1
Summary of Papers
1. P. Sauer and M. Pai, “Power System Steady-State Stability and the Load Flow Jacobian,” IEEE Transactions on Power Systems, Vol. 5, No. 4, Nov. 1990 2. V. Ajjarapu and C. Christy, “The Continuation Power Flow: A Tool for Steady-State Voltage Stability Analysis,” IEEE Transactions on Power Systems, Vol. 7, No. 1, Feb., 1992.3. S. Greene, I. Dobson, and F. Alvarado, “Sensitivity of the Loading Margin to Voltage Collapse with Respect to Arbitrary Parameters,” IEEE Transactions on Power Systems, Vol. 12, No. 1, Feb. 1997, pp. 232-240.4. S. Greene, I. Dobson, and F. Alvarado, “Contingency Ranking for Voltage Collapse via Sensitivities from a Single Nose Curve,” IEEE Transactions on Power Systems, Vol. 14, No. 1, Feb. 1999, pp. 262-272.
![Page 2: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/2.jpg)
2
Voltage Security
Voltage security is the ability of the system to maintainadequate and controllable voltage levels at all system load buses.The main concern is that voltage levels outside of a specifiedrange can affect the operation of the customer’s loads.
Voltage security may be divided into two main problems:1. Low voltage: voltage level is outside of pre-defined range. 2. Voltage instability: an uncontrolled voltage decline.
You should know that • low voltage does not necessarily imply voltage instability• no low voltage does not necessarily imply voltage stability• voltage instability does necessarily imply low voltage
![Page 3: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/3.jpg)
3
There have been several individuals that have significantlyprogressed the field of voltage security. These include:
• Ajjarapu from ISU
• Van Cutsem: See the book by Van Cutsem and Vournas.
• Alvarado, Dobson, Canizares, & Greene:
There are a couple other texts that provide good treatments ofthe subject:• Carson Taylor: “Power System Voltage Stability”• Prabha Kundur: “Power System Stability & Control”
Resources
![Page 4: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/4.jpg)
4
Our treatment of voltage security will proceed as follows:
• Voltage instability in a simple system• Voltage instability in a large system• Brief treatment of bifurcation analysis• Continuation power flow (path following) methods• Sensitivity methods
![Page 5: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/5.jpg)
5
Voltage instability in a simple system
Consider the per-phase equivalent of a very simple threephase power system given below:
Z=R+jXI
V1V2
S12
Node 1 Node 2
+
__
+
V1 V2
SD=-S12
![Page 6: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/6.jpg)
6
jBGYjXRZ
)sin(||||)cos(||||||
)sin(||||)cos(||||||
212121212
112
212121212
112
GVVBVVBVQ
BVVGVVGVP
121212 jQPS
Let G=0. Then….
)cos(||||||
)sin(||||
21212
112
212112
BVVBVQ
BVVP
Note B>0
![Page 7: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/7.jpg)
7
Now we can get SD=PD+jQD=-(P21+jQ21) by
•- exchanging the 1 and 2 subscripts in the previous equations.•- negating
)cos(||||||
)cos(||||||
)sin(||||
)sin(||||
21212
2
12212
221
2121
122121
BVVBV
BVVBVQQ
BVV
BVVPP
D
D
Define 12 =1- 2
12212
2
1221
cos||||||
sin||||
BVVBVQ
BVVP
D
D
![Page 8: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/8.jpg)
8
Define: is the power factor angle of the load, i.e.,
IV 2
Then we can also express SD as:
)tan1(
)cos
sin1(cos||||
)sin(cos||||
||||
2
2
2*
2
jP
jIV
jIV
eIVIVS
D
jD
Define β=tan. Then
)1( jPjQPS DDDD
Note that phi, andtherefore beta, is positive for lagging,negative for leading.
![Page 9: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/9.jpg)
9
So we have developed the following equations….
12212
2
1221
cos||||||
sin||||
BVVBVQ
BVVP
D
D
)1( jPjQPS DDDD
Equating the expressions for PD and for QD, we have:
1221 sin|||| BVVPD 12212
2
12212
2
cos||||||
cos||||||
BVVBVP
BVVBVPQ
D
DD
Square both equations and add them to get…..
![Page 10: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/10.jpg)
10
222
21
222
2
122
12222
22
122
22
||||)||(
)cos(sin||||)||(
BVVBVPP
BVVBVPP
DD
DD
Manipulation yields:
01||||2
|| 22
22
22
1
222
B
PVV
B
PV DD
Note that this is a quadratic in |V2|2. As such, it has the solution:
2/1
21
41
212
2 ||4
||
2
||||
VB
P
B
PV
B
PVV DDD
![Page 11: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/11.jpg)
11
Let’s assume that the sending end voltage is |V1|=1.0 puand B=2 pu. Then our previous equation becomes:
2
)2(11||
2/12
2
DDD PPPV
You can makethe P-V plot usingthe followingmatlab code.
