ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 1 OF 77
TEST REPORT FOR LINE DISTANCE PROTECTION RELAY
1. Designation: LINE DISTANCE PROTECTION RELAY
Location: 132/33KV , 70MVA TRANSFORMER / LINE BAY - 2C & R PANEL
2. Name Plate Details :
Manufacturer :Schweitzer Engineering Laboratories,Inc. Rated Current : 300/1.0 A
Type No. : SEL 311C Rated Voltage : 132000/110 VAC Serial No. : 2007039129 Rated Freq. : 50/60 Hz Model No. : SEL 311C Aux. Voltage : 110 VDC
3. Mechanical Check And Visual Inspection (Tick If Verified)
Item Description
1 Inspect for physical damage / defects. Yes N/A
2 Verify connections as per approved drawing. Yes N/A
3 Check tightness of all connections. Yes N/A
4. Electrical Tests (Tick If Verified) Date : 08.02.2012
1. Function Test 1. Function Test
Item Description
1 Human Machine Interface [ HMI ] checked. Yes N/A
2 Test switch checked for correct function. Yes N/A
3 Case earthing checked. Yes N/A
4 Indications checked. Yes N/A
5 Alarm contacts checked. Yes N/A
6 Trip contacts checked. Yes N/A
7 Reset of indications checked. Yes N/A
8 Carrier send checked. Yes N/A
9 Carrier receive checked. Yes N/A
11 Blocking inputs checked. Yes N/A
11 Switch onto fault checked. Yes N/A
12 Power swing blocking function checked. Yes N/A
13 Scheme function checked. Yes N/A
14 Week End Infeed Function checked Yes N/A
for ELSYTEC
2
ELSYTEC ENGINEERS AND COELSYTEC ENGINEERS AND COELSYTEC ENGINEERS AND COELSYTEC ENGINEERS AND CONSULTANTS PVT LTD NSULTANTS PVT LTD NSULTANTS PVT LTD NSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 2 OF 77
5. Secondary injection test : 6. Switch On to Fault Function.:
Energize the manual close Binary Input through a switch and simultaneously apply 3 phase current above setting
Amps but without 3phase voltage. The protection should Trip instantaneously. Measured Time : 0.036 msecs 7. Fuse Failure function.
Un =49.0 V
Settings Measured Values
Phase
3Uo> 3Io< 3Uo> 3Io< L12 50% - 47.81 V - 1. Apply 3 phase voltage to the relay and then remove 1ph voltage and the timer will start simultaneously “ Fuse Failure Alarm” Appeared in : sec Alarm” Appeared in :-1.00 sec 2. Apply Zone -1 1ph fault within “1 sec” of fuse failure status. Protection tripped in :0.035……. msec. 3. Apply Zone-1 1ph fault after 1sec of fuse failure status. Protection should blocked. ITEM DESCRIPTION CHECKED 1 Check operation on/off OK 2 Check operation of indication OK 3 Check operation of contacts OK 9.Powerswing test: PSB blocking function checked :OK
Test Equipment Details
Make : Doble Engineering Company U.S.A
3Ph = 0 – 15A
Type: F 6150
3Ph = 0 – 260V
8. Fault Locator : 100% - Z = 2. 34 Ω ∟67.25 for 22Km Fault type App. Imp(%&Z) Cal. Display Km Trip Display Km
A-N 45% 9.90 9.75 A-N 90% 19.80 19.46 A-N 100% 22.00 21.70 A-N -100% (Rev) - 2.20 - 2.25 A-B 45% 9.90 10.04 A-B 90% 19.80 20.06 A-B 100% 22.00 22.09 A-B -100% (Rev) - 2.20 - 2.25 9. Timing test : Fault type Zone 1(F) Zone 2(F) Zone 3 (R)
Ph-N Ph-Ph Refer Doble Test Report 3 Ph 10.Srvice Setting: File Attached Refer Page No : 11.Remarks:Relay operation found satisfactory
for ELSYTEC
3
F6TesT
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
VESTAS 132kv Location Path
Test Definition 1
Pass Evaluation R.kanagaraj
Auto saved
Tested By
Tested Date
Test Definition Description
Test Definition Name
2/8/2012
Relay Under Test General Parameters
A-B-C Vn
In 2000.000%
SEL311C
1000.00%
300 : 1 CTR
Phase Names And Rotation
Max Test Voltage
Max Test Current
Model
A V (Ph-Ph) Hz
1.000 110.00 50.000
132000 : 110
132KV line-2
In Vn fn
SEL
SEL311c
VTR
Nominal Ratings:
Station Name
Manufacturer
Serial Number
Relay Name
Protected Object Parameters
LINE Protected Object Name
Protected Object Parameters relay Setting
Relay Functions
Function Type ZONE Impedance Function Name
Display values in Inherent Op Time ms 20.0 Secondary
General Tolerances
ms 20.0 Absolute Minimum Time Absolute Minimum Ohm 0.010
Zone Elements
-% + % -% +%
Zone Name Char Type Fault Type
Z tol t tol t nom [ms]
Residual Compensation Characteristic Angle
Zone_1 0 10.00 10.00 10.00
10.00
General 3-Ph 67.25
Zone_1 0 10.00 10.00 10.00
10.00
General Ph-Ph 67.25
Zone_1 0 10.00 10.00 10.00
10.00
General Ph-N 0.75 -7.86 KN 67.25
Zone_2 300 10.00 10.00 10.00
10.00
General 3-Ph 67.25
Zone_2 300 10.00 10.00 10.00
10.00
General Ph-Ph 67.25
Zone_2 300 10.00 10.00 10.00
10.00
General Ph-N 0.75 -7.86 KN 67.25
Zone_3 300 10.00 10.00 10.00
10.00
General 3-Ph 67.25
Zone_3 300 10.00 10.00 10.00
10.00
General Ph-Ph 67.25
Zone_3 300 10.00 10.00 10.00
10.00
General Ph-N 0.75 -7.86 KN 67.25
Doble Page 1 of 9
4
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
F6000 Instrument HW and SW Information
F6TesT Software Version 2.21 Build 1165
F6000 Model Number F6150
Serial Number 67191328
F6000 Firmware Version 4.28.2
F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6825 : CPU2 F6875 : Variable Battery Simulator
F6844 : Logic I/O 4 board
Test Configuration
0.000
110.00
Constant Current
V
A
Test Method
Prefault Voltage
Prefault Current Angle 0 Deg
% of rating Max Acceptable Voltage
Desired Test Current A 2
90
dc transient, fault inception angle
ms 0.00 Time constant L/R
Minimum Offset
CT direction Towards Line
Values are in Secondary
cy
cy
cy
x Tmax
35.000
75.000
5.000
Test Timing Trigger Selection
Prefault Duration
Max. Fault Duration
Max Fault Duration For Faster Zones
Time between shots
Fault Type Trigger
AN
BN
CN
AB
BC
CA
ABC
CBTripTime cy 0.000
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
Doble Page 2 of 9
5
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[cy] [cy] [cy] [cy]
Err
[Ω] [V] [A] [°] [%]
Fault Type AN
Test Test
2.032 66.13 7.11 2.000 1.795 79.50 1.000 0.000 21.675 92.40 Zone_1 Pass
2.303 66.62 8.06 2.000 16.805 5.03 16.000 14.400 NoOp 94.00 Zone_2 Pass
2.641 66.39 9.24 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass
0.112 250.10 0.39 2.000 16.835 5.22 16.000 14.400 17.600 44.70 Zone_3 Pass
AN Fault Type
Doble Page 3 of 9
6
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[cy] [cy] [cy] [cy]
Err
[Ω] [V] [A] [°] [%]
Fault Type BN
Test Test
2.032 66.13 7.11 2.000 1.870 87.00 1.000 0.000 21.675 92.40 Zone_1 Pass
2.303 66.62 8.06 2.000 16.875 5.47 16.000 14.400 NoOp 94.00 Zone_2 Pass
2.641 66.39 9.24 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass
0.112 250.10 0.39 2.000 16.900 5.62 16.000 14.400 17.600 44.70 Zone_3 Pass
BN Fault Type
Doble Page 4 of 9
7
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[cy] [cy] [cy] [cy]
Err
[Ω] [V] [A] [°] [%]
Fault Type CN
Test Test
2.032 66.13 7.11 2.000 1.940 94.00 1.000 0.000 21.675 92.40 Zone_1 Pass
2.303 66.62 8.06 2.000 16.960 6.00 16.000 14.400 NoOp 94.00 Zone_2 Pass
2.641 66.39 9.24 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass
0.112 250.10 0.39 2.000 16.980 6.12 16.000 14.400 17.600 44.70 Zone_3 Pass
CN Fault Type
Doble Page 5 of 9
8
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[cy] [cy] [cy] [cy]
Err
[Ω] [V] [A] [°] [%]
Fault Type AB
Test Test
2.107 66.74 8.43 2.000 2.000 100.00 1.000 0.000 25.312 95.80 Zone_1 Pass
2.327 67.14 9.31 2.000 16.755 4.72 16.000 14.400 NoOp 95.00 Zone_2 Pass
2.658 66.08 10.63 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass
0.140 235.51 0.56 2.000 16.780 4.88 16.000 14.400 17.600 57.00 Zone_3 Pass
AB Fault Type
Doble Page 6 of 9
9
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[cy] [cy] [cy] [cy]
Err
[Ω] [V] [A] [°] [%]
Fault Type BC
Test Test
2.107 66.74 8.43 2.000 1.825 82.50 1.000 0.000 25.312 95.80 Zone_1 Pass
2.327 67.14 9.31 2.000 16.840 5.25 16.000 14.400 NoOp 95.00 Zone_2 Pass
2.658 66.08 10.63 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass
0.140 235.51 0.56 2.000 16.850 5.31 16.000 14.400 17.600 57.00 Zone_3 Pass
BC Fault Type
Doble Page 7 of 9
10
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[cy] [cy] [cy] [cy]
Err
[Ω] [V] [A] [°] [%]
