11-0207 - Metering Application Guide Rev 6

10

Click here to load reader

description

Utility Metering Application Guide

Transcript of 11-0207 - Metering Application Guide Rev 6

Page 1: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 1 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 1-Phase, 2W, 230V, Line-to-Neutral Service Sensitivity Classification: Company Use

/JEM

NEW OLD

Customer Classification

Max. Line

Current

kW Contracted Capacity

1

Rate Code

Meter Form

(Item Code)

Meter Prefix

Meter Form

(Item Code)

Meter Prefix

Socket or Cabinet (Item Code)

CT (Item Code)

CT Cabinet

Max. Wire Size in mm

2

(AWG)

Reference Drawing

100 A < 19 FM 1A (Bottom Connect)

23 series

RS (000418)

30 (# 2)

P-SM00 rev 3 (scheme A/D)

170 A 19 to < 34

BA1/BH2/BJ2

FM 1S (023849)

2

7xx series

N/A ST5

(001181)

N/A

60 (# 2/0)

P-SM00 rev 3 (scheme B/E)

CTC1 5

P-SM00 rev 3 (scheme G)

CTC2 6

P-SM00 rev 3 (scheme H)

Residential, Gov’t Hospital, Charitable Institution & Streetlights

435 A 34 to 85 BA1/BH2/BI2

FM 4S (025620)

3

2xx series

FM 4S (000793)

31 series

6-Terminal RS

4

(001739)

200:5 (000532) 1 unit

Small OCTC

Applicable wire or set of wires

that would fit the BCT Window

Diameter of 2 in. (50.80 mm)

P-SM00 rev 3 (scheme I)

25 A < 5 BA2 FM 1S

(023849) 2

7xx series

RS (000418)

30 (# 2)

P-SM00 rev 3 (scheme A/D)

170 A 5 to < 34 FM 1S

(026293) 2

7xx series (w/

Demand)

N/A ST5

(001181)

N/A 60

(# 2/0) P-SM00 rev 3 (scheme C/F)

CTC1 5

P-SM00 rev 3 (scheme G)

CTC2 6

P-SM00 rev 3 (scheme H)

Commercial & Industrial

435 A 34 to 85

BB2/BE3/BC2/BF3 FM 4S

(025620) 3

2xx series

FM 4S (000793)

31 series (w/ ID)

6-Terminal RS

4

(001739)

200:5 (000532) 1 unit

Small OCTC

Applicable wire or set of wires

that would fit the BCT Window

Diameter of 2 in. (50.80 mm)

P-SM00 rev 3 (scheme I)

REMARKS:

For EMC application, if and when available, kindly use Electromechanical Meters, 0XX series, (memo reference, “Alternative Metering Scheme for 1-Phase, 2W, L2N System” dated September 4, 2003); otherwise, use 7xx series (memo reference, “Metering Advisory 2009:3 – Electronic Meters on EMC”, memo-2009-8182 dated April 1, 2009) 1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM1S Item Code: 026477 (Plain TOU); 023620 (TOU with Demand) 3 Other FM4S Item Code: 023621 (TOU) 4 Wired-up for use in L2N system 5 (000765) CTC1 - 228 x 456 x 711 mm 6 (000848) CTC2 - 250 x 600 x 875 mm

Page 2: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 2 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 1-Phase, 3W, 230V, Line-to-Line Service Sensitivity Classification: Company Use

/JEM

NEW OLD

Customer Classification

Max. Line

Current

kW Contracted Capacity

1

Rate Code

Meter Form

(Item Code)

Meter Prefix

Meter Form

(Item Code)

Meter Prefix

Socket or Cabinet (Item Code)

CT (Item Code)

CT Cabinet

Max. Wire Size in mm

2

(AWG)

Reference Drawing

100 A < 19 33

series RS

(000418) 30 (# 2)

P-SM01 rev 1 (scheme A)

200 A 19 to < 40

BA1/BH2/BJ2

FM 2S (000407)

2

1xx series

FM 2S

34 series

ST5 (001181)

N/A

100 (# 4/0)

P-SM01 rev 1 (scheme B)

CTC1 4

P-SM01 rev 1 (scheme D)

CTC2 5

P-SM01 rev 1 (scheme E)

Residential, Gov’t Hospital, Charitable Institution & Streetlights

435 A 40 to 85 BA1/BI2

FM 4S (025620)

3

2xx series

FM 4S 31

series (w/ ID)

6-Terminal RS

(001739)

