7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 1/31  Materials System Specification  12-SAMSS-014 9 March 2008 Pre-Engineered Metal Buildings Onshore Structures Standards Committee Members  Baldwin, Charles Cummins, Chairman Sheref, Khaled Mohammad, Vice Chairman  Mohammed, Ammar Khalil Utaibi, Abdul Aziz Saud  Abu-Adas, Hisham A.W.  Henry, Michael Patrick  Abulhamayel, Ismat Abdulkader  Dakhil, Osamah Ali Grosch, Jonathan Joseph Kim, Steve Un Thompson, Scott Burnett Ghubari, Said Faleh  Marhoon, Saeed Ahmed  Hemler, Steven R. Saleh, Loay Abdullah Saudi Aramco DeskTop Standards  Table of Contents  1 Scope............................................................. 2 2 Conflicts and Deviations................................ 2 3 References ..................................................... 2 4 General.......................................................... 7 5 Design............................................................ 9 6 Material Specifications................................. 11 7 Finishes........................................................ 18 8 Accessories.................................................. 18 9 Building Foundations.................................... 24 10 Fabrication.................................................... 24 11 Drawings and Calculations........................... 27 12 Packing and Shipping.................................. 29  Appendix 1 – ASTM Material Equivalency......... 30  Attachment 1 – Pre-Engineered Metal Building Design Data Sheet...... 31 Previous Issue: 30 June 2002 Next Planned Update: 9 March 2013 Page 1 of 31 Primary contact: Baldwin, Charles Cummins on 966-3-8746149 Copyright©Saudi Aramco 2008. All rights reserved. 

Transcript of 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

Page 1: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 1/31

 

Materials System Specification  

12-SAMSS-014 9 March 2008

Pre-Engineered Metal Buildings

Onshore Structures Standards Committee Members Baldwin, Charles Cummins, Chairman

Sheref, Khaled Mohammad, Vice Chairman

 Mohammed, Ammar Khalil

Utaibi, Abdul Aziz Saud

 Abu-Adas, Hisham A.W.

 Henry, Michael Patrick

 Abulhamayel, Ismat Abdulkader

 Dakhil, Osamah Ali

Grosch, Jonathan Joseph

Kim, Steve Un

Thompson, Scott BurnettGhubari, Said Faleh

 Marhoon, Saeed Ahmed

 Hemler, Steven R.

Saleh, Loay Abdullah

Saudi Aramco DeskTop Standards  

Table of Contents 

1 Scope............................................................. 2

2 Conflicts and Deviations................................ 23 References..................................................... 24 General.......................................................... 75 Design............................................................ 96 Material Specifications................................. 117 Finishes........................................................ 188 Accessories.................................................. 189 Building Foundations.................................... 2410 Fabrication.................................................... 2411 Drawings and Calculations........................... 2712 Packing and Shipping.................................. 29

 Appendix 1 – ASTM Material Equivalency......... 30 Attachment 1 – Pre-Engineered Metal

Building Design Data Sheet...... 31

Previous Issue: 30 June 2002 Next Planned Update: 9 March 2013

Page 1 of 31Primary contact: Baldwin, Charles Cummins on 966-3-8746149

Copyright©Saudi Aramco 2008. All rights reserved. 

Page 2: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 2/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 2 of 31

1 Scope

This Specification defines the minimum mandatory requirements for the design,

material selection, fabrication and packaging of one story pre-engineered metal buildings with or without mezzanines. This specification also applies to unenclosedstructures such as sunshades and carports that are furnished by a pre-engineered metal

 building vendor.

This Specification does not address foundation requirements, interior finish out,

specialty requirements, or building systems such as fire protection, electrical, ormechanical systems. This specification also does not address proprietary space frame

structures, or composite buildings consisting of concrete wall panels and roof slabs

attached to metal framing.

2 Conflicts and Deviations

2.1 Any conflicts between this specification and other applicable Saudi Aramco

Materials System Specifications (SAMSSs), Engineering Standards (SAESs),Standard Drawings (SASDs), or industry standards, codes, and forms shall be

resolved in writing by the Company or Buyer Representative through theManager, Consulting Services Department of Saudi Aramco, Dhahran.

2.2 Direct all requests to deviate from this specification in writing to the Company or

Buyer Representative, who shall follow internal company procedure SAEP-302 

and forward such requests to the Manager, Consulting Services Department of

Saudi Aramco, Dhahran.

3 References

All referenced specifications, standards, codes, forms, drawings and similar material

shall be of the latest issue (including all revisions, addenda and supplements) unlessstated otherwise.

The design and fabrication of the metal building system shall conform to the applicable

sections of the following referenced codes and standards unless indicated otherwise inthis specification. In the event of conflicting criteria in the referenced documents, the

most stringent requirement shall be used.

3.1 Saudi Aramco References

Saudi Aramco Engineering Procedures

SAEP-302  Instructions for Obtaining a Waiver of a

 Mandatory Saudi Aramco Engineering

 Requirement

Page 3: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 3/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 3 of 31

SAEP-1142  Qualification of Non-Saudi Aramco NDT

Personnel

Saudi Aramco Engineering Standards

SAES-A-112  Meteorological and Seismic Design Data

SAES-H-100  Painting Requirements for Industrial Facilities

Saudi Aramco Inspection Requirements

Form 175-120200  Pre-Engineered Metal Buildings

3.2 Industry Codes and Standards

Architectural Aluminum Manufacturers Association

 AAMA 701 Combined Voluntary Specification for PileWeather Strip

American Institute of Steel Construction

 AISC Manual of Steel Construction, Allowable Stress

 Design - Ninth Edition

 AISC Specification for Structural Joints Using

 ASTM A325 or A490 Bolts

 AISC Design Guide No. 16: Flush and Extended

 Multiple-Row Moment End-Plate Connections

 AISC Design Guide No. 7: Industrial Buildings

American Iron and Steel Institute

 AISI Cold-Formed Steel Design Manual

 AISI Design of Light Gage Steel Diaphragms

American Society of Civil Engineers (ASCE)

 ASCE 7-05 Minimum Design Loads for Buildings and Other

Structures

American Society for Testing and Materials (ASTM)

 ASTM A1 Standard Specification for Carbon Steel Tee Rails

 ASTM A36/A36M Standard Specification for Carbon Structural Steel

 ASTM A53/A53M Standard Specification for Pipe, Black and Hot-

 Dipped, Zinc-Coated, Welded and Seamless

Page 4: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 4/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 4 of 31

 ASTM A106/A106M Standard Specification for Seamless Carbon Steel

Pipe for High-Temperature Service

 ASTM A123/A123M Standard Specification for Zinc (Hot-DipGalvanized) Coatings on Iron and Steel

Products

 ASTM A153/A153M Standard Specification for Zinc Coating (Hot-Dip)

on Iron and Steel Hardware

 ASTM A194/A194M Standard Specification for Carbon and Alloy Steel

 Nuts for Bolts for High-Pressure and High-

Temperature Service

 ASTM A242/A242M Standard Specification for High-Strength Low-

 Alloy Structural Steel

 ASTM A307 Standard Specification for Carbon Steel Bolts and

Studs, 60000 psi Tensile Strength

 ASTM A325 Standard Specification for Structural Bolts, Steel,

 Heat Treated, 120/105 ksi Minimum Tensile

Strength

 ASTM A325M Standard Specification for High-Strength Bolts for

Structural Steel Joints (Metric)

