1. Introduction to MV Design Guide

download 1. Introduction to MV Design Guide

of 53

Transcript of 1. Introduction to MV Design Guide

  • 7/30/2019 1. Introduction to MV Design Guide

    1/53

    Building a New Electric World

    Introduction to MVequipmentsTraining for internal group

    2006

  • 7/30/2019 1. Introduction to MV Design Guide

    2/53

    2T Limantoro Sch. Indonesia . Aug 2005

    Introduction to MV equipments

    Basic magnitude to define a MV Switchgear:

    Voltage

    Current

    Frequency

    Short Circuit power

    The Voltage, rated current and rated frequency are

    often known in the single line or specification or can

    easily be defined

    Short circuit power to choose various parts of a

    switchgear which must withstand significant

    temperature rises and electro dynamic constraint.

    Voltage to define the dielectric withstand of the

    components such as: CB, insulators, CTs,VTs,etc

  • 7/30/2019 1. Introduction to MV Design Guide

    3/53

    3T Limantoro Sch. Indonesia . Aug 2005

    Electrical network can be disconnect, protect and

    control by using SWITCHGEAR :

    METAL enclosed switchgear divided 3 types:

    Metal clad : example: MC set,NEX

    Compartmented : example: SM6

    Block : example Interface/joggle cubicle.

    Introduction to MV equipments

  • 7/30/2019 1. Introduction to MV Design Guide

    4/53

    4T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    VOLTAGE

    Operating/service Voltage U (kV): Voltage across the equipment terminals.

    example : 22kV, 3.3kV,

    Rated Voltage Ur (kV) : (nominal Voltage)

    Max rms (root mean square) value of the voltage that

    equipment can withstand under normal operating

    conditions.

    The rated voltage (Ur) is always greater than the

    operating voltage.

    The rated voltage associated with an insulation level

    Examples : Rated voltage 24kV, 17.5kV, 12kV and 7.2kV

  • 7/30/2019 1. Introduction to MV Design Guide

    5/535T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    VOLTAGE

    Insulation level Ud (kV rms, 1 minute) and Up (kV peak)

    This defines the electric withstand of equipment to switching under operation over

    voltages and lightning impulse.

    Ud: Over voltage due to of internal switchgear, which accompany all changes in

    the circuit: opening/closing CB or Switch, breakdown or shorting across an insulator,

    etc

    Simulated in laboratory by the power-frequency withstand voltage for 1 minute.

    Example : Ur : 24kV Ud : 50kVrms/1 min.

    Up: over voltage of external switchgear or atmospheric origin occur

    when lightning falls on or near a transmission line.

    Simulated in laboratory by the lightning impulse withstand voltage.

    Examples : Ur : 24kV Up : 125kVp

  • 7/30/2019 1. Introduction to MV Design Guide

    6/536T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Standard

    Merlin Gerin equipment is conformity with list 2 of the series 1 table IEC60 071 and 60 298.

    Insulation level apply to MV swgr at altitudes of less than 1000 meters,20 deg.C, 11 g/m3 humidity and press of 1.013 mbar.

    Above this ,derating should be considered.

    Rated

    Voltage

    Rated power-

    frequency

    withstand voltage

    Normal

    operating

    voltage

    kV rms 1minute kV rms kV rms

    list 1 list 2

    7.2 40 60 20 3.3 to 6.6

    12 60 75 28 10 to 11

    17.5 75 95 38 13.8 to 15

    24 95 125 50 20 to 22

    36 145 170 70 25.8 to 36

    Rated lightning

    impulse

    withstand voltage

    1.2/50us 50Hz

    .

    kV peak

  • 7/30/2019 1. Introduction to MV Design Guide

    7/537T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Standard

    Each insulation level corresponds to a distance in air whichguarantees withstand without a test certificate.

    lower than this distance, we need simulation/test in the laboratory tocheck lightning impulse withstand voltage.

    Rated

    Voltage

    Rated power-

    frequency

    withstand

    voltage

    Distance live

    to earth in air

    .

    kV rms 1minute kV rms cm

    7.2 20 9

    12 28 12

    17.5 38 16

    24 50 22

    36 70 32

    95

    125

    170

    Rated lightning

    impulse

    withstand voltage

    1.2/50us 50Hz

    .

    kV peak

    60

    75

  • 7/30/2019 1. Introduction to MV Design Guide

    8/538T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    IEC Standard Voltage

    20 7.2 60

    1217.5

    24

    36

    Ur

    957528

    38

    UpUd

    170

    12550

    70

    1.2/50us 50Hz

  • 7/30/2019 1. Introduction to MV Design Guide

    9/53

    9T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Current

    The rms value of current that equipment can withstand whencurrent flow without exceeding the temperature rise allowed in

    standards.