200:5 (000532) 2 units

Small OCTC

Applicable wire or set of wires

that would fit the BCT Window

Diameter of 2 in. (50.80 mm)

P-SM01 rev 1 (scheme F)

25 A < 5 BA2 FM 2S

(000407) 2

1xx series

33 series

RS (000418)

30 (# 2)

P-SM01 rev 1 (scheme A)

200 A 5 to < 40 BB2/BE3

FM 2S (016902)

2

1xx series (w/

Demand)

FM 2S 34

series (w/ ID)

ST5 (001181)

N/A

100 (# 4/0)

P-SM01 rev 1 (scheme C)

CTC1 4

P-SM01 rev 1 (scheme D)

CTC2 5

P-SM01 rev 1 (scheme E)

Commercial & Industrial

435 A 40 to 85 BC2/BF3

FM 4S (025620)

3

2xx series

FM 4S 31

series (w/ ID)

6-Terminal RS

(001739)

200:5 (000532) 2 units

Small OCTC

Applicable wire or set of wires

that would fit the BCT Window

Diameter of 2 in. (50.80 mm)

P-SM01 rev 1 (scheme F)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM 2S Item Codes: 026478 (Plain TOU); 023973 (TOU with Demand) 3 Other FM 4S Item Code: 023621 (TOU) 4 (000765) CTC1 - 228 x 456 x 711 mm

5 (000848) CTC2 - 250 x 600 x 875 mm

Page 3: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 3 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 1-Phase, 3W, 230V, Delta Derived Service Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line

Current

kW Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

Max. Wire Size in mm

2 (AWG)

Reference Drawing

100 A < 19 5-TRMS (027014) 30

(# 2) P-SM05 rev 1 (scheme A) Residential, Gov’t

Hospital, Charitable Institution & Streetlights 200 A 19 to < 40

BA1/BH2/ BJ2

ST5 (001181)

100 (# 4/0)

P-SM05 rev 1 (scheme B)

25 A < 5 BA2 5-TRMS (027014) 30 (# 2)

P-SM05 rev 1 (scheme A)

Commercial & Industrial

200 A 5 to < 40 BB2/BE3

FM 12S (018339)

2

5xxF series

ST5 (001181)

100 (# 4/0)

P-SM05 rev 1 (scheme B)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM12S Item Code: 026479 (TOU) 3

Page 4: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 4 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 1-Phase, 3W, 230V, Network / Wye Service Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line

Current

kW Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

Max. Wire Size in mm

2 (AWG)

Reference Drawing

100 A < 19 5-TRMS (027014) 30 (# 2)

P-SM25 rev 1 (scheme A) Residential, Gov’t

Hospital, Charitable Institution & Streetlights 200 A 19 to < 40

BA1/BH2/ BJ2

FM 25S (023848)

5xxBA series

ST5 (001181)

100 (# 4/0)

P-SM25 rev 1 (scheme B)

25 A < 5 BA2 FM 25S (023848)

5xxBA series 5-TRMS (027014) 30 (# 2)

P-SM25 rev 1 (scheme A)

Commercial & Industrial

200 A 5 to < 40 BB2/BE3 FM 12S (018339)

2 5xxF series

ST5 (001181)

100 (# 4/0)

P-SM25 rev 1 (scheme C)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM12S Item Code: 026479 (TOU)

Page 5: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 5 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 3-Phase, 4W, 230V, Wye Service Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line Current

kW Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

CT (Item Code)

CT Cabinet Max. Wire Size in

mm2 (AWG)

Reference Drawing

200 A < 67 BA1/BA2/BB2/BE3/BC2/BF3/

BH2/BI2

FM 16S (018327)

2

3xx series ST7

(020366) N/A

100 (# 4/0)

P-SM03 rev 1 (scheme A)

480 A 67 to < 162 BA1/BC2/BF3/

BI2

200:5 (000532) 3 units

Applicable wire or set of wires that would fit the BCT Window Diameter

of 2 in. (50.80 mm)

P-SM03 rev 1 (scheme B/E/K)

640 A 162 to < 217 BA1/BC2/BF3/BD2/BG3/BI2

400:5 (000563) 3 units

P-SM03 rev 1 (scheme C/F/L)

960 A 217 to < 325 600:5 (000615) 3 units

CTC1 4 /

CTC2 5 /

Small

OCTC

Applicable wire or set of wires that would fit the BCT Window Diameter

of 3 in. (76.2 mm) P-SM03 rev 1 (scheme D/G/M)