 ASTM A449 Standard Specification for Quenched and

Tempered Steel Bolts and Studs

 ASTM A475 Standard Specification for Zinc-Coated Steel WireStrand

 ASTM A500 Standard Specification for Cold-Formed Welded

and Seamless Carbon Steel Structural Tubing

in Rounds and Shapes

 ASTM A501 Standard Specification for Hot-Formed Welded

and Seamless Carbon Steel Structural Tubing

 ASTM A529/A529M Standard Specification for High-Strength Carbon-

 Manganese Steel of Structural Quality

 ASTM A563 Standard Specification for Carbon and Alloy Steel Nuts

 ASTM A563M Standard Specification for Carbon and Alloy Steel

 Nuts (Metric)

 ASTM A572/A572M Standard Specification for High-Strength Low-

 Alloy Columbium-Vanadium Structural Steel

Page 5: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 5/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 5 of 31

 ASTM A653/A653M Standard Specification for Steel Sheet, Zinc-

Coated (Galvanized) or Zinc-Iron Alloy-Coated

(Galvannealed) by the Hot-Dip Process

 ASTM A759 Standard Specification for Carbon Steel Crane

 Rails

 ASTM A792/A792M Standard Specification for Steel Sheet, 55%

 Aluminum-Zinc Alloy-Coated by the Hot-Dip

Process

 ASTM A992/A992M Standard Specification for Structural Steel Shapes

 ASTM A1008/A1008M Standard Specification for Steel, Sheet, Cold-

 Rolled, Carbon, Structural, High-Strength

 Low-Alloy and High-Strength Low-Alloy with

 Improved Formability

(NOTE: For the purposes of 12-SAMSS-014, ASTM A1008/A1008M replaces ASTM A607, whichhas been discontinued by ASTM.)

 ASTM A1011/A1011M Standard Specification for Steel, Sheet and Strip,

 Hot-Rolled, Carbon, Structural, High-Strength

 Low-Alloy and High-Strength Low-Alloy with

 Improved Formability

(NOTE: For the purposes of 12-SAMSS-014, ASTM A1011/A1011M replaces ASTM A715, which

has been discontinued by ASTM.)

 ASTM B221 Standard Specification for Aluminum and

 Aluminum-Alloy Extruded Bars, Rods, Wire,

Profiles, and Tubes

 ASTM B221M Standard Specification for Aluminum and

 Aluminum-Alloy Extruded Bars, Rods, Wire,

Profiles, and Tubes (Metric)

 ASTM B695 Standard Specification for Coatings of Zinc

 Mechanically Deposited on Iron and Steel

 ASTM C509 Standard Specification for Elastomeric Cellular

Preformed Gasket and Sealing Material

 ASTM C1036 Standard Specification for Flat Glass

 ASTM D1494 Standard Test Method for Diffuse Light

Transmission Factor of Reinforced Plastics

Panels

Page 6: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 6/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 6 of 31

 ASTM D2000 Standard Classification System for Rubber

Products in Automotive Applications

 ASTM D2287 Standard Specification for Nonrigid VinylChloride Polymer and Copolymer Molding and

 Extrusion Compounds

 ASTM F436 Standard Specification for Hardened Steel

Washers

 ASTM F436M Standard Specification for Hardened Steel

Washers (Metric)

 ASTM F844 Washers, Steel, Plain (Flat), Unhardened for

General Use

American Welding Society AWS D1.1 Structural Welding Code - Steel

 AWS D1.3 Structural Welding Code - Sheet Steel

Crane Manufacturers Association of America

CMAA SPEC #70 Specification for Electrical Overhead Traveling

Cranes

CMAA SPEC #74 Specification for Top Running and Under Running

Single Girder Electrical Traveling Cranes

Utilizing Under Running Trolley Hoist

Flat Glass Marketing Association

Glazing Manual

International Code Council

2006 International Building Code

International Electrotechnical Commission

 IEC 529 Degrees of Protection Provided by Enclosures

Metal Building Manufacturers Association

2006 Metal Building Systems Manual

Page 7: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 7/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 7 of 31

 National Electrical Manufacturers Association

 NEMA 250 Enclosures for Electrical Equipment

(1000 Volts Maximum) NEMA MG 1 Motors and Generators

Process Industry Practices

 ARS08111  Standard Steel Doors and Frames Specification

 ARS08710  Door Hardware Specification

4 General

4.1 The materials furnished shall include the structural framing, roofing, siding,

anchor bolts, flashing and trim, leveling plates, doors, windows, hardware,fasteners, sealants, and any other component parts for the metal buildings as

specified in the order and as required to make a complete system.

4.2 Unless otherwise provided in the Purchase Order the metal building does not

include:

a) Reinforced concrete foundations, grade beams and/or floor slabs.

 b) Grouting or filling of any kind under columns or door jambs or in a recess

at the base of wall covering panels.

c) Interior downspouts or their drains for valley or parapet gutters, either

under floor or otherwise.d) Materials which are required for the assembly or installation of accessories

supplied by others.

e) Glass for openings other than doors and windows.

f) Interior finishing material, including partition material, except for liner

 panels.

g) Electrical equipment and wiring.

h) Mechanical equipment, including exhaust fans.

i) Masonry materials.

 j) Field painting.

4.3 Building Description

4.3.1 The building type and dimensions shall be in accordance with the

drawings or detailed description attached to the Purchase Order.

Page 8: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 8/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 8 of 31

4.3.2 The minimum roof slope shall be not less than 1:12 for single-sheetand sandwich panel roofs with screw fasteners that penetrate the roof

sheet(s). The minimum roof slope for standing-seam roof systems

shall not be less than 1:25.

4.3.3 The following information will be provided by the buyer using the Pre-Engineered Metal Buildings Design Data Sheet (Attachment 1 to this

specification):

a) Building plans and/or description.

 b) Location of building (i.e., whether or not in coastal area). Unlessspecified otherwise in the Purchase Order, coastal areas are

defined as all locations within one kilometer from the shoreline

of the Arabian Gulf; all of the Ras Tanura Refinery and

Terminal; and within three kilometers from the shoreline of theRed Sea.

c) The building classification based on the nature of occupancy, as

 per 2006 IBC, Table 1604.5.

d) Maximum allowable heat transmission coefficient U and designinternal temperature (for walls and roof).

e) Glazing to be provided (yes or no).

f) Panels to be primed or completely pre-painted.

g) Floor or mezzanine live loads for use or occupancy that are not

defined in this specification (if applicable).

h) Crane capacities and service classifications in accordance withCMAA No. 70 or No. 74 Specifications (as applicable).

i) Collateral Loads - The weight of additional permanent materials

supported from the building frame such as mechanical systems,

electrical systems, sprinklers, ceilings and partitions (if designedand/or installed by others). Drawings shall be furnished that

clearly indicate the location and magnitude of these loads.

 j) Coating systems including colors for wall and roof panels and

structural members.

Commentary Note:

 All coating systems shall comply with SAES-H-Series Standardsor approved in writing to be suitable for the intended purpose bySaudi Aramco, also see paragraph 7.1.

k) Louver type (see 8.9), if applicable.

Page 9: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 9/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 9 of 31

The Vendor shall contact the Buyer in case all or some of the requiredinformation is missing. The Vendor shall inform the Buyer in writing

of any requirement(s) in this Specification that cannot be met during

the early bidding stage.