Fault Type CA
Test Test
2.107 66.74 8.43 2.000 1.895 89.50 1.000 0.000 25.312 95.80 Zone_1 Pass
2.327 67.14 9.31 2.000 16.900 5.62 16.000 14.400 NoOp 95.00 Zone_2 Pass
2.658 66.08 10.63 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass
0.140 235.51 0.56 2.000 16.940 5.88 16.000 14.400 17.600 57.00 Zone_3 Pass
CA Fault Type
Doble Page 8 of 9
11
Impedance Relay Timing Test Report 08-Feb-12
VESTAS 132kv/SEL311c
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[cy] [cy] [cy] [cy]
Err
[Ω] [V] [A] [°] [%]
Fault Type ABC
Test Test
2.130 66.71 4.26 2.000 1.965 96.50 1.000 0.000 26.704 96.80 Zone_1 Pass
2.331 66.91 4.66 2.000 16.970 6.06 16.000 14.400 NoOp 95.10 Zone_2 Pass
2.645 66.19 5.29 2.000 NoOp - NoOp 14.400 NoOp 0.00 Pass
0.089 228.21 0.18 2.000 16.740 4.62 16.000 14.400 17.600 37.50 Zone_3 Pass
ABC Fault Type
Doble Page 9 of 9
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 12 OF 77
TEST REPORT FOR TRANSFORMER PROTECTION RELAY
1. Designation:1. Designation:1. Designation:1. Designation: TRANSFORMER PROTECTION RELAY
Location: 132/33 KV ,70MVA TRANSFORMER C & R PANEL
2. Name Plate Details:2. Name Plate Details:2. Name Plate Details:2. Name Plate Details:
Make : REYROLLE Serial No. : BR 0701432
Type : DUOBIAS M Vaux. : 110V DC
Vu : NA In : 1.0 A
F : 50 HZ VTR : -----------
MVA : 70.0 HVCTR : 300/1A
HVNCTR: 400/1A LVCTR: 1600/1A
LVNCR: 1600/1A
3. General Inspection:3. General Inspection:3. General Inspection:3. General Inspection: OK Date :09.02.2012
4) Secondary Injection Test : 4) Secondary Injection Test : 4) Secondary Injection Test : 4) Secondary Injection Test :
(a):i) 87T Differential Current pickup Test : (i) (HV Side)
Phase Set. Current
(A)
Calculated Pickup Current (A) 3ø Pickup Current (A)
R 0.30 0.35 / 0.98 = 0.306 0.307 Y 0.30 0.35 / 0.98 = 0.306 0.307 B 0.30 0.35 / 0.98 = 0.306 0.307
(ii) LV Side Phase Set. Current (A) Calculated Pickup Current (A) 3ø Pickup Current
(A)
R 0.30 0.30 / 1.3 = 0.230 0.234
Y 0.30 0.30 / 1.3 = 0.230 0.234
B 0.30 0.30 / 1.3 = 0.230 0.234
(b):i) 87T Differential Inst pickup Test : (i) (HV Side) Phase Set.
Current (A)
Calculated Pickup Current (A) Pickup Current (A)
R 8.0 8.0 / 0.98 = 8.16 8.160 Y 8.0 8.0 / 0.98 = 8.16 8.160 B 8.0 8.0 / 0.98 = 8.16 8.160
(ii) LV Side Phase Set. Current (A) Calculated Pickup Current (A) Pickup Current
(A)
R 8.0 8.0 / 1.3 = 6.15 6.151 Y 8.0 8.0 / 1.3 = 6.15 6.151 B 8.0 8.0 / 1.3 = 6.15 6.151
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 13 OF 77
(b) Stability test : (at 100% load)
Phase App. HV Side Current (A)
App. LV Side Current (A)
Diff.Op.Relay Current (A)
Bias Current (A)
Diff.Relay
R 1.02 ∟0° 0.769 ∟180° 0.00 0.99 Not Operated
Y 1.02 ∟-120° 0.768 ∟60° 0.00 0.99 Not Operated
B 1.02 ∟120° 0.768 ∟300° 0.00 0.99 Not Operated
(c) Inrush Inhibit Set;
Phase ref Set. Current (A)
App. current (A)
App. current Freq(Hz)
Meg.Inrush Current (A)
Diff.Op.Relay Current (A)
Diff.Relay
R 0.2 0.30 100.0 0.30 0.30 Not Operated Y 0.2 0.30 100.0 0.30 0.30 Not Operated B 0.2 0.30 100.0 0.30 0.30 Not Operated
(d) Bias (or) Slope Test :
Phase Set. Bias Set. Diff Op. Bias Op. Diff
R Y Refer Doble Test Report B
(e) W1 Protection 51/51N : Inv – IEC NI
Phase Ref. Set. Current (A)
Time Mult Operating Time (Sec) at multiples of Set. Current
X 2 X 5 X 10
R 1.0 0.1 1.03 0.47 0.32
Y 1.0 0.1 1.03 0.47 0.32
B 1.0 0.1 1.03 0.47 0.32
N 0.2 0.1 1.05 0.48 0.31
(f) W1 Protection 50/50N :
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 8.0 8.00 0.00 0.04
Y 8.0 8.00 0.00 0.04
B 8.0 8.00 0.00 0.04
N 5.0 5.01 0.00 0.04
(g) W2 Protection 51/51N : Inv – IEC NI
Phase Ref. Set. Current (A) Time Mult Operating Time (Sec) at multiples of Set. Current
X 2 X 5 X 10
R 1.0 0.05 0.54 0.26 0.15
Y 1.0 0.05 0.54 0.26 0.15
B 1.0 0.05 0.54 0.26 0.15
N 0.2 0.05 0.57 0.26 0.16
for ELSYTEC
ELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 14 OF 77
(h) W2 Protection 50/50N :
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 6.0 6.00 0.00 0.04
Y 6.0 6.00 0.00 0.04
B 6.0 6.00 0.00 0.04
N 4.0 4.01 0.00 0.05
(i) HV REF – Earth current:
Phase ref Set. current (A)
Pickup. current for ST HV side(A)
Phase ref
Set. current (A)
Operating current (A)
Operating REF
R 0.2 0.21 Y 0.2 0.21 N,CT 0.2 0.201 OK B 0.2 0.21
(j) LV REF – Earth current:
Phase ref Set. current (A)
Pickup. current for ST HV side(A)
Phase ref
Set. current (A)
Operating current (A)
Operating REF
R 0.2 0.21 Y 0.2 0.21 N,CT 0.2 0.201 OK B 0.2 0.21
(k) 50 BF (LBB) set :
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
3Ø 0.2 0.21 INST 0.04
5555.Srvice Setting.Srvice Setting.Srvice Setting.Srvice Setting: File Attached Refer Page No :
6666.Remarks.Remarks.Remarks.Remarks:Relay operation found satisfactory
for ELSYTEC
F6TesT
Differential Relay Test Report 09-Feb-12
VESTAS 132kv/DuoBias M
VESTAS 132kv 70MVA TR Location Path
Test Definition 1
Pass Evaluation R.kanagaraj
Auto saved Auto saved
Tested By
Tested Date
Test Definition Description
Test Definition Name
2/9/2012
Relay Under Test General Parameters
A-B-C Vn
In 2000.000%
DIUOBIAS
181.81%
300 : 1 CTR
Phase Names And Rotation
Max Test Voltage
Max Test Current
Model
A V (Ph-Ph) Hz
1.000
110.00 50.000
132000 : 110
Substation
In Vn fn
REYROLLE
DuoBias M
VTR
Nominal Ratings:
Station Name
Manufacturer
Serial Number
Relay Name
Protected Object Parameters
Protected Object Name
Protected Object Parameters
Relay Functions
Function Type Duobias M Differential Function Name
General Tolerances
ms 20.0 Absolute Minimum Time Absolute Minimum A 0.050
Pickup Setting
Time Tolerance
Current Tolerance
Const B
Const A
Bias Equation Nominal Time
+% -% +% -%
Const C
Characteristic Name
x tap
35.00 (a*|Ip|+b*|Is|)/c 1.00 1.00 2.00 0.30
2.00 2.00 3.00 3.00 35.00 (a*|Ip|+b*|Is|)/c 1.00 1.00 2.00 8.00
F6000 Instrument HW and SW Information
F6TesT Software Version 2.21 Build 1165
F6000 Model Number F6150
Serial Number 67191328
F6000 Firmware Version 4.28.2
F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6825 : CPU2 F6875 : Variable Battery Simulator
F6844 : Logic I/O 4 board
Doble Page 1 of 4
Differential Relay Test Report 09-Feb-12
VESTAS 132kv/DuoBias M
F6000 Instrument HW and SW Information
F6TesT Software Version 2.21 Build 1165
F6000 Model Number F6150
Serial Number 67191328
F6000 Firmware Version 4.28.2
F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6825 : CPU2 F6875 : Variable Battery Simulator
F6844 : Logic I/O 4 board
Test Configuration
Angle of Ip = 0 deg; Angle of Is = 180 deg or 0 degFind | Ip | , | Is |, and Angle of Is for desired values of Ibias and Idiff
Test Method
6.000
Secondary Values are in
A 0.000 Prefault load current A Max test current
s
s
s
0.6000
0.4000
0.6000
Test Timing
Prefault Duration
Max. Fault Duration
Time between shots
Trigger Selection
Fault Type Trigger
A
B
C s
CBTripTime 0.0000
LN1 0->1
LN1 0->1
LN1 0->1
Doble Page 2 of 4
Differential Relay Test Report 09-Feb-12
VESTAS 132kv/DuoBias M
Fault Name Phase : A
Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval
0.283 -5.667 Pass 0.926 0.300 0.240 0.360
0.442 -9.426 Pass 2.439 0.488 0.390 0.585
0.727 -9.465 Pass 4.013 0.803 0.642 0.963
0.565 -9.455 Pass 3.118 0.624 0.499 0.748
0.309 -10.694 Pass 1.729 0.346 0.277 0.415
Fault Name Phase : A
Fault Name Phase : B
Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval
0.287 -4.333 Pass 0.926 0.300 0.240 0.360
0.460 -5.738 Pass 2.439 0.488 0.390 0.585
0.798 -0.623 Pass 4.013 0.803 0.642 0.963
0.588 -5.769 Pass 3.118 0.624 0.499 0.748
0.326 -5.780 Pass 1.729 0.346 0.277 0.415
Doble Page 3 of 4
Differential Relay Test Report 09-Feb-12
VESTAS 132kv/DuoBias M
Fault Name Phase : B
Fault Name Phase : C
Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval
0.291 -3.000 Pass 0.926 0.300 0.240 0.360
0.460 -5.738 Pass 2.439 0.488 0.390 0.585
0.778 -3.113 Pass 4.013 0.803 0.642 0.963
0.588 -5.769 Pass 3.118 0.624 0.499 0.748
