11_Currenttransformer
-
Upload
dhana-teja -
Category
Documents
-
view
155 -
download
13
Transcript of 11_Currenttransformer
© AB
B G
roup - 1 -Jan 5, 2012
Current Transformers
Protection Application Handbook
© AB
B G
roup - 2 -Jan 5, 2012
Current TransformersIntroduction
Main tasks of current transformer are
– Measurement of Current
– Measurement of Power
– Isolation between High voltage and Low Voltage
– Inputs to Relays & Protection Systems
I2
I1
I1 N1
N2I2
I1 = N2
I2 = N1
IEC 44-1 and IEC 44-6 covers instrument transformers
© AB
B G
roup - 3 -Jan 5, 2012
Current Transformers
CTs and VTs
Current transformer
I1/I2 = N2/N1
Magnetizing current is negligible
Voltage transformer
E1/E2 = N1/N2
Voltage drop by magnetizing current is negligible
© AB
B G
roup - 4 -Jan 5, 2012
Current Transformers
Sec. Cores
P1
P2
Bottom TankTerminal Box
Insulator
Pri. ConductorPri. Insulation
Conn. Head Pri. Terminal
Expan. TankOil Level Ind.
Nitrogen Gas
CT – Construction
© AB
B G
roup - 5 -Jan 5, 2012
Current Transformers
Vector diagram of current transformer
© AB
B G
roup - 6 -Jan 5, 2012
Current Transformers
Measuring errors
© AB
B G
roup - 7 -Jan 5, 2012
Current TransformersMeasuring errors
Ratio 1:1 assumed
P1
P2
S1
S2Zb
RctIm
IsIp
Is = Ip - Im
CT error = Im
relative CT error = Im / Is
since Is Ip
© AB
B G
roup - 8 -Jan 5, 2012
Current TransformersFactors influencing CT output and magnetising current
© AB
B G
roup - 9 -Jan 5, 2012
Current Transformers
Current Transformer output
Metering and instrument
High accuracy for 25-100 % of rated burden
Protection and DR
Lower accuracy but high capability to transform high fault current. Protection classes 5P and 10P are acc to IEC 44-1 and cores for transient behavior are acc to IEC 44-6
© AB
B G
roup - 10 -Jan 5, 2012
Current Transformers
• Metering Core
– VA Burden, Accuracy, ISF
– e.g. 15 VA, 0.5 Cl., ISF < 10
Metering
Protection
Types of current transformers
Protection Core
VA Burden, Accuracy, ALF
e.g. 15 VA, 5P20
PS Core
Vk, Io, Rct
e.g. Vk > 400 V, Io < 50 mA at Vk/2, Rct < 5 Ohms
© AB
B G
roup - 11 -Jan 5, 2012
Current Transformers
E / B
I0 /H
Eknee 1.5
E = 4.44BmAfN2 Volts
2 Tesla Saturated CRGO
x Bn
Bs
0.8 Tesla Saturated Mumetal
Bnx
Metering Core:CRGO – 0.4 to 0.8 Tmetal – 0.3 to 0.35 TProtection Core:CRGO – 1.5 to 1.6 T
Working Flux Density
B – H Characteristics
© AB
B G
roup - 12 -Jan 5, 2012
Current Transformers
Metering cores
Metering cores must saturate before 10-40 times rated current depending on burden. This is defined by Fs instrument security factor. At lower burdens the saturation value can be given by
© AB
B G
roup - 13 -Jan 5, 2012
Current TransformersMetering cores : ratio and angle errors for different classes acc to IEC 44-1
© AB
B G
roup - 14 -Jan 5, 2012
Current Transformers
100 12050205
Phase displacement (min)
90
60
30
10
Class 0.2
Class 0.5
Example:Plotted curves for class 0.5
Rated primary current (%)
+ 0.2
0.5
1.0
+ 1.5
100 1205020
0.75
0.5
0.75
- 1.5
- 0.2
1.0
Current error (%)
Class 0.2
Class 0.5
25% of rated burden
100% of rated burden
5
Accuracy Curves
© AB
B G
roup - 15 -Jan 5, 2012
Current Transformers
Protection cores
Main characteristics Lower accuracy than measuring core
High saturation voltage
Little or no turns correction
© AB
B G
roup - 16 -Jan 5, 2012
Current TransformersProtection cores
Examples: 30VA, 5P20 40VA, 10P20 20VA, 10P10 20VA, 5P40
30VA, 5P20
30VA rated burden at rated secondary current5 total error in % at accuracy limit and rated burdenP protection class20 minimum multiple of rated secondary current at which
the accuracy limit is reached with rated burden
Rct is often not noted and has to be measured.For new orders, Rct has to be specified.