% pf = 0.97 laggingbeta=0.25pdn=[0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.78];v2n=sqrt((1-beta.*pdn - sqrt(1-pdn.*(pdn+2*beta)))/2);pdp=[0.78 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0];v2p=sqrt((1-beta.*pdp + sqrt(1-pdp.*(pdp+2*beta)))/2);pd1=[pdn pdp];v21=[v2n v2p];% pf = 1.0beta=0pdn=[0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 0.99];v2n=sqrt((1-beta.*pdn - sqrt(1-pdn.*(pdn+2*beta)))/2);pdp=[0.99 0.9 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0];v2p=sqrt((1-beta.*pdp + sqrt(1-pdp.*(pdp+2*beta)))/2);pd2=[pdn pdp];v22=[v2n v2p];% pf = .97 leadingbeta=-0.25pdn=[0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3];v2n=sqrt((1-beta.*pdn - sqrt(1-pdn.*(pdn+2*beta)))/2);pdp=[1.3 1.2 1.1 1.0 0.9 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0];v2p=sqrt((1-beta.*pdp + sqrt(1-pdp.*(pdp+2*beta)))/2);pd3=[pdn pdp];v23=[v2n v2p];
plot(pd1,v21,pd2,v22,pd3,v23)
![Page 12: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/12.jpg)
12
Plots of the previous equation for different power factors
Real power loading, PD
|V2|
![Page 13: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/13.jpg)
13
Some comments regarding the PV curves:1. Each curve has a maximum load. This value is typically called the maximum system load or the system loadability.2. If the load is increased beyond the loadability, the voltages will decline uncontrollably.3. For a value of load below the loadability, there are two voltage solutions. The upper one corresponds to one that can be reached in practice. The lower one is correct mathematically, but I do not know of a way to reach these points in practice.4. In the lagging or unity power factor condition, it is clear that the voltage decreases as the load power increases until the loadability. In this case, the voltage instability phenomena is detectable, i.e., operator will be aware that voltages are declining before the loadability is exceeded.•5. In the leading case, one observes that the voltage is flat, or perhaps even increasing a little, until just before the loadability. Thus, in the leading condition, voltage instability is not very detectable. The leading condition occurs during high transfer conditions when the load is light or when the load is highly compensated.
![Page 14: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/14.jpg)
14
QV Curves
12212
2
1221
cos||||||
sin||||
BVVBVQ
BVVP
D
D
We consider our simple (lossless) system again, with the equations
Now, again assume that V1=1.0, and for a given value of PD
and V2, compute 12 from the first equation, and then Q from thesecond equation. Repeat for various values of V2 to obtain a QVcurve for the specified real load PD.
v1=1.0;b=1.0;
pd1=0.1v2=[1.1,1.05,1.0,.95,.90,.85,.80,.75,.70,.65,.60,.55,.50,.45,.40,.35,.30,.25,.20,.15];sintheta=pd1./(b*v1.*v2);theta=asin(sintheta);qd1=-v2.^2*b+v1*b*v2.*cos(theta); plot(qd1,v2);
You can make the P-V plot using the following matlab code.
The curve on the next page illustrates….
![Page 15: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/15.jpg)
15
Q-V Curve
QD
|V2|
![Page 16: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/16.jpg)
16
Homework
1. Draw the PV-curve for the following cases, and for each, determine the loadability.
a. B=2, |V1|=1.0, pf=0.97 lagging
b. B=2, |V1|=1.0, pf=0.95 lagging
c. B=2, |V1|=1.06, pf=0.97 lagging
d. B=10, |V1|=1.0, pf=0.97 lagging
Identify the effect on loadability of power factor, sending-end voltage, and line reactance.
2. Draw the QV-curves for the following cases, and for each, determine the maximum QD.
a. B=1, |V1|=1.0, PD=0.1
b. B=1, |V1|=1.0, PD=0.2
c. B=1, |V1|=1.06, PD=0.1
d. B=2, |V1|=1.0, PD=0.1
Identify the effect on maximum QD of real power demand, sending-end voltage, and line reactance.
![Page 17: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/17.jpg)
17
Some comments regarding the QV Curves• In practice, these curves may be drawn with a power flow program by
1. modeling at the target bus a synchronous condenser (a generator with P=0) having very wide reactive limits
2. Setting |V| to a desired value 3. Solving the power flow. 4. Reading the Q of the generator. 5. Repeat 2-4 for a range of voltages.
• QV curves have one advantage over PV curves: They are easier to obtain if you only have a power flow (standard power flows will not solve near or below the “nose” of PV curves but they will solve completely around the “nose” of QV curves.)
![Page 18: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/18.jpg)
18
Voltage instability in a large system:Influential factors:
• Load modeling• Reactive power limits on generators• Loss of a circuit• Availability of switchable shunt devices
1. Voltage instability occurs when the reactive power supply cannot meet the reactive power demand of the network.• Transmission line loading is too high• Reactive sources (generators) are too far from load centers• Generator terminal voltages are too low.• Insufficient load reactive compensation
2. Reactive power cannot be moved very far in a network (“vars do not travel”), since I2X is large.
Two important ideas on which understanding of the above influences rest:
Implication: The SYSTEM can have a var surplus but experiencevoltage instability if a local area has a var deficiency.
![Page 19: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/19.jpg)
19
Load modeling
In analyzing voltage instability, it is necessary to consider the networkunder various voltage profiles.
Voltage stability depends on the level of current drawn by the loads.
The level of current drawn by the loads can depend on the voltage seenby the loads.
Therefore, voltage instability analysis requires a model of how theload responds to load variations.
Thus, load modeling is very influential in voltage instability analysis.
![Page 20: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/20.jpg)
20
Exponential load model
A typical load model for a load at a bus is the exponential model:
00
00
V
VQQ
V
VPP
where the subscript 0 indicates the initial operating conditions. The exponents and are specific to the type of load, e.g.,
Incandescent lamps 1.54 -Room air conditioner 0.50 2.5Furnace fan 0.08 1.6Battery charger 2.59 4.06Electronic compact florescent 1.0 0.40Conventional florescent 2.07 3.21
![Page 21: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/21.jpg)
21
Polynomial load modelThe ZIP or polynomial model is a special case of the more general exponential model, given by a sum of 3 exponential models with specified subscripts:
3
02
2
0103
02
2
010 q
V
Vq
V
VqQQp
V
Vp
V
VpPP
where again the subscript 0 indicates the initial operating conditions.
0.1321 ppp
So this model is composed of three components:
• constant impedance component (p1, q1) - lighting• constant current component (p2, q2) – motor/lighting• constant power component (p3,, q3) – loads served by LTCs
0.1321 qqq
Usually, values p2 and q2 are the largest.
![Page 22: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/22.jpg)
22
Understanding the effect of each component on voltage instability depends on understanding two ideas:
1. Voltage instability is alleviated when the demand reduces. This is because I reduces and I2X reactive losses in the circuits reduce.
2. Since voltage instability causes voltage decline, alleviation of voltage instability results if demand reduces with voltage decline. This gives the key to understanding the effect of load modeling.
• constant impedance load (p1) is GOOD since demand reduces with square of voltage.• constant current load (p2) is OK since demand reduces with voltage.• Constant power load (p3) is BAD since demand does not change as voltage declines.
Effect of Load modeling
![Page 23: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/23.jpg)
23
The effects of voltage variation on loads, and thus of loads on voltage instability, cannot be fully captured using exponential orpolynomial load models because of the following three aspects.
• Thermostatic load recovery • Induction motor stalling/tripping• Load tap changers
Some considerations in load modeling
![Page 24: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/24.jpg)
24
Heating load is the most common type of thermostatic load, and it is one for which we are all quite familiar. Although much heating is done with natural gas as the primary fuel, some heating is done electrically, and even gas heating systems always contain some electric components as well, e.g., the fans.
Other thermostatic loads include space heaters/coolers, water heaters, and refrigerators.
When voltage drops, thermostatic loads initially decrease in power consumption. But after voltages remain low for a few minutes, the load regulation devices (thermostats) will start the loads or will maintain them for longer periods so that more of them are on at the same time. This is referred to as thermostatic load recovery, and it tends to exacerbate voltage problems at the high voltage level.
Thermostatic load recovery
![Page 25: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/25.jpg)
25
Three phase induction motors comprise a significant portion of the total load and so its response to voltage variation is important,especially since it has a rather unique response.
Consider the steady-state induction motor per-phase equivalent model.
Induction motor stalling/tripping
Za=R1+jX1
Zb=
Rc//jXm
X’2
R’2+R’2(1-s)/s =R’2 / s
V1
I’2
![Page 26: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/26.jpg)
26
The (referred to stator)rotor current is given by:
Induction motor stalling/tripping
222 ')/'('
jXsRZ
VI
th
th
where ba
bth ZZ
ZVV
1
andba
babath ZZ
ZZZZZ
//
Under normal conditions, the slip s is typically very small, less than 0.05 (5%). In this case, R’2/s >> R’2, and I’2 is small.
But as voltage V1 decreases, the electromagnetic torque developed decreases as well, the motor slows down. Ultimately, the motor may stall. In this case, s=1, causing R’2/s = R’2. Thus, one sees that the current I’2 is much larger for stalled conditions than for normal conditions. Because of X1 and X’2 of the induction motor, the large “stall” current represents a large reactive load.
Large motors have undervoltage tripping to guard against this, but smaller motors (refrigerators/air conditioners) may not.
![Page 27: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/27.jpg)
27
Tap changers:
Load tap changers (LTC, OLTC, ULTC, TCUL) are transformers thatconnect the transmission or subtransmission systems to the distributionsystems. They are typically equipped with regulation capability that allow them to control the voltage on the low side so that voltage deviation on the high side is not seen on the low side.
V1V1/t
In per unit, we say that the tap is t:1, where • t may range from 0.85-1.15 pu• a single step may be about 0.005 pu (5/8%=0.00625 is very common)• a change of one step typically requires about 5 seconds.• there is a deadband of 2-3 times the tap step to prevent excessive tap change.
t:1HV side
LV sideV1 and t are given in pu.
Under low voltage conditions at the high side, the LTC will decrease tin order to try and increase V1/t.
![Page 28: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/28.jpg)
28
Tap changers:
Thus, as long as the LTC is regulating (not at a limit), a voltage decline on the high side does not result in voltage decline at the load, in the steady-state, so that even if the load is constant Z,it appears to the high side as if it is constant power. So a simpleload model for voltage instability analysis, for systems using LTC,is constant power!
There are 2 qualifications to using such a simple model (constant power):1. “Fast” voltage dips are seen at the low side (since LTCaction typically requires minutes), and if the dip is low enough, induction motors may trip, resulting in an immediate decrease inload power. 2. Once the LTC hits its limit (minimum t), then the low sidevoltage begins to decline, and it becomes necessary to modelthe load voltage sensitivity.
![Page 29: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/29.jpg)
29
Generator capability curve:
P
Q
Field current limit due to field heating,enforced by overexcitation limiter on If.
Armature current limit due toarmature heating, enforced byoperator control of P and If.
Limit due to steady-state instability (small internal voltage E gives small |E||V|Bsin), and due to stator end-region heating from induced eddy currents, enforced by underexcitation limiter (UEL).
Qmax
Qmin
Typical approximationused in powerflow programs.
