11-0207 - Metering Application Guide Rev 6
Click here to load reader
description
Transcript of 11-0207 - Metering Application Guide Rev 6
PM-DME-400.01 Rev. Code: 6
Page 1 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 1-Phase, 2W, 230V, Line-to-Neutral Service Sensitivity Classification: Company Use
/JEM
NEW OLD
Customer Classification
Max. Line
Current
kW Contracted Capacity
1
Rate Code
Meter Form
(Item Code)
Meter Prefix
Meter Form
(Item Code)
Meter Prefix
Socket or Cabinet (Item Code)
CT (Item Code)
CT Cabinet
Max. Wire Size in mm
2
(AWG)
Reference Drawing
100 A < 19 FM 1A (Bottom Connect)
23 series
RS (000418)
30 (# 2)
P-SM00 rev 3 (scheme A/D)
170 A 19 to < 34
BA1/BH2/BJ2
FM 1S (023849)
2
7xx series
N/A ST5
(001181)
N/A
60 (# 2/0)
P-SM00 rev 3 (scheme B/E)
CTC1 5
P-SM00 rev 3 (scheme G)
CTC2 6
P-SM00 rev 3 (scheme H)
Residential, Gov’t Hospital, Charitable Institution & Streetlights
435 A 34 to 85 BA1/BH2/BI2
FM 4S (025620)
3
2xx series
FM 4S (000793)
31 series
6-Terminal RS
4
(001739)
200:5 (000532) 1 unit
Small OCTC
Applicable wire or set of wires
that would fit the BCT Window
Diameter of 2 in. (50.80 mm)
P-SM00 rev 3 (scheme I)
25 A < 5 BA2 FM 1S
(023849) 2
7xx series
RS (000418)
30 (# 2)
P-SM00 rev 3 (scheme A/D)
170 A 5 to < 34 FM 1S
(026293) 2
7xx series (w/
Demand)
N/A ST5
(001181)
N/A 60
(# 2/0) P-SM00 rev 3 (scheme C/F)
CTC1 5
P-SM00 rev 3 (scheme G)
CTC2 6
P-SM00 rev 3 (scheme H)
Commercial & Industrial
435 A 34 to 85
BB2/BE3/BC2/BF3 FM 4S
(025620) 3
2xx series
FM 4S (000793)
31 series (w/ ID)
6-Terminal RS
4
(001739)
200:5 (000532) 1 unit
Small OCTC
Applicable wire or set of wires
that would fit the BCT Window
Diameter of 2 in. (50.80 mm)
P-SM00 rev 3 (scheme I)
REMARKS:
For EMC application, if and when available, kindly use Electromechanical Meters, 0XX series, (memo reference, “Alternative Metering Scheme for 1-Phase, 2W, L2N System” dated September 4, 2003); otherwise, use 7xx series (memo reference, “Metering Advisory 2009:3 – Electronic Meters on EMC”, memo-2009-8182 dated April 1, 2009) 1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM1S Item Code: 026477 (Plain TOU); 023620 (TOU with Demand) 3 Other FM4S Item Code: 023621 (TOU) 4 Wired-up for use in L2N system 5 (000765) CTC1 - 228 x 456 x 711 mm 6 (000848) CTC2 - 250 x 600 x 875 mm
PM-DME-400.01 Rev. Code: 6
Page 2 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 1-Phase, 3W, 230V, Line-to-Line Service Sensitivity Classification: Company Use
/JEM
NEW OLD
Customer Classification
Max. Line
Current
kW Contracted Capacity
1
Rate Code
Meter Form
(Item Code)
Meter Prefix
Meter Form
(Item Code)
Meter Prefix
Socket or Cabinet (Item Code)
CT (Item Code)
CT Cabinet
Max. Wire Size in mm
2
(AWG)
Reference Drawing
100 A < 19 33
series RS
(000418) 30 (# 2)
P-SM01 rev 1 (scheme A)
200 A 19 to < 40
BA1/BH2/BJ2
FM 2S (000407)
2
1xx series
FM 2S
34 series
ST5 (001181)
N/A
100 (# 4/0)
P-SM01 rev 1 (scheme B)
CTC1 4
P-SM01 rev 1 (scheme D)
CTC2 5
P-SM01 rev 1 (scheme E)
Residential, Gov’t Hospital, Charitable Institution & Streetlights
435 A 40 to 85 BA1/BI2
FM 4S (025620)
3
2xx series
FM 4S 31
series (w/ ID)
6-Terminal RS
(001739)
200:5 (000532) 2 units
Small OCTC
Applicable wire or set of wires
that would fit the BCT Window
Diameter of 2 in. (50.80 mm)
P-SM01 rev 1 (scheme F)
25 A < 5 BA2 FM 2S
(000407) 2
1xx series
33 series
RS (000418)
30 (# 2)
P-SM01 rev 1 (scheme A)
200 A 5 to < 40 BB2/BE3