4.4 All framing members shall be made from structural steel designed and shopfabricated for bolted field assembly, unless otherwise noted on erection

drawings.

4.5 All framing members shall carry an easily visible identifying piece marks.

5 Design

5.1 Design Loads and Load Combinations

5.1.1 Minimum roof live loads and its design application shall be inaccordance with the requirements of the 2006 IBC, Section 1607.11, or

as set forth in Table 1607.1.

5.1.2 Floor design live loads shall conform to Section 1607 and Table1607.1 of the 2006 IBC. For occupancies or uses not defined, Saudi

Aramco shall be contacted for a ruling on the design values prior to the

start of the design.

5.1.3 Snow loads are not required for buildings located in Saudi Arabiaunless specifically called for in the purchase documents.

5.1.4 The design of pre-engineered buildings for wind and earthquake forces

shall be in compliance with Chapter 16 of the 2006 IBC.

5.1.4.1 SAES-A-112 shall be used to determine basic wind speed andseismic zone values for design.

5.1.4.2 All buildings shall be considered as Category IV "essentialfacilities" for selection of the importance factors in IBC 2006

Table 1604.5, unless indicated otherwise in the purchase

documents.

5.1.5 Crane beams, support brackets, connections to columns or roof beams,and all other components related to cranes, shall be designed for theapplicable crane loads as per Section II of the MBMA's 2006 Metal

Building Systems Manual.

5.1.6 The roof framing and the building columns shall be designed tosupport collateral loads that are supported from the roof framing such

as A.C. ducts, false ceiling, light fixtures and piping. The minimum

Page 10: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 10/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 10 of 31

design collateral load shall not be less than 0.25 kN/m² (5 lb/ft²).These loads shall be specified within the purchase documents if

designed by others.

5.1.7 Thermal loads shall be based on temperature difference that is based onthe temperature differential between the Highest and Lowest One-Day

Mean Temperature per SAES-A-112 plus 20°C.

5.1.8 Load combinations shall be in accordance with Section 1605 of the

2006 IBC.

5.2 Serviceability

The serviceability requirements for deflection, drift, and drainage to be used in

the design of PEB buildings shall be in accordance with MBMA 2006 MetalBuilding Systems Manual, Section III.

Commentary Note:

 A reduction factor of 0.706 (or 0.842) may be applied to wind force values

calculated as per SAES-A-112 design data, with an importance factor I = 1.0, toapproximate the equivalent 10 year mean recurrence interval (MRI) wind force,which is used for some MBMA serviceability criteria. Reference ASCE 7-05,Table C6-7.

Additionally, the lateral drift (displacement) of the building frame shall not inany way hamper the operation of equipment, doors, mechanical devices, storage

racks, cranes or other items which are not attached to the building frame.

Serviceability requirements related to floor vibrations caused by walkingexcitations shall comply with the criteria of AISC Design Guide No. 11: Floor

Vibrations Due to Human Activity.

5.3 Special Design Requirements

5.3.1 Crane runway beams shall be fabricated from hot-rolled structural steelshapes. Overhead crane beams and crane support bracket connections

shall utilize locknuts on all bolts to prevent loosening from vibration.

5.3.2 Jib crane support columns shall be checked for all load combinationsover the full swing of the jib crane. Deflection limits for jib cranes

shall include the portion of deflection resulting from the deformation

of the support column under the applied jib crane load.

5.3.3 Sag rods shall be furnished as necessary to support wall girts. A beamof sufficient strength to support the sag rod loads shall be furnished at

the top of the wall, as applicable.

Page 11: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 11/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 11 of 31

5.3.4 An eaves strut shall be furnished on the building column lines to provide an uninterrupted load path for forces being carried by the

 building's vertical bracing system.

5.3.5 The minimum thicknesses used in built-up members shall be 5 mm forflange plates and 3.5 mm for webs.

5.3.6 The minimum thickness of cold-formed steel members shall be 1.5 mm.

5.3.7 When it is desirable to provide for movement in a connection to

accommodate steel expansion, the bolts that are installed in slottedholes shall be finger tight with double nuts to prevent loosening.

5.3.8 All Slip-Critical connections shall be clearly marked on the shop

drawings.

5.3.9 Slip-Critical joints shall have uncoated faying surfaces or be coatedwith approved slip resistant paint, per AISC Specification for

Structural Joints using ASTM A325 or A490 Bolts.

5.3.10 Flush end-plate moment connections shall comply with AISC/MBMADesign Guide No. 16: Flush and Extended Multiple-Row Moment

End-Plate Connections.

5.3.11 Expansion joints shall be located and designed as recommended inAISC Design Guide No. 7: Industrial Buildings.

5.3.12 The use of cables for bracing is not allowed in pre-engineered metal

 buildings for Saudi Aramco facilities.

6 Material Specifications

All materials shall be new, free of defects and meet or exceed the physical requirements

of the design and fabrication process.

6.1 Structural Steel Shapes, Plates and Sheet

6.1.1 All steel for hot-rolled structural shapes, built-up shapes, plates and

tubes shall conform to one of the following specifications:

 ASTM A36/A36M

 ASTM A242/A242M

 ASTM A501

 ASTM A529/A529M

Page 12: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 12/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 12 of 31

 ASTM A572/A572M

 ASTM A992/A992M

6.1.2 All crane rails shall conform to one of the following specifications:

ASTM A1 for rails less 104 lb/yd

ASTM A759 for rails 104 lb/yd to 175 lb/yd

6.1.3 All steel for cold formed structural shapes shall conform to one of the

following specifications:

 ASTM A653/A653M

 ASTM A1008/A1008M

 ASTM A1011/A1011M

6.1.4 All material for cold formed tubing in rounds and shapes shall conform

to ASTM A500 Grade A, or better.

6.1.5 Galvanized steel sheet shall conform to ASTM A653/A653M GradeSS Class 1, Grade 50 (Grade 340) or better and shall be galvanized in

accordance with coating designation G90 (Z275). In addition, a milltreatment shall aid in the prevention of oxidation on the zinc coated

surfaces.

6.1.6 Aluminum-zinc alloy-coated steel sheet shall conform to ASTM

A792/A792M Grade 345 MPa (50 ksi) with a coating designation ofAZ50 (AZM150).

6.2 Structural Bolts, Nuts & Washers

6.2.1 All primary bolted connections, as shown on drawings, shall befurnished with high-strength bolts conforming to ASTM A325 or

ASTM A325M, Type-1, galvanized. All high-strength bolts are to be

tightened by the procedures outlined in AISC – "Specification forStructural Joints Using ASTM A325 or ASTM A490 Bolts".

6.2.2 All high-strength bolts shall be furnished with nuts and washers. Nuts

for high-strength bolts shall conform to either ASTM A194/A194M orASTM A563 or ASTM A563M. Washers shall conform to ASTM

F436 or ASTM F436M.

6.2.3 When high-strength bolts are required in sizes less than ½" diameter,

the bolts shall conform to ASTM A449, Type 1, galvanized.