0.326 -5.780 Pass 1.729 0.346 0.277 0.415
Fault Name Phase : C
Doble Page 4 of 4
ELSYTEELSYTEELSYTEELSYTEC ENGINEERS AND CONSULTANTS PVT LTD C ENGINEERS AND CONSULTANTS PVT LTD C ENGINEERS AND CONSULTANTS PVT LTD C ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 19 OF 77 CT/VT CONFIG MENU
W1 Input (1..5) 1A W1 CT Ratio (1:0.2..5000:7) 300:1 W1 REF Input (1..5) 1A W1 REF CT Ratio (1:0.2..5000:7) 400:1 W2 Input (1..5) 1A W2 CT Ratio (1:0.2..5000:7) 1600:1 W2 REF Input (1..5) 1A W2 REF CT Ratio (1:0.2..5000:7) 1600:1
BIASED DIFFERENTIAL MENU W1 Interposing CT Multiplier (0.25..3) 0.98x W1 Interposing CT Connection (Yy0,0..Ydy0,0) Yd1,-30deg W2 Interposing CT Multiplier (0.25..3) 1.3x W2 Interposing CT Connection (Yy0,0..Ydy0,0) Yd1,-30deg 87 Inrush Inhibit (Disabled..Enabled) Enabled 87 Inrush Bias (Phase..Sum) Cross 87 Inrush Setting (0.1..0.5) 0.2xId 87 Bias Differential (Disabled..Enabled) Enabled 87 Initial Setting (0.1..2) 0.3xIn 87 Bias Slope (0..0.7) 0.2x 87 Bias Slope Limit (1..20) 4xIn 87 Delay (0..1) 0s 87HS Differential HighSet (Disabled..Enabled) Enabled 87HS Setting (1..30) 8xIn 87HS Delay (0..1) 0s
WINDING 1 MENU W1 51 Element (Disabled..Enabled) Enabled W1 51 Setting (0.05..2.5) 1xIn W1 51 Char (IEC-NI..DTL) IEC-NI W1 51 Time Mult
(0.025..1.6) 0.1
W1 51 Delay (DTL) (INST..20) 5s W1 51 Reset ((ANSI) DECAYING..60) INST W1 50 Element (Disabled..Enabled) Enabled W1 50 Setting (0.05..25) 8xIn W1 50 Delay (0..864000) 0s W1 51N Element (Disabled..Enabled) Enabled W1 51N Setting (0.1..2.5) 0.2xIn W1 51N Char (IEC-NI..DTL) IEC-NI W1 51N Time Mult
(0.025..1.6) 0.1
W1 51N Delay (DTL) (INST..20) 5s W1 51N Reset ((ANSI) DECAYING..60) INST W1 50N Element (Disabled..Enabled) Enabled W1 50N Setting (0.1..25) 5xIn W1 50N Delay (0..864000) 0s W1 87REF Element (Disabled..Enabled) Enabled W1 87REF Setting (0.02..0.96) 0.2xIn W1 87REF Delay (0..864000) 0s
W1 50BF Trigger (12 Bit Binary) 87, 87HS, W1 50BF Element (Disabled..Enabled) Enabled W1 50BF Setting (0.05..2) 0.2xIn W1 50BF ReTrip Delay (0..60000) 60ms W1 50BF BackTrip Delay (0..60000) 200ms
WINDING 2 MENU W2 51 Element (Disabled..Enabled) Enabled W2 51 Setting (0.05..2.5) 1xIn W2 51 Char (IEC-NI..DTL) IEC-NI W2 51 Time Mult (IEC/ANSI) (0.025..1.6) 0.05 W2 51 Delay (DTL) (INST..20) 5s W2 51 Reset ((ANSI) DECAYING..60) INST W2 50 Element (Disabled..Enabled) Enabled W2 50 Setting (0.05..25) 6xIn W2 50 Delay (0..864000) 0s W2 51N Element (Disabled..Enabled) Enable
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD TS PVT LTD TS PVT LTD TS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 20 OF 77 W2 51N Setting (0.1..2.5) 0.2xIn W2 51N Char (IEC-NI..DTL) IEC-NI W2 51N Time Mult (IEC/ANSI) (0.025..1.6) 0.05 W2 51N Delay (DTL) (INST..20) 5s W2 51N Reset ((ANSI) DECAYING..60) INST W2 50N Element (Disabled..Enabled) Enabled W2 50N Setting (0.1..25) 4xIn W2 50N Delay (0..864000) 0s W2 87REF Element (Disabled..Enabled) Enabled W2 87REF Setting (0.02..0.96) 0.2xIn W2 87REF Delay (0..864000) 0s W2 50BF Trigger (12 Bit Binary) 87,87HS, W1 87REF W2 87REF W2 50BF Element (Disabled..Enabled) Enabled W2 50BF Setting (0.05..2) 0.2xIn W2 50BF ReTrip Delay (0..60000) 60ms W2 50BF BackTrip Delay (0..60000) 120ms
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 21 OF 77
TEST REPORT FOR DIRECTIONAL OVER CURRENT EARTH FAULT RELAY
1. Designation: DIRECTIONAL OVER CURRENT EARTH FAULT RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 CONTROL & PROTECTION PANEL
2. Name Plate Details :
Manufacturer : REYROLLE Rated Current : 1.0 A
Type No. : ARGUS – 2 Rated Voltage : 110 VAC
Serial No. : BR 0702445 Rated Freq. : 50/60 Hz
Model No. : DCD 814B Aux. Voltage : 90-250 VDC
3. Mechanical Check And Visual Inspection (Tick If Verified)
Item Description
1 Inspect for physical damage / defects. Yes N/A
2 Verify connections as per approved drawing. Yes N/A
3 Check tightness of all connections. Yes N/A
4. Electrical Tests Date : 08.02.2012
a. Function Test : Set.Direction ; OFF
Phase Ref Set Current(A) Inj.Current(A) Current Dir ection Relay operation
R 1.0 2.0 Forward RELAY OPERATED
2.0 Reverse RELAY OPERATED
Y 1.0 2.0 Forward RELAY OPERATED
2.0 Reverse RELAY OPERATED
B 1.0 2.0 Forward RELAY OPERATED
2.0 Reverse RELAY OPERATED
E/F 0.2 0.4 Forward RELAY OPERATED
0.4 Reverse RELAY OPERATED
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 22 OF 77
4. Secondary Injection Test: Date: 02.11.2011
a) Low Set O/C Unit: I> & Io>
Char Curve : NI
Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current
(A) X 2 X 5 X 10
R 1.0 0.125 1.25 0.54 0.38
Y 1.0 0.125 1.25 0.54 0.38
B 1.0 0.125 1.25 0.54 0.38
E/F 0.2 0.125 1.26 0.55 0.37
c) High Set O/C Unit: I>>& Io>>
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 10.0 10.02 0.00 0.043
Y 10.0 10.02 0.00 0.043
B 10.0 10.02 0.00 0.043
E/F 6.0 6.01 0.00 0.043
5. Service Setting :
Dir.Menu:
2 out of – 3 gate logic : OFF P/F Low set : OFF E/F Dir Setting : 60.0 A
P/F Char.Angle : +45° P/F Low Setting : O FF E/F Dir Char : NI
E/F Char.Angle : -15° P/F High set : OFF E/F Dir TMS : 0.125
Protection menu : P/F High Setting : 3000.0 A E/F Low set : OFF
P/F Dir Char : OFF P/F High setTime : 0.0 sec E/F Low Setting : OFF
P/F Dir Setting : 300.0 A P/F High set 2 : OFF E/F High set : OFF
P/F Dir Char : NI P/F High Setting 2 : OFF E/F High Setting : 1800.0 A
P/F Dir TMS : 0.125 E/F Dir Char : OFF E/F High set Time : 0.0 sec
E/F High set 2 : OFF
E/F High Setting 2 : OFF
6. Functional Checks
a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK
b) Correct Initiation Of Alarm Contacts: OK
c) Correct Circuit Breaker Tripping Contacts: OK
7. Remarks : RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 23 OF 77
TEST REPORT FOR OVER CURRENT AND EARTH FAULT RELAY
1. Designation: OVER CURRENT AND EARTH FAULT RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details :
Make: EASUN REYROLLE Serial No. : BR 0705231
In : 1 /5 A Fn : 50 HZ
Model : MIT 114 Vx : 43 - 280 V DC / 110 VDC
3. General Inspection Checks as per Checks List : OK
4. Secondary Injection Test: (a)Over Current (IP>& Earth Fault (IE>) : Date: 09.02.2012
Phase / Set. Current T.M.S Operating Time (Sec)
Unit (A) x 2 x 5 x 10
R 1.00 XIn 0.05 0.55 0.22 0.16
Y 1.00 XIn 0.05 0.55 0.22 0.16
B 1.00 XIn 0.05 0.55 0.22 0.16
E/F 0.20 xIn 0.05 0.50 0.26 0.15
c) High Set O/C Unit: IP>>& IE>>
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 6.00 6.01 - -
Y 6.00 6.01 - -
B 6.00 6.01 - -
E/F 4.0 4.01 - -
5. Service setting :
CP : SI 3.0 CE : SI 3.0 IP : 100 % IE : 20 %
tp : 0.05 tE : 0.05 Rt ; 0 HP:600%
HE : 400%
6. Remarks : RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 24 OF 77
TEST REPORT FOR OVER CURRENT AND EARTH FAULT RELAY
1. Designation: OVER CURRENT AND EARTH FAULT RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details :
Make: EASUN REYROLLE Serial No. : BR 0705233
In : 1 /5 A Fn : 50 HZ
Model : MIT 114 Vx : 43 - 280 V DC / 110 VDC
3. General Inspection Checks as per Checks List : OK
4. Secondary Injection Test: (a) Over Current (IP>& Earth Fault (IE>) :
Date: 09.02.2012
Phase / Set. Current T.M.S Operating Time (Sec) Unit (A) x 2 x 5 x 10
R 1.00 XIn 0.1 0.99 0.42 0.31
Y 1.00 XIn 0.1 0.99 0.42 0.31
B 1.00 XIn 0.1 0.99 0.42 0.31
E/F 0.20 xIn 0.1 0.99 0.42 0.31
c) High Set O/C Unit: IP>>& IE>>
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 8.0 8.01 - -
Y 8.0 8.01 - -
B 8.0 8.01 - -
E/F 5.0 5.01 - -
5. Service setting :
CP : SI 3.0 CE : SI 3.0 IP : 100 % IE : 20 %
tp : 0.1 tE : 0.1 Rt ; 0 HP:800%
HE : 500%
6. Remarks : RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 25 OF 77
TEST REPORT FOR OVER VOLTAGE AND UNDER VOLTAGE RELAY
1. Designation: OVER VOLTAGE AND UNDER VOLTAGE RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details:
Make : EASUN REYROLLE Serial No. : BR0705354
Model : MVT 181 Aux voltage : 43 – 230 V DC
Un : 110V AC
3. General Inspection Checks as per Check List: OK
