1 2 6 3 4 5FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FD FIRE DAMPER, FLOOR DRAIN FCVA FLOOR...

4
M000 MECHANICAL SYMBOLS & ABBREVIATIONS aaa aaa X X PIPING SYMBOLS D G M X X FS VS 1 1 R620 aaabb RL RS RHG HWR HWS CHR CHS CDR CDS T H F D RA F a bbb cc/dd aaa bbb ccc KW UP DN M B FS S H DUCTWORK 100 100 100 100 X X X X X X X X "aaa" DENOTES TYPE EXISTING PIPE, "aaa" DENOTES TYPE EXISTING PIPE TO BE REMOVED, EQUIPMENT REFERENCE OWNER OR CONTRACTOR FURNISHED "cc/dd" DENOTES NECK SIZE "a" DENOTES TYPE, "bbb" DENOTES CFM, AIR DISTRIBUTION DEVICE REFERENCE. APPLICABLE "ccc KW" DENOTES HEATING KW WHERE "aaa" DENOTES TYPE, "bbb" DENOTES CFM, HVAC TERMINAL UNIT REFERENCE. "bb" DENOTES NUMBER. "aaa" DENOTES TYPE, MECHANICAL EQUIPMENT REFERENCE. SUPPLY AIR, "RA" DENOTES RETURN AIR DUCT SMOKE DETECTOR. "SA" DENOTE NEW, "R" DENOTES RELOCATED EXISTING. SUPPLY AIR DIFFUSER, NO LETTER DENOTES REMOVED AND REUSED AS APPLICABLE. DENOTES TO REMAIN, "R" DENOTES TO BE EXISTING SUPPLY AIR DIFFUSER, NO LETTER EXISTING. DENOTES NEW, "R" DENOTES RELOCATED RETURN AIR OR EXHAUST GRILL, NO LETTER TO BE REMOVED AND REUSED AS APPLICABLE. NO LETTER DENOTES TO REMAIN, "R" DENOTES EXISTING RETURN AIR OR EXHAUST GRILL, "R" DENOTES RELOCATED EXISTING. SUPPLY AIR SLOT, NO LETTER DENOTES NEW, BE REMOVED AND REUSED AS APPLICABLE. DENOTES TO REMAIN, "R" DENOTES TO EXISTING SUPPLY AIR SLOT, NO LETTER "R" DENOTES RELOCATED EXISTING. RETURN AIR SLOT, NO LETTER DENOTES NEW, BE REMOVED AND RELOCATED AS APPLICABLE. DENOTES TO REMAIN, "R" DENOTES TO EXISTING RETURN AIR SLOT, NO LETTER AS APPLICABLE. NUMBER DENOTES CFM. "R" DENOTES TO BE REMOVED AND REUSED BOOTS, NO LETTER DENOTES TO REMAIN, EXISTING LIGHT TROFFER SUPPLY AIR RELOCATED EXISTING, NUMBER DENOTES CFM. NO LETTER DENOTES NEW, "R" DENOTES LIGHT TROFFER SUPPLY AIR BOOTS, OR ROUND DUCTWORK RELOCATED EXISTING RECTANGULAR RELOCATED AS APPLICABLE DUCTWORK TO BE REMOVED AND EXISTING RECTANGULAR OR ROUND HVAC TERMINAL UNIT SINGLE DUCT FAN POWERED BALANCING/STOP VALVE GATE VALVE, HVAC DIFFERENTIAL PRESSURE TAPS BALANCING VALVE WITH CONTROL VALVE TWO-WAY MODULATING CONTROL VALVE THREE-WAY MODULATING GAUGE COCK PRESSURE GAUGE WITH REFER TO SHEET NUMBER 1 RE:1MP100 MP100 DETAIL NUMBER DRAWING/ ZV ZONE VALVE Z ZONE XP EXPLOSION ROOF XFMR TRANSFORMER WWF WELDED WIRE FABRIC WT WATERTIGHT, WEIGHT WS WATER SOFTENER WPD WATER PRESSURE DROP WP WEATHERPROOF WM WATER METER WH WATER HEATER, WALL HYDRANT WCO WALL CLEANOUT WC WATER CLOSET