© AB
B G
roup - 17 -Jan 5, 2012
Current TransformersCT Effective accuracy limiting factor n'
n'
204 30
4 2113
CT's are normally not fully burdened, the effective accuracy limiting factor n' is therefore higher then the rated n
P1
P2
S1
S2
Rct=4
Im
IsIp
Ual
Ual = (Rct + Rbn) · Isn · n =(Rct + Rbeffective) · Isn · n'
Example: 30VA, 5P20, Rct = 4 n = 201000/1A effective burden = 2 n' = 113
Rbeffecitive =2
Rbn =30
n' nRct Rbn
Rct Rbn
Pct Pn
Pct Pbeffective effective
Example:
© AB
B G
roup - 18 -Jan 5, 2012
Current TransformersCT Class X according BS 3938
Class X is widely usedClass X (or TPS) is imperative for high impedance circulating current
protections and is also suitable for most other protection schemes.
Specify: Knee point voltageSecondary winding resistance at 75°Magnetising current at voltage specifiedmost frequently: full or half knee point voltage
Class X impliesLow stray reactanceclosed core and equally distributed secondary turns, among other parameters
No secondary winding turn correction# of secondary turns = theoretical #
© AB
B G
roup - 19 -Jan 5, 2012
Current Transformers
A CT in class 5Pn with Sn [VA]is approximately equal to a CT in class X with identical Rct andVk BS = ( Sn / Isn + Isn · Rct ) · n / 1.3
Factor is 1.3 due to different definitions of Ualf (= the knee point voltage)A CT in class X with Vk [V]is approximately equal to a CT in class 5Pn with identical Rct andSn [VA] = ( 1.3 VkBS / n - Isn · Rct ) · Isn
[V] ·
Example 1 Cl. 5P20 converted to Cl. X1000/1 A, 40VA, 5P20, Rct= 6 equals approximately to a CT in class X withVk = (40VA / 1A + 1A · 6 ) · 20 / 1.3 = 707V 1000/1 A, Vk=710V, Rct=6
Example 2 Cl. X converted to Cl. 5P201000/1 A, class X, Vk= 710 V; Rct= 6 equals approximately to a class 5P20 withSn = (1.3 · 700V / 20 - 1A · 6 ) · 1A = 40 VA 1000/1 A, 40 VA, 5P20, Rct=6
·
CT Conversion class X to 5Pn and vice versa
·
© AB
B G
roup - 20 -Jan 5, 2012
Current Transformers
Ual = Accuracy limiting voltage (secondary voltage)Former designation, still very popular:
Vk = knee-point voltage
Definitions according different standards:
BS Voltage at which an additional 10% increase in voltage requires an increase of 50% of magnetizing current
ANSI Voltage at which the slope is 45° for plots on log-log paper
IEC 5P Voltage at which the total error = 5% of current applied
CT Definitions of knee-point voltage
© AB
B G
roup - 21 -Jan 5, 2012
Current TransformersCT Definitions of knee-point voltage
+10%
+50%
U [V]
Im [A]
CT-ratio = 1200/1A
100
1000
10000
0.001 0.01 0.1 1.0 10
ANSI
Slope = 45°
5 P 20BS
© AB
B G
roup - 22 -Jan 5, 2012
Current Transformers
© AB
B G
roup - 23 -Jan 5, 2012
Current Transformers
Useful tips in selecting CT cores
Select primary rated current close to object rated current. Gives high resolution of metering CT.
For protection core have highest possible CT ratio. Gives least requirement of core.
With secondary taps output gets reduced
1 A CT is better. Cable burden reduces.
Do not overdimension burden of metering core. Security factor increases.
© AB
B G
roup - 24 -Jan 5, 2012
Current Transformers
Useful tips in selecting CT cores
Select current security factor and ALF depending on type of equipment connected
Do not specify higher accuracy requirements than necessary. Cost increases.
© AB
B G
roup - 25 -Jan 5, 2012
Current Transformers
Useful tips in selecting CT cores
Limit Rct specially for 1A CT ratio CTs to get best of CT output .Always have internal resistance much less than rated burden. Have Rct <0.2 – 0.5 ohms per 100 turns. Bigger value for bigger core and smaller value for smaller cores.
Cores are considered big when 1-2 V for 100 turns and medium when 0.5-1V per 100 turns
In 1 A core keep core size down to keep secondary resistance low
© AB
B G
roup - 26 -Jan 5, 2012
Current Transformers
© AB
B G
roup - 27 -Jan 5, 2012
Current Transformers
Short circuit current in a typical fault loop
Short circuit Current
L R
G
i = 2 Ipsc e-t/Tp Cos - Cos (t +)
DC component is zero when = 90 deg
DC component is maximum when = 0 deg
© AB
B G
roup - 28 -Jan 5, 2012
Current Transformers
Tp
-1
-0.5
0
0.5
1
1.5
2
0 10 20 30 40 50 60 70 80 90 100
time
cu
rren
t
ms
Short circuit Current with DC offset
© AB
B G
roup - 29 -Jan 5, 2012
Current TransformersEquivalent circuit of a CT
L2
R2
U1
UR
L0
UL
i1 i2
L0 is magnetizing Inductance of CTL2 is inductance of CT secondaryR2 is Resistance of CT secondaryTs = (Lo+L2)/R2 is Secondary time constant
© AB
B G
roup - 30 -Jan 5, 2012
Current Transformers
CT primary current
CT secondary current
current
time
CT Saturation due to DC-offset (Transient saturation)
© AB
B G
roup - 31 -Jan 5, 2012
Current Transformers
By analyzing the circuit we come to the conclusion that the CT needs to be overdimensioned by a factor Ktot
Ktot the total overdimensioning factor is defined as
Ktot = Kssc .Ktf . Krem.