FM 2S (016902)
2
1xx series (w/
Demand)
FM 2S 34
series (w/ ID)
ST5 (001181)
N/A
100 (# 4/0)
P-SM01 rev 1 (scheme C)
CTC1 4
P-SM01 rev 1 (scheme D)
CTC2 5
P-SM01 rev 1 (scheme E)
Commercial & Industrial
435 A 40 to 85 BC2/BF3
FM 4S (025620)
3
2xx series
FM 4S 31
series (w/ ID)
6-Terminal RS
(001739)
200:5 (000532) 2 units
Small OCTC
Applicable wire or set of wires
that would fit the BCT Window
Diameter of 2 in. (50.80 mm)
P-SM01 rev 1 (scheme F)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM 2S Item Codes: 026478 (Plain TOU); 023973 (TOU with Demand) 3 Other FM 4S Item Code: 023621 (TOU) 4 (000765) CTC1 - 228 x 456 x 711 mm
5 (000848) CTC2 - 250 x 600 x 875 mm
PM-DME-400.01 Rev. Code: 6
Page 3 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 1-Phase, 3W, 230V, Delta Derived Service Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line
Current
kW Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
Max. Wire Size in mm
2 (AWG)
Reference Drawing
100 A < 19 5-TRMS (027014) 30
(# 2) P-SM05 rev 1 (scheme A) Residential, Gov’t
Hospital, Charitable Institution & Streetlights 200 A 19 to < 40
BA1/BH2/ BJ2
ST5 (001181)
100 (# 4/0)
P-SM05 rev 1 (scheme B)
25 A < 5 BA2 5-TRMS (027014) 30 (# 2)
P-SM05 rev 1 (scheme A)
Commercial & Industrial
200 A 5 to < 40 BB2/BE3
FM 12S (018339)
2
5xxF series
ST5 (001181)
100 (# 4/0)
P-SM05 rev 1 (scheme B)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM12S Item Code: 026479 (TOU) 3
PM-DME-400.01 Rev. Code: 6
Page 4 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 1-Phase, 3W, 230V, Network / Wye Service Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line
Current
kW Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
Max. Wire Size in mm
2 (AWG)
Reference Drawing
100 A < 19 5-TRMS (027014) 30 (# 2)
P-SM25 rev 1 (scheme A) Residential, Gov’t
Hospital, Charitable Institution & Streetlights 200 A 19 to < 40
BA1/BH2/ BJ2
FM 25S (023848)
5xxBA series
ST5 (001181)
100 (# 4/0)
P-SM25 rev 1 (scheme B)
25 A < 5 BA2 FM 25S (023848)
5xxBA series 5-TRMS (027014) 30 (# 2)
P-SM25 rev 1 (scheme A)
Commercial & Industrial
200 A 5 to < 40 BB2/BE3 FM 12S (018339)
2 5xxF series
ST5 (001181)
100 (# 4/0)
P-SM25 rev 1 (scheme C)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM12S Item Code: 026479 (TOU)
PM-DME-400.01 Rev. Code: 6
Page 5 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 3-Phase, 4W, 230V, Wye Service Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line Current
kW Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
CT (Item Code)
CT Cabinet Max. Wire Size in
mm2 (AWG)
Reference Drawing
200 A < 67 BA1/BA2/BB2/BE3/BC2/BF3/
BH2/BI2
FM 16S (018327)
2
3xx series ST7
(020366) N/A
100 (# 4/0)
P-SM03 rev 1 (scheme A)
480 A 67 to < 162 BA1/BC2/BF3/
BI2
200:5 (000532) 3 units
Applicable wire or set of wires that would fit the BCT Window Diameter
of 2 in. (50.80 mm)
P-SM03 rev 1 (scheme B/E/K)
640 A 162 to < 217 BA1/BC2/BF3/BD2/BG3/BI2
400:5 (000563) 3 units
P-SM03 rev 1 (scheme C/F/L)
960 A 217 to < 325 600:5 (000615) 3 units
CTC1 4 /
CTC2 5 /
Small
OCTC
Applicable wire or set of wires that would fit the BCT Window Diameter
of 3 in. (76.2 mm) P-SM03 rev 1 (scheme D/G/M)
1280 A 325 to < 433 800:5 (000721) 3 units
P-SM03 rev 1 (scheme H/N)
1920 A 433 to < 650
BA1/BD2/BG3/BI2
1200:5 (000720) 3 units
P-SM03 rev 1 (scheme I/O)
All
3000 A 650 to 1000 BA1/BD2/BG3/BK2/BL3/BI2
FM 9S (018328)
3
4xx series
ST13 (002857)
or
EPC (018845)
