    12 Main Classes Of Power Transformer 

    SIEMENS – View of the main production hall of the Nuremberg transformer plant.

    Transformer Classes //

    Transformers are used for a wide variety of purposes, with the complete range of voltage

    and power ratings  as well as many special features for particular applications.

    The following covers the main types:

    1. Transformers for electronics

    Transformers for electronic circuits or for low-voltage power supplies are used to match the supply

    voltage to the operating voltage of components or accessories, or to match the impedance of a

    load to a supply in order to maximize power throughput. They may be used to match impedances

    in primary and secondary circuits.

    The core is usually constructed in low-power transformers from C- and I-laminations or from E-

    and I-laminations. The windings are usually of round enamelled wire, and the assembly may be

    http://electrical-engineering-portal.com/what-are-the-main-classes-of-transformerhttp://electrical-engineering-portal.com/change-output-voltage-of-transformer-with-tapshttp://electrical-engineering-portal.com/what-are-the-main-classes-of-transformer

  • 8/20/2019 12 Main Classes of Power Transformer _ EEP

    2/8

    varnished or encapsulated in resin for mechanical consolidation and to prevent ingress of 

    moisture.

    Increasing numbers of this type operate at high frequencies in the kilohertz range and use

    laminations of special steel often containing cobalt to reduce the iron losses

    2. Small transformers

    These are used for stationary, portable or hand-held power supply units, as isolating transformers

    and for special applications, such as burner ignition, shavers, shower heaters, bells and toys.

    They may be used to supply three-phase power up to 40 kVA at frequencies up to 1 MHz. These

    transformers are usually air insulated, the smaller units using enamelled windings wires and ring

    cores and the larger units using C- and I- or E- and I-laminated cores.

    Safety is a major concern for these transformers and they are identified as class I, class II or 

    class III. Class I units are insulated and protected by an earth terminal. Class II transformers have

    double insulation or reinforced insulation. Class III transformers have outputs at Safety Extra-Low

    Voltages (SELV) below 50 V ac or 120 V dc.

    3. Distribution transformers

    These are used to distribute power   to domestic or industrial premises. They may be single-

    phase or three-phase, pole-mounted or ground-mounted, and they have ratings ranging from 16kVA up to 2500 kVA.

    The windings and core are immersed in mineral oil, with natural cooling, and there are two

    windings per phase. The primary (high-voltage) winding has a highest voltage ranging from 3.6 kV

    to 36 kV; the secondary (low-voltage) winding voltage does not exceed 1.1 kV. The high-voltage

    winding is usually provided with off-circuit tappings of ± 2.5 per cent, or + 2 × 2.5 per cent, – 3 ×

    2.5 per cent.

    The preferred values of rated output are 16, 25, 50, 100, 160, 250, 400, 630, 1000,

    1600 and 2500 kVA, and the preferred values of short-circuit  impedance are 4 or 6

    per cent.

    Losses are assigned from lists, for instance from BS 7281-1, or by using a loss–capitalization

    formula.

    The core and windings of a typical distribution transformer rated at 800 kVA, 11 000/440 areshown in  Fig. 1.

    http://electrical-engineering-portal.com/short-circuit-currentshttp://electrical-engineering-portal.com/difference-between-power-transformer-and-distribution-transformerhttp://electrical-engineering-portal.com/transformer-losses-standards

  • 8/20/2019 12 Main Classes of Power Transformer _ EEP

    3/8

    Figure 1 – Core and winding of an 800 kVA, 11 000/440 V distribution

    transformer 

    4. Supply transformers

    These are used to supply larger industrial premises or distribution substations. Ratings range from

    4 MVA to 30 MVA, with primary windings rated up to 66 kV and secondary windings up to 36 kV.

    Transformers in this class are fluid cooled. Most supply transformers use mineral oil; but for 

    applications in residential buildings, oil rigs and some factories, the coolant may be synthetic

    esters, silicone fluid or some other fluid with a higher fire point than mineral oil.

    5. Transmission (or intertie) transformers

    These are among the largest and highest voltage transformers in use. They are used to transmit

  • 8/20/2019 12 Main Classes of Power Transformer _ EEP

    4/8

    power between high-voltage networks. Ratings range from 60 MVA to 1000 MVA and the

    windings are rated for the networks which they link, such as 33, 66, 132, 275 and 400 kV in the

    UK, or voltages up to 500 kV or 800 kV in other coun-tries.

    The impedance of a transmission transformer is usually 18 per cent in the UK, or 8 per cent in

    continental Europe, but for some system conditions, an impedance of up to 30 per cent is used.

    Figure 2 – Core and windings of a 1000 MVA, 400/275 kV transmission transformer 

    Transmission transformers are oil filled, and are usually fitted with oil pumps and radiator fans to

    assist cooling of the windings and cores. They are usually fitted with OLTCs, but some networks

    at 400 kV and 275 kV are linked by transformers without regulating windings.

    The core and windings of a three-legged transmission trans-former rated at 1000 MVA and 400

    kV/275 kV/11 kV are shown in Fig. 2 .

    6. Generator (or step-up) transformers

    Power is usually generated in large power stations at typically 18–20 kV, and generator 

    transformers are used to step up this voltage to the system voltage level. These trans-formers are

    usually rated at 400, 500, 630, 800 or 1000 MVA.

    Generator transformers are usually fitted with regulating windings and OLTCs.

