13. Fire Fighting System in E/R
Course
No.
2004
© Det Norske Veritas AS. All rights reserved.
02 September 2009
2
� Purpose of the rules and regulations;
Fire Fighting System - E/R
� To effectively control and extinguish fires
© Det Norske Veritas AS. All rights reserved.
02 September 2009
3
� The following systems are required;
Fire Fighting System - E/R
1. Fire water system with hydrant valves and hoses with nozzles.
2. Fixed fire extinguishing system
- A gas system (CO2)
- A high expansion foam system
- A water spraying system
If there is provided two type of fixed fire extinguishing system in E/R, what to be consider?
© Det Norske Veritas AS. All rights reserved.
02 September 2009
4
� The following systems are required;
Fire Fighting System - E/R
3. Fixed local fire extinguishing system covering:
SOLAS 2000Amendments, applicable for cat. A machinery spaces above 500 m3
4. Portable fire extinguishers : to be provided acc. to MSC.1/Circ.1275
- Boiler fronts
- Fire hazard portions of incinerators
- Purifiers for heated fuel oil
- Main and aux. engines
© Det Norske Veritas AS. All rights reserved.
02 September 2009
5
� Arrangement and number of fire pumps ;
Fire Fighting System - E/R
If both pumps are located in the same compartment (E.G. E/R), an independently driven emergency fire pump is to be provide in another compartment.
− Cargo ships of 1000 GRT and above is to be provided with two independently driven fire pumps.
© Det Norske Veritas AS. All rights reserved.
02 September 2009
6
Fire Fighting System - E/R
− Minimum total capacity for the main fire pumps ;
QF = 4/3 × QBP, QBP - bilge pump capacity
− Capacity of each fire pump ;
N - Number of required fire pumps.− Capacity of emergency fire pump ;
QEFP ≥ 4/3 × QBP × 0.4QEFP ≥ 25 m³/h
For cargo ships QF need not exceed 180 m³/h, but in no case less than 25m³/h.
� Arrangement and number of fire pumps ;
4/3 × QBP × 0.8NQFP ≥
© Det Norske Veritas AS. All rights reserved.
02 September 2009
7
� Number and position of hydrants ;
� The number and position of hydrants shall be such that at least two jets of water not emanating from the same hydrant, one of which shall be from a single length hose, may reach any part of the engine room.
� The hydrants should be positioned near the accesses to the protected spaces.
Fire Fighting System - E/R
© Det Norske Veritas AS. All rights reserved.
02 September 2009
8
Fire Fighting System - E/R
� Fire Hoses ;
� Each hose shall be provided with a nozzle and the necessary couplings.
� Fire hose shall have a length of at least 10m, but not more than 15m for machinery spaces.
� Common practice to provide 1 hose for each hydrant in E/R
Fire mains and hydrants with fire hoses
HB
HB
HB
HB
HB
HBHB
Port side acc. branch
Emergency fire pump Main fire pumps
Engine room
Steering gear & emergency fire pump room
HB
HB
HB
© Det Norske Veritas AS. All rights reserved.
02 September 2009
10
Fire Fighting System - E/R
� CO2 HP fire extinguishing sys. for machinery spaces.
� The CO2 bottles shall be stored in a readily accessible room outside the protected space(s).
� Automatic release of CO2 is not accepted.
� Pre-discharge alarm must be provided.To operate for the time required to evacuate the space, but not less than 20s.
� Means for release shall be grouped together in few locations outside the protected spaces
− .
© Det Norske Veritas AS. All rights reserved.
02 September 2009
11
Fire Fighting System - E/R
1. Discharge the CO2 from the bottles
2. Opening the master valve for the space.
− Two separate controls should be provided.
� CO2 HP fire extinguishing sys. for machinery spaces.
− The fixed piping system shall be such that 85% of the required CO2 can be discharged into the E/R within 2 minutes.
− Required quantity of CO2 : the larger of the following:
1. 35% of the gross volume of the engine room including the casing.
2. 40% of the gross volume of the engine room, excluding:
The casing above the level at which the horizontal area of the casing is 40% or less or the horizontal area of the E/R taken midway between the tank top and the lowest part of the casing.
© Det Norske Veritas AS. All rights reserved.
02 September 2009
12
Fire Fighting System - E/R
� CO2 HP fire extinguishing system for machinery spaces.