1280 A 325 to < 433 800:5 (000721) 3 units

P-SM03 rev 1 (scheme H/N)

1920 A 433 to < 650

BA1/BD2/BG3/BI2

1200:5 (000720) 3 units

P-SM03 rev 1 (scheme I/O)

All

3000 A 650 to 1000 BA1/BD2/BG3/BK2/BL3/BI2

FM 9S (018328)

3

4xx series

ST13 (002857)

or

EPC (018845)

1500:5 (000741) 3 units

CTC3 6 /

CTC4 7 /

Big OCTC

Applicable wires that would fit the BCT

Window Diameter of 5.8 in. (147.32 mm)

P-SM03 rev 1 (scheme J/P)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm 6 (000978) CTC3 – 400 x 800 x 900 mm 7 (000936) CTC4 – 400 x 1200 x 1200 mm

Page 6: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 6 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 3-Phase, 4W, 230V, Delta Service Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line Current

kW Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

CT (Item Code)

CT Cabinet Max. Wire Size in

mm2 (AWG)

Reference Drawing

200 A < 67 BA1/BA2/BB2/BE3/BC2/BF3/

BH2/BI2

FM 16S (018327)

2

3xx series ST7

(020366) N/A

100 (# 4/0)

P-SM03 rev 1 (scheme A)

480 A 67 to < 162 BA1/BC2/BF3/

BI2

200:5 (000532) 3 units

Applicable wire or set of wires that would fit the BCT Window Diameter

of 2 in. (50.80 mm)

P-SM03 rev 1 (scheme B/E/K) All

800 A 162 to 271 BA1/BC2/BF3/BD2/BG3/BI2

FM 9S (018328)

3

4xx series

ST13 (002857)

or EPC

(018845)

400:5 (000563) 3 units

CTC1 4 /

CTC2 5 /

Small

OCTC

Applicable wire or set of wires that would fit the BCT Window Diameter

of 3 in. (76.2 mm)

P-SM03 rev 1 (scheme C/F/L)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm

Page 7: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 7 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 3-Phase, 4W, 400/230V Wye Service Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line Current

kW Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

CT (Item Code)

CT Cabinet Max. Wire Size in

mm2 (AWG)

Reference Drawing

200 A < 118 BA1/BA2/BB2/BE3/BC2/BF3/

BH2/BI2

FM 16S (018327)

2

3xx series ST7

(020366) N/A

100 (# 4/0)

P-SM73 rev 0 (scheme A)

480 A 118 to < 283 BA1/BC2/BF3/BD2/BG3/BI2

200:5 (000532) 3 units

Applicable wire or set of wires that would fit the BCT Window Diameter

of 2 in. (50.80 mm)

P-SM73 rev 0 (scheme B/E/J)

640 A 283 to < 377 400:5 (000563) 3 units

P-SM73 rev 0 (scheme C/F/K)

960 A 377 to < 565

BA1/BD2/BG3/BI2 600:5

(000615) 3 units

CTC1 4 /

CTC2 5 /

Small OCTC

Applicable wire or set of wires that would fit the BCT Window Diameter

of 3 in. (76.2 mm) P-SM73 rev 0 (scheme D/G/L)

All

1600 A 565 to 942 BA1/BD2/BG3/BK2/BL3/BI2

FM 9S (018328)

3

4xx series

ST13 (002857)

or

EPC (018845)

800:5 (000721) 3 units

CTC3 6 /

CTC4 7 /

Big OCTC

Applicable wires that

would fit the BCT

Window Diameter of 5.8

in. (147.32 mm)

P-SM73 rev 0 (scheme H/I/M)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm 6 (000978) CTC3 – 400 x 800 x 900 mm 7 (000936) CTC4 – 400 x 1200 x 1200 mm

Page 8: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 8 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: 3-Phase, 4W, 460V Wye Service Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line Current

kW Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

CT (Item Code)

CT Cabinet Max. Wire Size in

mm2 (AWG)

Reference Drawing

200 A < 135 BA1/BA2/BB2/BE3/BC2/BF3/

BH2/BI2

FM 16S (018327)

2

3xx series ST7

(020366) N/A

100 (# 4/0)

P-SM63 rev 1 (scheme A)

480 A 135 to < 325 BA1/BC2/BF3/

BI2

200:5 (000532) 3 units

Applicable wire or set of wires that would fit the BCT Window Diameter

of 2 in. (50.80 mm)

P-SM63 rev 1 (scheme B/E/K)