Total overdimensioning factor
© AB
B G
roup - 32 -Jan 5, 2012
Current Transformers
The symmetrical short circuit current factor Kssc is defined
as ratio of rms value of short circuit current (Ipsc ) and rated
current ( Ipn )
Kssc = Ipsc / Ipn
Symmetrical short circuit current factor Kssc
© AB
B G
roup - 33 -Jan 5, 2012
Current Transformers
The transient dimensioning factor is the ratio of total flux in the CT core to peak value of AC component of flux
Ktf = Tp Ts . Cos / (Tp – Ts) . e-t/Tp - e-t/Ts + Sin .e-t/Ts - Sin (t +)
Considering Sin (t +) = -1.
The transient dimensioning factor Ktf can be expressed as
Ktf = Tp Ts . Cos / (Tp – Ts) . e-t/Tp - e-t/Ts + Sin .e-t/Ts + 1
Transient dimensioning factor Ktf
© AB
B G
roup - 34 -Jan 5, 2012
Current Transformers
Remanance factor ( Kr ) is ratio of remanant flux to saturation flux
Krem the remanance dimensioning factor is defined as
Krem = I/(1-Kr)
Remanance dimensioning factor Krem.
© AB
B G
roup - 35 -Jan 5, 2012
Current TransformersInfluence of Ts on Ktf
Influence of Ts
10 s
5 s
3 s
2 s
1 s
0 .5 s
10.2 0.4 0.6 0.8
5
10
15
20
K tf
Ts =
T im e in seconds
Except for CTs with big airgaps Ts is few or several seconds
Influence of this on Ktf is relatively small
During first 100 ms
Tp considered is 60 ms
© AB
B G
roup - 36 -Jan 5, 2012
Current TransformersInfluence of Tp on Ktf
Ktf increases when
Tp increases
Influence of Tp
300 m s
30 m s
200 m s
100 m s
10.5 1.5
20
40
60
80
K tf
50 m s
Tp =
T im e in seconds
Ts considered here is 3Secs
© AB
B G
roup - 37 -Jan 5, 2012
Current TransformersInfluence of tsat on Ktf
25 50 75 100
2 m s
3
K tf
4
1
2
10 m s
8 m s
6 m s
4 m s
tsat
Max DC and reduced DC
Tp in m sTp in m s50 100 150 200
20 m s
20
K tf
8
4
12
16
Max DC and reduced DC
70 m s
50 m s
40 m s
30 m s
tsat
tsat > 15msTs=3S,Full DC
tsat < 15msTs=3S
To be able to specify the CT requirements and the required Ktf factor one should
know the maximum time to saturation required by the protective relay viz tsat .
© AB
B G
roup - 38 -Jan 5, 2012
Current TransformersCT Transient performance classes
TPS complementary to class X (low leakage flux)TPX closed coreTPY core with anti remanence air gapsTPZ core wirh considerable air gaps, linearised core
Application examples:
TPS high impedance circulating current protectionTPX most commonTPY line protection with autoreclosingTPZ special applications (differential protection of large generators)
© AB
B G
roup - 39 -Jan 5, 2012
Current TransformersTP classes Error limits
At rated primary At accuracy limitcurrent condition
Class Ratio error Phase displacement Maximum peakin % instantaneous
Minutes Centirad error in %
TPX ± 0.5 ± 30 ± 0.9 = 10
TPY ± 1.0 ± 60 ± 1.8 = 10
TPZ ± 1.0 180 ± 18 5.3 ± 0.6 ac = 10
Remanent flux for TPS and TPX no limit specified (approx. 80% max.)for TPY < 10%for TPZ negligible
© AB
B G
roup - 40 -Jan 5, 2012
Current TransformersCT Small air gaps reduce remanence (TPY)
Drawing not to scale
Remanence
closed core, type TPS, TPX
core with small air gap(s) to reduce remanence type TPYTypically used for lines with autoreclosing
Im
flux
Reduced remanence
typical 80%
typical <10%
© AB
B G
roup - 41 -Jan 5, 2012
Current Transformers
When the CT requirements are specified for dependability
No need to consider remanance.
Risk of short delay is often acceptable .
When the CT requirements are specified for security (as for example for differential relays)
Consider remanance
Recommendations for Remanance
© AB
B G
roup - 42 -Jan 5, 2012
Current Transformers