WB WET BULB W/O WITHOUT W/ WITH WIRE, WOMEN W WATT, WIDTH, WASTE, WEST VSZDT VERTICAL SINGLE ZONE DRAW THRU VSZBT VERTICAL SINGLE ZONE BLOW THRU VR VARIABLE AIR VOLUME REHEAT VP VACUUM PUMP VOL VOLUME VFD VARIABLE FREQUENCY DRIVE VEST VESTIBULE VERT VERTICAL VEL VELOCITY VD VOLUME DAMPER VB VACUUM BREAKER VAV VARIABLE AIR VOLUME VAC VACUUM, VOLTS AC VA VOLT-AMPERE, VARIABLE V/D VOICE/DATA V VOLT, VENT UPS UNINTERRUPTIBLE POWER SUPPLY UON UNLESS OTHERWISE NOTED LABORATORIES, INC. UL UNDERWRITER'S UH UNIT HEATER UG UNDERGROUND U/S UNDERSLAB UF UNDERFLOOR 2S-2W TWO-SPEED, TWO WINDING 2S-1W TWO-SPEED, ONE WINDING TYP TYPICAL TXV THERMAL EXPANSION VALVE TW TREATED WATER, TEMPERED WATER TU TERMINAL UNIT TS TAMPER SWITCH TRD THREAD, THREADED TR TRENCH TP TRAP PRIMER, TOTAL PRESSURE TOT TOTAL TOS TOP OF SLAB TOIL TOILET TOF TOP OF FOOTING TOC TOP OF CURB TK TANK THK THICK TH BLK THRUST BLOCK TEMP TEMPORARY TF TRANSFER FAN TDH TOTAL DYNAMIC HEAD TD TRENCH DRAIN COMPRESSOR TCC TEMPERATURE CONTROL TC TEMPERATURE CONTROL T STAT THERMOSTAT/SENSOR T&P TEMPERATURE & PRESSURE SYS SYSTEM SYM SYMMETRICAL SWR SIDE WALL REGISTER SWGR SWITCHGEAR SWBD SWITCHBOARD SW SWITCH, SOFTENED WATER SV SANITARY VENT SUSP SUSPENDED SURF SURFACE STRUC STRUCTURE, STRUCTURAL STR STRAINER STOR STORAGE STM STEAM STL STEEL STD STANDARD STC SOUND TRANSMISSION CLASS STB STEAM BOILER STAP SURGE TANK ALARM PANEL STA STATION SURGE TANK ST SOUND TRAP, STEAM TRAP, SST STAINLESS STEEL SSD SUBSURFACE DRAIN SSSC SOLID STATE SPEED CONTROL STAINLESS STEEL SS STOP-START PUSH-BUTTON, SRF SMOKE REMOVAL FAN SQ IN SQUARE INCHES SQ SQUARE SPKLK SPRINKLER SPF STAIR PRESSURIZATION FAN SPEC SPECIFICATION, SPECIFIED SP STATIC PRESSURE, SUMP PUMP SKW STARTING KW SKVA STARTING KVA SL SLOPE SK SINK SIM SIMILAR SHWR SECONDARY HEATING WATER RETURN SHWP SECONDARY HEATING WATER PUMP SHT SHEET SHR SHOWER SH SHOWER SFCS SPRINKLER FLOOR CONTROL STATION SF SQUARE FEET SERV SERVICE SENS SENSIBLE SECT SECTION SEC SECONDARY SE SEWAGE EJECTOR SD SMOKE DETECTOR SCW SOFTENED COLD WATER SCR SILICON CONTROLLED RECTIFIER SCHS SECONDARY CHILLED WATER SUPPLY SCHR SECONDARY CHILLED WATER RETURN SCHP SECONDARY CHILLED WATER PUMP SCHED SCHEDULE(D) SC STEAM CONVERTER SAF SUPPLY AIR FAN SAD SUPPLY SIR DIFFUSER SOUND ATTENUATOR SA SUPPLY AIR, SHOP AIR S SOUTH, SUPPLY, SINK RVS REVERSE NON-REVERSING RVNR REDUCED-VOLTAGE, RV RELIEF VALVE RTU ROOFTOP UNIT RTAH ROOFTOP AIR HANDLING UNIT RS REFRIGERANT SUCTION RPM REVOLUTIONS