4. Secondary Injection Test : Date: 08.02.2012
(a) Under voltage (V<):
Set Voltage(V)
Op. Voltage(V) Set. Time (sec) Op. Time (sec)
88.0 88.01 1.0 1.00
(b) Over voltage (V>):
Set Voltage(V)
Op. Voltage(V) Set. Time (sec) Op. Time (sec)
- - - -
5. Service Setting :
E1 – Under , E2 – OFF
U1 – 88.0 , C1 – dtL
t1 – 1.0 , td – 1.0
tc - OFF
6.Remarks: RELAY OPERATION FOUND SATISFACTORY.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 26 OF 77
TEST REPORT FOR OVER VOLTAGE AND UNDER VOLTAGE RELAY
1. Designation: OVER VOLTAGE AND UNDER VOLTAGE RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details:
Make : EASUN REYROLLE Serial No. : BR0705355
Model : MVT 181 Aux voltage : 43 – 230 V DC
Un : 110V AC
3. General Inspection Checks as per Check List: OK
4. Secondary Injection Test : Date: 08.02.2012
(a) Under voltage (V<):
Set Voltage(V)
Op. Voltage(V) Set. Time (sec) Op. Time (sec)
- - - -
(b) Over voltage (V>):
Set Voltage(V)
Op. Voltage(V) Set. Time (sec) Op. Time (sec)
132.0 132.8 1.0 1.01
5. Service Setting :
E1 – Over , E2 – OFF
U1 – 132.0 , C1 – dtL
t1 – 1.0 , td – 1.0
tc - OFF
6.Remarks: RELAY OPERATION FOUND SATISFACTORY.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 27 OF 77
TEST REPORT FOR TRIPPING RELAY
1. Designation: TRIPPING RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details:
Make : ER Model : --------
Type : B24 H2 Rated Volts : 110V DC
3. General Inspection Check : OK
4. Pick up / Drop Off Check: Date: 08.02.2012
Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)
9, 10 A 24.0 Hand reset
HR 0704795
19, 10 B 34.0 Hand reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: Relay operation found satisfactory.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 28 OF 77
TEST REPORT FOR LBB TRIPPING RELAY
1. Designation: LBB TRIPPING RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details:
Make : ER Model : --------
Type : B24 H2 Rated Volts : 110V DC
3. General Inspection Check : OK
4. Pick up / Drop Off Check: Date: 08.02.2012
Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)
9, 10 A 24.28 Hand reset
HR 0704794
19, 10 B 74.49 Hand reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: Relay operation found satisfactory.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 29 OF 77
TEST REPORT FOR TRIPPING RELAY
1. Designation: TRIPPING RELAY
Location: 132/33KV,70MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : ER Model : --------
Type : B24 H2 Rated Volts : 110V DC
3. General Inspection Check : OK
4. Pick up / Drop Off Check: Date: 09.02.2012
Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)
9, 10 A 28.72 Hand reset
HR 0704793
19, 10 B 40.05 Hand reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: Relay operation found satisfactory.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 30 OF 77
TEST REPORT FOR TRIPPING RELAY
1. Designation: TRIPPING RELAY
Location: 132/33KV,70MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : ER Model : --------
Type : B24 H2 Rated Volts : 110V DC
3. General Inspection Check : OK
4. Pick up / Drop Off Check: Date: 09.02.2012
Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)
9, 10 A 26.19 Hand reset
HR 0704791
19, 10 B 35.13 Hand reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: Relay operation found satisfactory.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD TS PVT LTD TS PVT LTD TS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 31 OF 77
TEST REPORT FOR TRIPPING RELAY
1. Designation: TRIPPING RELAY
Location: 132/33KV,70MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : ER Model : --------
Type : B24 H2 Rated Volts : 110V DC
3. General Inspection Check : OK
4. Pick up / Drop Off Check: Date: 09.02.2012
Serial No. Ter. Ref Coil Ref Pickup Volts (V) Drop off Volts (V)
9, 10 A 30.59 Hand reset
HR 0704792
19, 10 B 37.79 Hand reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: Relay operation found satisfactory.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 32 OF 77
TEST REPORT FOR DC SUPERVISION RELAY
1. Designation: DC SUPERVISION RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details:
Make : EASUN REYROLLE Model No: ------
Type : AR121T3 / AR 101 Vn: 110VDC
Un: 230VAC
3. General Inspection checks as per check List: OK
4. Pickup Test : Date: 08.02.2012
Coil Ref Sl No Pick Up(Volts) Drop Off (Volts)
DC Coil BR0613064 56.28 12.10
AC Coil BR0613064 110.1 39.36
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks : RELAY OPERATION FOUND SATISFACTORY.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 33 OF 77
TEST REPORT FOR DC SUPERVISION RELAY
1. Designation: DC SUPERVISION RELAY
Location: 132/33KV,70MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : EASUN REYROLLE Model No: ------
Type : AR121T3 / AR 101 Vn: 110VDC
Un: 230VAC
3. General Inspection checks as per check List: OK
4. Pickup Test : Date: 09.02.2012
Coil Ref Sl No Pick Up(Volts) Drop Off (Volts)
DC Coil BR06132877 57.72 12.96
AC Coil BR06132877 135.16 20.19
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks : RELAY OPERATION FOUND SATISFACTORY.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 34 OF 77
TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY
1. Designation: TRIP CIRCUIT SUPERVISION RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details:
Make : EASUN REYROLLE Model No: --------
Type : AR101X2 Vn: 110VDC
3. General Inspection checks as per check List: OK
4. Pickup Test : Date: 08.02.2012
Circuit Reference SL No
Term. Reference Pick Up(Volts) Drop Off (Volts)
--- HR0710137 A 60.00 12.01
B 68.00 12.00
--- HR0642371 A 60.12 12.91
B 60.16 16.31
--- HR0710138 A 63.16 19.16
B 68.53 17.32
--- HR0642372 A 59.62 16.31
B 58.32 17.52
--- HR0641922 A 71.54 13.21
B 68.51 15.16
5. Remarks : RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 35 OF 77
TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY
1. Designation: TRIP CIRCUIT SUPERVISION RELAY
Location: 132/33KV,70MVA TRANSFORMER LINE BAY - 2 C & R PANEL
2. Name Plate Details:
Make : EASUN REYROLLE Model : -------
Type : XR351 SI NO: -------
Vx : 110/125 V DC
3. General Inspection checks as per check List: OK
4. Pickup Test : Date: 08.02.2012
Sr.No Terminal Reference Pick Up(Volts) Drop Off (Volts)
BR0701521 A 36.00 10.00
B 36.00 12.00
C 68.00 14.8
BR0701522 A 35.50 11.20
B 46.50 12.00
C 57.20 8.32
5. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENELSYTEC ENELSYTEC ENELSYTEC ENGINEERS AND CONSULTANTS PVT LTD GINEERS AND CONSULTANTS PVT LTD GINEERS AND CONSULTANTS PVT LTD GINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 36 OF 77
TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY
1. Designation: TRIP CIRCUIT SUPERVISION RELAY
Location: 132/33KV,70MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : EASUN REYROLLE Model : -------
Type : XR351 SI NO: -------
Vx : 110/125 V DC
3. General Inspection checks as per check List: OK
4. Pickup Test : Date: 09.02.2012
Sr.No Terminal Reference Pick Up(Volts) Drop Off (Volts)
BR0701524 A 34.51 5.92
B 34.61 6.56
C 55.34 16.16
BR0701523 A 36.04 5.12
B 39.14 9.12
C 65.92 5.96
BR0701518 A 35.12 9.61
B 40.16 5.12
C 68.32 5.19
5. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 37 OF 77
TEST REPORT FOR AUXILIARY RELAY
1. Designation: FAULT TRIP RELAY
Location: 132/33KV,70MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : ER
Type : B33 X3 Rated Volts : 110V DC
Model : -----
3. General Inspection Check : OK
4. Pick up / Drop Off Check: Date: 09.02.2012
Serial No. : Coil Ref Pickup Volts (V) Drop off Volts (V)
HR0643583 A 39.12 Hand reset
B 36.13 Hand reset
C 42.87 Hand reset
HR0643578 A 44.83 Hand reset
B 37.63 Hand reset
C 36.47 Hand reset
HR0643579 A 36.77 Hand reset
B 47.56 Hand reset
C 36.16 Hand reset
HR0641802 A 31.26 Hand reset
B 42.90 Hand reset
C 37.86 Hand reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: Relay operation found satisfactory.
