11KV Metal Clad VCB Specifications
Transcript of 11KV Metal Clad VCB Specifications
11KV OUT DOOR TYPE KIOSK WITH 11KV 1250A 25KA INDOOR VCB
S. No DESCRIPTION 1. 11KV 1250A 25KA VCB of horizontal isolation / draw out VCB fitted with
manual/motor operated spring charging mechanism with 220V AC Motor, shunt trip coil of 24V DC, closing coil of 24V DC, Aux. contact 4NO+4NC mechanical on/Off indicator and push button, mechanical operation counter - 1 No.
2. Current Transformers : The current transformers shall be single phase resin cast and suitable for system voltage of 11KV and of Ratio 125-100/5-5A, Core-1 Class 0.5, 15VA for metering, Core-2 class 5P10, 15VA for protection. – 3Nos.
3. Potential Transformers : The potential transformers shall be Single Phase resin cast suitable for system voltage 11kv and of ratio 11KV/√3/110V/√3 accuracy 1 100VA – 3Nos.
4. Metering 4.1 0 - 150A Digital Ammeter with ASS – 1 set 4.2 0-11KV Digital Voltmeter with VSS – 1 set 4.3 Digital Multifunction Meter – 1 No. 5. Protection
5.1 3O/C + 1E/F relay – 1 no. 5.2 Master Trip relay – 1 no. 5.3 Auxiliary Relays for Transformer Protection - 2Nos 6 CB On/Off/Trip/Spring Charge/Trip Circuit Healthy, and R,Y,B Indication Lamps
– 8nos. 7 Hooter – 1 No 8 8 Window Annunciator – 1 no. 9 Trip Circuit Healthy Push Button – 1 no
10 TNC Breaker Control Switch – 1 no. 11 24V DC battery charger -1 No.
MS sheet steel enclosure with paint shade 7035 suitable for outdoor installation with provision for connecting incoming and outgoing cable provision through bottom entry.
MAKES: VACCUM CIRCUIT BREAKER : ABB PROTECTION RELAYS : EASUN / AREVA AMMETER/VOLTMETER : AE / RISHAB DIGITAL MULTIFUNCTION METER : CONZERV / ELMEASURE ANNUNCIATOR, HOOTER : ALAN / JVS CT’s (OUTDOOR) : VAMET CT’s (INDOOR) : KALPA INDICATION LAMPS : ESBEE (L&T) PUSH BUTTONS : ESBEE (L&T) SELECTOR SWITCH : SALZER