PER MINUTE ROW RIGHT OF WAY RO ROUGH OPENING, REVERSE OSMOSIS RND,~ ROUND RM REFRIGERATION MACHINE, ROOM RLA RUNNING LOAD AMPS RL REFRIGERANT LIQUID RKW RUNNING KW RKVA RUNNING KVA RIO ROUGH-IN ONLY RIC ROUGH-IN AND CONNECT RHG REFRIGERANT HOT GAS RH RELATIVE HUMIDITY REV REVISION, REVISED REQD REQUIRED REINF REINFORCED, REINFORCING REG REGISTER REFR REFRIGERATOR RED REDUCER RECPT RECEPTACLE RECIRC RECIRCULATE, RECIRCULATING REC RECESSED RE: REFERENCE, REFER RD ROOF DRAIN RCP REFLECTED CEILING PLAN RAG RETURN AIR GRILLE RAF RETURN AIR FAN RAD REFRIGERATED AIR DRYER RA RETURN AIR R&D REMOVE & DISPOSE (R) RELOCATE R RISER QTY QUANTITY PWR POWER PW PRESSURED COLD WATER PVMT PAVEMENT PVDF POLYVINYLIDENE FLUORIDE PVC POLYVINYL CHLORIDE PV PLUG VALVE PT PLUMBING TRIM PSIG POUNDS PER SQUARE INCH GAUGE PSI POUNDS PER SQUARE INCH PSF POUNDS PER SQUARE FOOT PS PRESSURE SWITCH PRV PRESSURE REDUCING VALVE PRS PRESSURE REDUCING STATION PROP PROPERTY PROJ PROJECT PRI PRIMARY PRES PRESSURE PR PAIR, PRINTER PPM PARTS PER MILLION PP POLY PROPYLENE PNTH PENTHOUSE PNL PANEL PNEU PNEUMATIC PLUMB PLUMBING PL PILOT LIGHT PKG PACKAGE, PARKING PIV POST INDICATOR VALVE PHWS PRIMARY HEATING WATER SUPPLY PHWR PRIMARY HEATING WATER RETURN PHWP PRIMARY HEATING WATER PUMP PH PHASE PERF PERFORATED PEND PENDANT PD PRESSURE DROP PCW PUMPED COLD WATER PCHS PRIMARY CHILLED WATER SUPPLY PCHR PRIMARY CHILLED WATER RETURN PCHP PRIMARY CHILLED WATER PUMP PCR PUMPED CONDENSATE RETURN PERSONAL COMPUTER PC PLUMBING CONTRACTOR, PB PUSH BUTTON EQUIPMENT P PUMP, POLE, PLUMBING OZ OUNCE OS&Y OUTSIDE STEM & YOLK OPP OPPOSITE OPNG OPENING OPH OPPOSITE HAND OH OVERHEAD OFF OFFICE OD OUTSIDE DIAMETER OCEW ON CENTER EACH WAY OC ON CENTER OBD OPPOSED BLADE DAMPER OAF OUTSIDE AIR FAN OA OUTSIDE AIR O OXYGEN NTS NOT TO SCALE NOM NOMINAL N.O. NORMALLY OPEN NO NUMBER NIC NOT IN CONTRACT NFS NON-FUSED SWITCH NF NON-FUSED ASSOCIATION NFPA NATIONAL FIRE PROTECTION MANUFACTURER'S ASSOCIATION NEMA NATIONAL ELECTRICAL NEC NATIONAL ELECTRICAL CODE N.C. NORMALY CLOSED NC NOISE CRITERIA NAT NATURAL NA NOT ACCEPTABLE (N) NEW N NORTH, NITROGEN MZU MULTI-ZONE UNIT MVP MEDICAL VACUUM PUMP MVD MANUAL VOLUME DAMPER MVA MEGA VOLT-AMPS MV MEDICAL VACUUM MU MAKE-UP MTG MOUNTING MTD MOUNTED MSTM MEDIUM PRESSURE STEAM MSGR MAIN SWITCHGEAR MSB MAIN SWITCHBOARD MS MONITOR SWITCH MPT MALE PIPE THREAD MP MEDIUM PRESSURE MON MONITOR SWITCH ML MATCH LINE MISC MISCELLANEOUS MIN MINIMUM MI MALLEABLE IRON MH MANHOLE MG