    Temperature rises authorized by the IEC according to the type of

    contacts.

  • 7/30/2019 1. Introduction to MV Design Guide

    10/53

    10T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    OPERATING Current : I (A)

    Calculate from the consumption of the devices connected.

    Actual current passes through the equipment.

    generally customer provide its value

    calculate if we know the power of the load

    Exercise:

    A switchboard with a 630kW motor feeder and a 1250kVA

    xmer feeder at 5.5kV operating voltage, cos j = 0.9 and motor

    efficiency h = 90%

    How many ampere the operating current of Transformer and

    motor?

    81.74 A

  • 7/30/2019 1. Introduction to MV Design Guide

    11/53

    11T Limantoro Sch. Indonesia . Aug 2005

    Short Circuit Current

    Short circuit power depends on :

    Network configuration (exp: single source, parallelsource,network, generators)

    Impedance of each equipments or devices.(exp: lines, cables,

    transformers, motors)

    Maximum power that network or source can deliver to an

    installation during a fault, expressed in MVA or in kA rms at operating

    voltage.(Psc, for instance 500MVA)

    Determination of the short-circuit power requires analysis of the

    power flows feeding the short circuit in the worst possible case.

    What is short circuit level for 500MVA at 20KV ?

    14.5kA 13.13kA

  • 7/30/2019 1. Introduction to MV Design Guide

    12/53

    12T Limantoro Sch. Indonesia . Aug 2005

    Short Circuit Current

  • 7/30/2019 1. Introduction to MV Design Guide

    13/53

    13T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Minimum short-circuit current: Isc (kA rms.)

    Corresponds to a short circuit at one end of the fault point.

    This value allows us to choose the setting of thresholds for over current

    protection devices and fuses

    Example: Isc: 25kA rms

    source load

    Ith Is

    c

  • 7/30/2019 1. Introduction to MV Design Guide

    14/53

    14T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Maximum short-circuit current: Ith (kA rms. 1 s or 3 s)

    Corresponds to a short circuit in upstream terminals of the switchingdevice.

    This value is defined in kA for 1s or 3 s

    It is used to define the thermal withstand of the equipment

    Example: Isc: 31.5 kA rms. 1 s or 3 s

    source load

    IscIt

    h

  • 7/30/2019 1. Introduction to MV Design Guide

    15/53

    15T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Peak Value of the max.short circuit current (kA peak)

    value of the initial peak in the transient period

    I dyn = (kA peak)

    I dynamic is equal to :

    2.5 x Isc at 50 Hz (IEC)

    2.6 x Isc at 60 Hz (IEC)

    2.7 x Isc (ANSI) times the short circuit current calculated at a given

    point in the network.

    Example: Isc : 25kA Idyn: 2.5 x 25= 63.75kA peak (IEC 60 056)

    Idyn: 2.7 x 25= 67.50kA peak (ANSI), 25kA at

    a given point

    This value determines the breaking capacity and closing capacity of CBs and

    Switches, as well as the electro dynamic withstand of busbars and switchgear. IEC uses the following values: 8 12.5 16 20 25 31.5 40 kA rms

  • 7/30/2019 1. Introduction to MV Design Guide

    16/53

    16T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    The short circuit current depends on the type of equipment

    installed on the network (transformers, generators, motors, lines,etc)

    Transformer :

    To determine the short circuit current across the terminals of atransformer , we need to know short circuit voltage (Usc %)

    Usc % is defined by:

    1. The voltage xmer is not powered: U=0

    2. place the secondary in short circuit

    3. gradually increase voltage U at the primary up to the

    rated current Ir in the transformer secondary side The value U read across the primary is then equal to Usc

    The short circuit Isc = Ir / Usc

    Example : Transformer 20 MVA/10kV with Usc: 10%. Upstream

    power infinite

    Ir = Sr/ (V3 xU no-load) = 20.000/(V3x10) = 1150 A

    Isc = Ir / Usc = 1150 / 10% = 11.500A = 11.5kA

  • 7/30/2019 1. Introduction to MV Design Guide

    17/53

    17T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Synchronous Generators : (Alternator and Motor)

    To determine the short circuit current across the terminals of a

    synchronous generator is very complicated because the internal

    impedance of the generator varies according to time

    When the power gradually increases, the current reduces passing

    through three characteristic periods:

    Sub Transient, average duration 10 ms (enabling

    determination of the making capacity of the CB and electro

    dynamic constraint)

    Transient , average duration 250 ms (sets the equipments

    thermal constraints) Permanent (value of the short circuit current in steady state)

    The short circuit Isc = Ir / Xsc

    The most common values for a synchronous generator are:

    Example : Generator 15 MVA/10kV with Xd: 20%.