V × 0.35/0.4 [kg]0.56
M =
N = M/45 [number of 45kg bottles]
Typical arrangement HP CO2 system
PUMPROOM
CO2 ROOM
TO OPEN AIR
TDTD
E/R
ALARMALARM
TO E/R CO2 NOZZLES
PUM P ROOM
VENT STOPALARM
PUMP ROOM
E/RFIR CONTROL STATION
© Det Norske Veritas AS. All rights reserved.
02 September 2009
14
Engine Room Vent Fan
Main control panel for E/R space closing damper
© Det Norske Veritas AS. All rights reserved.
02 September 2009
15
Engine Room Funnel louver damper
© Det Norske Veritas AS. All rights reserved.
02 September 2009
16
Engine Room Vent Fan damper
© Det Norske Veritas AS. All rights reserved.
02 September 2009
17
Fire Fighting System - E/R
� High expansion foam systems:
� Only hot foam systems, using inside air to generate form, is used for machinery spaces today.
� The system must have been successfully tested according to IMO MSC/Circ. 668, Part B.
� Design requirements such as:
- Foam in-mix concentration & foam type
- Filling rate
- Foam generator capacity/design/arrangement
To be according to test documentation/certificate.The foam generator and foam concentrate must be of approved (i.e. certified) type.
© Det Norske Veritas AS. All rights reserved.
02 September 2009
18
Fire Fighting System - E/R
− The generators should be evenly distributed.
Where the engine room is divided into separate spaces (e.g. workshop, purifier room, ECR, etc.) each space must be provided with foam generator(s).
� High expansion foam systems:
− The Arrangement in the engine room is to be such that possible overpressure generated by the fire and application of foam can be relieved.
E.g. by keeping exhaust ventilation louvres in the casing open during foam application.
− The quantity of foam concentrate available shall be sufficient to produce a volume of foam equal to five times the volume of the space protected.
© Det Norske Veritas AS. All rights reserved.
02 September 2009
19
Fire Fighting System - E/R
− The expansion ratio of the foam shall not exceed 1,000 to 1.
� High expansion foam systems:
− The capacity of the system is to be sufficient to fill the whole space to the level of the main deck in course of maximum 10 minutes.
− The emergency fire pump capacity :
Supply foam generators with sufficient water for maximum production
+Water for 2 hydrants(min.25m3/h)
For the type approved hot foam systems the expansion ratio is 620-660 : 1.
Easier flow-out/distribution.
Typical arrangement high expansion foam system
E/R
FOAM TANK
TO E/RFOAM GENERATORS
EMERGENCYFIRE PUMP
FIREMAIN
FOAMROOM
PUMP ROOMEMERGENCY FIREPUMP ROOM
MAIN FIRE PUMPS
FOAMPUMP
© Det Norske Veritas AS. All rights reserved.
02 September 2009
21
Fire Fighting System - E/R
© Det Norske Veritas AS. All rights reserved.
02 September 2009
22
Fire Fighting System - E/R
© Det Norske Veritas AS. All rights reserved.
02 September 2009
23
Fire Fighting System - E/R
• SOLAS 2000 AMENDMENTS
SOLAS CH. II-2,
REGULATION 10.5.6
FIXED LOCAL APPLICATION
FIRE FIGHTING SYSTEM
© Det Norske Veritas AS. All rights reserved.
02 September 2009
24
Fire Fighting System - E/R
• Fixed Local Application Fire Fighting System
Applicable for :
− Passenger Ships of 2000GRT and above constructed before 1 July 2002, provided that such ships comply with the requirements not later than 1 October 2005.
− NIS/NOR Flag passenger vessel 2000
− Machinery spaces of category A above 500m³ in gross volume.
− Passenger Ships of 500GRT and above and cargo ships of 2000GRT and above constructed on or after 1 July 2002.
© Det Norske Veritas AS. All rights reserved.
02 September 2009
25
Fire Fighting System - E/R
− E0, system to have both automatic and Manual release capabilities.
− Visual and Distinct Audible Alarm in protected Space and Continuously Manned Stations.
− The Alarm shall indicate the Specific System Activated
− Fire Fighting Medium is not to Endanger Life.
• Characteristics
© Det Norske Veritas AS. All rights reserved.
02 September 2009
26
Fire Fighting System - E/R
− Boiler fronts
− Fire hazard portions of incinerators
− Purifiers for heated fuel oil
− Fire hazard portions of internal combustion machinery used for the ships main propulsion and power generation (i.e. main and aux. engines.)