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 38 OF 77
TEST REPORT FOR DISTANCE PROTECTION RELAY
1. Designation: DISTANCE PROTECTION RELAY
Location: 132/33KV,30MVA TRANSFORMER LINE BAY – 1 C & R PANEL
2. Name Plate Details:
Make: ABB Serial No. : 0405004
Type : RAZOA Model : RGZB 030
I : 1.0 A EL : 110 V DC
RL : 110 V DC Un : 50 HZ, 110 V AC
X = (3.2 / In) X (F / 50) X (a / p )
R = (3.2 / In) X (b / p)
3. Mechanical Check And Visual Inspection (Tick If Verified)
Item Description
1 Inspect for physical damage / defects. Yes N/A
2 Verify connections as per approved drawing. Yes N/A
3 Check tightness of all connections. Yes N/A
4. Electrical Tests (Tick If Verified) Date : 10.02.2012
a. Function Test 1. Function Test Item Description
1 Human Machine Interface [ HMI ] checked. Yes N/A
2 Test switch checked for correct function. Yes N/A
3 Case Earthing checked. Yes N/A
4 Indications checked. Yes N/A
5 Alarm contacts checked. Yes N/A
6 Trip contacts checked. Yes N/A
7 Reset of indications checked. Yes N/A
8 Carrier send checked. Yes N/A
9 Carrier receive checked. Yes N/A
11 Blocking inputs checked. Yes N/A
11 Switch onto fault checked. Yes N/A
12 Power swing blocking function checked. Yes N/A
13 Scheme function checked. Yes N/A
14 Week End Infeed Function checked Yes N/A
5. Service Setting :
Zα : 2 x c/In Ins : 1 x 0.2 In F : 15 KN : 8 x 0.1 PS : 5
a : 25 b : 27 P1 : 99 P2 : 67 P3 : 40
T2 : 1 x 100 ms T3 : 2 x 200 ms T4 : 1 x 400 ms for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 39 OF 77
5. Secondary injection test :
6. Switch On to Fault Function.:
Distance prot. SOTF-On Trip time (msec)
Remarks
Internal SOTF -- Not connected to DLD Function.
External SOTF 50.0 Z1 start and Manual close CMD.
7. Fuse Failure function.
ITEM DESCRIPTION CHECKED 1 Check operation on/off --- 2 Check operation of indication OK 3 Check operation of contacts OK
Test Equipment Details
Make : DOBLE - U.S.A
Type: F6150
8. Impedance Timing test
Fault type ZONE1 ZONE2 ZONE3
A-N
B-N
C-N
A-B Refer Page No.
B-C
C-A
A-B-C
9. Remarks: TEST RESULTS FOUND SATISFACTORY.
for ELSYTEC
F6TesT
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
VESTAS 132kv Location Path
Test Definition 1
Pass Evaluation R.kanagaraj
Auto saved
Tested By
Tested Date
Test Definition Description
Test Definition Name
10.02.2012
Relay Under Test General Parameters
A-B-C Vn
In 2000.000%
RAZOA
1000.00%
300 : 1 CTR
Phase Names And Rotation
Max Test Voltage
Max Test Current
Model
A V (Ph-Ph) Hz
1.000 110.00 50.000
132000 : 110
132KV ,30MVA LINE
0404
In Vn fn
ABB
RAZOA
VTR
Nominal Ratings:
Station Name
Manufacturer
Serial Number
Relay Name
Protected Object Parameters
LINE Protected Object Name
Protected Object Parameters
Relay Functions
Function Type Distance Relay Impedance Function Name
Display values in Inherent Op Time ms 0 Secondary
General Tolerances
ms 20.0 Absolute Minimum Time Absolute Minimum Ohm 0.050
Zone Elements
-% + % -% +%
Zone Name Char Type Fault Type
Z tol t tol t nom [ms]
Residual Compensation Characteristic Angle
Zone3 435 5.00 5.00 5.00 5.00 General 3-Ph 70.00
Zone3 435 5.00 5.00 5.00 5.00 General Ph-Ph 70.00
Zone3 435 5.00 5.00 5.00 5.00 General Ph-N 0.80 0.00 KN 70.00
Zone1 35 5.00 5.00 5.00 5.00 General 3-Ph 70.00
Zone1 35 5.00 5.00 5.00 5.00 General Ph-Ph 70.00
Zone1 35 5.00 5.00 5.00 5.00 General Ph-N 0.80 0.00 KN 70.00
Zone2 135 5.00 5.00 5.00 5.00 General 3-Ph 70.00
Zone2 135 5.00 5.00 5.00 5.00 General Ph-Ph 70.00
Zone2 135 5.00 5.00 5.00 5.00 General Ph-N 0.80 0.00 KN 70.00
Doble Page 1 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
Test Configuration
0.000
110.00
Constant Current
V
A
Test Method
Prefault Voltage
Prefault Current Angle 0 Deg
% of rating Max Acceptable Voltage
Desired Test Current A 2
90
dc transient, fault inception angle
ms 0.00 Time constant L/R
Minimum Offset
CT direction Towards Line
Values are in Secondary
s
s
s
x Tmax
0.7000
1.5000
0.1000
Test Timing Trigger Selection
Prefault Duration
Max. Fault Duration
Max Fault Duration For Faster Zones
Time between shots
Fault Type Trigger
AN
BN
CN
AB
BC
CA
ABC
CBTripTime s 0.0000
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
LN1 0->1
Doble Page 2 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[s] [s] [s] [s]
Err
[Ω] [V] [A] [°] [%]
Fault Type AN
Test Test
0.726 46.12 2.61 2.000 0.0351 0.29 0.0350 0.0150 0.0550 64.70 Zone1 Pass
1.490 41.08 5.36 2.000 0.1344 -0.44 0.1350 0.1150 0.1550 87.10 Zone2 Pass
2.478 43.23 8.92 2.000 0.4331 -0.44 0.4350 0.4133 0.4568 84.80 Zone3 Pass
2.478 43.23 8.92 2.000 NoOp - 0.4350 0.4133 NoOp 97.60 Zone3 Pass
AN Fault Type
Doble Page 3 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[s] [s] [s] [s]
Err
[Ω] [V] [A] [°] [%]
Fault Type BN
Test Test
0.726 46.12 2.61 2.000 0.0352 0.57 0.0350 0.0150 0.0550 64.70 Zone1 Pass
1.490 41.08 5.36 2.000 0.1352 0.15 0.1350 0.1150 0.1550 87.10 Zone2 Pass
2.478 43.23 8.92 2.000 0.4393 0.99 0.4350 0.4133 0.4568 84.80 Zone3 Pass
2.478 43.23 8.92 2.000 NoOp - 0.4350 0.4133 NoOp 97.60 Zone3 Pass
BN Fault Type
Doble Page 4 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[s] [s] [s] [s]
Err
[Ω] [V] [A] [°] [%]
Fault Type CN
Test Test
0.726 46.12 2.61 2.000 0.0348 -0.57 0.0350 0.0150 0.0550 64.70 Zone1 Pass
1.490 41.08 5.36 2.000 0.1355 0.37 0.1350 0.1150 0.1550 87.10 Zone2 Pass
2.478 43.23 8.92 2.000 0.4392 0.97 0.4350 0.4133 0.4568 84.80 Zone3 Pass
2.478 43.23 8.92 2.000 NoOp - 0.4350 0.4133 NoOp 97.60 Zone3 Pass
CN Fault Type
Doble Page 5 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[s] [s] [s] [s]
Err
[Ω] [V] [A] [°] [%]
Fault Type AB
Test Test
0.754 43.93 3.02 2.000 0.0350 0.00 0.0350 0.0150 0.0550 64.70 Zone1 Pass
1.441 45.45 5.76 2.000 0.1339 -0.81 0.1350 0.1150 0.1550 86.00 Zone2 Pass
2.363 44.57 9.45 2.000 0.4394 1.01 0.4350 0.4133 0.4568 82.90 Zone3 Pass
AB Fault Type
Doble Page 6 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[s] [s] [s] [s]
Err
[Ω] [V] [A] [°] [%]
Fault Type BC
Test Test
0.754 43.93 3.02 2.000 0.0351 0.29 0.0350 0.0150 0.0550 64.70 Zone1 Pass
1.441 45.45 5.76 2.000 0.1337 -0.96 0.1350 0.1150 0.1550 86.00 Zone2 Pass
2.363 44.57 9.45 2.000 0.4357 0.16 0.4350 0.4133 0.4568 82.90 Zone3 Pass
BC Fault Type
Doble Page 7 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[s] [s] [s] [s]
Err
[Ω] [V] [A] [°] [%]
Fault Type CA
Test Test
0.754 43.93 3.02 2.000 0.0347 -0.86 0.0350 0.0150 0.0550 64.70 Zone1 Pass
1.441 45.45 5.76 2.000 0.1339 -0.81 0.1350 0.1150 0.1550 86.00 Zone2 Pass
2.363 44.57 9.45 2.000 0.4377 0.62 0.4350 0.4133 0.4568 82.90 Zone3 Pass
CA Fault Type
Doble Page 8 of 9
Impedance Relay Timing Test Report 10-Feb-12
VESTAS 132kv/RAZOA
V
Z t exp t max t min t act Eval I
Angle %Zone Zone
[s] [s] [s] [s]
Err
[Ω] [V] [A] [°] [%]
Fault Type ABC
Test Test