    Ir = Sr/ (V3 xU) = 15.000/(V3x10) = 867 A

    Isc = Ir / Xd = 867/ 20% = 4.330A = 4.33kA

  • 7/30/2019 1. Introduction to MV Design Guide

    18/53

    18T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Frequency fr (Hz)

    Two frequency are usually used throughout the world:

    50 Hz in Europe

    60 Hz in the USA

    several countries use both frequencies indiscriminately

    Instrument Voltage Transformer rated 50 can operate at 60Hz

    Instrument Current Transformer rated 50 can operate at 60Hz.

    But CT with rated 60Hz can not be operated at 50Hz.

  • 7/30/2019 1. Introduction to MV Design Guide

    19/53

    19T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    SWITCHGEAR FUNCTION

  • 7/30/2019 1. Introduction to MV Design Guide

    20/53

    20T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    DIFFERENT ENCLOSURE TYPE

    metal clad

    compartment

    Block type

  • 7/30/2019 1. Introduction to MV Design Guide

    21/53

    21T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    DIELECTRIC WITHSTAND

    depends on 3 parameters:

    The Dielectric strength of the medium

    The Shape of the parts The distance :

    ambient air between the live parts

    insulating air interface between the live parts

    Dielectric Strength of air depends on ambient conditions:

    Pollution reducing the insulating performance by a factor

  • 7/30/2019 1. Introduction to MV Design Guide

    22/53

    22T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    The Shape of the parts

    It is essential to eliminate any peak effect to avoid disastrous effect

    on the impulse wave withstand in particular and on the surface ageing of

    insulator.

    Air Ionization Generate Ozone Breakdown of insulator surface or

    skin

    Distance between parts

    Ambient air between live parts

    For installations sometime we can not test under impulse conditions,

    the table below gives the minimum distance to comply with in air either

    phase to earth or phase to phase .

    The table based on IEC 71-2 according to the rated lightning impulse

    withstand voltage

  • 7/30/2019 1. Introduction to MV Design Guide

    23/53

    23T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    CURRENT TRANSFORMER

    To provide a secondary current that is proportional tothe primary current.

    Transformation ratio (Kn) :

    Kn = I primary/Isecondary = N2/N1

    Current transformer must be conformity with IEC 185 and BS3038 and ANSI

    One CT comprises one or several primary windings or one or several secondary windings and all being

    encapsulated in an insulating resin

    Dont leave a CT in open circuit because dangerous voltages for people and equipment may appear

    across its terminal

    CT defined at 50Hz can be installed on a 60Hz network. The opposite is not correct.

    Rated primary Voltage (Upr) > rated insulation voltage

    Special case for CT is core balance or ring CT installed on a cable. The dielectric insulation is provided

    by the cable and the air located between them. The core balance or ring CT is itself insulated.

  • 7/30/2019 1. Introduction to MV Design Guide

    24/53

    24T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    Ifj and h are not known, use

    approx value cos j: 0.8 and h = 0.8

    Capacitor Feeder :

    Derating coefficient of 30% to takeinto account of temp. rise due to

    capacitor harmonic

    Bus section

    The greatest value of current that

    can flow in the bus section on a

    permanent basis.

    Ips = In bus

    Standardized values :

    10-12.5-15-20-25-30-40-50-60-75 andtheir multiples and factors

    CT must be able to withstand 120% the

    rated current

    f

  • 7/30/2019 1. Introduction to MV Design Guide

    25/53

    25T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment CURRENT TRANSFORMER

    Example:

    A thermal protection device for a motor has a setting range of between 0.6 and 1.2 x Ir (CT).

    In order to protect this motor, the required setting must correspond to the motors rated current.

    If we assume that Ir for the motor = 45 A, the required setting is therefore: 45A

    If we use a 100/5A CT, the relay will never see 45A , because: 100A x 0.6 = 60A > 45A.