1500:5 (000741) 3 units
CTC3 6 /
CTC4 7 /
Big OCTC
Applicable wires that would fit the BCT
Window Diameter of 5.8 in. (147.32 mm)
P-SM03 rev 1 (scheme J/P)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm 6 (000978) CTC3 – 400 x 800 x 900 mm 7 (000936) CTC4 – 400 x 1200 x 1200 mm
PM-DME-400.01 Rev. Code: 6
Page 6 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 3-Phase, 4W, 230V, Delta Service Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line Current
kW Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
CT (Item Code)
CT Cabinet Max. Wire Size in
mm2 (AWG)
Reference Drawing
200 A < 67 BA1/BA2/BB2/BE3/BC2/BF3/
BH2/BI2
FM 16S (018327)
2
3xx series ST7
(020366) N/A
100 (# 4/0)
P-SM03 rev 1 (scheme A)
480 A 67 to < 162 BA1/BC2/BF3/
BI2
200:5 (000532) 3 units
Applicable wire or set of wires that would fit the BCT Window Diameter
of 2 in. (50.80 mm)
P-SM03 rev 1 (scheme B/E/K) All
800 A 162 to 271 BA1/BC2/BF3/BD2/BG3/BI2
FM 9S (018328)
3
4xx series
ST13 (002857)
or EPC
(018845)
400:5 (000563) 3 units
CTC1 4 /
CTC2 5 /
Small
OCTC
Applicable wire or set of wires that would fit the BCT Window Diameter
of 3 in. (76.2 mm)
P-SM03 rev 1 (scheme C/F/L)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm
PM-DME-400.01 Rev. Code: 6
Page 7 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 3-Phase, 4W, 400/230V Wye Service Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line Current
kW Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
CT (Item Code)
CT Cabinet Max. Wire Size in
mm2 (AWG)
Reference Drawing
200 A < 118 BA1/BA2/BB2/BE3/BC2/BF3/
BH2/BI2
FM 16S (018327)
2
3xx series ST7
(020366) N/A
100 (# 4/0)
P-SM73 rev 0 (scheme A)
480 A 118 to < 283 BA1/BC2/BF3/BD2/BG3/BI2
200:5 (000532) 3 units
Applicable wire or set of wires that would fit the BCT Window Diameter
of 2 in. (50.80 mm)
P-SM73 rev 0 (scheme B/E/J)
640 A 283 to < 377 400:5 (000563) 3 units
P-SM73 rev 0 (scheme C/F/K)
960 A 377 to < 565
BA1/BD2/BG3/BI2 600:5
(000615) 3 units
CTC1 4 /
CTC2 5 /
Small OCTC
Applicable wire or set of wires that would fit the BCT Window Diameter
of 3 in. (76.2 mm) P-SM73 rev 0 (scheme D/G/L)
All
1600 A 565 to 942 BA1/BD2/BG3/BK2/BL3/BI2
FM 9S (018328)
3
4xx series
ST13 (002857)
or
EPC (018845)
800:5 (000721) 3 units
CTC3 6 /
CTC4 7 /
Big OCTC
Applicable wires that
would fit the BCT
Window Diameter of 5.8
in. (147.32 mm)
P-SM73 rev 0 (scheme H/I/M)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm 6 (000978) CTC3 – 400 x 800 x 900 mm 7 (000936) CTC4 – 400 x 1200 x 1200 mm
PM-DME-400.01 Rev. Code: 6
Page 8 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: 3-Phase, 4W, 460V Wye Service Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line Current
kW Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
CT (Item Code)
CT Cabinet Max. Wire Size in
mm2 (AWG)
Reference Drawing
200 A < 135 BA1/BA2/BB2/BE3/BC2/BF3/
BH2/BI2
FM 16S (018327)
2
3xx series ST7
(020366) N/A
100 (# 4/0)
P-SM63 rev 1 (scheme A)
480 A 135 to < 325 BA1/BC2/BF3/
BI2
200:5 (000532) 3 units
Applicable wire or set of wires that would fit the BCT Window Diameter
of 2 in. (50.80 mm)
P-SM63 rev 1 (scheme B/E/K)
640 A 325 to < 433 400:5 (000563) 3 units
P-SM63 rev 1 (scheme C/F/L)
960 A 433 to < 650
BA1/BD2/BG3/BI2 600:5
(000615) 3 units
CTC1 4 /
CTC2 5 /
Small OCTC
Applicable wire or set of wires that would fit the BCT Window Diameter
of 3 in. (76.2 mm) P-SM63 rev 1 (scheme D/G/M)
1280 A 650 to < 867 BA1/BD2/BG3/BLK2/BL3/BI2