6.2.4 All primary bolted connections shall contain at least two bolts.

Page 13: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 13/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 13 of 31

6.2.5 All machine bolts shall conform to ASTM A307 and shall be galvanizedto either ASTM A153/A153M or ASTM B695. ASTM A307 bolts are

only allowed for the attachment of secondary members such as girts and

 purlins, and items such as stair treads, handrail, ladders, etc. WhenASTM A307 bolts are used, the sizes used should not be the same

diameter as any A325/A325M or A449 bolts used for the same Purchase

Order. ASTM A307 bolts are to be limited to sizes 5/8" diameter andsmaller.

6.2.6 ASTM A307 bolts shall be furnished with nuts that conform to

ASTM A563 and washers conforming to ASTM F436, ASTM F436Mor ASTM F844.

6.2.7 Eyebolts used to attach cable bracing shall be forged steel, load rated

eyebolts and shall be galvanized to ASTM A153/153M. The ultimateload for the eyebolt shall be 5 times the safe working load limit.

6.3 Structural pipe shall conform to ASTM A53/A53M Type E or S, Grade B orASTM A106/A106M, Grade B.

6.4 Wire strand (cable) shall conform to ASTM A475, zinc coated, extra highstrength (7 wires per strand).

6.5 Roof and Wall Coverings

Unless indicated in the Purchase Order, the vendor shall select either single

sheet or sandwich type roof and wall panels based on the required maximumheat transmission coefficient and required internal design temperature. The

choice of panels is subject to prior written approval of the buyer.

6.5.1 Roof Panels (Single Sheet Roof Panels)

a) Roof panels shall be made of a minimum 0.5 mm (26 gage) thick

galvanized or aluminum-zinc alloy-coated steel sheet. Roof panels for buildings in coastal areas, or as specified in the

 purchase order, shall be made of a minimum 0.7 mm thickness

aluminum sheet.

 b) Roof panels shall be ribbed to provide adequate rigidity.c) Panels shall provide a net coverage width of 900 mm (3 ft

nominal) minimum. Roof panels shall be laid full length from

ridge to eaves where possible to minimize the possibility of water

leaks at the end laps. When required, end lap shall be a minimumof 100 mm (4 inches nominal).

d) Panel joints shall interlock in such a way as to provide complete

Page 14: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 14/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 14 of 31

water-tightness and an allowance for thermal expansion for athermal differential of 67°C.

e) Material for prepainted galvanized steel panels shall have aminimum yield of 230 MPa (33 ksi) and conform to ASTM

A653/A653M SS Grade 33 (Grade 230) or better and galvanizedin accordance with coating designation of G90 (Z275).

f) Aluminum-zinc alloy-coated steel sheet panels shall conform to

ASTM A792/A792M Grade 345 MPa (50ksi) with a coating

designation of AZ50 (AZM150).

g) The roof panels shall be insulated to provide the maximum heat

transmission coefficient (U) as specified in the Purchase Order.

However, the maximum "U" coefficient shall not be greater than

0.45 W/(m² K) [0.08 BTU/(hr ft² °F)] through the installed roof.

h) The use of fiberglass insulation shall meet the following

conditions: flexible; resilient; odorless; shall not contribute to

corrosion of steel or aluminum; flame spread rating of 25 or less

and shall comply with the provisions of Section 707 of theUniform Building Code; facing shall cover the width of the

fiberglass blanket plus two flanges each 50 mm wide; vapor

 barrier to be aluminum foil or equal placed on the outside.Interior exposed insulation shall receive a quilted covering

(preferably a fiberglass scrim) on the interior surface to protect

the insulation.

i) Fasteners shall be provided to secure the roof panels against winduplift, mechanical movement, and to maintain water-tight panel

 joints. Particular care should be taken to ensure compliance with

UBC Section 1622 and Table 16-H with regard to local wind pressure effects.

6.5.2 Alternate Roof Panels (Sandwich Roof Panels): Further to the

requirements of paragraph 6.5.1, sandwich roof panels shall complywith the following:

a) Roof panels shall be self contained, factory assembled foam

 plastic insulated units having a nominal covering width of notless than 900 mm (3 ft nominal) unless approved otherwise bySaudi Aramco.

 b) The exterior face sheet shall be made of minimum 0.5 mm (26

gage) thick galvanized or aluminum-zinc alloy-coated sheet steel

and shall be formed architecturally to provide adequate rigidity.For buildings in coastal areas, or as specified in the purchase

Page 15: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 15/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 15 of 31

order the external face sheet shall be made of a minimum 0.7 mmthickness aluminum sheet.

c) The interior face sheet shall be minimum 0.5 mm (26 gage) thickgalvanized or aluminum-zinc alloy-coated sheet steel and shall be

formed into a plane surface.

d) Foam plastic insulation shall have a flame spread rating of 25 or

less. The vendor is cautioned that the Section 2602 of the

Uniform Building Code contains certain restrictive requirements

for the use of foam plastic insulation that must be complied with.Accordingly, the building design should incorporate appropriate

details which will satisfy the code requirements.

6.5.3 Wall Panels (Single sheet wall panels)

a) Wall panels shall have nominal covering width not less than900 mm (3 ft nominal) unless approved otherwise by Saudi

Aramco.

 b) The panel shall be made of a minimum 0.5 mm (26 gage) thick

galvanized or aluminum-zinc alloy-coated steel sheet, oraluminum as applicable, formed architecturally consistent with

the ribbing of the roof.

c) Wall panels for buildings in coastal areas, or as specified in the

Purchase Order, shall be minimum 0.7 mm thickness aluminumand shall be ribbed to provide adequate rigidity.

d) The panels shall be in one length from base to building eaves.

Wall panel length for above and below windows shall be as

indicated on the drawings. Wall panels shall be supported at their base by a raised curb or grade beam that is a minimum of 150

mm above the building floor level. Wall panels shall extend not

less than 38 mm below the concrete support, and sit in a recess inthe concrete grade beam or curb to close off the lower end of the

 panels. The panels shall be self-draining to the exterior.

e) Galvanized sill angles shall be provided to secure wall panels to

the grade beam or curb.

f) Wall panels shall be insulated to provide the maximum heattransmission coefficient (U) specified in the Purchase Order.

However, the maximum "U" coefficient shall be as follows:

1) The exterior walls of areas indicated as non-air conditioned

are to have a "U" coefficient not greater than 1.19 W/(m² K){0.21 BTU/ (hr ft² °F)}.

Page 16: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 16/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 16 of 31

2) The exterior walls of air conditioned rooms are to have a"U" coefficient not greater than 0.568 W/(m² K) {0.10

BTU/(hr ft² °F)}.

g) The use of fiberglass insulation shall meet the following

conditions: flexible; resilient; odorless; shall not contribute tocorrosion of steel or aluminum; flame spread rating of 25 or less

and shall comply with the provisions Section 707 of the Uniform

Building Code; facing shall cover the width of the fiberglass blanket plus two flanges each 50 mm wide; vapor barrier to be

aluminum foil or equal placed on the outside. Interior exposed

insulation shall receive a quilted covering (preferably a fiberglassscrim) on the interior surface to protect the insulation. When

required by the Purchase Order, additional protection for the

insulation shall be provided (such as a liner panel).

6.5.4 Alternate Wall Panels (Sandwich Wall Panels): In addition to therequirements of paragraph 6.5.3, sandwich wall panels shall comply

with the following:

a) Wall panels shall be self contained, factory assembled foam plastic insulated units, having a nominal covering width not less

than 900 mm (3 ft nominal) unless approved otherwise by Saudi

Aramco.

 b) The prepainted exterior face sheet shall be made of a minimum0.5 mm (26 gage) galvanized or aluminum-zinc alloy-coated steel

sheet and shall be formed architecturally to provide adequate

rigidity. For buildings in coastal areas, or as specified in the

 purchase order the prepainted exterior face sheet shall be made ofa minimum 0.7 mm thickness aluminum sheet.

c) The prepainted interior face sheet shall be made of a minimum

0.5 mm (26 gage) galvanized or aluminum-zinc alloy-coated steel

sheet shall be formed into a plane surface.

d) Metal to metal contact between the interior and exterior faces on

vertical edges shall be prevented.

e) The vertical joints shall overlap having a thermal break and providing for mechanical, as well as thermal, horizontalmovement. The panel design shall provide for expansion and/or

contraction as caused by an ambient temperature range without

causing harmful buckling, opening of joints, or other detrimental

effects.

e) Foam plastic insulation shall have a flame spread rating of 25 or

less. The vendor is cautioned that the Section 2602 of the

Page 17: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 17/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 17 of 31

Uniform Building Code contains certain restrictive requirementsfor the use of foam plastic insulation that must be complied with.

Accordingly, building design should incorporate appropriate

details which will satisfy the code requirements.

6.6 Roof and Wall Fasteners

All panels shall be attached to secondary framing members by means of self-

drilling or self-tapping screws. The screws shall be hex head carbon steel

screws assembled with an EPDM washer and mechanically zinc coating inaccordance with ASTM B695, Class 50. However, in coastal areas, as defined

in paragraph 4.3.3(b), an austenitic (300 series) stainless steel fasteners shall be

used. Fastener heads shall be coated the same color as the panels.

6.7 Sealants and Closures

6.7.1 Sealant

a) A sealing compound shall be provided to seal ends and side laps

of panels. The material shall consist of a blend of non-toxic,synthetic resin base ingredients and inert extenders. Asphalt or

asphalt derivatives are not permitted.

 b) The application of sealant shall be of a cross-sectional area to

 provide a positive seal between adjacent surfaces.

c) The material shall have sufficient adhesion to metal and plastic so

as to remain in place during normal handling operations.Adhesive tensile strength shall be a minimum of 28 kPa (4 psi).

d) The sealing compound shall prevent the entry of water by

capillary action or otherwise when used in a properly installedroof or wall system.

6.7.2 Flashing, Trim and Closures

a) Flashing and/or trim shall be furnished at the rake, corners, eaves,

at framed openings, and wherever necessary to provide weathertightness and a finished appearance. Color will be as specified in

the purchase order. b) Galvanized or aluminum-zinc steel for flashing, metal closures,

trim and other miscellaneous uses shall be 0.5 mm (26 gage)conforming paragraphs 6.1.5 or 6.1.6 of this standard.

c) A formed panel matching the slope and profile of adjoining

 panels shall be provided along the building ridge.

Page 18: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 18/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 18 of 31

d) Preformed closures matching the profile of the panel shall beinstalled along the eave and other locations as specified on

drawings or as required for weather tightness, and may be made

of solid or closed cell plastic materials subject to Buyer'sapproval.

7 Finishes

7.1 Finish Panel Paint

Vendor shall submit detailed specifications covering the finish of exterior andinterior surfaces of sheet metal paneling, trim and related components, for Saudi

Aramco written approval. The procedures shall cover surface cleaning, pretreatments, quality of coating materials, application of primer and finish,

curing or baking, thickness of coating and color. The Vendor shall maintain thequality of work and records as specified in SAES-H-100.

7.2 Dissimilar Materials

Dissimilar Materials which are not compatible with the adjoining materialswhen exposed to moisture must be separated by means of approved coatings,

gaskets, or other effective means. Aluminum alloys shall be consideredcompatible with zinc and cadmium coated surfaces and the 300 and 400 AISI

Series Stainless Steel Alloys and do not require application of barrier material.

8 Accessories

8.1 General

Standard manufacturer's building accessories may be furnished if the accessoriesequal or exceed the minimum requirements of this Section.

8.2 Aluminum Windows

Aluminum windows shall be designed and constructed for integral installationwith the system. Unless required otherwise in the contract documents, provide

 building manufacturer's standard insulated double-pane window (AAMA HS-

C20 horizontal sliding, commercial grade) with medium natural anodized finish(NAAMM AA-C22A31). (Alternative if selected by buyer: fixed sash AAMA,

Grade C20.)

8.2.1 Aluminum Extruded Frame: Material shall comply with ASTM B221or ASTM B221M.

Page 19: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 19/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 19 of 31

8.2.1.1 Provide "thermal-break" construction. Separate frame andsash members exposed on the exterior from metal parts

exposed on the interior by a continuous gasket or filler of

rubber or plastic, locked into construction.

8.2.1.2 Mullions: Provide mullions between adjacent windows,fabricated of extruded aluminum matching the finish of

window units.

8.2.2 Fasteners: Provide aluminum, stainless steel, or other materialwarranted by the manufacturer to be non-corrosive and compatible

with aluminum window members, trim, hardware, anchors, and other

components of window units.

8.2.3 Anchors, Clips, and Window Accessories: Depending on strength andcorrosion-inhibiting requirements, fabricate from aluminum, stainless

steel, or hot-dip zinc-coated steel (complying with ASTMA123/A123M).

8.2.4 Compression Glazing Strips and Weather-Stripping: Provide molded

EPDM, neoprene gaskets complying with ASTM D2000 designation2BC415 to 3BC620, molded PVC gaskets complying with ASTM

D2287, Grade 4, or molded expanded neoprene gaskets complying

with ASTM C509.

8.2.5 Sliding Weather-Stripping: Provide woven pile weather-stripping of

wool, polypropylene, or nylon pile and resin-impregnated backingfabric, with aluminum backing strip. Comply with AAMA 701.

8.2.6 Sealants: Provide manufacturer's standard for the joint size or

anticipated movement. The sealant shall remain permanently elasticand be non-shrinking and non-migrating.

8.2.7 Insect Screens: Provide removable insect screen on each operable

exterior sash, with finish matching window.

8.2.8 Pre-glazed Construction: To the greatest extent possible, glaze units atthe shop before installation.

8.2.9 Glass: Unless required otherwise in the contract documents, comply

with ASTM C1036 for glass type, class, quality, style, kind, and formand with recommendations of the FGMA Glazing Manual.

8.3 Personnel Doors and Door Hardware

8.3.1 Doors shall comply with PIP Specification ARS08111. Door leaves

Page 20: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 20/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 20 of 31

shall be 45 mm thick, full flush, fabricated from Class G90 (Z275) zinccoated sheets or better. Jamb extensions shall be furnished where

required to provide secure attachment to the wall framing.

8.3.2 Door hardware shall comply with PIP Specification ARS08710.

8.3.3 Each door leaf shall be installed with three 114 mm x 114 mmgalvanized steel, interlocking, template butt hinges.

8.3.4 Door leaves and frames shall be shop-painted with one coat of primer

or finished to match the walls.

8.3.5 The threshold shall be an extruded aluminum shape to provide positiveweather seal.

8.3.6 All exit doors shall be a minimum of 915 mm wide x 2035 mm high.

8.4 Equipment Doors

8.4.1 Door leaves shall be constructed of steel framing and panels asspecified for the walls. The door leaves shall be adequately flashed

and counter-flashed for weather tightness. Large doors may be fieldassembled with bolted connections.