0.888 43.40 1.78 2.000 0.0348 -0.57 0.0350 0.0150 0.0550 75.50 Zone1 Pass
1.507 43.49 3.01 2.000 0.1338 -0.89 0.1350 0.1150 0.1550 86.80 Zone2 Pass
2.316 42.67 4.63 2.000 0.4333 -0.39 0.4350 0.4133 0.4568 78.80 Zone3 Pass
2.997 51.24 5.99 2.000 NoOp - NoOp NoOp NoOp 0.00 Pass
ABC Fault Type
Doble Page 9 of 9
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 49 OF 77
TEST REPORT FOR DIFFERENTIAL RELAY
1. Designation: DIFFERENTIAL RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make ABB Model No. : ------
Type SPAD 346 C Serial No. : 465369
In (A) : 1.0 Aux. Volts : 48 - 250 V DC
MVA : 30.0
3. General Inspection : OK
4. Secondary Injection Test: Date : 10.02.2012
a) Differential Current Check : (Pickup Test) : (HV Side) :
Phase Ref Set current (A) Calculated current (A) Op.current (A)
R 0.2 0.2 x 1.00 = 0.20 0.201
Y 0.2 0.2 x 1.00 = 0.20 0.201
B 0.2 0.2 x 1.00 = 0.20 0.201 b) LV Side :
Phase Ref Set current (A) Calculated current (A) Op.current (A)
R 0.2 0.2 x 1.00 = 0.20 0.201
Y 0.2 0.2 x 1.00 = 0.20 0.201
B 0.2 0.2 x 1.00 = 0.20 0.201
c) Differential Current Check : (High Pickup Test) : (HV Side) :
Phase Ref Set current (A) Calculated current (A) Op.current (A)
R 5.0 5.0 x 1.00 = 5.00 5.01
Y 5.0 5.0 x 1.00 = 5.00 5.01
B 5.0 5.0 x 1.00 = 5.00 5.01
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 50 OF 77
d) LV Side :
Phase Ref Set current (A) Calculated current (A) Op.current (A)
R 5.0 5.0 x 1.00 = 5.00 5.01
Y 5.0 5.0 x 1.00 = 5.00 5.01
B 5.0 5.0 x 1.00 = 5.00 5.01
(e) Stability test : (at 100% load)
Phase App. HV Side Current (A)
App. LV Side Current (A)
Diff.Op.Relay Current (A)
Bias Current (A)
Diff.Relay
R 1.02 ∟0° 0.769 ∟180° 0.00 0.99 Not Operated
Y 1.02 ∟-120° 0.768 ∟60° 0.00 0.99 Not Operated
B 1.02 ∟120° 0.768 ∟300° 0.00 0.99 Not Operated
(f)2nd Inrush Inhibit Set;
Phase ref Set. Current
(A) App. current
(A) App. current
Freq(Hz) Meg.Inrush Current (A)
Diff.Op.Relay Current (A)
Diff.Relay
R 0.2 0.30 100.0 0.30 - Not Operated Y 0.2 0.30 100.0 0.30 - Not Operated B 0.2 0.30 100.0 0.30 - Not Operated
(g) Bias (or) Slope Test :
Phase Set. Bias Set. Diff Op. Bias Op. Diff
R Y Refer Doble Test Report B
(h) Protection 51/51N : Inv – IEC NI Phase Ref.
Set. Current (A) Time Mult Operating Time (Sec) at multiples of Set.
Current X 2 X 5 X 10
R 0.9 0.1 1.02 0.42 0.31
Y 0.9 0.1 1.02 0.42 0.31
B 0.9 0.1 1.02 0.42 0.31
N 0.2 0.1 1.01 0.48 0.31
(f) Protection 50/50N :
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 3.5 3.51 0.2 0.21
Y 3.5 3.51 0.2 0.21
B 3.5 3.51 0.2 0.21
N 1.4 1.41 0.2 0.21
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 51 OF 77
(g) Protection I>>> :
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 9.0 9.01 0.04 0.04
Y 9.0 9.01 0.04 0.04
B 9.0 9.01 0.04 0.04
(h) HV REF – Earth current:
Phase ref Set. current (A)
Pickup. current for ST HV side(A)
Phase ref
Set. current (A)
Operating current (A)
Operating REF
R 0.1 - Y 0.1 - N,CT 0.1 0.11 OK B 0.1 -
(i) LV REF – Earth current:
Phase ref Set. current (A)
Pickup. current for ST HV side(A)
Phase ref
Set. current (A)
Operating current (A)
Operating REF
R 0.1 - Y 0.1 - N,CT 0.1 0.11 OK B 0.1 -
5. Service Setting : SPCD3D Diff. Setting : P/% : 20 % Bias Setting : S/% : 20 % I2tp / In : 1.0 Id / In >> : 5.0 Id2f / Id1f > (%) : 20 Id5f / Id1f > (%) : 15 Id5f / Id1f >> (%) : 15 I1 / In : 1.00 I2 / In : 1.00
SPCD 2D P1% : 10 P2% : 10 Io1 : 1.0 Io2 ; 1.0 I2f / Id Io1f > (%) : 30 I2f / Id Io2f > (%) : 30 I1 : 1.00 I2 : 1.00
SPCD 4D I> ; 0.9 K :0.1 I>> : 3.5 t>> 0.2 I>>> : 9.0 t>>> : 0.04 Io> : 0.2 K : 0.1 Io>> :1.4 tIo>> :0.2
SGF :
1 2 3 4 5 6 7 8 9
15 7 84 0 15 3 4 0 0
SGB :
1 2 3 4 5 6 7 8
0 0 0 0 0 0 0 0
SGR :
1 2 3 4 5 6 7 8 9
136 136 0 0 0 0 0 0 0
6. Functional Checks:
a. Correct operation of appropriate indicator/relay: OK
b. Correct initiation of alarm contacts: OK
c. Correct circuit breaker tripping Contacts: OK
7.Remarks RELAY OPERATION FOUND SATISFACTORY.
for ELSYTEC
F6TesT
Differential Relay Test Report 10-Feb-12
VESTAS 132kv/SPAD346C
VESTAS 132kv Location Path
Test Definition 1
Pass Evaluation R.kanagaraj
Auto saved
Tested By
Tested Date
Test Definition Description
Test Definition Name
2/10/2012
Relay Under Test General Parameters
A-B-C Vn
In 1500.000%
SPAD346C
181.81%
150 : 1 CTR
Phase Names And Rotation
Max Test Voltage
Max Test Current
Model
A V (Ph-Ph) Hz
1.000
110.00 50.000
132000 : 110
-ADDRESS n/a
465369
In Vn fn
ABB
SPAD346C
VTR
Nominal Ratings:
Station Name
Manufacturer
Serial Number
Relay Name
Protected Object Parameters
Protected Object Name
Protected Object Parameters
Relay Functions
Function Type SPAD346C-TR1 Differential Function Name
General Tolerances
ms 0.0 Absolute Minimum Time Absolute Minimum A 0.000
Pickup Setting
Time Tolerance
Current Tolerance
Const B
Const A
Bias Equation Nominal Time
+% -% +% -%
Const C
Characteristic Name
x tap
50.00 (a*Ip-b*Is)/c 1.00 1.00 2.00 0.20
30.00
30.00
30.00
30.00
50.00 (a*Ip-b*Is)/c 1.00 1.00 2.00 5.00
F6000 Instrument HW and SW Information
F6TesT Software Version 2.21 Build 1165
F6000 Model Number F6150
Serial Number 67191328
F6000 Firmware Version 4.28.2
F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6825 : CPU2 F6875 : Variable Battery Simulator
F6844 : Logic I/O 4 board
Doble Page 1 of 4
Differential Relay Test Report 10-Feb-12
VESTAS 132kv/SPAD346C
F6000 Instrument HW and SW Information
F6TesT Software Version 2.21 Build 1165
F6000 Model Number F6150
Serial Number 67191328
F6000 Firmware Version 4.28.2
F6000 Options F6810 : High power convertible voltage/current sources F6909 : Front Panel Interface
F6910 : Simulator control and automation interface
F6825 : CPU2 F6875 : Variable Battery Simulator
F6844 : Logic I/O 4 board
Test Configuration
Angle of Ip = 0 deg; Angle of Is = 180 deg or 0 degFind | Ip | , | Is |, and Angle of Is for desired values of Ibias and Idiff
Test Method
6.000
Secondary Values are in
A 0.000 Prefault load current A Max test current
s
s
s
0.6000
0.4000
0.6000
Test Timing
Prefault Duration
Max. Fault Duration
Time between shots
Trigger Selection
Fault Type Trigger
A
B
C s
CBTripTime 0.0000
LN1 0->1
LN1 0->1
LN1 0->1
Doble Page 2 of 4
Differential Relay Test Report 10-Feb-12
VESTAS 132kv/SPAD346C
Fault Name Phase : A
Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval
0.198 -1.000 Pass 0.148 0.200 0.140 0.260
0.194 -3.000 Pass 0.438 0.200 0.140 0.260
0.234 3.084 Pass 0.736 0.227 0.159 0.295
0.272 1.115 Pass 0.946 0.269 0.188 0.350
Fault Name Phase : A
Fault Name Phase : B
Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval
0.198 -1.000 Pass 0.148 0.200 0.140 0.260
0.198 -1.000 Pass 0.438 0.200 0.140 0.260
0.246 8.370 Pass 0.736 0.227 0.159 0.295
0.287 6.691 Pass 0.946 0.269 0.188 0.350
Fault Name Phase : B
Fault Name Phase : C
Doble Page 3 of 4
Differential Relay Test Report 10-Feb-12