![Page 30: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/30.jpg)
30
Effect of generator reactive power limits:1. Voltage instability is typically preceded by generators hitting their upper reactive limit, so modeling Qmax is very important to analysis of voltage instability.2. Most power flow programs represent generator Qmax as fixed. However, this is an approximation, and one that should be recognized. In reality, Qmax is not fixed. The reactive capability diagram shows quite clearly that Qmax is a function of P and becomes more restrictive as P increases. A first-order improvement to fixed Qmax
is to model Qmax as a function of P. 3. Qmax is set according to the Over-eXcitation Limiter (OXL). The field circuit has a rated steady-state field current If-max, set by field circuit heating limitations. Since heating is proportional to , we see that smaller overloads can be tolerated for longer times. Therefore, most modern OXLs are set with a time-inverse characteristic:4. As soon as the OXL acts to limit If, then no further increase in reactive power is possible. When drawing PV or QV curves, the action of a generator hitting Qmax, will manifest itself as a sharp discontinuity in the curve.
timeoverload
2dtI f
Overload time (sec)
If
Irated
1.0
2.0
120
10
OXL characteristic
![Page 31: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/31.jpg)
31
P(demand)
|V|
No reactive limits modeled
One generator hits reactive limit
o
Note: Georgia Power Co. models its loadability limit at point x, not point o.
Effect of OXL action on PV curve:
![Page 32: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/32.jpg)
32
Loss of a circuit
I/2
I/2
I
P P
Compare reactive losses with and without second circuit
Qloss=(I/2)2X+ (I/2)2X=I2X/2
Assume both circuits have reactance of X.
Qloss=I2X
Implication: Loss of a circuit will always increase reactive losses in the network. This effect is compounded by the fact that losing a circuit also means losing its line charging capacitance.
X
X
![Page 33: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/33.jpg)
33
Kundur, on pp. 979-990, has an excellent example which illustratesmany of the aforementioned effects. The illustration was done usinga long-term time domain simulation program (Eurostag).
![Page 34: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/34.jpg)
34
Influence of switched shunt capacitors
I
P
I
P
P(demand)
|V|
With capacitorWithout capacitor
![Page 35: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/35.jpg)
35
But, shunt compensation has some drawbacks:
• It produces reactive power in proportion to the square of the the voltage, therefore when voltages drop, so does the reactive power supplied by the capacitor. • It has a maximum compensation level beyond which stable operation is not possible (See pg. 972 of Kundur, and next slide).
(A synchronous condenser and an SVC do not have these 2 drawbacks)
• It results in a flatter PV curve and therefore makes voltage instability less detectable. Therefore, as the load grows in areas lacking generation, more and more shunt compensation is used to keep voltages in normal operating ranges. By so doing, normal operating points progressively approach loadability.
![Page 36: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/36.jpg)
36
2004006008001000120014001600
Capacitive Mvars
0.6
0.8
1.0
1.2
|V2|
V1=1.0 V2
PL
QL=0
PL =1300 mw
PL=1500 mw
PL=1700 mwPL=1900 mw
QV-curves drawnusing synchronouscondensor approach.
300 Mvar450 Mvar675 Mvar
950 Mvar
Each QV curve/Capacitor characteristic intersection shows the operating point. Note that for the first three operating points, a small increase in Q-comp (indicated by arrows) results in voltage increase, but for the last operating point (950), more Q-comp (say 960) results in a voltage decrease.S=|V2|2B*Sbase
with |V2|=1.0
![Page 37: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/37.jpg)
37
Bifurcation analysis (ref: A. Gaponov-Grekhov, “Nonlinearities in action” andalso Van Cutsem & Vournas, “Voltage stability of electric power systems.”)
Consider representing the dynamics of the power system as:
),,(0
),,(
pyxG
pyxFx
A differential-algebraic system (DAS): Here x represents state variables of the system (e.g., rotor angles, rotorspeed, etc), y represents the algebraic variables (bus voltage magnitudes & voltage angles), and p represents the real and reactive power injections at each bus. The function F represents the differential equations for the generators, and the function G represents the power flow equations.
A bifurcation, for a dynamic system, is an acquisition of a new quality by the motion the dynamic system, caused by small changes in its parameters. A power system that has experienced a bifurcation will generally have corresponding motion that is undesirable.
Eqts. 1
![Page 38: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/38.jpg)
38
There are at least two types of bifurcation:• Hopf: two eigenvalues become purely imaginary:a birth of oscillatory or periodic motion.• Saddle node: a disappearance of an equilibrium state. The stable operating equilibrium coalesces with an unstable equilibrium and disappears. The dynamic consequence of a generic saddle node bifurcation is:
a monotonic decline in system variables.
So we think it is the saddle node bifurcation that causesvoltage instability.
Types of bifurcations
![Page 39: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/39.jpg)
39
The Jacobian matrix of eqts. 1 is
Y
Y
X
X
G
F
G
FJ
The unreduced Jacobian:
and it is referred to as the unreduced Jacobian of the DAS, where
y
xJ
x
0
Eqt. 2
![Page 40: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/40.jpg)
40
We may reduce eq. 2 by eliminating the variable y
y
x
G
F
G
Fx
Y
Y
X
X
0
The reduced Jacobian:
This means we need to force the top right hand submatrix to 0, which we can do by multiplying the bottom row by -FYGY
-1 and then adding to the top row.
y
x
GG
GGFFx
YX
XYYX0
0
1
This results in: xGGFFx XYYX 1So that the reduced Jacobian matrix is a Schur’s complement:
XYYX GGFFA 1
![Page 41: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/41.jpg)
41
Implications 2: 1. If GY is nonsingular, then singularity of A implies singularity of J so
that we may analyze eigenvalues of A to ascertain stability.2. The fact that GY may be nonsingular, yet A singular, means that
load flow convergence is not a sufficient condition for voltage stability.
