’s and keyboard

Standard communication ports RS232 serial port, USB port, Emergency Power Off input, battery switch monitoring portOptional Web/SNMP, ModBus, relay, modem cards; remote panel; monitoring, managing and shutdown software

ENVIRONMENTAL

Operating temperature 0°C – +40°C

Storage temperature -10°C – +70°C

Altitude <1000 m

Audible noise at 1 meter (dBA) <60

STANDARDS & CERTIFICATION

Marking CE

Safety IEC EN 62040-1

EMC IEC EN 62040-2

Test and Performance IEC EN 62040-3

Quality ISO9001 :2000

 The data and text contained within this brochure are for general information only and can not be deemed as definitive, specifications can change without notice.

Page 8: (14)Aec t6c - Aec_t6c Brochure

8/3/2019 (14)Aec t6c - Aec_t6c Brochure

http://slidepdf.com/reader/full/14aec-t6c-aect6c-brochure 8/8

 AEC UK

Systems House

Eckington Business Park

Rotherside RoadEckington

Sheffield. S21 4HL

Tel: 0044 01246 431431

Fax: 0044 01246 431444

Email: [email protected]

  Web: www.aeceuro.co.uk