MEDICAL GAS OUTLET MFGR MANUFACTURER MEZZ MEZZANINE M/E/P MECHANICAL/ELECTRICAL/PLUMBING MEMB MEMBRANE MED MEDIUM MECH MECHANICAL MDP MAIN DISTRIBUTION PANEL MCC MOTOR CONTROL CENTER MCB MAIN CIRCUIT BREAKER MC MECHANICAL CONTRACTOR MBH THOUSANDS OF BTU'S MAX MAXIMUM MAP MASTER ALARM PANEL MAC MEDICAL AIR COMPRESSOR MA MEDICAL AIR M METER, MALE, MEN LWT LEAVING WATER TEMPERATURE LWCO LOW WATER CUT OFF LWB LEAVING WET BULB LW LAUNDRY LINT WASTE LVP LABORATORY VACUUM PUMP LVL LEVEL LV LAB VACUUM LTG LIGHTING LSTM LOW PRESSURE STEAM LRA LOCKED ROTOR AMPS LPT LOW POINT LP LOW PRESSURE CONSTRUCTION LOC LOCATION, LIMIT OF LH LEFT HAND LG LAB GAS OUTLET LF LINEAR FEET LED LIGHT EMITTING DIODE LDB LEAVING DRY BULB LD LINEAR DIFFUSER LCS LIQUID CRYSTAL DISPLAY LB(S) POUND(S) LATENT LAT LEAVING AIR TEMPERATURE, LAV LAVATORY LAB LABORATORY LAC LAB AIR COMPRESSOR LA LAB AIR COMPRESSOR L LENGTH, LONG, LAVATORY KWH KILOWATT-HOUR KW KILOWATTS KVA KILOVOLT-AMPS KO KNOCKOUT KIT KITCHEN KEC KITCHEN EQUIPMENT CONTRACTOR JT JOINT JST JOIST JS JANITOR SINK JPC JOCKEY PUMP CONTROLLER JP JOCKEY PUMP JB JUNCTION BOX JAN JANITOR IW ICE WATER IPS IRON PIPE SIZE INV INVERT INT INTERNAL, INTERIOR INSUL INSULATE, INSULATION INC INCLUDE, INCLUSIVE INCAND INCANDESCENT IN INCH IF INTERMITTENT FAN VAV IG IRRIGATION IE INVERT ELEVATION ID INSIDE DIAMETER HZ HERTZ HWS HOT WATER SUPPLY HWR HOT WATER RETURN HWP HEATING WATER PUMP HWC HOT WATER CIRCULATOR HWB HOT WATER BOILER HW HOT WATER HVU HEATING AND VENTILATING UNIT CONDITIONING HVAC HEATING, VENTILATING & AIR HUH HOT WATER/GAS UNIT HEATER HTR HEATER HTG HEATING HT HEIGHT DRAW-THRU HSZDT HORIZONTAL, SINGLE-ZONE, BLOW-THRU HSZBT HORIZONTAL, SINGLE-ZONE, HSTM HIGH PRESSURE STEAM HSC HORIZONTAL SPLIT CASE HS HOT WATER SUPPLY HR HOUR, HOT WATER RETURN HPT HIGH POINT HP HORSEPOWER, HIGH PRESSURE HORIZ HORIZONTAL HND D HAND DRYER HKP HOUSEKEEPING PAD HGR HANGER HE HEAT EXCHANGER DETECTOR HD HEAD, HUB DRAIN, HEAT HC HEATING COIL HB HOSE BIBB H STAT HUMIDISTAT/SENSOR H-O-A HAND-OFF-AUTOMATIC H HIGH, HEIGHT, HUMIDIFIER GW GREASE WASTE GV GATE VALVE GTH GRAND TOTAL HEAT GSH GRAND SENSIBLE HEAT GRV GRAVITY ROOF VENT GRD GRADE GR GRILLE GPM GALLONS PER MINUTE GPH GALLONS PER HOUR GPD GALLONS PER DAY GOVT GOVERNMENT GND GROUND GLV GLOBE VALVE GL GLASS GKT GASKET GEN GENERATOR GCO GRADE CLEAN OUT GC GENERAL CONTRACTOR GB GRADE BEAM GALV GALVANIZED GAL GALLON GA GAGE G GAS FVR FULL-VOLTAGE, REVERSING FVNR FULL-VOLTAGE, NON-REVERSING FVC