Stability:Fact 1 : The conditions for a saddle node bifurcation are 1. Equilibrium:
2. Singularity of the unreduced Jacobian det(J)=0 (a 0 eigenvalue, J noninvertible) .
),,(0
),,(
pyxG
pyxFx
Y
Y
X
X
G
F
G
FJ
Fact 2: The determinant of a Schur’s complement times the determinant of GY gives the determinant of the original matrix: det(J)=det(A)*det(GY)if GY is nonsingular.
Implication 1: The stability of an equilibrium point of the DAS depends on the eigenvalues of the unreduced Jacobian J. The system will experience a SNB as parameter p increases when J has a zero eigenvalue.
![Page 42: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/42.jpg)
42
Singularity of load flow Jacobian:
Singular
NonsingularAGY J
Singular
Nonsingular
Singular (unstable)
Nonsingular (stable)
Implications 2: 1. If GY is nonsingular, then singularity of A implies singularity of J so
that we may analyze eigenvalues of A to ascertain stability.2. The fact that GY may be nonsingular, yet A singular, means that
load flow convergence is not a sufficient condition for voltage stability.
![Page 43: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/43.jpg)
43
Singularity of load flow Jacobian:
So voltage instability analysis using only a load flow Jacobian may yield optimistic results when compared to results from analysis of A,that is, stable points (based on Gy) may not be really stable. => However, I believe it is true that points identified as unstable using the load flow Jacobian will be really unstable (Schur’s complement does not support that singularity of GY implies singularity of J, however, because it is only valid if GY is nonsingular).
Note: Sauer and Pai, 1990, provide an in-depth analysis of the relationbetween singularity of GY and singularity of J, and show some specialcases for which singularity of GY implies singularity of J.
Singular (unstable)
Nonsingular (stable) AGY J
Singular (unstable)
Nonsingular (stable)
Singular (unstable)
Nonsingular (stable)
![Page 44: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/44.jpg)
44
Singularity of load flow Jacobian:
So, we assume that load flow Jacobian analysis provides an upper bound on stability.
Fact: The bifurcation (zero eigenvalue of GY) of the load flow Jacobian corresponds to the “turn-around point” (i.e., the “nose” point) of a P-V or Q-V curve drawn using a power flow program.
This can be proven using an optimization approach. See pp. 218-220 of the text by Van Cutsem and Vournas.
We have previously denoted the power flow equations as G(x,y,p)=0, but now we denote them as G(y,p)=0, without the dependence on the state variables x (which relate to the machine modeling and include, minimally, and of each machine).
![Page 45: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/45.jpg)
45
So we turn our effort to identifying the saddle node bifurcation(SNB) for the power flow Jacobian matrix.
The Jacobian can reach a SNB in many ways. For example,• increase the impedance in a key tie line• increase the generation level at a generator with weak transmission, while decreasing generation at all other generators.• increase the load at a single bus• increase the load at all buses.In all cases, we are looking for the “nose” point of the V- curve, where is the parameter that is being increased.)
Most applications focus on the last method (increase load at all buses). Key questions here are:• “direction” of increase: are bus loads increased proportionally, or in some other way?• dispatch policy: how do the generators pick up the load increase ?
We will assume proportional load increase with “governor” load flow(generators pick up in proportion to their rating)
|V|
![Page 46: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/46.jpg)
46
|V|
Define: critical point - the operating conditions, characterized by a certain value of , beyond which operation is not acceptable.
Question 1:What can cause the critical point to differfrom the SNB point ?
Question 2:How can knowledge of the critical point provide a security measure?
Question 3:Does the P-V curve provide a forecast of the system trajectory ?
![Page 47: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/47.jpg)
47
Solution approaches to finding *, the value of corresponding to SNB.
Approach 1: Search for * using some iterative search procedure. 1. i=12. Using (i), solve power flow using Newton-Raphson. Here, we iteratively solve G(y,p)=0. At each step, we must solve for y in the eqt: GY y = p3. If solved,
(i+1)= (i)+ .i=i+1go to 2
else if not solved, *= (i+1)
endif4. End
But big problem: as gets close to *, GY becomes ill-conditioned (close to singular). This means that at some point before the criticalpoint, step 2 will no longer be feasible.
![Page 48: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/48.jpg)
48
Approach 2: Use the continuation power flow (CPF).
Predictor step
Corrector step
Pass * ?Select
continuationparameter
Stop
No.
Yes.
![Page 49: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/49.jpg)
49
The predictor step:
),(0 pyG
The power flow equations are functions of the bus voltages andbus angles and the bus injections:
Augment the power flow equations so that they are functions of (dependence on p is carried through the dependence on ).
),(0 yG
Now recognize that
V
y
so that ),,(0 VG
If we want to compute the change in the power flow equations dGdue to small changes in the variables , V, and , • that move us closer to the loadability point• as we move from one solution i to another “close” solution i+1, thendG= G((i),V(i),(i))- G((i+1),V(i+1),(i+1)) = 0 – 0 = 0
pp0
![Page 50: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/50.jpg)
50
0
dd
GdVd
Vd
Gdd
d
GdGd
BUT, we have added one unknown, , to the power flow problem without adding acorresponding equation, i.e., in G(,V,)=0, there are are N equations but N+1 variables, so that in eq. 3, the matrix [G GV, G], has N rows (the number of eqts being differentiated) and N+1 columns (the number of variables for which each eqt is differentiated). So we need another equation in order to solve this. What to do ?