800:5 (000721) 3 units
P-SM63 rev 1 (scheme H/N)
1920 A 867 to < 1300
1200:5 (000720) 3 units
P-SM63 rev 1 (scheme I/O)
All
3000 A 1300 to 2000
BA1/BK2/BL3/BI2
FM 9S (018328)
3
4xx series
ST13 (002857)
or
EPC (018845)
1500:5 (000741) 3 units
CTC3 6 /
CTC4 7 /
Big OCTC
Applicable wires that would fit the BCT
Window Diameter of 5.8 in. (147.32 mm)
P-SM63 rev 1 (scheme J/P)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 Other FM16S Item Codes: 023852 (alternative IC); 026480 (TOU) 3 Other FM 9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU) 4 (000765) CTC1 – 228 x 456 x 711 mm 5 (000848) CTC2 – 250 x 600 x 875 mm 6 (000978) CTC3 – 400 x 800 x 900 mm 7 (000936) CTC4 – 400 x 1200 x 1200 mm
PM-DME-400.01 Rev. Code: 6
Page 9 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: Primary Metering Scheme (3-Phase, 4W, 13.8 kV, Wye Service) Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line Current
Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
ERCT 2
(Item Code) PT
Max. Wire Size in mm
2 (AWG)
Reference Drawing
24 A < 488 kW BD2/BG3/BH2/
BI2 FM 9S
(018328) 4
34.5 kV 20:5
(024526) 3 units
60 A 488 kW to < 1.2 MW
BD2/BG3/BK2/
BL3/BI2
34.5 kV 50:5
(025702) 3 units
120 A 1.2 MW to < 2.4 MW
34.5 kV 100:5 (024943) 3 units
240 A 2.4 MW to < 4.9 MW
34.5 kV 200:5 (019761) 3 units
All
450 A 4.9 MW to 9 MW
3
BK2/BL3/BI2
FM 9S (029252)
4
4xx series EPC
(018845)
34.5 kV 300:5 (025703) 3 units
15 kV 70:1
(001785) 3 units
Refer to Overhead Standard
Constructive Units Book
P-MN03U (Standard Constructive
Units – Overhead Distribution Facilities)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 ERCT – Extended Range Current Transformer, with 0.15 accuracy class, accuracy ranging from 1% to 150 % of rated primary current. 3 Applied capacity within or beyond this range requires Distribution Impact Study (DIS) for approval of Network Asset Planning - Network System Development. 4 Other FM9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU)
PM-DME-400.01 Rev. Code: 6
Page 10 of 10
Section: Metering Application Guide Effective Date: February 14, 2011
Subject: Primary Metering Scheme (3-Phase, 4W, 34.5 kV, Wye Service) Sensitivity Classification: Company Use
/JEM
Customer Classification
Max. Line Current
Contracted Capacity
1
Rate Code Meter Form
(Item Code) Meter Prefix
Socket or Cabinet (Item Code)
ERCT 2
(Item Code) PT
Max. Wire Size in mm
2 (AWG)
Reference Drawing
24 A < 1.2 MW
34.5 kV 20:5
(024526) 3 units
60 A 1.2 MW to < 3 MW
34.5 kV 50:5
(025702) 3 units
120 A 3 MW to < 6 MW
BK2/BL3/BH2/
BI2
34.5 kV 100:5 (024943) 3 units
240 A 6 MW to < 12 MW
3
34.5 kV 200:5 (019761) 3 units
All
450 A 12 MW to 22.8 MW
3
BN3/BO2/BI2
FM 9S (029252)
4
4xx series EPC
(018845)
34.5 kV 300:5 (025703) 3 units
34.5 kV 175:1 (001788) 3 units
Refer to Overhead Standard
Constructive Units Book
P-ML03U (Standard Constructive
Units – Overhead Distribution Facilities)
REMARKS:
1 Assumed power factor is 0.85. For other power factors, the maximum line current shall be used as basis. 2 ERCT – Extended Range Current Transformer, with 0.15 accuracy class, accuracy ranging from 1% to 150 % of rated primary current. 3 Applied capacity within or beyond this range requires Distribution Impact Study (DIS) for approval of Network Asset Planning - Network System Development. 4 Other FM9S Item Codes: 018328 (±AMR); 029252 (Standard w/ AMR); 015936 (w/ TLC); 024079 (MaxSys); 026481 (TOU)