640 A 325 to < 433 400:5 (000563) 3 units

P-SM63 rev 1 (scheme C/F/L)

960 A 433 to < 650

BA1/BD2/BG3/BI2 600:5

(000615) 3 units

CTC1 4 /

CTC2 5 /

Small OCTC

Applicable wire or set of wires that would fit the BCT Window Diameter

of 3 in. (76.2 mm) P-SM63 rev 1 (scheme D/G/M)

1280 A 650 to < 867 BA1/BD2/BG3/BLK2/BL3/BI2

800:5 (000721) 3 units

P-SM63 rev 1 (scheme H/N)

1920 A 867 to < 1300

1200:5 (000720) 3 units

P-SM63 rev 1 (scheme I/O)

All

3000 A 1300 to 2000

BA1/BK2/BL3/BI2

FM 9S (018328)

3

4xx series

ST13 (002857)

or

EPC (018845)

1500:5 (000741) 3 units

CTC3 6 /

CTC4 7 /

Big OCTC

Applicable wires that would fit the BCT

Window Diameter of 5.8 in. (147.32 mm)

P-SM63 rev 1 (scheme J/P)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm 6 (000978) CTC3 – 400 x 800 x 900 mm 7 (000936) CTC4 – 400 x 1200 x 1200 mm

Page 9: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 9 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: Primary Metering Scheme (3-Phase, 4W, 13.8 kV, Wye Service) Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line Current

Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

ERCT 2

(Item Code) PT

Max. Wire Size in mm

2 (AWG)

Reference Drawing

24 A < 488 kW BD2/BG3/BH2/

BI2 FM 9S

(018328) 4

34.5 kV 20:5

(024526) 3 units

60 A 488 kW to < 1.2 MW

BD2/BG3/BK2/

BL3/BI2

34.5 kV 50:5

(025702) 3 units

120 A 1.2 MW to < 2.4 MW

34.5 kV 100:5 (024943) 3 units

240 A 2.4 MW to < 4.9 MW

34.5 kV 200:5 (019761) 3 units

All

450 A 4.9 MW to 9 MW

3

BK2/BL3/BI2

FM 9S (029252)

4

4xx series EPC

(018845)

34.5 kV 300:5 (025703) 3 units

15 kV 70:1

(001785) 3 units

Refer to Overhead Standard

Constructive Units Book

P-MN03U (Standard Constructive

Units – Overhead Distribution Facilities)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 ERCT – Extended Range Current Transformer, with 0.15 accuracy class, accuracy ranging from 1% to 150 % of rated primary current. 3 Applied capacity within or beyond this range requires Distribution Impact Study (DIS) for approval of Network Asset Planning - Network System Development. 4 Other FM9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU)

Page 10: 11-0207 - Metering Application Guide Rev 6

PM-DME-400.01 Rev. Code: 6

Page 10 of 10

Section: Metering Application Guide Effective Date: February 14, 2011

Subject: Primary Metering Scheme (3-Phase, 4W, 34.5 kV, Wye Service) Sensitivity Classification: Company Use

/JEM

Customer Classification

Max. Line Current

Contracted Capacity

1

Rate Code Meter Form

(Item Code) Meter Prefix

Socket or Cabinet (Item Code)

ERCT 2

(Item Code) PT

Max. Wire Size in mm

2 (AWG)

Reference Drawing

24 A < 1.2 MW

34.5 kV 20:5

(024526) 3 units

60 A 1.2 MW to < 3 MW

34.5 kV 50:5

(025702) 3 units

120 A 3 MW to < 6 MW

BK2/BL3/BH2/

BI2

34.5 kV 100:5 (024943) 3 units

240 A 6 MW to < 12 MW

3

34.5 kV 200:5 (019761) 3 units

All

450 A 12 MW to 22.8 MW

3

BN3/BO2/BI2

FM 9S (029252)

4

4xx series EPC

(018845)

34.5 kV 300:5 (025703) 3 units

34.5 kV 175:1 (001788) 3 units

Refer to Overhead Standard

Constructive Units Book

P-ML03U (Standard Constructive

Units – Overhead Distribution Facilities)

REMARKS:

1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 ERCT – Extended Range Current Transformer, with 0.15 accuracy class, accuracy ranging from 1% to 150 % of rated primary current. 3 Applied capacity within or beyond this range requires Distribution Impact Study (DIS) for approval of Network Asset Planning - Network System Development. 4 Other FM9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU)