1 ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11 PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 1 OF 77 TEST REPORT FOR LINE DISTANCE PROTECTION RELAY 1. Designation: LINE DISTANCE PROTECTION RELAY Location: 132/33KV , 70MVA TRANSFORMER / LINE BAY - 2C & R PANEL 2. Name Plate Details : Manufacturer :Schweitzer Engineering Laboratories,Inc. Rated Current : 300/1.0 A Type No. : SEL 311C Rated Voltage : 132000/110 VAC Serial No. : 2007039129 Rated Freq. : 50/60 Hz Model No. : SEL 311C Aux. Voltage : 110 VDC 3. Mechanical Check And Visual Inspection (Tick If Verified) Item Description 1 Inspect for physical damage / defects. Yes N/A 2 Verify connections as per approved drawing. Yes N/A 3 Check tightness of all connections. Yes N/A 4. Electrical Tests (Tick If Verified) Date : 08.02.2012 1. Function Test 1. Function Test Item Description 1 Human Machine Interface [ HMI ] checked. Yes N/A 2 Test switch checked for correct function. Yes N/A 3 Case earthing checked. Yes N/A 4 Indications checked. Yes N/A 5 Alarm contacts checked. Yes N/A 6 Trip contacts checked. Yes N/A 7 Reset of indications checked. Yes N/A 8 Carrier send checked. Yes N/A 9 Carrier receive checked. Yes N/A 11 Blocking inputs checked. Yes N/A 11 Switch onto fault checked. Yes N/A 12 Power swing blocking function checked. Yes N/A 13 Scheme function checked. Yes N/A 14 Week End Infeed Function checked Yes N/A for ELSYTEC

Transcript of 132kv Ss Vestas Test Report

Page 1: 132kv Ss Vestas Test Report

1

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 1 OF 77

TEST REPORT FOR LINE DISTANCE PROTECTION RELAY

1. Designation: LINE DISTANCE PROTECTION RELAY

Location: 132/33KV , 70MVA TRANSFORMER / LINE BAY - 2C & R PANEL

2. Name Plate Details :

Manufacturer :Schweitzer Engineering Laboratories,Inc. Rated Current : 300/1.0 A

Type No. : SEL 311C Rated Voltage : 132000/110 VAC Serial No. : 2007039129 Rated Freq. : 50/60 Hz Model No. : SEL 311C Aux. Voltage : 110 VDC

3. Mechanical Check And Visual Inspection (Tick If Verified)

Item Description

1 Inspect for physical damage / defects. Yes N/A

2 Verify connections as per approved drawing. Yes N/A

3 Check tightness of all connections. Yes N/A

4. Electrical Tests (Tick If Verified) Date : 08.02.2012

1. Function Test 1. Function Test

Item Description

1 Human Machine Interface [ HMI ] checked. Yes N/A

2 Test switch checked for correct function. Yes N/A

3 Case earthing checked. Yes N/A

4 Indications checked. Yes N/A

5 Alarm contacts checked. Yes N/A

6 Trip contacts checked. Yes N/A

7 Reset of indications checked. Yes N/A

8 Carrier send checked. Yes N/A

9 Carrier receive checked. Yes N/A

11 Blocking inputs checked. Yes N/A

11 Switch onto fault checked. Yes N/A

12 Power swing blocking function checked. Yes N/A

13 Scheme function checked. Yes N/A

14 Week End Infeed Function checked Yes N/A

for ELSYTEC

Page 2: 132kv Ss Vestas Test Report

2

ELSYTEC ENGINEERS AND COELSYTEC ENGINEERS AND COELSYTEC ENGINEERS AND COELSYTEC ENGINEERS AND CONSULTANTS PVT LTD NSULTANTS PVT LTD NSULTANTS PVT LTD NSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 2 OF 77

5. Secondary injection test : 6. Switch On to Fault Function.:

Energize the manual close Binary Input through a switch and simultaneously apply 3 phase current above setting

Amps but without 3phase voltage. The protection should Trip instantaneously. Measured Time : 0.036 msecs 7. Fuse Failure function.

Un =49.0 V

Settings Measured Values

Phase

3Uo> 3Io< 3Uo> 3Io< L12 50% - 47.81 V - 1. Apply 3 phase voltage to the relay and then remove 1ph voltage and the timer will start simultaneously “ Fuse Failure Alarm” Appeared in : sec Alarm” Appeared in :-1.00 sec 2. Apply Zone -1 1ph fault within “1 sec” of fuse failure status. Protection tripped in :0.035……. msec. 3. Apply Zone-1 1ph fault after 1sec of fuse failure status. Protection should blocked. ITEM DESCRIPTION CHECKED 1 Check operation on/off OK 2 Check operation of indication OK 3 Check operation of contacts OK 9.Powerswing test: PSB blocking function checked :OK

Test Equipment Details

Make : Doble Engineering Company U.S.A

3Ph = 0 – 15A

Type: F 6150

3Ph = 0 – 260V

8. Fault Locator : 100% - Z = 2. 34 Ω ∟67.25 for 22Km Fault type App. Imp(%&Z) Cal. Display Km Trip Display Km

A-N 45% 9.90 9.75 A-N 90% 19.80 19.46 A-N 100% 22.00 21.70 A-N -100% (Rev) - 2.20 - 2.25 A-B 45% 9.90 10.04 A-B 90% 19.80 20.06 A-B 100% 22.00 22.09 A-B -100% (Rev) - 2.20 - 2.25 9. Timing test : Fault type Zone 1(F) Zone 2(F) Zone 3 (R)

Ph-N Ph-Ph Refer Doble Test Report 3 Ph 10.Srvice Setting: File Attached Refer Page No : 11.Remarks:Relay operation found satisfactory

for ELSYTEC

Page 3: 132kv Ss Vestas Test Report

3

F6TesT

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

VESTAS 132kv Location Path

Test Definition 1

Pass Evaluation R.kanagaraj

Auto saved

Tested By

Tested Date

Test Definition Description

Test Definition Name

2/8/2012

Relay Under Test General Parameters

A-B-C Vn

In 2000.000%

SEL311C

1000.00%

300 : 1 CTR

Phase Names And Rotation

Max Test Voltage

Max Test Current

Model

A V (Ph-Ph) Hz

1.000 110.00 50.000

132000 : 110

132KV line-2

In Vn fn

SEL

SEL311c

VTR

Nominal Ratings:

Station Name

Manufacturer

Serial Number

Relay Name

Protected Object Parameters

LINE Protected Object Name

Protected Object Parameters relay Setting

Relay Functions

Function Type ZONE Impedance Function Name

Display values in Inherent Op Time ms 20.0 Secondary

General Tolerances

ms 20.0 Absolute Minimum Time Absolute Minimum Ohm 0.010

Zone Elements

-% + % -% +%

Zone Name Char Type Fault Type

Z tol t tol t nom [ms]

Residual Compensation Characteristic Angle

Zone_1 0 10.00 10.00 10.00

10.00

General 3-Ph 67.25

Zone_1 0 10.00 10.00 10.00

10.00

General Ph-Ph 67.25

Zone_1 0 10.00 10.00 10.00

10.00

General Ph-N 0.75 -7.86 KN 67.25

Zone_2 300 10.00 10.00 10.00

10.00

General 3-Ph 67.25

Zone_2 300 10.00 10.00 10.00

10.00

General Ph-Ph 67.25

Zone_2 300 10.00 10.00 10.00

10.00

General Ph-N 0.75 -7.86 KN 67.25

Zone_3 300 10.00 10.00 10.00

10.00

General 3-Ph 67.25

Zone_3 300 10.00 10.00 10.00

10.00

General Ph-Ph 67.25

Zone_3 300 10.00 10.00 10.00

10.00

General Ph-N 0.75 -7.86 KN 67.25

Doble Page 1 of 9

Page 4: 132kv Ss Vestas Test Report

4

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

F6000 Instrument HW and SW Information

F6TesT Software Version 2.21 Build 1165

F6000 Model Number F6150

Serial Number 67191328

F6000 Firmware Version 4.28.2

F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface

F6910 : Simulator control and automation interface

F6825 : CPU2 F6875 : Variable Battery Simulator

F6844 : Logic I/O 4 board

Test Configuration

0.000

110.00

Constant Current

V

A

Test Method

Prefault Voltage

Prefault Current Angle 0 Deg

% of rating Max Acceptable Voltage

Desired Test Current A 2

90

dc transient, fault inception angle

ms 0.00 Time constant L/R

Minimum Offset

CT direction Towards Line

Values are in Secondary

cy

cy

cy

x Tmax

35.000

75.000

5.000

Test Timing Trigger Selection

Prefault Duration

Max. Fault Duration

Max Fault Duration For Faster Zones

Time between shots

Fault Type Trigger

AN

BN

CN

AB

BC

CA

ABC

CBTripTime cy 0.000

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

Doble Page 2 of 9

Page 5: 132kv Ss Vestas Test Report

5

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[cy] [cy] [cy] [cy]

Err

[Ω] [V] [A] [°] [%]

Fault Type AN

Test Test

2.032 66.13 7.11 2.000 1.795 79.50 1.000 0.000 21.675 92.40 Zone_1 Pass

2.303 66.62 8.06 2.000 16.805 5.03 16.000 14.400 NoOp 94.00 Zone_2 Pass

2.641 66.39 9.24 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass

0.112 250.10 0.39 2.000 16.835 5.22 16.000 14.400 17.600 44.70 Zone_3 Pass

AN Fault Type

Doble Page 3 of 9

Page 6: 132kv Ss Vestas Test Report

6

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[cy] [cy] [cy] [cy]

Err

[Ω] [V] [A] [°] [%]

Fault Type BN

Test Test

2.032 66.13 7.11 2.000 1.870 87.00 1.000 0.000 21.675 92.40 Zone_1 Pass

2.303 66.62 8.06 2.000 16.875 5.47 16.000 14.400 NoOp 94.00 Zone_2 Pass

2.641 66.39 9.24 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass

0.112 250.10 0.39 2.000 16.900 5.62 16.000 14.400 17.600 44.70 Zone_3 Pass

BN Fault Type

Doble Page 4 of 9

Page 7: 132kv Ss Vestas Test Report

7

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[cy] [cy] [cy] [cy]

Err

[Ω] [V] [A] [°] [%]

Fault Type CN

Test Test

2.032 66.13 7.11 2.000 1.940 94.00 1.000 0.000 21.675 92.40 Zone_1 Pass

2.303 66.62 8.06 2.000 16.960 6.00 16.000 14.400 NoOp 94.00 Zone_2 Pass

2.641 66.39 9.24 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass

0.112 250.10 0.39 2.000 16.980 6.12 16.000 14.400 17.600 44.70 Zone_3 Pass

CN Fault Type

Doble Page 5 of 9

Page 8: 132kv Ss Vestas Test Report

8

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[cy] [cy] [cy] [cy]

Err

[Ω] [V] [A] [°] [%]

Fault Type AB

Test Test

2.107 66.74 8.43 2.000 2.000 100.00 1.000 0.000 25.312 95.80 Zone_1 Pass

2.327 67.14 9.31 2.000 16.755 4.72 16.000 14.400 NoOp 95.00 Zone_2 Pass

2.658 66.08 10.63 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass

0.140 235.51 0.56 2.000 16.780 4.88 16.000 14.400 17.600 57.00 Zone_3 Pass

AB Fault Type

Doble Page 6 of 9

Page 9: 132kv Ss Vestas Test Report

9

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[cy] [cy] [cy] [cy]

Err

[Ω] [V] [A] [°] [%]

Fault Type BC

Test Test

2.107 66.74 8.43 2.000 1.825 82.50 1.000 0.000 25.312 95.80 Zone_1 Pass

2.327 67.14 9.31 2.000 16.840 5.25 16.000 14.400 NoOp 95.00 Zone_2 Pass

2.658 66.08 10.63 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass

0.140 235.51 0.56 2.000 16.850 5.31 16.000 14.400 17.600 57.00 Zone_3 Pass

BC Fault Type

Doble Page 7 of 9

Page 10: 132kv Ss Vestas Test Report

10

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[cy] [cy] [cy] [cy]

Err

[Ω] [V] [A] [°] [%]

Fault Type CA

Test Test

2.107 66.74 8.43 2.000 1.895 89.50 1.000 0.000 25.312 95.80 Zone_1 Pass

2.327 67.14 9.31 2.000 16.900 5.62 16.000 14.400 NoOp 95.00 Zone_2 Pass

2.658 66.08 10.63 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass

0.140 235.51 0.56 2.000 16.940 5.88 16.000 14.400 17.600 57.00 Zone_3 Pass

CA Fault Type

Doble Page 8 of 9

Page 11: 132kv Ss Vestas Test Report

11

Impedance Relay Timing Test Report 08-Feb-12

VESTAS 132kv/SEL311c

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[cy] [cy] [cy] [cy]

Err

[Ω] [V] [A] [°] [%]

Fault Type ABC

Test Test

2.130 66.71 4.26 2.000 1.965 96.50 1.000 0.000 26.704 96.80 Zone_1 Pass

2.331 66.91 4.66 2.000 16.970 6.06 16.000 14.400 NoOp 95.10 Zone_2 Pass

2.645 66.19 5.29 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass

0.089 228.21 0.18 2.000 16.740 4.62 16.000 14.400 17.600 37.50 Zone_3 Pass

ABC Fault Type

Doble Page 9 of 9

Page 12: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 12 OF 77

TEST REPORT FOR TRANSFORMER PROTECTION RELAY

1. Designation:1. Designation:1. Designation:1. Designation: TRANSFORMER PROTECTION RELAY

Location: 132/33 KV ,70MVA TRANSFORMER C & R PANEL

2. Name Plate Details:2. Name Plate Details:2. Name Plate Details:2. Name Plate Details:

Make : REYROLLE Serial No. : BR 0701432

Type : DUOBIAS M Vaux. : 110V DC

Vu : NA In : 1.0 A

F : 50 HZ VTR : -----------

MVA : 70.0 HVCTR : 300/1A

HVNCTR: 400/1A LVCTR: 1600/1A

LVNCR: 1600/1A

3. General Inspection:3. General Inspection:3. General Inspection:3. General Inspection: OK Date :09.02.2012

4) Secondary Injection Test : 4) Secondary Injection Test : 4) Secondary Injection Test : 4) Secondary Injection Test :

(a):i) 87T Differential Current pickup Test : (i) (HV Side)

Phase Set. Current

(A)

Calculated Pickup Current (A) 3ø Pickup Current (A)

R 0.30 0.35 / 0.98 = 0.306 0.307 Y 0.30 0.35 / 0.98 = 0.306 0.307 B 0.30 0.35 / 0.98 = 0.306 0.307

(ii) LV Side Phase Set. Current (A) Calculated Pickup Current (A) 3ø Pickup Current

(A)

R 0.30 0.30 / 1.3 = 0.230 0.234

Y 0.30 0.30 / 1.3 = 0.230 0.234

B 0.30 0.30 / 1.3 = 0.230 0.234

(b):i) 87T Differential Inst pickup Test : (i) (HV Side) Phase Set.

Current (A)

Calculated Pickup Current (A) Pickup Current (A)

R 8.0 8.0 / 0.98 = 8.16 8.160 Y 8.0 8.0 / 0.98 = 8.16 8.160 B 8.0 8.0 / 0.98 = 8.16 8.160

(ii) LV Side Phase Set. Current (A) Calculated Pickup Current (A) Pickup Current

(A)

R 8.0 8.0 / 1.3 = 6.15 6.151 Y 8.0 8.0 / 1.3 = 6.15 6.151 B 8.0 8.0 / 1.3 = 6.15 6.151

for ELSYTEC

Page 13: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 13 OF 77

(b) Stability test : (at 100% load)

Phase App. HV Side Current (A)

App. LV Side Current (A)

Diff.Op.Relay Current (A)

Bias Current (A)

Diff.Relay

R 1.02 ∟0° 0.769 ∟180° 0.00 0.99 Not Operated

Y 1.02 ∟-120° 0.768 ∟60° 0.00 0.99 Not Operated

B 1.02 ∟120° 0.768 ∟300° 0.00 0.99 Not Operated

(c) Inrush Inhibit Set;

Phase ref Set. Current (A)

App. current (A)

App. current Freq(Hz)

Meg.Inrush Current (A)

Diff.Op.Relay Current (A)

Diff.Relay

R 0.2 0.30 100.0 0.30 0.30 Not Operated Y 0.2 0.30 100.0 0.30 0.30 Not Operated B 0.2 0.30 100.0 0.30 0.30 Not Operated

(d) Bias (or) Slope Test :

Phase Set. Bias Set. Diff Op. Bias Op. Diff

R Y Refer Doble Test Report B

(e) W1 Protection 51/51N : Inv – IEC NI

Phase Ref. Set. Current (A)

Time Mult Operating Time (Sec) at multiples of Set. Current

X 2 X 5 X 10

R 1.0 0.1 1.03 0.47 0.32

Y 1.0 0.1 1.03 0.47 0.32

B 1.0 0.1 1.03 0.47 0.32

N 0.2 0.1 1.05 0.48 0.31

(f) W1 Protection 50/50N :

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 8.0 8.00 0.00 0.04

Y 8.0 8.00 0.00 0.04

B 8.0 8.00 0.00 0.04

N 5.0 5.01 0.00 0.04

(g) W2 Protection 51/51N : Inv – IEC NI

Phase Ref. Set. Current (A) Time Mult Operating Time (Sec) at multiples of Set. Current

X 2 X 5 X 10

R 1.0 0.05 0.54 0.26 0.15

Y 1.0 0.05 0.54 0.26 0.15

B 1.0 0.05 0.54 0.26 0.15

N 0.2 0.05 0.57 0.26 0.16

for ELSYTEC

Page 14: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 14 OF 77

(h) W2 Protection 50/50N :

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 6.0 6.00 0.00 0.04

Y 6.0 6.00 0.00 0.04

B 6.0 6.00 0.00 0.04

N 4.0 4.01 0.00 0.05

(i) HV REF – Earth current:

Phase ref Set. current (A)

Pickup. current for ST HV side(A)

Phase ref

Set. current (A)

Operating current (A)

Operating REF

R 0.2 0.21 Y 0.2 0.21 N,CT 0.2 0.201 OK B 0.2 0.21

(j) LV REF – Earth current:

Phase ref Set. current (A)

Pickup. current for ST HV side(A)

Phase ref

Set. current (A)

Operating current (A)

Operating REF

R 0.2 0.21 Y 0.2 0.21 N,CT 0.2 0.201 OK B 0.2 0.21

(k) 50 BF (LBB) set :

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

3Ø 0.2 0.21 INST 0.04

5555.Srvice Setting.Srvice Setting.Srvice Setting.Srvice Setting: File Attached Refer Page No :

6666.Remarks.Remarks.Remarks.Remarks:Relay operation found satisfactory

for ELSYTEC

Page 15: 132kv Ss Vestas Test Report

F6TesT

Differential Relay Test Report 09-Feb-12

VESTAS 132kv/DuoBias M

VESTAS 132kv 70MVA TR Location Path

Test Definition 1

Pass Evaluation R.kanagaraj

Auto saved Auto saved

Tested By

Tested Date

Test Definition Description

Test Definition Name

2/9/2012

Relay Under Test General Parameters

A-B-C Vn

In 2000.000%

DIUOBIAS

181.81%

300 : 1 CTR

Phase Names And Rotation

Max Test Voltage

Max Test Current

Model

A V (Ph-Ph) Hz

1.000

110.00 50.000

132000 : 110

Substation

In Vn fn

REYROLLE

DuoBias M

VTR

Nominal Ratings:

Station Name

Manufacturer

Serial Number

Relay Name

Protected Object Parameters

Protected Object Name

Protected Object Parameters

Relay Functions

Function Type Duobias M Differential Function Name

General Tolerances

ms 20.0 Absolute Minimum Time Absolute Minimum A 0.050

Pickup Setting

Time Tolerance

Current Tolerance

Const B

Const A

Bias Equation Nominal Time

+% -% +% -%

Const C

Characteristic Name

x tap

35.00 (a*|Ip|+b*|Is|)/c 1.00 1.00 2.00 0.30

2.00 2.00 3.00 3.00 35.00 (a*|Ip|+b*|Is|)/c 1.00 1.00 2.00 8.00

F6000 Instrument HW and SW Information

F6TesT Software Version 2.21 Build 1165

F6000 Model Number F6150

Serial Number 67191328

F6000 Firmware Version 4.28.2

F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface

F6910 : Simulator control and automation interface

F6825 : CPU2 F6875 : Variable Battery Simulator

F6844 : Logic I/O 4 board

Doble Page 1 of 4

Page 16: 132kv Ss Vestas Test Report

Differential Relay Test Report 09-Feb-12

VESTAS 132kv/DuoBias M

F6000 Instrument HW and SW Information

F6TesT Software Version 2.21 Build 1165

F6000 Model Number F6150

Serial Number 67191328

F6000 Firmware Version 4.28.2

F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface

F6910 : Simulator control and automation interface

F6825 : CPU2 F6875 : Variable Battery Simulator

F6844 : Logic I/O 4 board

Test Configuration

Angle of Ip = 0 deg; Angle of Is = 180 deg or 0 degFind | Ip | , | Is |, and Angle of Is for desired values of Ibias and Idiff

Test Method

6.000

Secondary Values are in

A 0.000 Prefault load current A Max test current

s

s

s

0.6000

0.4000

0.6000

Test Timing

Prefault Duration

Max. Fault Duration

Time between shots

Trigger Selection

Fault Type Trigger

A

B

C s

CBTripTime 0.0000

LN1 0->1

LN1 0->1

LN1 0->1

Doble Page 2 of 4

Page 17: 132kv Ss Vestas Test Report

Differential Relay Test Report 09-Feb-12

VESTAS 132kv/DuoBias M

Fault Name Phase : A

Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval

0.283 -5.667 Pass 0.926 0.300 0.240 0.360

0.442 -9.426 Pass 2.439 0.488 0.390 0.585

0.727 -9.465 Pass 4.013 0.803 0.642 0.963

0.565 -9.455 Pass 3.118 0.624 0.499 0.748

0.309 -10.694 Pass 1.729 0.346 0.277 0.415

Fault Name Phase : A

Fault Name Phase : B

Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval

0.287 -4.333 Pass 0.926 0.300 0.240 0.360

0.460 -5.738 Pass 2.439 0.488 0.390 0.585

0.798 -0.623 Pass 4.013 0.803 0.642 0.963

0.588 -5.769 Pass 3.118 0.624 0.499 0.748

0.326 -5.780 Pass 1.729 0.346 0.277 0.415

Doble Page 3 of 4

Page 18: 132kv Ss Vestas Test Report

Differential Relay Test Report 09-Feb-12

VESTAS 132kv/DuoBias M

Fault Name Phase : B

Fault Name Phase : C

Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval

0.291 -3.000 Pass 0.926 0.300 0.240 0.360

0.460 -5.738 Pass 2.439 0.488 0.390 0.585

0.778 -3.113 Pass 4.013 0.803 0.642 0.963

0.588 -5.769 Pass 3.118 0.624 0.499 0.748

0.326 -5.780 Pass 1.729 0.346 0.277 0.415

Fault Name Phase : C

Doble Page 4 of 4

Page 19: 132kv Ss Vestas Test Report

ELSYTEELSYTEELSYTEELSYTEC ENGINEERS AND CONSULTANTS PVT LTD C ENGINEERS AND CONSULTANTS PVT LTD C ENGINEERS AND CONSULTANTS PVT LTD C ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 19 OF 77 CT/VT CONFIG MENU

W1 Input (1..5) 1A W1 CT Ratio (1:0.2..5000:7) 300:1 W1 REF Input (1..5) 1A W1 REF CT Ratio (1:0.2..5000:7) 400:1 W2 Input (1..5) 1A W2 CT Ratio (1:0.2..5000:7) 1600:1 W2 REF Input (1..5) 1A W2 REF CT Ratio (1:0.2..5000:7) 1600:1

BIASED DIFFERENTIAL MENU W1 Interposing CT Multiplier (0.25..3) 0.98x W1 Interposing CT Connection (Yy0,0..Ydy0,0) Yd1,-30deg W2 Interposing CT Multiplier (0.25..3) 1.3x W2 Interposing CT Connection (Yy0,0..Ydy0,0) Yd1,-30deg 87 Inrush Inhibit (Disabled..Enabled) Enabled 87 Inrush Bias (Phase..Sum) Cross 87 Inrush Setting (0.1..0.5) 0.2xId 87 Bias Differential (Disabled..Enabled) Enabled 87 Initial Setting (0.1..2) 0.3xIn 87 Bias Slope (0..0.7) 0.2x 87 Bias Slope Limit (1..20) 4xIn 87 Delay (0..1) 0s 87HS Differential HighSet (Disabled..Enabled) Enabled 87HS Setting (1..30) 8xIn 87HS Delay (0..1) 0s

WINDING 1 MENU W1 51 Element (Disabled..Enabled) Enabled W1 51 Setting (0.05..2.5) 1xIn W1 51 Char (IEC-NI..DTL) IEC-NI W1 51 Time Mult

(0.025..1.6) 0.1

W1 51 Delay (DTL) (INST..20) 5s W1 51 Reset ((ANSI) DECAYING..60) INST W1 50 Element (Disabled..Enabled) Enabled W1 50 Setting (0.05..25) 8xIn W1 50 Delay (0..864000) 0s W1 51N Element (Disabled..Enabled) Enabled W1 51N Setting (0.1..2.5) 0.2xIn W1 51N Char (IEC-NI..DTL) IEC-NI W1 51N Time Mult

(0.025..1.6) 0.1

W1 51N Delay (DTL) (INST..20) 5s W1 51N Reset ((ANSI) DECAYING..60) INST W1 50N Element (Disabled..Enabled) Enabled W1 50N Setting (0.1..25) 5xIn W1 50N Delay (0..864000) 0s W1 87REF Element (Disabled..Enabled) Enabled W1 87REF Setting (0.02..0.96) 0.2xIn W1 87REF Delay (0..864000) 0s

W1 50BF Trigger (12 Bit Binary) 87, 87HS, W1 50BF Element (Disabled..Enabled) Enabled W1 50BF Setting (0.05..2) 0.2xIn W1 50BF ReTrip Delay (0..60000) 60ms W1 50BF BackTrip Delay (0..60000) 200ms

WINDING 2 MENU W2 51 Element (Disabled..Enabled) Enabled W2 51 Setting (0.05..2.5) 1xIn W2 51 Char (IEC-NI..DTL) IEC-NI W2 51 Time Mult (IEC/ANSI) (0.025..1.6) 0.05 W2 51 Delay (DTL) (INST..20) 5s W2 51 Reset ((ANSI) DECAYING..60) INST W2 50 Element (Disabled..Enabled) Enabled W2 50 Setting (0.05..25) 6xIn W2 50 Delay (0..864000) 0s W2 51N Element (Disabled..Enabled) Enable

for ELSYTEC

Page 20: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD TS PVT LTD TS PVT LTD TS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 20 OF 77 W2 51N Setting (0.1..2.5) 0.2xIn W2 51N Char (IEC-NI..DTL) IEC-NI W2 51N Time Mult (IEC/ANSI) (0.025..1.6) 0.05 W2 51N Delay (DTL) (INST..20) 5s W2 51N Reset ((ANSI) DECAYING..60) INST W2 50N Element (Disabled..Enabled) Enabled W2 50N Setting (0.1..25) 4xIn W2 50N Delay (0..864000) 0s W2 87REF Element (Disabled..Enabled) Enabled W2 87REF Setting (0.02..0.96) 0.2xIn W2 87REF Delay (0..864000) 0s W2 50BF Trigger (12 Bit Binary) 87,87HS, W1 87REF W2 87REF W2 50BF Element (Disabled..Enabled) Enabled W2 50BF Setting (0.05..2) 0.2xIn W2 50BF ReTrip Delay (0..60000) 60ms W2 50BF BackTrip Delay (0..60000) 120ms

for ELSYTEC

Page 21: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 21 OF 77

TEST REPORT FOR DIRECTIONAL OVER CURRENT EARTH FAULT RELAY

1. Designation: DIRECTIONAL OVER CURRENT EARTH FAULT RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 CONTROL & PROTECTION PANEL

2. Name Plate Details :

Manufacturer : REYROLLE Rated Current : 1.0 A

Type No. : ARGUS – 2 Rated Voltage : 110 VAC

Serial No. : BR 0702445 Rated Freq. : 50/60 Hz

Model No. : DCD 814B Aux. Voltage : 90-250 VDC

3. Mechanical Check And Visual Inspection (Tick If Verified)

Item Description

1 Inspect for physical damage / defects. Yes N/A

2 Verify connections as per approved drawing. Yes N/A

3 Check tightness of all connections. Yes N/A

4. Electrical Tests Date : 08.02.2012

a. Function Test : Set.Direction ; OFF

Phase Ref Set Current(A) Inj.Current(A) Current Dir ection Relay operation

R 1.0 2.0 Forward RELAY OPERATED

2.0 Reverse RELAY OPERATED

Y 1.0 2.0 Forward RELAY OPERATED

2.0 Reverse RELAY OPERATED

B 1.0 2.0 Forward RELAY OPERATED

2.0 Reverse RELAY OPERATED

E/F 0.2 0.4 Forward RELAY OPERATED

0.4 Reverse RELAY OPERATED

for ELSYTEC

Page 22: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 22 OF 77

4. Secondary Injection Test: Date: 02.11.2011

a) Low Set O/C Unit: I> & Io>

Char Curve : NI

Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current

(A) X 2 X 5 X 10

R 1.0 0.125 1.25 0.54 0.38

Y 1.0 0.125 1.25 0.54 0.38

B 1.0 0.125 1.25 0.54 0.38

E/F 0.2 0.125 1.26 0.55 0.37

c) High Set O/C Unit: I>>& Io>>

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 10.0 10.02 0.00 0.043

Y 10.0 10.02 0.00 0.043

B 10.0 10.02 0.00 0.043

E/F 6.0 6.01 0.00 0.043

5. Service Setting :

Dir.Menu:

2 out of – 3 gate logic : OFF P/F Low set : OFF E/F Dir Setting : 60.0 A

P/F Char.Angle : +45° P/F Low Setting : O FF E/F Dir Char : NI

E/F Char.Angle : -15° P/F High set : OFF E/F Dir TMS : 0.125

Protection menu : P/F High Setting : 3000.0 A E/F Low set : OFF

P/F Dir Char : OFF P/F High setTime : 0.0 sec E/F Low Setting : OFF

P/F Dir Setting : 300.0 A P/F High set 2 : OFF E/F High set : OFF

P/F Dir Char : NI P/F High Setting 2 : OFF E/F High Setting : 1800.0 A

P/F Dir TMS : 0.125 E/F Dir Char : OFF E/F High set Time : 0.0 sec

E/F High set 2 : OFF

E/F High Setting 2 : OFF

6. Functional Checks

a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK

b) Correct Initiation Of Alarm Contacts: OK

c) Correct Circuit Breaker Tripping Contacts: OK

7. Remarks : RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 23: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 23 OF 77

TEST REPORT FOR OVER CURRENT AND EARTH FAULT RELAY

1. Designation: OVER CURRENT AND EARTH FAULT RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details :

Make: EASUN REYROLLE Serial No. : BR 0705231

In : 1 /5 A Fn : 50 HZ

Model : MIT 114 Vx : 43 - 280 V DC / 110 VDC

3. General Inspection Checks as per Checks List : OK

4. Secondary Injection Test: (a)Over Current (IP>& Earth Fault (IE>) : Date: 09.02.2012

Phase / Set. Current T.M.S Operating Time (Sec)

Unit (A) x 2 x 5 x 10

R 1.00 XIn 0.05 0.55 0.22 0.16

Y 1.00 XIn 0.05 0.55 0.22 0.16

B 1.00 XIn 0.05 0.55 0.22 0.16

E/F 0.20 xIn 0.05 0.50 0.26 0.15

c) High Set O/C Unit: IP>>& IE>>

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 6.00 6.01 - -

Y 6.00 6.01 - -

B 6.00 6.01 - -

E/F 4.0 4.01 - -

5. Service setting :

CP : SI 3.0 CE : SI 3.0 IP : 100 % IE : 20 %

tp : 0.05 tE : 0.05 Rt ; 0 HP:600%

HE : 400%

6. Remarks : RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 24: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 24 OF 77

TEST REPORT FOR OVER CURRENT AND EARTH FAULT RELAY

1. Designation: OVER CURRENT AND EARTH FAULT RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details :

Make: EASUN REYROLLE Serial No. : BR 0705233

In : 1 /5 A Fn : 50 HZ

Model : MIT 114 Vx : 43 - 280 V DC / 110 VDC

3. General Inspection Checks as per Checks List : OK

4. Secondary Injection Test: (a) Over Current (IP>& Earth Fault (IE>) :

Date: 09.02.2012

Phase / Set. Current T.M.S Operating Time (Sec) Unit (A) x 2 x 5 x 10

R 1.00 XIn 0.1 0.99 0.42 0.31

Y 1.00 XIn 0.1 0.99 0.42 0.31

B 1.00 XIn 0.1 0.99 0.42 0.31

E/F 0.20 xIn 0.1 0.99 0.42 0.31

c) High Set O/C Unit: IP>>& IE>>

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 8.0 8.01 - -

Y 8.0 8.01 - -

B 8.0 8.01 - -

E/F 5.0 5.01 - -

5. Service setting :

CP : SI 3.0 CE : SI 3.0 IP : 100 % IE : 20 %

tp : 0.1 tE : 0.1 Rt ; 0 HP:800%

HE : 500%

6. Remarks : RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 25: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 25 OF 77

TEST REPORT FOR OVER VOLTAGE AND UNDER VOLTAGE RELAY

1. Designation: OVER VOLTAGE AND UNDER VOLTAGE RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details:

Make : EASUN REYROLLE Serial No. : BR0705354

Model : MVT 181 Aux voltage : 43 – 230 V DC

Un : 110V AC

3. General Inspection Checks as per Check List: OK

4. Secondary Injection Test : Date: 08.02.2012

(a) Under voltage (V<):

Set Voltage(V)

Op. Voltage(V) Set. Time (sec) Op. Time (sec)

88.0 88.01 1.0 1.00

(b) Over voltage (V>):

Set Voltage(V)

Op. Voltage(V) Set. Time (sec) Op. Time (sec)

- - - -

5. Service Setting :

E1 – Under , E2 – OFF

U1 – 88.0 , C1 – dtL

t1 – 1.0 , td – 1.0

tc - OFF

6.Remarks: RELAY OPERATION FOUND SATISFACTORY.

for ELSYTEC

Page 26: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 26 OF 77

TEST REPORT FOR OVER VOLTAGE AND UNDER VOLTAGE RELAY

1. Designation: OVER VOLTAGE AND UNDER VOLTAGE RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details:

Make : EASUN REYROLLE Serial No. : BR0705355

Model : MVT 181 Aux voltage : 43 – 230 V DC

Un : 110V AC

3. General Inspection Checks as per Check List: OK

4. Secondary Injection Test : Date: 08.02.2012

(a) Under voltage (V<):

Set Voltage(V)

Op. Voltage(V) Set. Time (sec) Op. Time (sec)

- - - -

(b) Over voltage (V>):

Set Voltage(V)

Op. Voltage(V) Set. Time (sec) Op. Time (sec)

132.0 132.8 1.0 1.01

5. Service Setting :

E1 – Over , E2 – OFF

U1 – 132.0 , C1 – dtL

t1 – 1.0 , td – 1.0

tc - OFF

6.Remarks: RELAY OPERATION FOUND SATISFACTORY.

for ELSYTEC

Page 27: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 27 OF 77

TEST REPORT FOR TRIPPING RELAY

1. Designation: TRIPPING RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details:

Make : ER Model : --------

Type : B24 H2 Rated Volts : 110V DC

3. General Inspection Check : OK

4. Pick up / Drop Off Check: Date: 08.02.2012

Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)

9, 10 A 24.0 Hand reset

HR 0704795

19, 10 B 34.0 Hand reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: Relay operation found satisfactory.

for ELSYTEC

Page 28: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 28 OF 77

TEST REPORT FOR LBB TRIPPING RELAY

1. Designation: LBB TRIPPING RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details:

Make : ER Model : --------

Type : B24 H2 Rated Volts : 110V DC

3. General Inspection Check : OK

4. Pick up / Drop Off Check: Date: 08.02.2012

Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)

9, 10 A 24.28 Hand reset

HR 0704794

19, 10 B 74.49 Hand reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: Relay operation found satisfactory.

for ELSYTEC

Page 29: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 29 OF 77

TEST REPORT FOR TRIPPING RELAY

1. Designation: TRIPPING RELAY

Location: 132/33KV,70MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : ER Model : --------

Type : B24 H2 Rated Volts : 110V DC

3. General Inspection Check : OK

4. Pick up / Drop Off Check: Date: 09.02.2012

Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)

9, 10 A 28.72 Hand reset

HR 0704793

19, 10 B 40.05 Hand reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: Relay operation found satisfactory.

for ELSYTEC

Page 30: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 30 OF 77

TEST REPORT FOR TRIPPING RELAY

1. Designation: TRIPPING RELAY

Location: 132/33KV,70MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : ER Model : --------

Type : B24 H2 Rated Volts : 110V DC

3. General Inspection Check : OK

4. Pick up / Drop Off Check: Date: 09.02.2012

Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)

9, 10 A 26.19 Hand reset

HR 0704791

19, 10 B 35.13 Hand reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: Relay operation found satisfactory.

for ELSYTEC

Page 31: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD TS PVT LTD TS PVT LTD TS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 31 OF 77

TEST REPORT FOR TRIPPING RELAY

1. Designation: TRIPPING RELAY

Location: 132/33KV,70MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : ER Model : --------

Type : B24 H2 Rated Volts : 110V DC

3. General Inspection Check : OK

4. Pick up / Drop Off Check: Date: 09.02.2012

Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)

9, 10 A 30.59 Hand reset

HR 0704792

19, 10 B 37.79 Hand reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: Relay operation found satisfactory.

for ELSYTEC

Page 32: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 32 OF 77

TEST REPORT FOR DC SUPERVISION RELAY

1. Designation: DC SUPERVISION RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details:

Make : EASUN REYROLLE Model No: ------

Type : AR121T3 / AR 101 Vn: 110VDC

Un: 230VAC

3. General Inspection checks as per check List: OK

4. Pickup Test : Date: 08.02.2012

Coil Ref Sl No Pick Up(Volts) Drop Off (Volts)

DC Coil BR0613064 56.28 12.10

AC Coil BR0613064 110.1 39.36

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks : RELAY OPERATION FOUND SATISFACTORY.

for ELSYTEC

Page 33: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 33 OF 77

TEST REPORT FOR DC SUPERVISION RELAY

1. Designation: DC SUPERVISION RELAY

Location: 132/33KV,70MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : EASUN REYROLLE Model No: ------

Type : AR121T3 / AR 101 Vn: 110VDC

Un: 230VAC

3. General Inspection checks as per check List: OK

4. Pickup Test : Date: 09.02.2012

Coil Ref Sl No Pick Up(Volts) Drop Off (Volts)

DC Coil BR06132877 57.72 12.96

AC Coil BR06132877 135.16 20.19

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks : RELAY OPERATION FOUND SATISFACTORY.

for ELSYTEC

Page 34: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 34 OF 77

TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY

1. Designation: TRIP CIRCUIT SUPERVISION RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details:

Make : EASUN REYROLLE Model No: --------

Type : AR101X2 Vn: 110VDC

3. General Inspection checks as per check List: OK

4. Pickup Test : Date: 08.02.2012

Circuit Reference SL No

Term. Reference Pick Up(Volts) Drop Off (Volts)

--- HR0710137 A 60.00 12.01

B 68.00 12.00

--- HR0642371 A 60.12 12.91

B 60.16 16.31

--- HR0710138 A 63.16 19.16

B 68.53 17.32

--- HR0642372 A 59.62 16.31

B 58.32 17.52

--- HR0641922 A 71.54 13.21

B 68.51 15.16

5. Remarks : RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 35: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 35 OF 77

TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY

1. Designation: TRIP CIRCUIT SUPERVISION RELAY

Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL

2. Name Plate Details:

Make : EASUN REYROLLE Model : -------

Type : XR351 SI NO: -------

Vx : 110/125 V DC

3. General Inspection checks as per check List: OK

4. Pickup Test : Date: 08.02.2012

Sr.No Terminal Reference Pick Up(Volts) Drop Off (Volts)

BR0701521 A 36.00 10.00

B 36.00 12.00

C 68.00 14.8

BR0701522 A 35.50 11.20

B 46.50 12.00

C 57.20 8.32

5. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 36: 132kv Ss Vestas Test Report

ELSYTEC ENELSYTEC ENELSYTEC ENELSYTEC ENGINEERS AND CONSULTANTS PVT LTD GINEERS AND CONSULTANTS PVT LTD GINEERS AND CONSULTANTS PVT LTD GINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 36 OF 77

TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY

1. Designation: TRIP CIRCUIT SUPERVISION RELAY

Location: 132/33KV,70MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : EASUN REYROLLE Model : -------

Type : XR351 SI NO: -------

Vx : 110/125 V DC

3. General Inspection checks as per check List: OK

4. Pickup Test : Date: 09.02.2012

Sr.No Terminal Reference Pick Up(Volts) Drop Off (Volts)

BR0701524 A 34.51 5.92

B 34.61 6.56

C 55.34 16.16

BR0701523 A 36.04 5.12

B 39.14 9.12

C 65.92 5.96

BR0701518 A 35.12 9.61

B 40.16 5.12

C 68.32 5.19

5. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 37: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 37 OF 77

TEST REPORT FOR AUXILIARY RELAY

1. Designation: FAULT TRIP RELAY

Location: 132/33KV,70MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : ER

Type : B33 X3 Rated Volts : 110V DC

Model : -----

3. General Inspection Check : OK

4. Pick up / Drop Off Check: Date: 09.02.2012

Serial No. : Coil Ref Pickup Volts (V) Drop off Volts (V)

HR0643583 A 39.12 Hand reset

B 36.13 Hand reset

C 42.87 Hand reset

HR0643578 A 44.83 Hand reset

B 37.63 Hand reset

C 36.47 Hand reset

HR0643579 A 36.77 Hand reset

B 47.56 Hand reset

C 36.16 Hand reset

HR0641802 A 31.26 Hand reset

B 42.90 Hand reset

C 37.86 Hand reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: Relay operation found satisfactory.

for ELSYTEC

Page 38: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 38 OF 77

TEST REPORT FOR DISTANCE PROTECTION RELAY

1. Designation: DISTANCE PROTECTION RELAY

Location: 132/33KV,30MVA TRANSFORMER LINE BAY – 1 C & R PANEL

2. Name Plate Details:

Make: ABB Serial No. : 0405004

Type : RAZOA Model : RGZB 030

I : 1.0 A EL : 110 V DC

RL : 110 V DC Un : 50 HZ, 110 V AC

X = (3.2 / In) X (F / 50) X (a / p )

R = (3.2 / In) X (b / p)

3. Mechanical Check And Visual Inspection (Tick If Verified)

Item Description

1 Inspect for physical damage / defects. Yes N/A

2 Verify connections as per approved drawing. Yes N/A

3 Check tightness of all connections. Yes N/A

4. Electrical Tests (Tick If Verified) Date : 10.02.2012

a. Function Test 1. Function Test Item Description

1 Human Machine Interface [ HMI ] checked. Yes N/A

2 Test switch checked for correct function. Yes N/A

3 Case Earthing checked. Yes N/A

4 Indications checked. Yes N/A

5 Alarm contacts checked. Yes N/A

6 Trip contacts checked. Yes N/A

7 Reset of indications checked. Yes N/A

8 Carrier send checked. Yes N/A

9 Carrier receive checked. Yes N/A

11 Blocking inputs checked. Yes N/A

11 Switch onto fault checked. Yes N/A

12 Power swing blocking function checked. Yes N/A

13 Scheme function checked. Yes N/A

14 Week End Infeed Function checked Yes N/A

5. Service Setting :

Zα : 2 x c/In Ins : 1 x 0.2 In F : 15 KN : 8 x 0.1 PS : 5

a : 25 b : 27 P1 : 99 P2 : 67 P3 : 40

T2 : 1 x 100 ms T3 : 2 x 200 ms T4 : 1 x 400 ms for ELSYTEC

Page 39: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 39 OF 77

5. Secondary injection test :

6. Switch On to Fault Function.:

Distance prot. SOTF-On Trip time (msec)

Remarks

Internal SOTF -- Not connected to DLD Function.

External SOTF 50.0 Z1 start and Manual close CMD.

7. Fuse Failure function.

ITEM DESCRIPTION CHECKED 1 Check operation on/off --- 2 Check operation of indication OK 3 Check operation of contacts OK

Test Equipment Details

Make : DOBLE - U.S.A

Type: F6150

8. Impedance Timing test

Fault type ZONE1 ZONE2 ZONE3

A-N

B-N

C-N

A-B Refer Page No.

B-C

C-A

A-B-C

9. Remarks: TEST RESULTS FOUND SATISFACTORY.

for ELSYTEC

Page 40: 132kv Ss Vestas Test Report

F6TesT

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

VESTAS 132kv Location Path

Test Definition 1

Pass Evaluation R.kanagaraj

Auto saved

Tested By

Tested Date

Test Definition Description

Test Definition Name

10.02.2012

Relay Under Test General Parameters

A-B-C Vn

In 2000.000%

RAZOA

1000.00%

300 : 1 CTR

Phase Names And Rotation

Max Test Voltage

Max Test Current

Model

A V (Ph-Ph) Hz

1.000 110.00 50.000

132000 : 110

132KV ,30MVA LINE

0404

In Vn fn

ABB

RAZOA

VTR

Nominal Ratings:

Station Name

Manufacturer

Serial Number

Relay Name

Protected Object Parameters

LINE Protected Object Name

Protected Object Parameters

Relay Functions

Function Type Distance Relay Impedance Function Name

Display values in Inherent Op Time ms 0 Secondary

General Tolerances

ms 20.0 Absolute Minimum Time Absolute Minimum Ohm 0.050

Zone Elements

-% + % -% +%

Zone Name Char Type Fault Type

Z tol t tol t nom [ms]

Residual Compensation Characteristic Angle

Zone3 435 5.00 5.00 5.00 5.00 General 3-Ph 70.00

Zone3 435 5.00 5.00 5.00 5.00 General Ph-Ph 70.00

Zone3 435 5.00 5.00 5.00 5.00 General Ph-N 0.80 0.00 KN 70.00

Zone1 35 5.00 5.00 5.00 5.00 General 3-Ph 70.00

Zone1 35 5.00 5.00 5.00 5.00 General Ph-Ph 70.00

Zone1 35 5.00 5.00 5.00 5.00 General Ph-N 0.80 0.00 KN 70.00

Zone2 135 5.00 5.00 5.00 5.00 General 3-Ph 70.00

Zone2 135 5.00 5.00 5.00 5.00 General Ph-Ph 70.00

Zone2 135 5.00 5.00 5.00 5.00 General Ph-N 0.80 0.00 KN 70.00

Doble Page 1 of 9

Page 41: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

Test Configuration

0.000

110.00

Constant Current

V

A

Test Method

Prefault Voltage

Prefault Current Angle 0 Deg

% of rating Max Acceptable Voltage

Desired Test Current A 2

90

dc transient, fault inception angle

ms 0.00 Time constant L/R

Minimum Offset

CT direction Towards Line

Values are in Secondary

s

s

s

x Tmax

0.7000

1.5000

0.1000

Test Timing Trigger Selection

Prefault Duration

Max. Fault Duration

Max Fault Duration For Faster Zones

Time between shots

Fault Type Trigger

AN

BN

CN

AB

BC

CA

ABC

CBTripTime s 0.0000

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

LN1 0->1

Doble Page 2 of 9

Page 42: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[s] [s] [s] [s]

Err

[Ω] [V] [A] [°] [%]

Fault Type AN

Test Test

0.726 46.12 2.61 2.000 0.0351 0.29 0.0350 0.0150 0.0550 64.70 Zone1 Pass

1.490 41.08 5.36 2.000 0.1344 -0.44 0.1350 0.1150 0.1550 87.10 Zone2 Pass

2.478 43.23 8.92 2.000 0.4331 -0.44 0.4350 0.4133 0.4568 84.80 Zone3 Pass

2.478 43.23 8.92 2.000 NoOp - 0.4350 0.4133 NoOp 97.60 Zone3 Pass

AN Fault Type

Doble Page 3 of 9

Page 43: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[s] [s] [s] [s]

Err

[Ω] [V] [A] [°] [%]

Fault Type BN

Test Test

0.726 46.12 2.61 2.000 0.0352 0.57 0.0350 0.0150 0.0550 64.70 Zone1 Pass

1.490 41.08 5.36 2.000 0.1352 0.15 0.1350 0.1150 0.1550 87.10 Zone2 Pass

2.478 43.23 8.92 2.000 0.4393 0.99 0.4350 0.4133 0.4568 84.80 Zone3 Pass

2.478 43.23 8.92 2.000 NoOp - 0.4350 0.4133 NoOp 97.60 Zone3 Pass

BN Fault Type

Doble Page 4 of 9

Page 44: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[s] [s] [s] [s]

Err

[Ω] [V] [A] [°] [%]

Fault Type CN

Test Test

0.726 46.12 2.61 2.000 0.0348 -0.57 0.0350 0.0150 0.0550 64.70 Zone1 Pass

1.490 41.08 5.36 2.000 0.1355 0.37 0.1350 0.1150 0.1550 87.10 Zone2 Pass

2.478 43.23 8.92 2.000 0.4392 0.97 0.4350 0.4133 0.4568 84.80 Zone3 Pass

2.478 43.23 8.92 2.000 NoOp - 0.4350 0.4133 NoOp 97.60 Zone3 Pass

CN Fault Type

Doble Page 5 of 9

Page 45: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[s] [s] [s] [s]

Err

[Ω] [V] [A] [°] [%]