FIRE VALVE CABINET FUT FUTURE FURND FURNISHED FURN FURNITURE FTR FINNED TUBE RADIATION FTG FOOTING FT FOOT, FEET PANEL FSCP FIRE SUPPRESSION CONTROL FIRE SPRINKLER, FLOOR SINK FS FUSED SWITCH, FLOW SWITCH, FRZR FREEZER FRM FRAME FR FLOOR REGISTER FPT FEMALE PIPE THREAD FPC FIRE PUMP CONTROLLER FIRE PUMP FP FAN POWERED MIXING BOX, FOV FUEL OIL VALVE FOS FUEL OIL SUPPLY FOR FUEL OIL RETURN FOP FUEL OIL PUMP FO FUEL OIL FM FACTORY MUTUAL FLR FLOOR FLEX FLEXIBLE FLA FULL LOAD AMPERES FL FLOW LINE FIXT FIXTURE FIN FINISH FHV FIRE HOSE VALVE FHR FIRE HOSE RACK FHC FIRE HOSE CABINET FH FIRE HYDRANT FG FINISHED GRADE FFE FINISHED FLOOR ELEVATION FF FINAL FILTER, FINISHED FLOOR FEC FIRE EXTINGUISHER CABINET FE FIRE EXTINGUISHER FDV FIRE DEPARTMENT VALVE FDS FIRE DEPARTMENT SIAMESE FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FD FIRE DAMPER, FLOOR DRAIN FCVA FLOOR CONTROL VALVE ASSEMBLY FCU FAN COIL UNIT FCS FLOOR CONTROL STATION FCO FLOOR CLEAN OUT FBO FURNISHED BY OTHERS FACP FIRE ALARM CONTROL PANEL FAB(D) FABRICATE (D) FA FIRE ALARM F & E FURNITURE & EQUIPMENT F to F FACE TO FACE F FAHRENHEIT, FAN, FIRE, FEMALE EXT EXTERNAL EXPD EXPOSED EXP EXPANSION EXIST EXISTING EXH EXHAUST EXCV EXCAVATE, EXCAVATION EX EXPLOSION PROOF EWT ENTERING WATER TEMPERATURE EWC ELECTRIC WATER COOLER EWB ENTERING WET BULB EW EACH WAY EVAP EVAPORATOR EUH ELECTRIC UNIT HEATER EVAC EVACUATION PUMP ETR EXISTING TO REMAIN ET EXPANSION TANK ES END SUCTION EQUIV EQUIVALENT EQUIP EQUIPMENT EQ EQUAL AGENCY EPA ENVIRONMENTAL PROTECTION ENGR ENGINEER ENCL ENCLOSURE EMER EMERGENCY ELEV ELEVATOR ELEC ELECTRIC, ELECTRICAL EL ELEVATION, EXPANSION LOOP EJ EXPANSION JOINT EF EXHAUST FAN EDB ENTERING DRY BULB ECC ECCENTRIC EC ELECTRICAL CONTRACTOR EAT ENTERING AIR TEMPERATURE EA EACH (E) EXISTING E EAST COIL UNIT DXFC DIRECT EXPANSION FAN DX DIRECT EXPANSION DWS DRINKING WATER SUPPLY DWR DRINKING WATER RETURN DWP DOMESTIC WATER PUMP DWH DOMESTIC WATER HEATER DWG DRAWING DWC DRINKING WATER COOLER DW DISHWASHER, DISTILLED WATER DV DOUBLE DUCT VAV DS DOUBLE SUCTION, DOWN SPOUT DPR DAMPER DP DIFFERENTIAL PRESSURE DN DOWN DMH DRAIN MANHOLE DL DOOR LOUVER DIV DIVISION DIST DISTRIBUTION DISC DISCONNECT DIS DEIONIZED WATER SUPPLY DIR DEIONIZED WATER RETURN DIM DIMENSION DIFF DIFFUSER DIA DIAMETER DEIONIZED WATER DI DUCTILE IRON, DRAIN INLET, DF DRINKING FOUNTAIN DET DETAIL DESIG DESIGNATION DEPT DEPARTMENT DEP DEIONIZED WATER PUMP DEG DEGREE DDC DIRECT DIGITAL CONTROL DD DECK DRAIN, DOUBLE