8.4.2 The leaves of sliding doors shall be suspended from a "C" section or

other appropriate structural member as a track header with thegalvanized track field bolted. Trolleys shall be galvanized steel with

dual, nylon wheels. The track and trolleys shall be protected by a

counter-flashed hood. When the door is in the closed position thevertical gaps between the door outer edges and wall shall be

automatically sealed with a closure device.

8.4.3 The doors shall have inside and outside locking devices.

8.4.4 Equipment door jambs and jamb support members shall be finished asspecified for the structural frame.

8.5 Overhead Roll-up Doors

8.5.1 Provide complete overhead roll-up door assemblies including door

curtain, guides, counterbalance, hardware, operators, and installationaccessories as specified herein, unless otherwise required in the

contract documents.

8.5.2 Doors and Frames: Design for the wind loading specified in Paragraph5.1.5.

Page 21: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 21/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 21 of 31

8.5.3 Door Curtain: Provide interlocking steel slat door curtain with one- piece slats for the full length of door width. Form from minimum

0.8mm

(22-gage) or 1mm (20 gage), structural sheet steel.

8.5.4 Bottom Bar: Provide bottom bar on door curtain consisting extrudedaluminum or two 3 mm (1/8") thick angles of the same metal as the

door curtain slats. A flexible rubber, EPDM, vinyl, or neopreneweather seal and cushion bumper shall be provided on the bottom bar.

8.5.5 Vision Panel: Where vision panels are shown, provide ¼" thick cast

thermo-plastic, methyl methacrylate vision panels set in neoprene or

vinyl glazing channels in the arrangement indicated

8.5.6 Weather Seals: At exterior doors, provide 3 mm (1/8") thickcontinuous rubber or neoprene sheet weather seals on metal pressure

 bars secured to inside of curtain coil hood. At doorjambs, use 3 mm(1/8") thick continuous strip secured to exterior side of jamb guide.

8.5.7 Hood: Form to enclose the coiled curtain and operating mechanism

entirely at the opening head and to act as a weather seal. Contour tosuit end brackets to which attached. Roll and reinforce top and bottom

edges for stiffness. Provide closed ends for surface-mounted hoods

and any portion of between-jamb mounting projecting beyond wall

face. Provide intermediate support brackets to prevent sag. Fabricatehoods for steel doors from minimum 24-gage zinc-coated steel sheet

(phosphate-treat before fabrication).

8.5.8 Shop Finish: Provide shop finish as specified in the contractdocuments.

8.5.9 Chain Hoist Operation: Provide operator assembly consisting of an

endless cadmium-plated alloy steel hand chain, chain pocket wheel and

guard, and geared reduction unit with maximum 16 kg (35 lb) pull fordoor operation. Design chain hoist with self-locking mechanism

allowing curtain to be stopped at any point in its travel and to remain in

that position until movement is reactivated. Furnish chain with chain

holder secured to operator guide.

8.5.10 Electric Door Operators: Furnish electric operator assembly of size

and capacity recommended by manufacturer. Operators shall becomplete with NEMA MG 1 or IEC-rated motor and factory-prewired

motor controls, gear reduction unit, solenoid-operated brake, remote

control stations, control devices, conduit and wiring from controls to

motor and central stations, and accessories required for proper

Page 22: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 22/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 22 of 31

operation. Electric operator shall meet the buyer's area classificationrequirements in accordance with the contract documents.

a. Provide a hand-operated disconnect or mechanism forautomatically engaging a sprocket and chain operator and

releasing the brake for emergency manual operation. Includeinterlock device to automatically prevent motor from operating

when manual operator is engaged.

 b. Electric Motors: Provide high-starting torque, reversible, constant

duty; Class A insulated electric motor with overload protection.Motors shall be sized to move door in either direction, from any

 position, at not less than 200 mm (2 /3 ft) or more than 300 mm

(1 ft) per second. Coordinate wiring requirements and currentcharacteristics of motors with building electrical system.

c. Furnish open-drip-proof-type motor and controller with NEMA

250, Type 1 enclosure or IEC equivalent.

d. Remote Control Station: Provide NEMA or IEC-approved,

momentary contact, three-button control station with push-buttoncontrols labeled "open," "close," and "stop."

•  Interior Units: Full-guarded, surface-mounted, heavy-dutyremote control stations, with general-purpose NEMA 250,

Type 1 enclosure or IEC equivalent.

•  Exterior Units: Full-guarded, surface-mounted, standard-duty

weatherproof-type remote control stations with NEMA 250,Type 4 enclosures or IEC equivalent. Provide units designed

for key operation.

e. Automatic Reversing Control: Furnish each door with an electric

automatic safety switch, extending the full width of the door bottom, located within a neoprene or rubber astragal mounted to

 bottom rail of the door or an electric eye (should be "electric

eye") system. The mechanism shall be manufactured so thatcontact with an obstruction before fully closing will immediately

stop downward travel and reverse the travel direction so that the

door is returned to the fully opened position.

8.6 Translucent Wall and Roof Panels

8.6.1 Wall and roof light-transmitting panels shall conform to the wall androof panel configurations and shall be a minimum of 2.4 kg/m

2 (8-oz.),

one-piece, flexible, translucent, fiberglass-reinforced resins. Roof

 panels shall be capable of supporting a 200-pound concentrated load

Page 23: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 23/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 23 of 31

without failure. The panels shall be uniformly white with heattransmission of 25% and light transmission of 55% in accordance with

ASTM D1494, unless noted otherwise in the contract documents. Other

types of skylights may be used when specified or approved by buyer.

8.6.2 Panels are to be fire retardant; having a flame spread rating of 25 or less.

8.7 Eave Gutters and Downspouts

8.7.1 Eave Gutters shall be box shaped 0.5 mm (26 gage) galvanized or

aluminum-zinc alloy-coated steel. The outside face of the gutter shall be supported with 2.0 mm galvanized steel straps to the eave member

at a maximum spacing of 1000 mm.

8.7.2 Downspouts shall be round or rectangular shaped 0.5 mm (26 gage)galvanized or aluminum-zinc alloy-coated steel. Downspouts shall

have a 45 degree elbow at the bottom and shall be supported by

attachment to the wall covering at 3 meters maximum spacing.

8.8 Ventilators and Roof Openings

Ventilators and roof openings shall be weather tight and shall be framed and

 braced adequately to sustain the design wind and roof loads around the

openings. Ventilators shall be furnished with bird screen.

8.9 Louvers

Louver frames shall be fabricated from 1.22 mm (18 gage) galvanized steel, and

 blades from 0.91 mm (20 gage) galvanized steel. Louvers shall have blades ofthe overlapping type providing maximum weather tightness while allowing free

air flow. Louvers are to be fixed sand trap type or adjustable by means of a

crank, as specified in the Purchase Documents. Louver frames and bladefabricated from extruded aluminum sheet of 1.22 mm (18 gage) thickness are

also acceptable.

8.9.1 Provide vertical mullions for louvers 1220 mm (4 ft) and wider with

one mullion for each 1220 mm (4 ft) of width.

8.9.2 Provide flanges on interior face of frames where air intake or exhaustlouvers are indicated to be connected with mechanically operated

dampers or metal ductwork.