• Coverage
© Det Norske Veritas AS. All rights reserved.
02 September 2009
27
� Fixed local application fire fighting systems ;
Fire Fighting System - E/R
− The system must have been successfully tested according to IMO MSC/Circ.913.
− Design requirements such as ;- Detailed nozzle arrangement- Minimum operation pressure- Nozzle types (k-factor , Q = k × p )- System components
To be according to test documentation/certificate.
½
SKETCH LOCAL WATER FOG SYSTEM
* MIN. 20 MINOPERATION
LCB
AD
FLAME DETECTOR
SMOKE DETECTOR
LOCAL RELEASE
ALARM HORN
ADLCB
12 12
20 20
LCB
ADLCB
12 12
20 20
ADLCB
20 20
LCB
20 20
ADLCB
ADLCB
12
M
M
M
M
M
M
M
P
M
DRAIN
25A
FW TK
LS
DRAIN
15A
15A AIRTEST
CONNECTION
25A50A ST
15A
15A
15A
20A
15A
15A
15A
15A
TESTLINE
INCINERATOR AREA
AUX. BOILER AREA
MAIN ENGINE AREA
NO. 1, 2, 3 D/G ENG. AREA
HYD. POWER PACKENG. AREA
I.G.G AREA
HFO PURIFIER AREA
HIGH PRESSURE PUMP
ENGINE ROOM
NO
15A
AD
AD
GEN. SERVICE
NO*
© Det Norske Veritas AS. All rights reserved.
02 September 2009
29
Local Fire Fighting Remote Control
© Det Norske Veritas AS. All rights reserved.
02 September 2009
30
Local Fire Fighting System Pump
© Det Norske Veritas AS. All rights reserved.
02 September 2009
31
Local Fire Fighting System V/V Block
© Det Norske Veritas AS. All rights reserved.
02 September 2009
32
Fire Fighting System - E/R
� Fire extinguishers;
− All fire extinguishers shall be of approved types (i.e., certified.)
− Designs shall be based upon IMO Resolution A.602(15).
Basic requirements:
© Det Norske Veritas AS. All rights reserved.
02 September 2009
33
� Definition portable foam applicator unit;
Fire Fighting System - E/R
− Consist of a foam nozzle of an inductor type.
− Capable of being connected to the fire main by a fire hose.
− One 20l foam tank plus one space.
− The nozzle shall produce effective foam at the rate of at least 1.5m³/min.
© Det Norske Veritas AS. All rights reserved.
02 September 2009
34
� Spaces containing both oil fired boilers and internal combustion machinery;
Fire Fighting System - E/R
Equipment required Location
1 portable foam applicator unit Nearby boilers/combustion machineryNearby hydrant valve
45l foam extinguisher with hose or reel (1) In each space containing internal combustionmachinery
9l foam extinguishers
In each space containing internal combustionmachinery. Located so that no point is more than10m walking distance from an extinguisher.The number not to be less than 2.
9l foam extinguishers (≥ 2) In each boiler firing space
135l foam extinguisher with hose or reel (1) In each boiler firing space
A receptacle containing at least 0.1m3 sand,sawdust impregnated with soda, or otherapproved material.An approved portable extinguisher may beaccepted as an alternative.
In each boiler firing space
© Det Norske Veritas AS. All rights reserved.
02 September 2009
35
� Equivalents :
Fire Fighting System - E/R
25 kg dry power
20 kg CO2
45l foam
© Det Norske Veritas AS. All rights reserved.
02 September 2009
36
� References;
Fire Fighting System - E/R
- SOLAS 2000 Amendments Ch.II-2 Reg.10
- International Code for Fire Safety Systems Ch.4/5/6
- SOLAS 1974 as amended Ch.II-2 Reg.4/5/6/7/9
- IMO MSC/Circ.688 Part B
- IMO Resolution A.602(15)
- IACS F35
- DNV Rules for Ships Pt.4 Ch.1 Sec.3 A400
© Det Norske Veritas AS. All rights reserved.
02 September 2009
37
Case 12; Please review the below design as to acceptability. Present your comments, if any.
Fire Fighting System - E/R
PORT SIDEACC. BRANCH
EMERGENCYFIRE PUMP MAIN FIRE PUMPS
ENGINE ROOMSTEERING GEAR & EMERGENCY FIRE PUMPROOM