VESTAS 132kv/SPAD346C
Ibias Exp. Idiff Idiff (Min.) Idiff (Max.) Act. Idiff Error [%] Eval
0.198 -1.000 Pass 0.148 0.200 0.140 0.260
0.198 -1.000 Pass 0.438 0.200 0.140 0.260
0.246 8.370 Pass 0.736 0.227 0.159 0.295
0.287 6.691 Pass 0.946 0.269 0.188 0.350
Fault Name Phase : C
Doble Page 4 of 4
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 56 OF 77
TEST REPORT FOR UNDER VOLTAGE RELAY
1. Designation: UNDER VOLTAGE RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL
2. Name Plate Details:
Make : JVS Aux. Volts : 75 – 150 V DC / AC
Type. : JRV 022 Serial No. : V 35422
Rated Voltage : 110 V AC
Time Setting : 0 – 25 Sec
Voltage Setting : 30 – 90 %
3. General Inspection and Pre-Commissioning Checks as per Check List: OK
4. Pick up / Drop Out Test: Date: 10.02.2012
Setting Voltage (V) Operating Voltage (V) Set. Time (Sec) Op. Time (Sec)
60 % Vn 65.92 10.0 10.02
80 % Vn 89.1 10.0 10.12
5.Functional Checks :
a) Operation of appropriate indicator/Aux relay : OK
b) Correct operation of Alarm/Trip Contact : OK
6.Service Setting: Tip.swt.Set : 60% Time. Set : 10.0 sec
7.Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 57 OF 77
TEST REPORT FOR AUXILIARY RELAY
1. Designation: TRIP CIRCUIT SUPERVISION RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL
2. Name Plate Details:
Make : JVS
Type : JRV 111 Rated Volts : 110 V DC
Model : JRV 111 00F
3. General Inspection : OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Serial No. Pick Up Volts (V) Drop Off Volts (V)
V 35112 33.91 12.15
V 35110 40.62 19.12
V 36109 41.32 18.61
V 35078 46.36 19.39
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
c. Correct initiation of scheme function: OK
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 58 OF 77
TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY
1. Designation: OVER CURRENT AND EARTH FAULT RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL
2. Name Plate Details:
Make: JVS Serial No. : C 35418
Type : JRC CT Sec. Current (A) : 1.0
Model : JRC 053 17P Aux. Voltage : 75 – 150 V DC
Available Setting O/C E/F
PS (A) (50 – 200) % (5 – 80) %
TMS 0 – 1.0 0 – 1.0
Operating time(Sec) at PS X 10 with TMS 1.0: 3.0
3. General Inspection : OK
4. Secondary Injection Test: Date: 10.02.2012
Phase / Unit PS (A) TMS Operating Time (Sec) at multiples of PS
2 5 10
R 1.0 0.12 1.21 0.49 0.37
1.0 9.98 4.28 2.98
B 1.0 0.12 1.21 0.49 0.37
1.0 9.93 4.26 2.98
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 59 OF 77
Phase / Unit PS (A) TMS Operating Time (Sec) at multiples of PS
2 5 10
E/F 0.2 0.12 1.21 0.49 0.37
1.0 10.01 4.30 3.06
5. Functional Checks
a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK
b) Correct Initiation Of Alarm Contacts: OK
c) Correct Circuit Breaker Tripping Contacts: OK
6. Service Setting:
O/C (R) E/F O/C (B)
PS (A) : 100 % 20 % 100 %
TMS : 0.12 0.12 0.12
7. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS ANELSYTEC ENGINEERS AND CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD D CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 60 OF 77
TEST REPORT FOR FUSE FAILURE RELAY
1. Designation: FUSE FAILURE RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL
2. Name Plate Details:
Make : ABB Serial No. : J040014
Type : FFR Rated Volts : 110 V AC
Model : 1MYN563005-B Fn : 50 Hz
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Phase Ref. Pick Up Volts (V) Drop Off Volts (V)
R 31.16 16.12
Y 35.21 12.31
B 36.91 16.17
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
c. Correct initiation of scheme function: -
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 61 OF 77
TEST REPORT FOR TRIPPING RELAY
1. Designation: TRIPPING RELAY
2. Name Plate Details:
Make : ABB Model : -----
Type : PC8QW2J Aux. Volts : 110 V DC
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Location Serial No. Pick Up Volts (V) Drop Off Volts (V)
132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL
M04 – 0148 43.12 Hand Reset
132 / 33 KV , 30MVA TRANSFORMER LINE BAY – 1 C & R PANEL
M04 – 0146 36.32 Hand Reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
For ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 62 OF 77
TEST REPORT FOR AUXILIARY RELAY
1. Designation: AUXILIARY RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL
2. Name Plate Details:
Make : ALSTOM Serial No : 1305 3639 0409 001
Model No: VAA 11 YF 8402 FCH Type: VAA 11
LH volts: 110 / 125 V DC RH volts: -
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Pick Up (volts) Drop Off (volts)
63.91 13.92
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 63 OF 77
TEST REPORT FOR TRIPPING RELAY
1. Designation: TRIPPING RELAY.
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL
2. Name Plate Details:
Make : AREVA Serial No : 130520410404001
Type : VAJH 23 Model No : VAJH 23 ZG22D
Operating Volt: 110V DC Reset Volt: -
3. General Inspection : OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Coil ref: Pick up volts Drop Off (volts)
A 39.16 HAND RESET
B 42.72 HAND RESET
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
c. Correct initiation of scheme function: -
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 64 OF 77
TEST REPORT FOR AUXILIARY RELAY
1. Designation: AUXILIARY RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL
2. Name Plate Details:
Make : ALSTOM Serial No : 1305 20340404001
Model No: VAJHM 13 ZG11D Type: VAJH 13
LH volts: 110 / 125 V DC RH volts: -
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Pick Up (volts) Drop Off (volts)
39.40 HAND RESET
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 65 OF 77
TEST REPORT FOR BUSBAR SUPERVISION RELAY
1. Designation: BUSBAR SUPERVISION RELAY.
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL
2. Name Plate Details:
Make : ALSTOM Serial No: 1304 354 5032 6001
Type : VTX 31 Model No: VTX 31 AF 8002 ACH
Aux.volts: 110 V DC Frequency: 50 Hz
Time delay : 3 Sec (Use with Ext.Res)
Available setting : (2-14) volts(operating volts)
3. General Inspection : OK
4. Secondary Injection Test : Date: 10.02.2012
Setting voltage (volts) Operating voltage (volts) Operating Time (Sec)
6.0 6.01 3.02
10.0 9.99 3.01
14.0 13.98 3.01
5. Service setting :
Operating volts: 10 V
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 66 OF 77
TEST REPORT FOR DIFFERENTIAL RELAY
1. Designation: DIFFERENTIAL RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL
2. Name Plate Details:
Make : ALSTOM Serial No. : 200001620410001
Type : CAG 34 CT Sec : 1 A
Model : CAG 34 AF 59A f : 50 HZ
Available setting : 0.2 – 0.8 A
3. General Inspection Checks as per Check List: OK
4. Secondary Injection Test : Date: 10.02.2012
Phase Ref Set Current (A) Op. Current (A)
R 0.5 0.520
Y 0.5 0.520
B 0.5 0.520
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6.Service Setting :