Fault Type AB

Test Test

0.754 43.93 3.02 2.000 0.0350 0.00 0.0350 0.0150 0.0550 64.70 Zone1 Pass

1.441 45.45 5.76 2.000 0.1339 -0.81 0.1350 0.1150 0.1550 86.00 Zone2 Pass

2.363 44.57 9.45 2.000 0.4394 1.01 0.4350 0.4133 0.4568 82.90 Zone3 Pass

AB Fault Type

Doble Page 6 of 9

Page 46: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[s] [s] [s] [s]

Err

[Ω] [V] [A] [°] [%]

Fault Type BC

Test Test

0.754 43.93 3.02 2.000 0.0351 0.29 0.0350 0.0150 0.0550 64.70 Zone1 Pass

1.441 45.45 5.76 2.000 0.1337 -0.96 0.1350 0.1150 0.1550 86.00 Zone2 Pass

2.363 44.57 9.45 2.000 0.4357 0.16 0.4350 0.4133 0.4568 82.90 Zone3 Pass

BC Fault Type

Doble Page 7 of 9

Page 47: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[s] [s] [s] [s]

Err

[Ω] [V] [A] [°] [%]

Fault Type CA

Test Test

0.754 43.93 3.02 2.000 0.0347 -0.86 0.0350 0.0150 0.0550 64.70 Zone1 Pass

1.441 45.45 5.76 2.000 0.1339 -0.81 0.1350 0.1150 0.1550 86.00 Zone2 Pass

2.363 44.57 9.45 2.000 0.4377 0.62 0.4350 0.4133 0.4568 82.90 Zone3 Pass

CA Fault Type

Doble Page 8 of 9

Page 48: 132kv Ss Vestas Test Report

Impedance Relay Timing Test Report 10-Feb-12

VESTAS 132kv/RAZOA

V

Z t exp t max t min t act Eval I

Angle %Zone Zone

[s] [s] [s] [s]

Err

[Ω] [V] [A] [°] [%]

Fault Type ABC

Test Test

0.888 43.40 1.78 2.000 0.0348 -0.57 0.0350 0.0150 0.0550 75.50 Zone1 Pass

1.507 43.49 3.01 2.000 0.1338 -0.89 0.1350 0.1150 0.1550 86.80 Zone2 Pass

2.316 42.67 4.63 2.000 0.4333 -0.39 0.4350 0.4133 0.4568 78.80 Zone3 Pass

2.997 51.24 5.99 2.000 NoOp - NoOp NoOp NoOp 0.00 Pass

ABC Fault Type

Doble Page 9 of 9

Page 49: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 49 OF 77

TEST REPORT FOR DIFFERENTIAL RELAY

1. Designation: DIFFERENTIAL RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make ABB Model No. : ------

Type SPAD 346 C Serial No. : 465369

In (A) : 1.0 Aux. Volts : 48 - 250 V DC

MVA : 30.0

3. General Inspection : OK

4. Secondary Injection Test: Date : 10.02.2012

a) Differential Current Check : (Pickup Test) : (HV Side) :

Phase Ref Set current (A) Calculated current (A) Op.current (A)

R 0.2 0.2 x 1.00 = 0.20 0.201

Y 0.2 0.2 x 1.00 = 0.20 0.201

B 0.2 0.2 x 1.00 = 0.20 0.201 b) LV Side :

Phase Ref Set current (A) Calculated current (A) Op.current (A)

R 0.2 0.2 x 1.00 = 0.20 0.201

Y 0.2 0.2 x 1.00 = 0.20 0.201

B 0.2 0.2 x 1.00 = 0.20 0.201

c) Differential Current Check : (High Pickup Test) : (HV Side) :

Phase Ref Set current (A) Calculated current (A) Op.current (A)

R 5.0 5.0 x 1.00 = 5.00 5.01

Y 5.0 5.0 x 1.00 = 5.00 5.01

B 5.0 5.0 x 1.00 = 5.00 5.01

for ELSYTEC

Page 50: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 50 OF 77

d) LV Side :

Phase Ref Set current (A) Calculated current (A) Op.current (A)

R 5.0 5.0 x 1.00 = 5.00 5.01

Y 5.0 5.0 x 1.00 = 5.00 5.01

B 5.0 5.0 x 1.00 = 5.00 5.01

(e) Stability test : (at 100% load)

Phase App. HV Side Current (A)

App. LV Side Current (A)

Diff.Op.Relay Current (A)

Bias Current (A)

Diff.Relay

R 1.02 ∟0° 0.769 ∟180° 0.00 0.99 Not Operated

Y 1.02 ∟-120° 0.768 ∟60° 0.00 0.99 Not Operated

B 1.02 ∟120° 0.768 ∟300° 0.00 0.99 Not Operated

(f)2nd Inrush Inhibit Set;

Phase ref Set. Current

(A) App. current

(A) App. current

Freq(Hz) Meg.Inrush Current (A)

Diff.Op.Relay Current (A)

Diff.Relay

R 0.2 0.30 100.0 0.30 - Not Operated Y 0.2 0.30 100.0 0.30 - Not Operated B 0.2 0.30 100.0 0.30 - Not Operated

(g) Bias (or) Slope Test :

Phase Set. Bias Set. Diff Op. Bias Op. Diff

R Y Refer Doble Test Report B

(h) Protection 51/51N : Inv – IEC NI Phase Ref.

Set. Current (A) Time Mult Operating Time (Sec) at multiples of Set.

Current X 2 X 5 X 10

R 0.9 0.1 1.02 0.42 0.31

Y 0.9 0.1 1.02 0.42 0.31

B 0.9 0.1 1.02 0.42 0.31

N 0.2 0.1 1.01 0.48 0.31

(f) Protection 50/50N :

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 3.5 3.51 0.2 0.21

Y 3.5 3.51 0.2 0.21

B 3.5 3.51 0.2 0.21

N 1.4 1.41 0.2 0.21

for ELSYTEC

Page 51: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 51 OF 77

(g) Protection I>>> :

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 9.0 9.01 0.04 0.04

Y 9.0 9.01 0.04 0.04

B 9.0 9.01 0.04 0.04

(h) HV REF – Earth current:

Phase ref Set. current (A)

Pickup. current for ST HV side(A)

Phase ref

Set. current (A)

Operating current (A)

Operating REF

R 0.1 - Y 0.1 - N,CT 0.1 0.11 OK B 0.1 -

(i) LV REF – Earth current:

Phase ref Set. current (A)

Pickup. current for ST HV side(A)

Phase ref

Set. current (A)

Operating current (A)

Operating REF

R 0.1 - Y 0.1 - N,CT 0.1 0.11 OK B 0.1 -

5. Service Setting : SPCD3D Diff. Setting : P/% : 20 % Bias Setting : S/% : 20 % I2tp / In : 1.0 Id / In >> : 5.0 Id2f / Id1f > (%) : 20 Id5f / Id1f > (%) : 15 Id5f / Id1f >> (%) : 15 I1 / In : 1.00 I2 / In : 1.00

SPCD 2D P1% : 10 P2% : 10 Io1 : 1.0 Io2 ; 1.0 I2f / Id Io1f > (%) : 30 I2f / Id Io2f > (%) : 30 I1 : 1.00 I2 : 1.00

SPCD 4D I> ; 0.9 K :0.1 I>> : 3.5 t>> 0.2 I>>> : 9.0 t>>> : 0.04 Io> : 0.2 K : 0.1 Io>> :1.4 tIo>> :0.2

SGF :

1 2 3 4 5 6 7 8 9

15 7 84 0 15 3 4 0 0

SGB :

1 2 3 4 5 6 7 8

0 0 0 0 0 0 0 0

SGR :

1 2 3 4 5 6 7 8 9

136 136 0 0 0 0 0 0 0

6. Functional Checks:

a. Correct operation of appropriate indicator/relay: OK

b. Correct initiation of alarm contacts: OK

c. Correct circuit breaker tripping Contacts: OK

7.Remarks RELAY OPERATION FOUND SATISFACTORY.

for ELSYTEC

Page 52: 132kv Ss Vestas Test Report

F6TesT

Differential Relay Test Report 10-Feb-12

VESTAS 132kv/SPAD346C

VESTAS 132kv Location Path

Test Definition 1

Pass Evaluation R.kanagaraj

Auto saved

Tested By

Tested Date

Test Definition Description

Test Definition Name

2/10/2012

Relay Under Test General Parameters

A-B-C Vn

In 1500.000%

SPAD346C

181.81%

150 : 1 CTR

Phase Names And Rotation

Max Test Voltage

Max Test Current

Model

A V (Ph-Ph) Hz

1.000

110.00 50.000

132000 : 110

-ADDRESS n/a

465369

In Vn fn

ABB

SPAD346C

VTR

Nominal Ratings:

Station Name

Manufacturer

Serial Number

Relay Name

Protected Object Parameters

Protected Object Name

Protected Object Parameters

Relay Functions

Function Type SPAD346C-TR1 Differential Function Name

General Tolerances

ms 0.0 Absolute Minimum Time Absolute Minimum A 0.000

Pickup Setting

Time Tolerance

Current Tolerance

Const B

Const A

Bias Equation Nominal Time

+% -% +% -%

Const C

Characteristic Name

x tap

50.00 (a*Ip-b*Is)/c 1.00 1.00 2.00 0.20

30.00

30.00

30.00

30.00

50.00 (a*Ip-b*Is)/c 1.00 1.00 2.00 5.00

F6000 Instrument HW and SW Information

F6TesT Software Version 2.21 Build 1165

F6000 Model Number F6150

Serial Number 67191328

F6000 Firmware Version 4.28.2

F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface

F6910 : Simulator control and automation interface

F6825 : CPU2 F6875 : Variable Battery Simulator

F6844 : Logic I/O 4 board

Doble Page 1 of 4

Page 53: 132kv Ss Vestas Test Report

Differential Relay Test Report 10-Feb-12

VESTAS 132kv/SPAD346C

F6000 Instrument HW and SW Information

F6TesT Software Version 2.21 Build 1165

F6000 Model Number F6150

Serial Number 67191328

F6000 Firmware Version 4.28.2

F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface

F6910 : Simulator control and automation interface

F6825 : CPU2 F6875 : Variable Battery Simulator

F6844 : Logic I/O 4 board

Test Configuration

Angle of Ip = 0 deg; Angle of Is = 180 deg or 0 degFind | Ip | , | Is |, and Angle of Is for desired values of Ibias and Idiff