8.9.3 Provide galvanized steel insect/bird screens in rewirable frames onexterior face of louvers. Grid dimensions of insect/ bird screen mesh

will be 12 mm square unless a specific size is specified in the purchase

Page 24: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 24/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 24 of 31

order. Secure with clips to ensure ease of removal for cleaning andrewiring. Fabricate screen frames to match louvers.

9 Build ing Foundations

Design: The design of the foundation is not included in the supply of the metal buildingdocumentation. Vendor shall furnish the Buyer with all necessary information to

 properly design the foundations, including loads, anchor bolt details and locations, and

required recesses.

10 Fabrication

10.1 Fabrication

10.1.1 Metal building system structural framing shall be fabricated inaccordance with the requirements of the AISC- "Specification for

Structural Steel for Buildings - Allowable Stress and Plastic Design" or

AISC – "Load and Resistance Factor Design Specification forStructural Steel Buildings".

10.1.2 Welding procedures and individual welders shall be qualified in

accordance with the requirements of ANSI/AWS D1.1 or AWS D1.3for sheet steel. All welding procedures and welding performance

qualification records shall be made available to the Buyer's Inspector

for review. All welders must be properly qualified for the weld

 procedure of the type of welding performed.

10.1.3 All fabricated structural steel shapes such as beams, columns, channelsor tubes shall be either hot rolled, full penetration or double-sided fillet

welded. Single-sided fillet welded structural shapes are not permitted.

10.2 Piece Marking and Identification

All parts and bundles of identical parts shall be clearly marked for identification.Bolts and fasteners shall be packaged according to type, size, and length. Loose

nuts and washers shall be packaged according to size. The shipping documentsshall include a master packing list which shows the quantity, description and

 piece mark of the various parts.

10.3 Inspection and Testing

10.3.1 All NDT procedures shall be submitted to the Inspection Department /Operations Inspection Division (OID) ASNT Level-III for acceptance

 prior to work commencing.

Page 25: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 25/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 25 of 31

10.3.2 The Buyer has the Right to inspect all materials and workmanship, andshall have unrestricted entry to the shop of the PEB Manufacturer at all

times while work is being performed. The Buyer may reject improper,

inferior, defective, or unsuitable materials and workmanship. Allmaterials and workmanship rejected shall be repaired or replaced by

the PEB Manufacturer as directed by the Buyer. The company

inspector shall have access to the vendor's facilities to see that SAES-H-100 quality elements are in place prior to and during blasting,

 priming and coating operations.

10.3.3 The Inspection Test Plan (ITP) shall be provided for review andapproval by the company inspector.

10.3.4 Inspection and testing shall conform to this Specification and Saudi

Aramco Inspection Requirements Form 175-120200 attached to thePurchase Order.

10.3.5 Welding procedures and individual welders shall be qualified inaccordance with the requirements of ANSI/AWS D1.1/D1.1M or

ANSI/AWS D1.3 as appropriate. All welding procedures and welding

 performance qualification records shall be made available to theBuyer's Inspector for review.

10.3.6 Inspection of welding shall be performed in accordance with the

Structural Welding Code, ANSI/AWS D1.1/D1.1M. Ultrasonic testingmay be substituted for radiography if approved by Saudi Aramco

Inspection.

a) All welds shall have 100% visual inspection performed per

ANSI/AWS D1.1. In addition, any strikes, gouges, and otherindications of careless workmanship (such as surface porosity)

shall be removed by grinding.

 b) The butt-welded flange sections for all primary load-bearing

members shall be 100% radiographed at the weld. Primary load- bearing members shall be defined as the main frames and any

members that are part of the lateral load carrying system.

c) Secondary members such as purlins, girts or rafters that are not part of the main sway frame, the butt-welds can be tested asfollows; 10% of the buttwelds of each days production (randomly

selected) shall have radiographic tests performed on the welds.

d) The minimum percent coverage of the specified NDT method

may be increased (at any level up to 100%) if, in the opinion ofthe Company Inspector, the welds are of questionable

Page 26: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 26/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 26 of 31

workmanship or NDT indicates an excessive number of defects.Additional or alternative NDT methods may be used at the

discretion of the Company Inspector in order to assist in

determining the type or extent of defects.

10.3.7 Material test reports for each heat of structural steel, each lot of high-strength and ASTM A307 bolts shall be available for review by the

Buyer. Material test reports shall conform to EN 10204, Type 3.1.

10.3.8 The Buyer may require a quantity of representative samples of boltassemblies which the PEB Manufacturer shall supply to the Buyer for

testing. Testing in accordance with ASTM F606 or ASTM F606M

will be at the Buyer's expense.

10.3.9 If any damage is discovered, or any parts, components, ordocumentation are missing or otherwise defective, the occurrence shall

 be immediately reported to the Buyer in writing.

10.3.10 Shop inspection may include, but not be limited to the following:

Verification of conformance of materials with this Specification and

the drawings. The limits of acceptability and repair of surfaceimperfections for structural steel shall be in accordance with

ASTM A6 / ASTM A6M.

10.3.11 Inspection of high-strength bolted connections shall be in accordance

with AISC Specification for Structural Joints Using ASTM A325 orASTM A490 Bolts.

10.3.12 The buyer reserves the right to inspect and reject all galvanized steel inaccordance with ASTM A123/A123M and ASTM E376.

10.3.13 All web and flange splices shall be spot radiographed per AWS D1.1.

10.3.14 Additional welding inspection beyond that required by the contract or

 purchase order may be requested by the Saudi Aramco Inspection

Department under the guidelines established per AWS D1.1.

10.3.15 Saudi Aramco's inspection and acceptance of the material shall notrelieve the Vendor of his responsibility to comply with all

requirements of the order and material specification, including but not

limited to the requirement that all components shall properly fit whenthe building is erected.

Page 27: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 27/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 27 of 31

11 Drawings and Calculations

11.1 Unless otherwise specified by the Company, the following drawings shall be

furnished:

11.1.1 Proposal Drawings and Technical Specifications

Two copies of the building drawings and technical specifications are to be included in Vendors formal proposal. These drawings are for

 proposal evaluations and become property of the Company.

The Vendor shall list in his proposal any deviations from this SAMSS,and shall state what he intends to furnish as part of the contract.

Failure to list exceptions, if any, shall be construed as acceptance by

the Vendor of these Specifications.

11.1.2 For Approval Drawings

Five sets of preliminary drawings composed of roof framing plans,elevations, and sections through the building shall be furnished for

approval of the Company.

Fabrication of any part of the metal building system by the Vendor prior to receiving approved plans, is done at no liability to the

Company.

11.1.3 Erection Drawings

Five copies of certified erection drawings for the Metal Building

System shall be furnished by the Vendor to the Buyer. Such drawings

and erection instructions shall identify all individual parts of the metal building system in sufficient detail to permit proper erection and

installation of said parts.

11.1.4 Anchor Bolt Plan

Submit within two weeks after award of contract a drawing that clearlyshows the size, location and projection of all anchor bolts for the metal

 building system components and the location and size of anyfoundation block-outs that are required. The minimum anchor bolt size

shall be 20 mm (¾"). All anchor bolts shall be furnished with double

nuts and the projection of the anchor bolt shall be sufficient for twonuts. Unfactored column reactions (magnitude and direction - broken

down by individual load case), and base plate dimensions are also to be

included.