    7. Phase-shifting transformers

  • 8/20/2019 12 Main Classes of Power Transformer _ EEP

    5/8

    Where power is transmitted along two or more parallel transmission lines, the power flow divides

    between the lines in inverse proportion to the line impedances. Higher power is therefore

    transmitted through the line with lowest impedance and this can result in overload on that line,

    when the parallel line is only partly loaded.

    Phase-shifting transformers are used to link two parallel lines and to control power 

    flow  by injecting a voltage 90° out of phase (in quadrature) with the system voltage into

    one line, at either leading or lagging power factor. Where the transformer controls the

    phase angle but not the voltage, the unit is known as a quadrature booster. Where the

    voltage is also controlled, the unit is known as a phase-shifting transformer.

    Figure 3  shows a 2000 MVA, 400 kV quadrature booster transformer on site; the unit is split

    between two tanks in order to meet construction limitations of size and weight.

    Figure 3 – 2000 MVA 400 kV quadrature booster transformer in two tanks on site

    8. Converter transformers

    Where power is transmitted through an HVDC system, a converter station is used to change AC

    power to DC using multiple rectifier bridges. Direct current power is converted back to ac using

    inverter bridges. Converter transformers handle ac power and power at mixed AC/DC voltages by

    combining the power flow through 12 phases of rectifier/inverter bridges through dc valve

    windings.

    The insulation structure must withstand all normal and abnormal conditions when ac voltage is

    mixed with DC voltage of differing polarities over the operating temperature range.

  • 8/20/2019 12 Main Classes of Power Transformer _ EEP

    6/8

    The presence of DC currents may also cause DC saturation of the core, leading to abnormal

    magnetizing currents and variations in sound.

    Figure 4 – Schematic diagram of ac/dc transmission system

     A phase of a three-phase converter transformer bank typically comprises a high-voltage primary

    winding and two secondary AC/DC valve windings. Three such transformers together form the two

    secondary three-phase systems; one is connected in delta and the other in star. Each secondary

    system feeds a six-pulse bridge and the two bridges are connected in series to form a 12-pulse

    arrangement, as shown schematically in Figure 4

    Two such transformer banks are used with the secondary circuits connected in opposite polarity

    to form a ± 215 kV dc transmission system.

    9. Railway transformers

  • 8/20/2019 12 Main Classes of Power Transformer _ EEP

    7/8

    Transformers for railway applications may be trackside units to supply power to the track, or on-

    board transformers in the locomotive or under the coaches, to power the drive motors.

    Trackside transformers are subjected to uneven loading depending upon the posi-tion of the train

    in the railway system. On-board transformers are designed for the low-est possible weight,

    resulting in a high-loss performance. Modern train control systems using thyristors, GTOs or 

    IGBTs subject the transformers to severe harmonic currents that require special design

    consideration.

    10. Rectifier and furnace transformers

    Special consideration is needed for transformers in industrial applications involving arc furnaces or 

    heavy-current dc loads in electrochemical plant.

    The primary windings in such cases are usually rated at 33 kV or 132 kV in theUK , but the secondary windings carry many thousands of amperes and are

    rated at less than 1 kV .

    Current sharing between parallel paths in the transformer becomes important because of the

    magnetic fields created by the high currents. These strong magnetic fields can cause excess

    heat-ing in magnetic steels if these are used in the structure of the transformer, because of the

    flow of proximity currents in the steel. To reduce this excess heating, non-magnetic steel is often

    used to form part of the tank or the cover.

    The OLTCs in furnace transformers are subject to a heavy duty; they may perform hundreds of 

    thousands of operating cycles a year, which is more than a lifetime’s duty for many transmission

    transformers.

    11. Dry-type transformers

     A dry-type construction is possible where a higher-temperature class of insulation is required than

    is offered by cellulose and a class ‘O’ or class ‘K’ fluid.

    Dry-type trans-formers use non-cellulosic solid insulation and the windings may be varnish dipped

    to provide a class ‘C’ capability, or vacuum encapsulated in epoxy resin to form a class ‘F’ or 

    class ‘H’ system. Ratings are generally up to 30 MVA at voltages up to 36 kV, but cast resin

    transformers have recently been successfully manufactured at 110 kV using a novel winding

    design. Overload performance is limited but it can be augmented by the use of cooling fans.

    This type is more expensive than a fluid-filled equivalent, and because of the reduced fire risk

    they are used in special applications where the public are involved, such as underground tunnels,

    residential blocks of flats or oil-rigs.

  • 8/20/2019 12 Main Classes of Power Transformer _ EEP

    8/8

    Figure 5 – Dry-type 2500 kVA, 11 000/440 V transformer with cast resin

    encapsulation

     A typical cast-resin transformer rated 2500 kVA, 11 000/440 V is shown in Figure 5.

    12. Gas-filled transformers

    For applications where low flammability is paramount, designs have been developed in which the

    transformer is insulated and cooled with SF6 gas. This provides an alternative to dry-typeconstruction where the risk of fire must be eliminated and the possible contamination of the

    environment by oil spillage must be avoided.

    High-voltage SF6 transformers are available at ratings up to 300 MVA at 275 kV and prototype

    designs have been tested at up to 500 kV. Gas-filled transformers and reactors are more expen-

    sive than oil-filled units but the costs may be justified to eliminate a risk of fire, particularly at a

    site where the cost of land is high and where the overall ‘footprint’ of the unit can be reduced by

    the elimination of fire-fighting equipment.

    SOURCE:  Newnes Electrical Power Engineer’s Handbook – D.F. Warne