Test Method

6.000

Secondary Values are in

A 0.000 Prefault load current A Max test current

s

s

s

0.6000

0.4000

0.6000

Test Timing

Prefault Duration

Max. Fault Duration

Time between shots

Trigger Selection

Fault Type Trigger

A

B

C s

CBTripTime 0.0000

LN1 0->1

LN1 0->1

LN1 0->1

Doble Page 2 of 4

Page 54: 132kv Ss Vestas Test Report

Differential Relay Test Report 10-Feb-12

VESTAS 132kv/SPAD346C

Fault Name Phase : A

Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval

0.198 -1.000 Pass 0.148 0.200 0.140 0.260

0.194 -3.000 Pass 0.438 0.200 0.140 0.260

0.234 3.084 Pass 0.736 0.227 0.159 0.295

0.272 1.115 Pass 0.946 0.269 0.188 0.350

Fault Name Phase : A

Fault Name Phase : B

Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval

0.198 -1.000 Pass 0.148 0.200 0.140 0.260

0.198 -1.000 Pass 0.438 0.200 0.140 0.260

0.246 8.370 Pass 0.736 0.227 0.159 0.295

0.287 6.691 Pass 0.946 0.269 0.188 0.350

Fault Name Phase : B

Fault Name Phase : C

Doble Page 3 of 4

Page 55: 132kv Ss Vestas Test Report

Differential Relay Test Report 10-Feb-12

VESTAS 132kv/SPAD346C

Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval

0.198 -1.000 Pass 0.148 0.200 0.140 0.260

0.198 -1.000 Pass 0.438 0.200 0.140 0.260

0.246 8.370 Pass 0.736 0.227 0.159 0.295

0.287 6.691 Pass 0.946 0.269 0.188 0.350

Fault Name Phase : C

Doble Page 4 of 4

Page 56: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 56 OF 77

TEST REPORT FOR UNDER VOLTAGE RELAY

1. Designation: UNDER VOLTAGE RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL

2. Name Plate Details:

Make : JVS Aux. Volts : 75 – 150 V DC / AC

Type. : JRV 022 Serial No. : V 35422

Rated Voltage : 110 V AC

Time Setting : 0 – 25 Sec

Voltage Setting : 30 – 90 %

3. General Inspection and Pre-Commissioning Checks as per Check List: OK

4. Pick up / Drop Out Test: Date: 10.02.2012

Setting Voltage (V) Operating Voltage (V) Set. Time (Sec) Op. Time (Sec)

60 % Vn 65.92 10.0 10.02

80 % Vn 89.1 10.0 10.12

5.Functional Checks :

a) Operation of appropriate indicator/Aux relay : OK

b) Correct operation of Alarm/Trip Contact : OK

6.Service Setting: Tip.swt.Set : 60% Time. Set : 10.0 sec

7.Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 57: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 57 OF 77

TEST REPORT FOR AUXILIARY RELAY

1. Designation: TRIP CIRCUIT SUPERVISION RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL

2. Name Plate Details:

Make : JVS

Type : JRV 111 Rated Volts : 110 V DC

Model : JRV 111 00F

3. General Inspection : OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Serial No. Pick Up Volts (V) Drop Off Volts (V)

V 35112 33.91 12.15

V 35110 40.62 19.12

V 36109 41.32 18.61

V 35078 46.36 19.39

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

c. Correct initiation of scheme function: OK

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 58: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 58 OF 77

TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY

1. Designation: OVER CURRENT AND EARTH FAULT RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL

2. Name Plate Details:

Make: JVS Serial No. : C 35418

Type : JRC CT Sec. Current (A) : 1.0

Model : JRC 053 17P Aux. Voltage : 75 – 150 V DC

Available Setting O/C E/F

PS (A) (50 – 200) % (5 – 80) %

TMS 0 – 1.0 0 – 1.0

Operating time(Sec) at PS X 10 with TMS 1.0: 3.0

3. General Inspection : OK

4. Secondary Injection Test: Date: 10.02.2012

Phase / Unit PS (A) TMS Operating Time (Sec) at multiples of PS

2 5 10

R 1.0 0.12 1.21 0.49 0.37

1.0 9.98 4.28 2.98

B 1.0 0.12 1.21 0.49 0.37

1.0 9.93 4.26 2.98

for ELSYTEC

Page 59: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 59 OF 77

Phase / Unit PS (A) TMS Operating Time (Sec) at multiples of PS

2 5 10

E/F 0.2 0.12 1.21 0.49 0.37

1.0 10.01 4.30 3.06

5. Functional Checks

a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK

b) Correct Initiation Of Alarm Contacts: OK

c) Correct Circuit Breaker Tripping Contacts: OK

6. Service Setting:

O/C (R) E/F O/C (B)

PS (A) : 100 % 20 % 100 %

TMS : 0.12 0.12 0.12

7. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 60: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 60 OF 77

TEST REPORT FOR FUSE FAILURE RELAY

1. Designation: FUSE FAILURE RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL

2. Name Plate Details:

Make : ABB Serial No. : J040014

Type : FFR Rated Volts : 110 V AC

Model : 1MYN563005-B Fn : 50 Hz

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Phase Ref. Pick Up Volts (V) Drop Off Volts (V)

R 31.16 16.12

Y 35.21 12.31

B 36.91 16.17

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

c. Correct initiation of scheme function: -

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 61: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 61 OF 77

TEST REPORT FOR TRIPPING RELAY

1. Designation: TRIPPING RELAY

2. Name Plate Details:

Make : ABB Model : -----

Type : PC8QW2J Aux. Volts : 110 V DC

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Location Serial No. Pick Up Volts (V) Drop Off Volts (V)

132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL

M04 – 0148 43.12 Hand Reset

132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL

M04 – 0146 36.32 Hand Reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

For ELSYTEC

Page 62: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 62 OF 77

TEST REPORT FOR AUXILIARY RELAY

1. Designation: AUXILIARY RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL

2. Name Plate Details:

Make : ALSTOM Serial No : 1305 3639 0409 001

Model No: VAA 11 YF 8402 FCH Type: VAA 11

LH volts: 110 / 125 V DC RH volts: -

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Pick Up (volts) Drop Off (volts)

63.91 13.92

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 63: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 63 OF 77

TEST REPORT FOR TRIPPING RELAY

1. Designation: TRIPPING RELAY.

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL

2. Name Plate Details:

Make : AREVA Serial No : 130520410404001

Type : VAJH 23 Model No : VAJH 23 ZG22D

Operating Volt: 110V DC Reset Volt: -

3. General Inspection : OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Coil ref: Pick up volts Drop Off (volts)

A 39.16 HAND RESET

B 42.72 HAND RESET

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

c. Correct initiation of scheme function: -

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 64: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 64 OF 77

TEST REPORT FOR AUXILIARY RELAY

1. Designation: AUXILIARY RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL

2. Name Plate Details:

Make : ALSTOM Serial No : 1305 20340404001

Model No: VAJHM 13 ZG11D Type: VAJH 13

LH volts: 110 / 125 V DC RH volts: -

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Pick Up (volts) Drop Off (volts)

39.40 HAND RESET

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 65: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 65 OF 77

TEST REPORT FOR BUSBAR SUPERVISION RELAY

1. Designation: BUSBAR SUPERVISION RELAY.

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL

2. Name Plate Details:

Make : ALSTOM Serial No: 1304 354 5032 6001

Type : VTX 31 Model No: VTX 31 AF 8002 ACH

Aux.volts: 110 V DC Frequency: 50 Hz

Time delay : 3 Sec (Use with Ext.Res)

Available setting : (2-14) volts(operating volts)

3. General Inspection : OK

4. Secondary Injection Test : Date: 10.02.2012

Setting voltage (volts) Operating voltage (volts) Operating Time (Sec)

6.0 6.01 3.02

10.0 9.99 3.01

14.0 13.98 3.01

5. Service setting :

Operating volts: 10 V

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 66: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 66 OF 77

TEST REPORT FOR DIFFERENTIAL RELAY

1. Designation: DIFFERENTIAL RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL

2. Name Plate Details:

Make : ALSTOM Serial No. : 200001620410001

Type : CAG 34 CT Sec : 1 A

Model : CAG 34 AF 59A f : 50 HZ

Available setting : 0.2 – 0.8 A

3. General Inspection Checks as per Check List: OK

4. Secondary Injection Test : Date: 10.02.2012

Phase Ref Set Current (A) Op. Current (A)

R 0.5 0.520

Y 0.5 0.520

B 0.5 0.520

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6.Service Setting :

PS( A) : 0.5

7. Remarks: Relay operation found satisfactory.

For ELSYTEC

Page 67: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONELSYTEC ENGINEERS AND CONELSYTEC ENGINEERS AND CONELSYTEC ENGINEERS AND CONSULTANTS PVT LTD SULTANTS PVT LTD SULTANTS PVT LTD SULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 67 OF 77

TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY

1. Designation: TRIP CIRCUIT SUPERVISION RELAY

2. Name Plate Details:

Make : ABB Model : 1MYN740601-DBG

Type : VIRI-2JA Aux. Volts : 110 V DC

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 11.02.2012

Location Serial No. Pick Up Volts (V) Drop Off Volts (V)

132 / 33 KV , 30MVA TRANSFORMER C & R PANEL

V03 - 3645 Post Close : 46.82 12.21

Pre Close :39.54 12.34

132 / 33 KV , 30MVA TRANSFORMER C & R PANEL

V03 - 3644 Post Close : 49.14 14.23

Pre Close : 39.93 12.32

132 / 33 KV , 30MVA TRANSFORMER C & R PANEL

V03 - 3641 Post Close : 45.29 13.21

Pre Close : 40.37 15.23

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 68: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 68 OF 77

TEST REPORT FOR AUX .TRIPPING RELAY

1. Designation: AUX.TRIPPING RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : ABB Model : -----

Type : ---- Aux. Volts : 110 V DC

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Cir.Ref Serial No. Pick Up Volts (V) Drop Off Volts (V)

BUCH Alarm -- 38.9 Hand Reset

BUCH Trip -- 37.6 Hand Reset

WDG Alarm -- 38.4 Hand Reset

WDG Trip -- 39.1 Hand Reset

OTI Alarm -- 36.8 Hand Reset

OTI Trip -- 38.1 Hand Reset

MOG Alarm -- 37.5 Hand Reset

OSR Trip -- 39.4 Hand Reset

PRD Trip -- 35.6 Hand Reset

OLTC PRD Trip -- 36.1 Hand Reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