Eq. 3
dd
GdVd
Vd
Gdd
d
GdGd
Here, each set of partial derivatives are evaluated at the operating conditions corresponding to the old solution. If the power flow equations are linear with the 3 sets of variables in the region between the old solution and the (close) new one, the following is satisfied:
0
d
Vd
d
GGG V
![Page 51: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/51.jpg)
51
The answer to this can be found by identifying how we will be using using the solution to eqt. 3. Note the solution corresponding to the “new” point is:
'
'
'
)(
)(
)(
),1(
),1(
),1(
d
Vd
d
VVi
i
i
pi
pi
pi
If we define to be the “step size,” then we can rewrite this as
d
Vd
d
VVi
i
i
pi
pi
pi
)(
)(
)(
)1(
),1(
),1(
d
Vd
d
d
Vd
d
'
'
'where
Here the “p” indicatesthat this is the “predicted” point.
![Page 52: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/52.jpg)
52
We call the update vector (with the differentials) the “tangent” vector, denoted by t.
This vector provides the direction to move in order to find a new solution (i+1,p) from the old one (i). We can think of this in terms of the following picture…..
d
dV
d
t
![Page 53: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/53.jpg)
53
|V|
Tangent vector
![Page 54: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/54.jpg)
54
So we can set one of the tangent vector elements to any value we like, then compute the other elements.This provides us with our other equation….
For example, consider a 2-dimensional vector….
Direction = 30o
x1
x2
x2=x1tan(30) so:
- the direction is specified by selecting x1=1, x2=0.5774,- the direction is specified by selecting x1=0.5, x2=0.2246.
Note: In specifying a direction using an n-dimensional vector, only n-1 of the elements are constrained - one element can be chosen to be any value we like.
![Page 55: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/55.jpg)
55
Suppose that we set the k-th parameter in the tangent vector to be 1.0. Then our equation given as eq. 3 can be augmented to become:
1
0
d
dV
dG
e
GG
k
V
where
To select , we would have:
k
]0...010...00[
=ke
]1...000...00[=ke Which would force d=1.
![Page 56: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/56.jpg)
56
The parameter for which we select k is called the continuationparameter, and it can be any load level (or group of load levels),or it can be a voltage magnitude. Initially, when the solution is far from the nose, the continuation parameter is typically .
d
dV
d
VVi
i
i
pi
pi
pi
)(
)(
)(
),1(
),1(
),1(
The parameter is called the step size, and it can be selectedusing various techniques. The simplest of these is to just set it to a constant. Let’s try this on our simple problem formulated at the beginning of these slides.
tyy ipi )(),1(
![Page 57: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/57.jpg)
57
HOMEWORK #2, Due Monday, Jan 26.1. Using the equations at the bottom of slide 7, with the left-hand side (PD and QD) and also V1 given by the problem statement, we know everything except V2 and theta.2. Now, just bring the right hand side of these 2 equations over to the left-hand side, and you have the 2 equations that correspond to G(y,p)=0. 3. Solve these equations to get the corresponding power flow solution (but you do not need Newton-Raphson to do this – you can just use the equation at the bottom of slide 10).4. Now you need to replace the value specified in the equations for PD (which is 0.4 according to the problem statement) with 0.4*lambda. This gives you the equations in the form of slide 49: 0=G(theta,V,lambda). Note, however, that G is really two equations: G1 and G2.5. Now you need to formulate the equations on the slide 55. This is a matter of taking derivatives and then evaluating those derivatives at the solution that you obtained above. Note, however, the each element in the matrix of slide 55 actually represents 2 elements. That is:
| dG1/dtheta dG1/dV dG1/dlambda|| dG2/dtheta dG2/dV dG2/dlambda|| 0 0 1 |
6. Evaluate each of the above matrix elements at the solution obtained in step 3.7. Then solve these equations for the tangent vector. You can do this by inverting the above matrix (use matlab or a calculator to do this) and then multiply the right-hand-side by this inverted matrix. 8. Then take a “step” using an appropriately chosen step size per the equation on slide 56.9. Beginning from your predicted point that you identified in step 8 of #2a, develop equations for approach a, solve them, and identify the resulting corrected point in terms of voltage and power.10. Repeat #9 except implement approach b.
12212
2
1221
cos||||||
sin||||
BVVBVQ
BVVP
D
D
#9 and #10 will be explained in next few slides.
![Page 58: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/58.jpg)
58
Note, however, that the predicted point will satisfy thepower flow equations only if the power flow equations arelinear, which they are not.
So our point needs correction. This leads to the corrector step.
There are two different approaches for performing thecorrector step.
Approach a: Perpendicular intersection method.
Approach b: Parameterization method
Corrector step
![Page 59: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/59.jpg)
59
Approach a: perpendicular intersection
Here, we find the intersection between the power flowequations (the PV curve) and a plane that is perpendicular tothe tangent vector.
|V|
0),1()1( tyy pii
t
),(0 )1( iyG y(i+1)
y(i+1,p)
y(i)
Solve simultaneously,for y(i+1)
Use Newton-Raphson to solve the above (requires only 1-3 iterations since we have good starting point). If no convergence, cut step size () by half and repeat.
The last equation says the inner (dot) product of 2 vectors is zero.
![Page 60: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/60.jpg)
60
Approach b: ParameterizationThe corrector step is performed by •identifying a continuation parameter (see slide 62) – can be λ• fixing it at the value found in the predictor step;• then solving the power flow equations.
|V|
t
y(i+1)
y(i+1,p)
y(i)
0),(
)1(
)1(
i
k
i
y
yG
Here, yk(i+1) is the continuation parameter; it is the variable yk
(i+1) that corresponds to the k-th element dyk
(i+1) in the tangent vector and is usually λ at first but often becomes something else as the nose point is neared. The parameter is the value to which yk is set, which would be the value found in the predictor step. As in approach a, we can solve this using Newton-Raphson. If no convergence, cut step size () by half and repeat.