PS( A) : 0.5
7. Remarks: Relay operation found satisfactory.
For ELSYTEC
ELSYTEC ENGINEERS AND CONELSYTEC ENGINEERS AND CONELSYTEC ENGINEERS AND CONELSYTEC ENGINEERS AND CONSULTANTS PVT LTD SULTANTS PVT LTD SULTANTS PVT LTD SULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 67 OF 77
TEST REPORT FOR TRIP CIRCUIT SUPERVISION RELAY
1. Designation: TRIP CIRCUIT SUPERVISION RELAY
2. Name Plate Details:
Make : ABB Model : 1MYN740601-DBG
Type : VIRI-2JA Aux. Volts : 110 V DC
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 11.02.2012
Location Serial No. Pick Up Volts (V) Drop Off Volts (V)
132 / 33 KV , 30MVA TRANSFORMER C & R PANEL
V03 - 3645 Post Close : 46.82 12.21
Pre Close :39.54 12.34
132 / 33 KV , 30MVA TRANSFORMER C & R PANEL
V03 - 3644 Post Close : 49.14 14.23
Pre Close : 39.93 12.32
132 / 33 KV , 30MVA TRANSFORMER C & R PANEL
V03 - 3641 Post Close : 45.29 13.21
Pre Close : 40.37 15.23
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 68 OF 77
TEST REPORT FOR AUX .TRIPPING RELAY
1. Designation: AUX.TRIPPING RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : ABB Model : -----
Type : ---- Aux. Volts : 110 V DC
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Cir.Ref Serial No. Pick Up Volts (V) Drop Off Volts (V)
BUCH Alarm -- 38.9 Hand Reset
BUCH Trip -- 37.6 Hand Reset
WDG Alarm -- 38.4 Hand Reset
WDG Trip -- 39.1 Hand Reset
OTI Alarm -- 36.8 Hand Reset
OTI Trip -- 38.1 Hand Reset
MOG Alarm -- 37.5 Hand Reset
OSR Trip -- 39.4 Hand Reset
PRD Trip -- 35.6 Hand Reset
OLTC PRD Trip -- 36.1 Hand Reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
For ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 69 OF 77
TEST REPORT FOR DC SUPERVISION RELAY
1. Designation: DC SUPERVISION RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL
2. Name Plate Details:
Make : ABB Serial No : M 030303
Model No: ------ Type: PNBnCH2J
LH volts: 110 V DC RH volts: -
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Pick Up (volts) Drop Off (volts)
46.82 Hand Reset
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 70 OF 77
TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY
1. Designation: OVER CURRENT AND EARTH FAULT RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL - 132KV SIDE
2. Name Plate Details:
Make ABB Serial No. M 03 – 6282
Type SPAJ 140C In : 1.0 A
Model 1MYN 742751A Aux. Voltage (V) 110 V DC
Available & Service Setting: Relay setting Setting range Service setting
Definite Time Low Set Over Current : 0.5 …. 5.0 x In I> - In
Definite Time characteristic : 0.05 – 300 Sec t> -
Inverse Time Low set Over Current : 0.5 ….. 2.5 x In I> 0.9 In
Time Multiplier : 0.05 …. 1.0 K 0.1
Characteristics : EI / VI / NI / LTI / RI / RXIDG NI
High set Over Current : 0.5 ….. 40 x In (or) ∝ I>> 3.5 In
Operating Time : 0.04 …. 300 Sec t>> 0.2
Definite Time Low Set Earth Fault : 0.1….0.8 x In Io> -
Definite Time characteristic : 0.05 – 300 Sec to> -
Inverse Time Low set Earth Fault : 0.1….0.8 x In Io> 0.2 In
Time Multiplier : 0.05 …. 1.0 K 0.1
Characteristics : EI / VI / NI / LTI / RI / RXIDG NI
High set Earth Fault : 0.1 ….. 10 x In (or) ∝ Io>> 1.4 In
Operating Time : 0.05 …. 300 Sec to>> 0.2
Switch Group Function : SGF 099
Switch Group Blocking : SGB 000
Switch Group Register : SGR 170
Operating time(Sec)PS X 10 with TMS 1.0: 3.0
3. General Inspection: OK
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS ELSYTEC ENGINEERS AND CONSULTANTS ELSYTEC ENGINEERS AND CONSULTANTS ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD PVT LTD PVT LTD PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 71 OF 77
4. Secondary Injection Test: Date: 10.02.2012
a) Low Set O/C Unit: I>
Char Curve : NI
Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current
(A) X 2 X 5 X 10
R 0.9 0.1 1.02 0.48 0.32
Y 0.9 0.1 1.02 0.48 0.32
B 0.9 0.1 1.02 0.48 0.32
b) Low set E/F unit : Io>
Char Curve : NI
Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current
(A) X 2 X 5 X 10
E/F 0.2 0.1 1.02 0.48 0.32
c) High Set O/C Unit: I>>
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 3.5 3.52 0.2 0.21
Y 3.5 3.52 0.2 0.21
B 3.5 3.52 0.2 0.21
d) High set E/F Unit: Io>>
Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
1.4 1.41 0.2 0.21
5. Functional Checks
a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK
b) Correct Initiation Of Alarm Contacts: OK
c) Correct Circuit Breaker Tripping Contacts: OK
6. Remarks : RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 72 OF 77
TEST REPORT FOR OVER CURRENT / EARTH FAULT RELAY
1. Designation: OVER CURRENT AND EARTH FAULT RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER C & R PANEL - 33KV SIDE
2. Name Plate Details:
Make ABB Serial No. M 03 – 6280
Type SPAJ 140C In : 1.0 A
Model 1MYN 742751A Aux. Voltage (V) 110 V DC
Available & Service Setting: Relay setting Setting range Service setting
Definite Time Low Set Over Current : 0.5 …. 5.0 x In I> - In
Definite Time characteristic : 0.05 – 300 Sec t> -
Inverse Time Low set Over Current : 0.5 ….. 2.5 x In I> 0.9 In
Time Multiplier : 0.05 …. 1.0 K 0.08
Characteristics : EI / VI / NI / LTI / RI / RXIDG NI
High set Over Current : 0.5 ….. 40 x In (or) ∝ I>> 3.00 In
Operating Time : 0.04 …. 300 Sec t>> 0.2
Definite Time Low Set Earth Fault : 0.1….0.8 x In Io> -
Definite Time characteristic : 0.05 – 300 Sec to> -
Inverse Time Low set Earth Fault : 0.1….0.8 x In Io> 0.2 In
Time Multiplier : 0.05 …. 1.0 K 0.08
Characteristics : EI / VI / NI / LTI / RI / RXIDG NI
High set Earth Fault : 0.1 ….. 10 x In (or) ∝ Io>> 1.20 In
Operating Time : 0.05 …. 300 Sec to>> 0.2
Switch Group Function : SGF 099
Switch Group Blocking : SGB 000
Switch Group Register : SGR 170
Operating time(Sec)PS X 10 with TMS 1.0: 3.0
3. General Inspection: OK
for ELSYTEC
ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD ELSYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 73 OF 77
4. Secondary Injection Test: Date: 10.02.2012
a) Low Set O/C Unit: I>
Char Curve : NI
Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current
(A) X 2 X 5 X 10
R 0.9 0.08 0.82 0.40 0.26
Y 0.9 0.08 0.82 0.40 0.26
B 0.9 0.08 0.82 0.40 0.26
b) Low set E/F unit : Io>
Char Curve : NI
Phase Set. Current TMS Operating Time (Sec) at multiples of Set. Current
(A) X 2 X 5 X 10
E/F 0.2 0.08 0.82 0.42 0.26
c) High Set O/C Unit: I>>
Phase Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
R 3.0 3.01 0.2 0.21
Y 3.0 3.01 0.2 0.21
B 3.0 3.01 0.2 0.21
d) High set E/F Unit: Io>>
Set. Current (A) Op. Current (A) Set. Time (Sec) Op. Time (Sec)
1.20 1.19 0.2 0.21
5. Functional Checks
a) Correct Operation Of Appropriate Indicator/Aux. Relay: OK
b) Correct Initiation Of Alarm Contacts: OK
c) Correct Circuit Breaker Tripping Contacts: OK
6. Remarks : RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
ELELELELSYTEC ENGINEERS AND CONSULTANTS PVT LTD SYTEC ENGINEERS AND CONSULTANTS PVT LTD SYTEC ENGINEERS AND CONSULTANTS PVT LTD SYTEC ENGINEERS AND CONSULTANTS PVT LTD Engineering Service Excellence
CLIENT VESTAS WIND TECH (I) PVT LTD, TR NO : EE/TR/RK/XX/11
PROJECT MAINTENANCE TESTING OF 132/33KV SS , SHIKARPUR SHEET : 74 OF 77
TEST REPORT FOR POWER SWING RELAY
1. Designation: POWER SWING RELAY
Location: 132 / 33 KV , 30MVA TRANSFORMER LINE BAY -1 C & R PANEL
2. Name Plate Details:
Make : ABB Serial No : P 030024
Model No: IMYN742007 - E Type: RXZD 4
Aux volts: 110 / 125 V DC EL volts: 24.0VDC
3. General Inspection Checks as per Check List: OK
4. Pick up / Drop Off Check: Date: 10.02.2012
Pick Up (Z) Drop Off (Z)
Refer Doble Test Report
5. Functional Checks:
a. Correct Operation of Contacts: OK
b. Correct operation of appropriate indicator / flag: OK
6. Service Setting : Zo = d.q / Is , Is – 1.0A , d – 2.0 , q - 1.0
7. Remarks: RELAY OPERATION FOUND SATISFACTORY
for ELSYTEC
F6TesT
Wavesim Test Report 10-Feb-12
VESTAS 132kv/RXZD 4
VESTAS 132kv Location Path
Test Definition 1
NoOp Evaluation R.kanagaraj
Auto saved Auto saved Auto saved Auto saved
Tested By
Tested Date
Test Definition Description
Test Definition Name
02/10/2012
Relay Under Test General Parameters
A-B-C Vn
In 2000.000%
RXZD 4
1000.00%
300 : 1 CTR
Phase Names And Rotation
Max Test Voltage
Max Test Current
Model
A V (Ph-Ph) Hz
1.000
110.00 50.000
132000 : 110
132KV ,30MVA LINE
P030024
In Vn fn
ABB
RXZD 4
VTR
Nominal Ratings:
Station Name
Manufacturer
Serial Number
Relay Name
Protected Object Parameters
LINE Protected Object Name
Protected Object Parameters
-%
KN Theta
+ % -% +%
Zone Name Char Type Fault Type Zone Tested Impedance Tolerance
Time Tolerance
Nominal Time
StartUni 0 10.00 10.00 10.00 10.00General Ph-N Yes 1.00 0.00
Doble Page 1 of 3
Wavesim Test Report 10-Feb-12
VESTAS 132kv/RAZOA
Test Method: User-specified load, faults, dz/dt, Zs
Protected Line
Pos.sequence
Zero sequence
KL magnitude
Angle, deg
° KL angle 1.000 0.00
Prefault Voltage 69.00
Z [Ω] R [Ω] X [Ω]
V
1.000 70.00 0.940 0.342
70.004.000 3.759 1.368
1 Number of Test Repetitions
[s] /s]
Ks Zs Zp
[Ω [°] [°] [°] [Ω] [Ω] [Ω] [Ω] [Ω]
Simulation Points Zp Remarks Ks Zs Duration
dz/dt Xp Rp
Type Direction
1.000 70.00 1.00
0.00 Initial load Load Forward þ 117.51
46.62 80.721 85.409 0 0.5000
1.000 70.00 1.00
0.00Load Forward þ 51.675 54.14 30.270 41.881
1.000 70.00 1.00
0.00Load Forward þ 110.17
74.44 29.550 106.13
1.000 70.00 1.00
0.00Load Forward þ 95.830 -14.03 -
23.226
1.000 70.00 1.00
0.00Load Forward þ 98.574 1.05 98.557 1.808
1.000 70.00 1.00
0.00Load Forward þ 102.92
6.70 - -
0.587 0.5000 A Maximum test current Simulation duration s
t exp Eval Error t actual +t tol -t tol Test No. TimeNo. Timer Name [%] [s] [s] [s] [s]
Trigger
1 1 Timer NoOp
LN1
Doble Page 2 of 3
Wavesim Test Report 10-Feb-12
VESTAS 132kv/RAZOA
Oscillograph
Doble Page 3 of 3