For ELSYTEC

Page 69: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 69 OF 77

TEST REPORT FOR DC SUPERVISION RELAY

1. Designation: DC SUPERVISION RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL

2. Name Plate Details:

Make : ABB Serial No : M 030303

Model No: ------ Type: PNBnCH2J

LH volts: 110 V DC RH volts: -

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Pick Up (volts) Drop Off (volts)

46.82 Hand Reset

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 70: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 70 OF 77

TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY

1. Designation: OVER CURRENT AND EARTH FAULT RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL - 132KV SIDE

2. Name Plate Details:

Make ABB Serial No. M 03 – 6282

Type SPAJ 140C In : 1.0 A

Model 1MYN 742751A Aux. Voltage (V) 110 V DC

Available & Service Setting: Relay setting Setting range Service setting

Definite Time Low Set Over Current : 0.5 …. 5.0 x In I> - In

Definite Time characteristic : 0.05 – 300 Sec t> -

Inverse Time Low set Over Current : 0.5 ….. 2.5 x In I> 0.9 In

Time Multiplier : 0.05 …. 1.0 K 0.1

Characteristics : EI / VI / NI / LTI / RI / RXIDG NI

High set Over Current : 0.5 ….. 40 x In (or) ∝ I>> 3.5 In

Operating Time : 0.04 …. 300 Sec t>> 0.2

Definite Time Low Set Earth Fault : 0.1….0.8 x In Io> -

Definite Time characteristic : 0.05 – 300 Sec to> -

Inverse Time Low set Earth Fault : 0.1….0.8 x In Io> 0.2 In

Time Multiplier : 0.05 …. 1.0 K 0.1

Characteristics : EI / VI / NI / LTI / RI / RXIDG NI

High set Earth Fault : 0.1 ….. 10 x In (or) ∝ Io>> 1.4 In

Operating Time : 0.05 …. 300 Sec to>> 0.2

Switch Group Function : SGF 099

Switch Group Blocking : SGB 000

Switch Group Register : SGR 170

Operating time(Sec)PS X 10 with TMS 1.0: 3.0

3. General Inspection: OK

for ELSYTEC

Page 71: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS ELSYTEC ENGINEERS AND CONSULTANTS ELSYTEC ENGINEERS AND CONSULTANTS ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD PVT LTD PVT LTD PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 71 OF 77

4. Secondary Injection Test: Date: 10.02.2012

a) Low Set O/C Unit: I>

Char Curve : NI

Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current

(A) X 2 X 5 X 10

R 0.9 0.1 1.02 0.48 0.32

Y 0.9 0.1 1.02 0.48 0.32

B 0.9 0.1 1.02 0.48 0.32

b) Low set E/F unit : Io>

Char Curve : NI

Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current

(A) X 2 X 5 X 10

E/F 0.2 0.1 1.02 0.48 0.32

c) High Set O/C Unit: I>>

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 3.5 3.52 0.2 0.21

Y 3.5 3.52 0.2 0.21

B 3.5 3.52 0.2 0.21

d) High set E/F Unit: Io>>

Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

1.4 1.41 0.2 0.21

5. Functional Checks

a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK

b) Correct Initiation Of Alarm Contacts: OK

c) Correct Circuit Breaker Tripping Contacts: OK

6. Remarks : RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 72: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 72 OF 77

TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY

1. Designation: OVER CURRENT AND EARTH FAULT RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL - 33KV SIDE

2. Name Plate Details:

Make ABB Serial No. M 03 – 6280

Type SPAJ 140C In : 1.0 A

Model 1MYN 742751A Aux. Voltage (V) 110 V DC

Available & Service Setting: Relay setting Setting range Service setting

Definite Time Low Set Over Current : 0.5 …. 5.0 x In I> - In

Definite Time characteristic : 0.05 – 300 Sec t> -

Inverse Time Low set Over Current : 0.5 ….. 2.5 x In I> 0.9 In

Time Multiplier : 0.05 …. 1.0 K 0.08

Characteristics : EI / VI / NI / LTI / RI / RXIDG NI

High set Over Current : 0.5 ….. 40 x In (or) ∝ I>> 3.00 In

Operating Time : 0.04 …. 300 Sec t>> 0.2

Definite Time Low Set Earth Fault : 0.1….0.8 x In Io> -

Definite Time characteristic : 0.05 – 300 Sec to> -

Inverse Time Low set Earth Fault : 0.1….0.8 x In Io> 0.2 In

Time Multiplier : 0.05 …. 1.0 K 0.08

Characteristics : EI / VI / NI / LTI / RI / RXIDG NI

High set Earth Fault : 0.1 ….. 10 x In (or) ∝ Io>> 1.20 In

Operating Time : 0.05 …. 300 Sec to>> 0.2

Switch Group Function : SGF 099

Switch Group Blocking : SGB 000

Switch Group Register : SGR 170

Operating time(Sec)PS X 10 with TMS 1.0: 3.0

3. General Inspection: OK

for ELSYTEC

Page 73: 132kv Ss Vestas Test Report

ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 73 OF 77

4. Secondary Injection Test: Date: 10.02.2012

a) Low Set O/C Unit: I>

Char Curve : NI

Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current

(A) X 2 X 5 X 10

R 0.9 0.08 0.82 0.40 0.26

Y 0.9 0.08 0.82 0.40 0.26

B 0.9 0.08 0.82 0.40 0.26

b) Low set E/F unit : Io>

Char Curve : NI

Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current

(A) X 2 X 5 X 10

E/F 0.2 0.08 0.82 0.42 0.26

c) High Set O/C Unit: I>>

Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

R 3.0 3.01 0.2 0.21

Y 3.0 3.01 0.2 0.21

B 3.0 3.01 0.2 0.21

d) High set E/F Unit: Io>>

Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)

1.20 1.19 0.2 0.21

5. Functional Checks

a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK

b) Correct Initiation Of Alarm Contacts: OK

c) Correct Circuit Breaker Tripping Contacts: OK

6. Remarks : RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 74: 132kv Ss Vestas Test Report

ELELELELSYTEC ENGINEERS AND CONSULTANTS PVT LTD SYTEC ENGINEERS AND CONSULTANTS PVT LTD SYTEC ENGINEERS AND CONSULTANTS PVT LTD SYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence

CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11

PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 74 OF 77

TEST REPORT FOR POWER SWING RELAY

1. Designation: POWER SWING RELAY

Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL

2. Name Plate Details:

Make : ABB Serial No : P 030024

Model No: IMYN742007 - E Type: RXZD 4

Aux volts: 110 / 125 V DC EL volts: 24.0VDC

3. General Inspection Checks as per Check List: OK

4. Pick up / Drop Off Check: Date: 10.02.2012

Pick Up (Z) Drop Off (Z)

Refer Doble Test Report

5. Functional Checks:

a. Correct Operation of Contacts: OK

b. Correct operation of appropriate indicator / flag: OK

6. Service Setting : Zo = d.q / Is , Is – 1.0A , d – 2.0 , q - 1.0

7. Remarks: RELAY OPERATION FOUND SATISFACTORY

for ELSYTEC

Page 75: 132kv Ss Vestas Test Report

F6TesT

Wavesim Test Report 10-Feb-12

VESTAS 132kv/RXZD 4

VESTAS 132kv Location Path

Test Definition 1

NoOp Evaluation R.kanagaraj

Auto saved Auto saved Auto saved Auto saved

Tested By

Tested Date

Test Definition Description

Test Definition Name

02/10/2012

Relay Under Test General Parameters

A-B-C Vn

In 2000.000%

RXZD 4

1000.00%

300 : 1 CTR

Phase Names And Rotation

Max Test Voltage

Max Test Current

Model

A V (Ph-Ph) Hz

1.000

110.00 50.000

132000 : 110

132KV ,30MVA LINE

P030024

In Vn fn

ABB

RXZD 4

VTR

Nominal Ratings:

Station Name

Manufacturer

Serial Number

Relay Name

Protected Object Parameters

LINE Protected Object Name

Protected Object Parameters

-%

KN Theta

+ % -% +%

Zone Name Char Type Fault Type Zone Tested Impedance Tolerance

Time Tolerance

Nominal Time

StartUni 0 10.00 10.00 10.00 10.00General Ph-N Yes 1.00 0.00

Doble Page 1 of 3

Page 76: 132kv Ss Vestas Test Report

Wavesim Test Report 10-Feb-12

VESTAS 132kv/RAZOA

Test Method: User-specified load, faults, dz/dt, Zs

Protected Line

Pos.sequence

Zero sequence

KL magnitude

Angle, deg

° KL angle 1.000 0.00

Prefault Voltage 69.00

Z [Ω] R [Ω] X [Ω]

V

1.000 70.00 0.940 0.342

70.004.000 3.759 1.368

1 Number of Test Repetitions

[s] /s]

Ks Zs Zp

[Ω [°] [°] [°] [Ω] [Ω] [Ω] [Ω] [Ω]

Simulation Points Zp Remarks Ks Zs Duration

dz/dt Xp Rp

Type Direction

1.000 70.00 1.00

0.00 Initial load Load Forward þ 117.51

46.62 80.721 85.409 0 0.5000

1.000 70.00 1.00

0.00Load Forward þ 51.675 54.14 30.270 41.881

1.000 70.00 1.00

0.00Load Forward þ 110.17

74.44 29.550 106.13

1.000 70.00 1.00

0.00Load Forward þ 95.830 -14.03 -

23.226

1.000 70.00 1.00

0.00Load Forward þ 98.574 1.05 98.557 1.808

1.000 70.00 1.00

0.00Load Forward þ 102.92

6.70 - -

0.587 0.5000 A Maximum test current Simulation duration s

t exp Eval Error t actual +t tol -t tol Test No. TimeNo. Timer Name [%] [s] [s] [s] [s]

Trigger

1 1 Timer NoOp

LN1

Doble Page 2 of 3

Page 77: 132kv Ss Vestas Test Report

Wavesim Test Report 10-Feb-12

VESTAS 132kv/RAZOA

Oscillograph

Doble Page 3 of 3