Page 28: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 28/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 28 of 31

11.1.5 All drawings shall be made using SI Metric system of units, unlessinstructed otherwise in writing by the Buyer.

11.2 Drawings not Provided

Detailed shop drawings of individual parts of the metal building system are not

required to be furnished by the Vendor unless requested by the Company.

11.3 Design Calculations

Design calculations shall be assembled in an orderly manner, checked and shall be subject to periodic review as requested by the Company and as required for

the approval of Vendor's drawings.

11.3.1 The building structural design calculations shall include a summary of

all loads and load combinations considered in the design and a clearstatement of design assumptions. All computer models shall beaccompanied by sketches that show joint and member numbers,

support conditions, and loadings. All design information shall be

 based on checked calculations.

11.3.2 Summary Sheet for Deflections and Drifts: A summary sheet shall be

 provided listing the maximum actual deflections in all items such as

 purlins, girts, crane beams, jib cranes and floor beams compared withthe corresponding allowable values. The maximum longitudinal and

transverse drifts of the building shall be listed and compared with

corresponding allowable values.

11.3.3 Load Derivations: The calculations shall show the derivation of allloads such as roof and floor, dead and live loads, crane loads and all

wind and earthquake loads as applicable. The calculations shall deriveall such loads used in the calculations as input for computer analysis so

that any one load used in the input can be traced back in the load

derivation.

When roof or floor metal decking is used as a diaphragm to carrylateral forces, both the metal deck and the deck attachments to the

 building frame shall be designed to transfer the lateral forces and shall

comply with the requirements of AISI, "Design of Light Gage SteelDiaphragms".

11.3.4 The design of all built-up and hot-rolled steel members shall comply

with the AISC - "Manual of Steel Construction, Allowable StressDesign - Ninth Edition" or AISC – "Load and Resistance Factor

Design Specification for Structural Steel Buildings".

Page 29: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 29/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 29 of 31

11.3.5 The design of all cold-formed steel members shall comply with theAISI - "Cold-Formed Steel Design Manual".

12 Packing and Shipping

12.1 Packing shall be done in accordance with Company's packing specification No.18. (not applicable for buildings manufactured in-Kingdom.)

12.2 Sandwich panels shall be packaged for delivery in banded stacks with suitable

foam or cardboard separators between each panel to prevent damage to thefinished paint surfaces. The bands shall also be prevented from damaging the

 panels. Structural steel members shall be suitably separated by timber or similar

during transport and storage.

12.3  Bolts, Nuts and Washers shall be shipped prior to or with the first lot ofstructural steel. Anchor bolts shall be shipped in time to accommodate the

construction schedule for the building foundations.

Revision Summary9 March 2008 Major revision.

Page 30: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 30/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

Page 30 of 31

 Appendix 1 – ASTM Material Equivalency

 ASTM Materials EN Materials ISO Materials JIS Mater ials

ASTM A36/A36M EN 10025-2, Gr S275J0 ISO 630-95, E275 C G3106-95, SM490A

EN 10025-2, Gr S275JR

ASTM A53 ISO 9329-1, TS430 G3454-88, STPG 410

ISO 9330-1, TW430

ASTM A108, G1010 EN 10016-2, C10D ISO 4954, CC 11 X

G1015 EN 10016-2, C15D ISO 4954, CC 15 K

G1020 EN 10016-2, C20D ISO 4954, CC 21 K

ASTM A307 No Substitute No Substitute No SubstituteASTM A325 No Substitute No Substitute No Substitute

ASTM A325M No Substitute ISO 7412 per ASTM A325M No Substitute

ASTM A500 EN 10219-1, S355J0H G3444-94, STK490

G3466-88, STKR490

ASTM A501 EN 10210-1, S275J0H G3444-94, STK490

G3466-88, STKR490

ASTM A563 No Substitute No Substitute No Substitute

ASTM A563M No Substitute ISO 4775 per ASTM A563M No Substitute

ASTM A1011/A1011M EN 10025-2, Gr S235JR ISO 3573, HR1 G3131, SPHC

ASTM A572/A572M, G50 EN 10025-2, Gr S355JR ISO 4950-2, E355DD G3106, SM490YA

G65 EN 10025-2, Gr S450JO ISO 4950-2, E460CC G3106, SM570

ASTM A759 None ISO 5003 E1101, E1103

ASTM A992/A992M EN 10025-2, Gr S355JR ISO 630-95, E355 C G3106, SM490YA

EN 10025-2, Gr S355J0 G3106, SM570

G3136

Note:  The minimum published yield strength may vary based on the material thickness. Refer to the appropriatematerial specification.

Page 31: 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

7/18/2019 12-SAMSS-014 - Pre-Engineered Metal Buildings.pdf

http://slidepdf.com/reader/full/12-samss-014-pre-engineered-metal-buildingspdf 31/31

Document Responsibility: Onshore Structures 12-SAMSS-014

Issue Date: 9 March 2008

 Next Planned Update: 9 March 2013 Pre-Engineered Metal Buildings

 At tachment 1 – Pre-Engineered Metal Bui ld ing Design Data Sheet

Location of Building Site: ___________________________________________________

Building Name: ___________________________________________________

Building Data and Dimensions 

(Refer to drawings and other purchase order

documents)

Building Width ______ mm

Bay Spacing ______ mm

Eave Height ______ mmRoof Slope ______ (See paragraph 4.3.2)

Occupancy Category: ______Wind Importance Factor: ______

Seismic Design Category: ______

(ASCE 7-05, Tables 11.6-1 and 11.6-2)

Glazing to be provided: [ ] Yes [ ] NoLouver Type: [ ] Galvanized [ ] Aluminum

Meteorological Data

Wind Data: Refer to SAES-A-112

Basic Wind Speed: ______ kph

Coastal Area: [ ] Yes (See paragraph 4.3.3.b)

[ ] No

Insulation Requirements

Building is Air Conditioned: [ ] Yes [ ] No

Transmission (U)

Roof: _____ W/(m² K) *

Exterior Walls: _____ W/(m² K) *

* If the heat transmission coefficients (U) are not

specified, the vendor is to select the insulation based on (Sections 6.5.1g & 6.5.3.f). 

Design Loadings

Seismic Data: Refer to SAES-A-112

  Short Period Acceleration (SS) ____ %g

1-Sec Period Acceleration (S1) ____ %g

Site Class ______Collateral Loads: _____ kN/m²

(0.25 kN/m² minimum)

Mezzanine Load: _____ kN/m²Special Floor Live Load: _____ kN/m²

Auxiliary Loads: [ ] Yes [ ] NoDynamic __________

Static __________

(location & magnitude shown on drawings)

Crane Type: [ ] Jib [ ] OverheadCrane Capacity _________ Ton

Crane Service Classification:

[ ] A [ ] B [ ] C [ ] D

Panel System Requirements

Walls Roof

Single Sheet [ ] [ ]

Insulated Sandwich Panel [ ] [ ]

Panel Material: [ ] Aluminum-Zinc Coated Steel Sheet(0.5 mm minimum thickness)

[ ] Galvanized-Steel Sheet

(0.5 mm minimum thickness)

[ ] Aluminum *

(0.70 mm minimum thickness)* Aluminum roof and wall panels must be used in

coastal areas.

Panels: [ ] Primed [ ] Prepainted

Coating System: ________________

Color: Walls ______

Roof ______Structural Members ______

Flushing & Trims ______