    If we use a 75/5A CT, the relay will see , 75 x 0.6 = 45 A

    The range of setting will be: 0.6 < 45/75 < 1.2 . This CT is suitable.

    RATED THERMAL SHORT CIRCUIT CURRENT (Ith)

    Value of the installation max. short circuit current and the duration 1s or 3 s.

    Each CT must be able to withstand short circuit current both thermally and dynamically until the fault is

    effectively cut off.

    Ith = Ssc / (U x V3), Ssc = power short circuit MVA

    When the CT is installed in a fuse protected, the Ith = apprx. 80 Ir.

    RATED SECONDARY CURRENT:

    Local use or inside switchgear Isr = 5A

    Remote use or long distance Isr = 1A

    M t l l d f t b ilt i t

  • 7/30/2019 1. Introduction to MV Design Guide

    26/53

    26T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    ACCURACY CLASS

    Metering: class 0.5

    Switchboard metering : class 1

    Over current protection : class 10P or 5P

    Differential protection : class X or 5P20

    Zero sequence protection: class 5P

    REAL POWER OUTPUT

    The total (sum) of the consumption of the cabling, protection or metering device connected to the CTsecondary circuit.

    Consumption of the cooper cable (losses in the cable):

    where :

    Consumption of each metering or protecting devices are given in the technical specification

    0.0225

    0.5625

    M t l l d f t b ilt i t

  • 7/30/2019 1. Introduction to MV Design Guide

    27/53

    27T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    SAFETY FACTOR (SF)

    Safety Factor is protection of metering device in case of a fault

    SF will chosen according to the current metering short time withstand current: 5 < SF< 10.

    SF is ratio between the limit of rated primary current (Ipl) and the rated primary current (Ipr)

    where : Ipl is the value of primary current for which the error in secondary current = 10%

    Example: an ammeter is guaranteed to withstand a SC of 10 Ir, I.e. 50A for a 5A (secondary CT/device

    input). To avoid ammeter will not be destroyed in the case of primary fault, the CT must be saturated

    before 10 Ir in the secondary side. A safety factor of 5 is suitable.

    Schneider CTs have a safety factor of 10, however lower SF can be requested.

    ACCURACY LIMIT FACTOR (ALF)

    Protection application : accuracy limit factor and accuracy class

    Example: Definite time OC relay

    The relay will function perfectly if : ALF real CT > 2 (Irs / Isr)

    where : Irs : relay threshold setting, Isr : rated secondary CT

    CT 100A/5A, I relay setting : 5 times , so the ALF = 2 (5x5/5) = 10, Actual ALF CT > 15 or 20

    Metal enclosed factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    28/53

    28T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    CLASS X (DIFFERENTIAL PROTECTION)

    The short circuit current is chosen as

    a function of the application:

    generator differential

    motor differential

    Transformer differential

    busbar differential

    Metal enclosed factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    29/53

    29T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    CLASS X (DIFFERENTIAL PROTECTION)

    Metal enclosed factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    30/53

    30T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    CLASS X (DIFFERENTIAL PROTECTION)

    Metal-enclosed factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    31/53

    31T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    CLASS X (DIFFERENTIAL PROTECTION)

    Metal-enclosed factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    32/53

    32T Limantoro Sch. Indonesia . Aug 2005

    Metal-enclosed, factory built equipment

    VOLTAGE TRANSFORMER

    To provide secondary voltage that is proportional to the primary voltage.

    IEC Standard 60 186 defines the conditions which voltage transformer must meet.

    One VT comprises a primary windings and one or several secondary windings and all

    being encapsulated in an insulating resin

    RATED VOLTAGE FACTOR (KT)

    The rated voltage factor is the rated primary voltage has to be multiplied in order to

    determine the max. voltage for which the transformer must comply with the specified

    temperature rise and accuracy recommendations.

    According earthing system of the network, the VT must be able to withstand this max.

    voltage for the time that is required to eliminate the fault.

    Generally VT manufactures comply with : VT phase to earth: 1.9 for 8 h and VT phase to

    phase : 1.2 continuous.