Solve simultaneously,for y(i+1)
Vertical correctionscorrespond to a fixedload-continuationparameter, horizontalcorrections to a fixedvoltage-continuation parameter.
![Page 61: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/61.jpg)
61
Detection of critical point:
We will know that we have surpassed the critical point when the sign of d in the tangent vector becomes negative, because it is at this point where the loading reaches a maximum point and begins to decrease.
|V|
x
increasing
decreasing
![Page 62: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/62.jpg)
62
Selection of continuation parameter:
d
dV
d
VVi
i
i
pi
pi
pi
)(
)(
)(
),1(
),1(
),1(
Typically, yk
is going to beone of these.
The continuation parameter is selected from among and the state variables in y according to the one that ischanging the most with . This will be the parameter thathas the largest element in the tangent vector. • relatively unstressed conditions (far from nose): generally • relatively stressed conditions (close to nose): generally the voltage magnitude of the weakest bus, as it changes a great deal as is changed, when we are close to *.
The one changingthe most with λ is most sensitive andrepresents a variable that we want to be carefulwith as we look for another solution, so it makes sense to keep it constant.
![Page 63: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/63.jpg)
63
Selection of continuation parameter (unstressed condition):
|V|
y(i+1)
y(i+1,p)
y(i)
Here, is fixed.
The continuation parameter is selected from among and the state variables in y according to the one that ischanging the most with . This will be the parameter thathas the largest element in the tangent vector. • relatively unstressed conditions (far from nose): generally .=> This looks like below.
![Page 64: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/64.jpg)
64
• relatively stressed conditions (close to nose): generally the voltage magnitude of the weakest bus. Here, the voltage being plotted is chosen as the continuation parameter.
|V|
y(i+1)
y(i+1,p)
y(i)
Here, |V| is fixed.
“Essentially, a variable is fixed as a parameter (the voltage), andthe parameter () is treated as a variable. This process of selectinga variable to fix is sometimes called the parameterization step.”
-Scott Greene, Ph.D. dissertation, 1998.
Selection of continuation parameter (stressed condition):
![Page 65: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/65.jpg)
65
A central question:
How does the continuation technique alleviate the ill-conditioning problem experienced by a regular power flow ?
0),1()1( tyy pii
),(0 )1( iyG0
)(
)1(
)1(
i
k
i
y
yG
Refer to the solutions procedures for the two corrector approaches.Perpendicular interesectionSolve simultaneously,for y(i+1)
ParameterizationSolve simultaneously,for y(i+1)
In both cases, we use Newton-Raphson to solve, so we need to obtain theJacobian. But the Jacobian is slightly different than in normal power flow.
![Page 66: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/66.jpg)
66
The Jacobian of the power flow equations is just Gy, but the Jacobian of the equations in the two corrector approaches will have an extra row and column.
k
k
x
x
y
y
C
G
C
G
Here, C is the additional equation, and xk is the selectedcontinuation parameter.
This addition of a row and column to the Jacobian has theeffect of improving the conditioning so that the previouslysingular points can in fact be obtained. In other words, theadditional row and column provides that this Jacobian is nonsingular at * where the standard Jacobian is singular.
![Page 67: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/67.jpg)
67
Known codes for continuation methods:
1. Claudio Canizarres at University of Waterloo: C-code See http://www.power.uwaterloo.ca/~claudio/claudio.htmlUWPFLOW is a research tool that has been designed to calculate local bifurcations related to system limits or singularities in the system Jacobian. The program also generates a series of output files that allow further analyses, such as tangent vectors, left and right eigenvectors at a singular bifurcation point, Jacobians, power flow solutions at different loading levels, voltage stability indices, etc
2. I have Matlab code that does it – from Scott Greene.3. Venkataramana Ajjarapu (ISU): Fortran code4. Powertech has a program
![Page 68: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/68.jpg)
68
Calculation of sensitivities for voltage instability analysis
What is a sensitivity ?
It is the derivative of an equation with respect to a variable.It shows how parameter 1 changes with parameter 2.
It is: exact when parameter 2 depends linearly on parameter 1.It is approximate when parameter 2 depends nonlinearly on parameter 1,
but it is quite accurate if it is only used close to where it is calculated.
![Page 69: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/69.jpg)
69
Consider the system characterized by G(y). Thenis the sensitivity of the equation G with respect to y,evaluated at y*.
*yy
G
G(y)
yy*
Slope is G/y evaluated at y*.
y
It’s usefulness is that once it is calculated, it can be used to QUICKLY evaluate f(y) from G(y)G(y*)+ (G/y|y*)y,
BUT ONLY AS LONG AS y IS CLOSE TO y*.
y
![Page 70: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/70.jpg)
70
Consider parameter p: we desire to obtain the sensitivity ofG(y,p) to p. Typical parameters p would be a bus load, a buspower factor, or a generation level.
Very important to distinguish between • voltage sensitivities
• voltage instability sensitivities
What is the difference between them in terms of • what they mean ?• how to compute them ?
![Page 71: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/71.jpg)
71
Sensitivities for bus voltage
These we compute at the current operating condition.
For a given continuation parameter, they can be obtainedfrom the first predictor step in the continuation power flow.
|V|
Current operating point
d
dV
d
tRecall that this provides us withthe tangent vector, given by:
The tangent vector is the vector of sensitivities with respect to a smallchange in , so the portion of the vectordesignated as dV is exactly the voltagesensitivities.