    Metal-enclosed factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    33/53

    33T Limantoro Sch. Indonesia . Aug 2005

    Metal enclosed, factory built equipment

    RATED PRIMARY VOLTAGE (Upr)

    According to the design, VT will be connected :

    Phase to earth 22.000V/V3 / 110V/V3, where Upr = U/V3

    Phase to phase 22.000 / 110V, where Upr = U

    RATED SECONDARY VOLTAGE (Usr)

    Phase to phase VT, rated secondary voltage : 100V or 110 V

    Phase to Ground VT, rated secondary voltage : 100/V3 or 110V/V3

    RATED OUTPUT

    The apparent power output that VT can supply the secondary circuit

    when connected at rated primary voltage and connected to the nominal

    load.

    It must not introduce any error exceeding the values guaranteed by the

    accuracy class . (S = V3. U. I in 3 phase circuit)

    Standardized value are:

    10-15-25-30-50-75-100-150-200-300-400-500 VA

    Metal-enclosed, factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    34/53

    34T Limantoro Sch. Indonesia . Aug 2005

    Metal enclosed, factory built equipment

    ACCURACY CLASS

    The limits of errors guaranteed in terms of transformation ratio and phase under the specified conditions

    of both power and voltage.

    PROTECTION ACCORDING TO IEC 60 186

    Classes 3P and 6P (but in practice only class 3P is used)

    The accuracy class is guaranteed for values :

    of voltage of between 5% of the primary voltage and the max. value of this voltage which is the

    product of the primary voltage and the rated voltage factor (kT x Upr)

    For secondary load between 25% and 100% of the rated output with a power factor of 0.8

    inductive.

    Metal-enclosed, factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    35/53

    35T Limantoro Sch. Indonesia . Aug 2005

    Metal enclosed, factory built equipment

    Transformation Ratio (Kn)

    Voltage ratio error

    This is the error that the transformer introduces into the voltage measurement

    Phase error or phase shift error

    This is the phase difference between the primary voltage Upr and the secondary voltage Usr.

    the error expressed in minutes of angle

    Thermal power limit or Rated continuous power

    This is the apparent power that transformer can supply in steady state at its rated secondary

    voltage without exceeding the temperature rise limits set by the standards.

    Metal-enclosed, factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    36/53

    36T Limantoro Sch. Indonesia . Aug 2005

    , y q p

    PROTECTION INDEX

    Protection of people against direct contact and protection of equipment

    against certain external influences.

    Requested by international standard for electrical installations and

    products (IEC 60 529)

    The protection index is the level of protection provided by an enclosure

    against access to hazardous parts, penetration of solid foreign bodies

    and of water.

    The IP code is a coding system to indicate the protection index.

    Metal-enclosed, factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    37/53

    37T Limantoro Sch. Indonesia . Aug 2005

    , y q p

    PROTECTION INDEX: first index

    Metal-enclosed, factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    38/53

    38T Limantoro Sch. Indonesia . Aug 2005

    y q p PROTECTION INDEX: second index

    Metal-enclosed, factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    39/53

    39T Limantoro Sch. Indonesia . Aug 2005

    PROTECTION INDEX: third index

    Definitions

    The protection mentions correspond to impact energy

    levels expressed in joules hammer blow applied directly to the equipment

    impact transmitted by the supports, expressed in terms of

    vibrations therefore in terms of frequency and acceleration

    The protection indices against mechanical impact can be

    checked by different types of hammer: pendulum hammer,

    spring-loaded hammer or vertical free-fall hammer (diagram

    below).

    Metal-enclosed, factory built equipment

  • 7/30/2019 1. Introduction to MV Design Guide

    40/53

    40T Limantoro Sch. Indonesia . Aug 2005

    PROTECTION INDEX: third index

  • 7/30/2019 1. Introduction to MV Design Guide

    41/53

    Sepam 1000+

    Presentation

    Sepam 1000+d d li i

  • 7/30/2019 1. Introduction to MV Design Guide

    42/53

    42T Limantoro Sch. Indonesia . Aug 2005

    standard applications

    For industrial and service

    sector site networks

    For public distribution

    networks

    For all voltage levels

    S20 substation applicationS i 20

  • 7/30/2019 1. Introduction to MV Design Guide

    43/53

    43T Limantoro Sch. Indonesia . Aug 2005

    Series 20

    Substation incomer and feeder

    applications

    Protection functions:

    50/51, phase overcurrent

    50N/51N, earth fault

    46, negative sequence /

    unbalance

    Logic discrimination

    4-cycle recloser

    Substation application(S40/S41/S42 t ) S i 40

  • 7/30/2019 1. Introduction to MV Design Guide

    44/53

    44T Limantoro Sch. Indonesia . Aug 2005

    (S40/S41/S42types) Series 40

    Parallel incomers or closed ring

    networks

    Isolated or compensated

    neutral networks

    Protection functions:

    50/51,50N/51N,46,50BF 67N/67NC,

    directional earth fault

    67, directional phase

    overcurrent

    32P, reverse power

    I, U, P, E metering

    T20 transformer applicationS i 20

  • 7/30/2019 1. Introduction to MV Design Guide

    45/53

    45T Limantoro Sch. Indonesia . Aug 2005

    Series 20

    Protection functions:

    50/51, 50N/51N and 46

    49RMS, thermal overload

    38/49T, temperature

    monitoring (8 sensors)

    Processing of faults detectedby transformer Buchholz or

    thermostat

    (MES module required)

    Transformer application(T40/T42 t ) S i 40

  • 7/30/2019 1. Introduction to MV Design Guide

    46/53

    46T Limantoro Sch. Indonesia . Aug 2005

    (T40/T42 types) Series 40

    Parallel transformers

    Isolated or compensatedneutral networks

    Protection functions: 50/51,50N/51N, 46,50BF 49RMS and 38/49T

    67N/67NC, directional earthfault

    67, directional phaseovercurrent

    I, U, P, E metering

    M20 motor applicationSeries 20

  • 7/30/2019 1. Introduction to MV Design Guide

    47/53

    47T Limantoro Sch. Indonesia . Aug 2005

    Series 20

    Protection functions:

    50/51, 50N/51N, 46

    49RMS

    38/49T

    Specific functions:

    37, phase undercurrent

    48/51LR, excessive starting

    time and locked rotor

    66, starts per hour

    specific motor-related function

    (MES114)

    Motor application(M41 type) Series 40

  • 7/30/2019 1. Introduction to MV Design Guide

    48/53

    48T Limantoro Sch. Indonesia . Aug 2005

    (M41 type) Series 40

    Isolated or compensated

    neutral networks

    All the M20 protectionfunctions, plus: 67N/67NC, directional earth

    fault 32P, reverse power

    27/59, 81L/81H,

    Automatic load shedding

    I, U, P, E metering

    Generator application(G40 type) Series 40

  • 7/30/2019 1. Introduction to MV Design Guide

    49/53

    49T Limantoro Sch. Indonesia . Aug 2005

    (G40 type) Series 40

    Protection functions:

    50/51, 50N/51N,46,50BF 49RMS and 38/49T 27/59, 81L/81H,

    Specific functions: 50V/51V, voltage restraint

    overcurrent 32P, 32Q/40, directional active

    and reactive overpower

    I, U, P, E measurements

    B21 busbar applicationSeries 20

  • 7/30/2019 1. Introduction to MV Design Guide

    50/53

    50T Limantoro Sch. Indonesia . Aug 2005

    Series 20

    Voltage protection functions:

    27/59, phase-to-phase

    under/overvoltage 81L/81H, under/overfrequency

    59N, neutral voltage

    displacement

    27D/47, positive sequence

    undervoltage and phaserotation direction

    27R, remanent undervoltage

    27S, 3 phase-to-phase

    undervoltages V1,V2,V3

    B22 busbar applicationSeries 20

  • 7/30/2019 1. Introduction to MV Design Guide

    51/53

    51T Limantoro Sch. Indonesia . Aug 2005

    Series 20

    Voltage protection functions:

    27/59, 27S, 59N 81L/81H 27D/47, 27R

    Loss of mains protection 81R,rate of change of frequency(ROCOF)

    fast, reliable detection of lossof mains for substations with generators

    in parallel with the mainnetwork

    Sepam 1000+Selection guide

  • 7/30/2019 1. Introduction to MV Design Guide

    52/53

    52T Limantoro Sch. Indonesia . Aug 2005

    Selection criteria series 20 series 40

    Measurements I U U I and U I and U I et U

    Specific protection Loss of mains Directional Directional

    functions (ROCOF) earth fault earth fault &phase O/C

    Applications series 20 series 40

    Substation S20 S40 S41 S42

    Transformer T20 T40 T42

    Motor M20 M41

    Generator G40

    Busbar B21 B22

  • 7/30/2019 1. Introduction to MV Design Guide

    53/53

    53T Limantoro Sch. Indonesia . Aug 2005

    Basic electrical knowledge is needed to understand MV SWGR