![Page 72: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/72.jpg)
72
Sensitivities for voltage instability
Here, it is important to realize that the measure of voltage instability,the loading margin, depends on an operating condition
different from the present operating condition.
The implication is that we must look at sensitivities of the loading margin, not of the voltage.
|V|
Current operating point
So we want the sensitivities evaluated at this point, i.e., the SNB point.
Loading margin
![Page 73: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/73.jpg)
73
Let S be the vector of real and reactive load powers,and k be the direction of load increase.
kSS 0 Also, define L as the loading margin (a scalar), so thatthe load powers resulting in the SNB point are given by:
Derivation of loading margin sensitivities at SNB point.
We desire to find the sensitivity of the loading margin L to a change in the parameter p. We denote this sensitivity by Lp.
kSS L0
![Page 74: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/74.jpg)
74
Consider the system characterized by
G(y,S, p) = 0
Assumption: the system has a SNB at (y*,S*, p*), i.e., :
1. G(y*,S*, p*) = 0 (an equilibrium point)
2. Gy(y*,S*, p*) is singular (zero eigenvalue), and w is a left eigenvector of Gy(y*,S*, p*), corresponding to the zero eigenvalue so that (by definition of the left eigenvector) wT Gy(y*,S*, p*) =0 wT=0 Note that Gy(y*,S*, p*), being singular, cannot be inverted, but we can compute it (that is, Gy (y*,S*, p*)), and its eigenvectors.
3. wT GS(y*,S*, p*) 0
We want the sensitivity of the loading margin to p.
![Page 75: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/75.jpg)
75
The points (y,S, p) satisfying numbers 1 and 2 correspond to SNB points,
and we can obtain a curve of such points byvarying p about its nominal value p*.
Linearization of this curve about the SNB point results in
0***
pGSGyG pSy
where the notation |* indicates the derivatives are evaluated at the SNB point. Pre-multiplication by the left eigenvector w results in:
0***
pGwSGwyGw pT
ST
yT
By #2 on the previous slide, the first term in the above is zero. So...
![Page 76: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/76.jpg)
76
0**
pGwSGw pT
ST
pGwkGwLpGwkLGw pTT
pTT
****0
kLS
kSS
L0
kGw
Gw
p
LL
ST
pT
p
*
*
*
Now recall the relation of the load powers to the loading margin….
Substituting this expression for the load powers into eqt. *,
Eqt. *
And the loading margin sensitivity to parameter p is:So p may be, for example,real power load at a bus (to detect the most effective loadshedding) or reactive power at a bus (to determine where to site a shunt cap).
![Page 77: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/77.jpg)
77
Some comments about computing Lp
• The left eigenvector w must be computed for the Jacobian Gy evaluated at the SNB point.
• You only need to compute w and GS once, independent of how many sensitivities you need. Methods to compute the left eigenvector w include QR or inverse iteration.
• The vector of derivatives with respect to the parameter p, which is Gp, is typically sparse. For example, if you want to compute the sensitivity to a bus power, then there would be only 1 non-zero entry in Gp.
• The matrix of derivatives with respect to the load powers, GS, using constant power load models, is a diagonal matrix with ones in the rows corresponding to load buses. This is because a particular load variable would ONLY occur in the equation corresponding to the bus where it is located, and for these equations, these variables appear linearly with 1 as coefficient.
kGw
GwL
ST
pT
p
*
*
*
![Page 78: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/78.jpg)
78
Some comments about extensions
• Multiple sensitivities may be computed using Gp (a matrix) instead of Gp (a vector). In this case, the result is a vector.
• A sensitivity to a line outage may be obtained by letting p contain elements corresponding to the outaged line parameters.
kGw
GwL
ST
pT
p
*
*
*
• Getting multiple sensitivities can be especially attractive when we want to find the sensitivity to several simultaneous changes. One good example is to find the sensitivity to changes in multiple loads.
• A special case of this is to find the sensitivity to changes at ALL loads, which is very typical, given a particular loading direction k . Then
i
pi iLkL
*loads all
![Page 79: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/79.jpg)
79
Some comments about extensions
• A sensitivity to a line outage may be obtained by letting p contain elements corresponding to the outaged line parameters: R (series conductance), X (series reactance), and B (line charging). Then use the multiple parameter approach.
kGw
GwL
ST
pT
p
*
*
*
pLL p *
3 3Zpq=R + jX
p q
jB jB• Here, p = [R X B]T.
• Note that p is NOT SMALL ! Therefore L may have considerable error. For that reason, this one needs to be careful about using this approach to compute the actual loading margins following contingencies.
• However, it certainly can be used for RANKING contingencies. One might consider having a “quick approximation” and a “long exact” risk calculation.
![Page 80: 1 Summary of Papers 1. P. Sauer and M. Pai, Power System Steady-State Stability and the Load Flow Jacobian, IEEE Transactions on Power Systems, Vol. 5,](https://reader036.fdocuments.net/reader036/viewer/2022081421/551661d7550346a2698b51e2/html5/thumbnails/80.jpg)
80
• Greene, et al., also propose a quadratic sensitivity which requires calculation of a second order term Lpp . This is used together with the linear sensitivity according to
Some comments about alternatives
• Invariant Subspace Parametic Sensitivity (ISPS) by Ajjarapu. Advantages:
– based on differential-algebraic model– provides sensitivities at ANY point on the P-V curve
2
**
)(2
1pLpLL ppp
It requires significantly more computation but can provide greateraccuracy over a larger range of p.