DUCT CONSTANT VOLUME DC DIRECT CURRENT, DOUBLE DUCT DBL DOUBLE DB DRY BULB Db DECIBEL D DEPTH, DRAIN CVRH CONSTANT VOLUME REHEAT CW COLD WATER CV CONTROL VALVE, CHECK VALVE Cv CAPACITY INDEX CU FT CUBIC FEET CU COPPER CTR CENTER CT COOLING TOWER CSS CLINICAL SERVICE SINK CRU CONDENSATE RETURN UNIT CRT CATHODE RAY TUBE CRAC COMPUTER ROOM A/C UNIT CONDENSTAE RETURN CR CONSTANT VOLUME REHEAT, CPUC CPU CHILLER CHLORIDE CPVC CHLORINATED POLYVINYL CPI CAST IRON PIPE INSTITUTE CO2 CARBON DIOXIDE CORR CORRIDOR CONV CONVERTER CONTR CONTRACTOR CONTINUATION CONT CONTINUOUS, CONTROLLER CONST CONSTRUCTION CONN CONNECTION COND CONDENSER, CONDENSATE CONC CONCRETE, CONCENTRIC COMP COMPRESSOR COMB COMBINATION COL COLUMN CHR CHILLED WATER RETURN CO CLEANOUT CMU CONCRETE MASONRY UNIT CMP CORRUGATED METAL PIPE CLG CEILING CL CENTER LINE CIRC CIRCULATING CIP CAST IN PLACE CI CAST IRON CHV CHECK VALVE CHS CHILLED WATER SUPPLY CHP CHILLED WATER PUMP CH CHILLER CG CEILING GRILL CFS CUBIC FEET PER SECOND CFM CUBIC FEET PER MINUTE CFH CUBIC FEET PER HOUR CDS CONDENSER WATER SUPPLY CDR CONDENSER WATER RETURN CDP CONDENSER WATER PUMP CD CEILING DIFFUSER CC CENTER TO CENTER CB CATCH BASIN CAB CABINET CA CONTROL AIR, COMPRESSED AIR C CELSIUS, CONDUIT BWV BACKWATER VALVE BALANCING VALVE BV BUTTERFLY VALVE, BALL VALVE, BT BATH TUB, BREAK TANK BSMT BASEMENT BS BLACK STEEL BKT BRACKET BOT BOTTOM BOS BOTTOM OF STRUCTURE BOP BOTTOM OF PIPE BOH BOTTOM OF HUB BOF BOTTOM OF FOOTING BOB BOTTOM OF BEAM BM BEAM, BENCH MARK BLDG BUILDING BH BOX HYDRANT BFW BOILER FEED WATER BFV BOILER FEED VALVE PREVENTER BFP BOILER FEED PUMP, BACKFLOW BFD BOILER FEED DEAERATOR BC BELOW COUNTER ASSOCIATION AWWA AMERICAN WATER WORKS AWS AMERICAN WELDING SOCIETY AW ACID WASTE AVTR ACID VENT THRU ROOF AVG AVERAGE AV AREA VALVE, ACID VENT AUX AUXILIARY AUTO AUTOMATIC ATT(S) ATTENUATOR(S) ATS AUTOMATIC TRANSFER SWITCH ATP AUTOMATIC TRAP PRIMER AND MATERIALS ASTM AMERICAN SOCIETY FOR TESTING MECHANICAL ENGINEERS ASME AMERICAN SOCIETY OF CONDITIONING ENGINEERS AND REFRIGERATION AND AIR ASHRAE AMERICAN SOCIETY OF HEATING AS AIR SEPARATOR INSTITUTE ARI AMERICAN REFRIGERATION ARCH ARCHITECT, ARCHITECTURAL APD AIR PRESSURE DROP AP ACCESS PANEL, ALARM PANEL INSTITUTE ANSI AMERICAN NATIONAL STANDARDS ANOD ANODIZED AMB AMBIENT ALT ALTERNATE AL ALUMINUM CAPACITY AIC AMPERES INTERRUPTING AHU AIR HANDLING UNIT AFG ABOVE FINISHED GRADE AFF ABOVE FINISHED FLOOR AFC ABOVE FINISHED CEILING AF AIR FILTER ADJ ADJUSTABLE AD ACCESS DOOR, AIR DRYER ACCU AIR COOLED CONDENSING UNIT ACC AIR COOLED CHILLER A/C AIR CONDITIONING AIR COMPRESSOR AC ALTERNATING CURRENT, ABV ABOVE AAP AREA ALARM PANEL A AMPS, AIR (COMPRESSED) ABBREVIATIONS MECHANICAL SYMBOLS PIPING TYPES MISCELLANEOUS (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS) GENERAL NOTES DRAIN LINE REFRIGERANT LIQUID LINE REFRIGERANT SUCTION LINE REFRIGERANT HOT GAS LINE HEATING HOT WATER RETURN HEATING HOT WATER SUPPLY CHILLED WATER RETURN CHILLED WATER SUPPLY CONDENSER WATER RETURN CONDENSER WATER SUPPLY FLOOR DRAIN DRAWING NOTE REFERENCE FLOW SWITCH VALVE SUPERVISORY SWITCH THERMOSTAT HUMIDISTAT FIRESTAT FLOW SWITCH PNEUMATIC TUBING OR CONTROL WIRING EXISTING POINT OF NEW CONNECTION TO ELBOW UP ELBOW DOWN VALVE IN DROP VALVE IN RISE DIRECTION OF FLOW DIRECTION OF SLOPE DOWN CONCENTRIC REDUCER ECCENTRIC REDUCER TEE OUTLET UP TEE OUTLET DOWN UNION PIPE ANCHOR EXPANSION JOINT STRAINER WITH BLOWDOWN VALVE GLOBE VALVE BALL VALVE OS&Y VALVE CHECK VALVE PRESSURE REDUCING VALVE MANUAL AIR VENT AUTOMATIC AIR VENT T&P RELIEF VALVE VACUUM BREAKER LINE CLEANOUT THERMOMETER WATER METER FLEXIBLE CONNECTION TWO POSITION CONTROL VALVE PRESSURE AND TEMPERATURE TAP FLOW VENTURI EXISTING DUCTWORK SUPPLY OR OUTSIDE AIR DUCT RETURN, RELIEF, OR EXHAUST AIR DUCT FLEXIBLE DUCT CONNECTION INCLINED RISE IN DUCT INCLINED DROP IN DUCT TURNING VANES DUCT EXTRACTOR SPLITTER DAMPER DUCT MOUNTED HEATING COIL DUCT MOUNTED FILTER DUCT MOUNTED HUMIDIFIER DOUBLE DUCT HVAC TERMINAL UNIT SINGLE DUCT HVAC TERMINAL UNIT FIRE DAMPER SMOKE DAMPER FIRE|SMOKE DAMPER MANUAL BALANCING DAMPER GRAVITY BACKDRAFT DAMPER MOTORIZED DAMPER EXISTING FLEXIBLE DUCT TO BE REMOVED NEW FLEXIBLE DUCT NEW RECTANGULAR OR ROUND DUCTWORK EXISTING FLEXIBLE DUCT DRAWING LIST DRAWING/DETAIL REFERENCE KEY FOR TAB REQUIREMENTS. ENGINEER AND OWNER UPON PROJECT COMPLETION. RE: SPECIFICATIONS W. TEST AND BALANCE REPORT SHALL BE SUBMITTED FOR APPROVAL BY THE FLOOR NUMBER. V. ASTERISK (*) IN EQUIPMENT DESIGNATIONS CORRESPONDS TO THE GENERAL CONTRACTOR PRIOR TO EACH CONCRETE POUR. U. COORDINATE ALL SLAB PENETRATIONS AND SLEEVES WITH THE PRIOR TO FABRICATION. ARCHITECTURAL DRAWINGS. LENGTHS SHALL BE FIELD COORDINATED ARE APPROXIMATE. EXACT LENGTHS SHALL BE AS SHOWN ON THE T. LENGTHS OF SUPPLY AND RETURN AIR SLOT DIFFUSERS SHOWN AIR METHOD IS SHOWN ON THIS DRAWINGS. AS THE RETURN AIR PATH TO THE PLENUM, UNLESS ANOTHER RETURN PROJECT. IN GENERAL, RETURN AIR LIGHT FIXTURES WILL BE USED S. THE CEILING PLENUM IS USED AS A RETURN AIR PATH ON THIS AND PARTITION SUPPORT SYSTEMS. R. CONDUIT, PIPING AND DUCTWORK SHALL BE INDEPENDENT OF CEILING FLAT BLACK. ABOVE CEILING ITEMS WHICH ARE VISIBLE THROUGH AIR SLOTS OF GRILLS Q. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING ANY EXTENDING 12 INCHES ON EITHER SIDE OF PARTITION. PENETRATES A PARTITION TO DECK, PROVIDE INSULATED RIGID DUCT PARTITIONS SHALL BE INSTALLED AS DETAILED. WHERE FLEXIBLE DUCTWORK EXTEND TO DECK. EACH DUCT AND PIPE PENETRATION THROUGH THESE P. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF PARTITIONS WHICH MECHANICAL DRAWINGS. SHALL BE PROVIDED BY CODE, EVEN IF THEY ARE NOT SHOWN ON THE ARCHITECTURAL DRAWINGS. FIRE, SMOKE AND FIRE/SMOKE DAMPERS FIRE, SMOKE AND FIRE/SMOKE PARTITIONS SHOWN ON THE COORDINATING THE DUCTWORK FABRICATION DRAWINGS WITH THE O. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE DRAWINGS BY APPLICABLE CODES,REGARDLESS OF WHETHER A DAMPER IS SHOWN ON BE PROVIDED WITH A FIRE, FIRE/SMOKE OR SMOKE DAMPER AS REQUIRED SPECIFIED. EACH DUCT PENETRATION THROUGH THESE PARTITIONS SHALL PARTITIONSSHALL BE INSTALLED AND FIRESTOPPPED AS DETAILED AND RATED PARTITIONS TO DECK. EACH PIPE PENETRATION THROUGH THESE N. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE CONCEALED MECHANICAL EQUIPMENT, VALVES, CONTROLS AND OTHER DEVICES. CONTRACTOR IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO M. FURNISH ACCESS DOORS FOR INSTALLATION BY THE GENERAL LIGHT FIXTURES AND OTHER CEILING MOUNTED DEVICES. VALVES AND OTHER DEVICES REQUIRING ACCESS WITH THE LOCATIONS OF L. COORDINATE THE LOCATION OF NEW ABOVE CEILING MECHANICAL EQUIPMENT, REQUIRED FOR COORDINATED INSTALLATION. DIVISIONSAND EXISITING CONDITIONS AND PROVIDING OFFSETS AS THE LOCATION OF DUCTWORK AND PIPING WITH THE WORK OF OTHER K. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING CONDUIT AND LIGHTING FIXTURES. 8 INCHES ABOVE FINISHED CEILING TO PROVIDE CLEARANCE FOR ELECTRIAL THE ARCHITECTURAL DRAWINGS,ALL DUCTWORK/PIPING SHALL BE INSTALLED CONSTRUCTION, HEIGHTS AND LIGHT FIXTURE LOCATIONS TO BE AS SHOWN IN J. IT IS THE INTENT OF THESE DOCUMENTS TO ALLOW THE CEILING I. ALL SUPPLY AIR DEVICES SHALL BE 4-WAY THROW, UNLESS NOTED OTHERWISE. H. ALL DUCTWORK SIZES SHOWN ARE FREE AIR STREAM DIMENSIONS. ARCHITECT/ENGINEER PRIOR TO SUBMITTING BIDS DURING THE VISIT SHALL BE BROUGHT TO THE ATTENTION OF THE DISCREPANCIES IN THE CONSTRUCTION DOCUMENTS WHICH ARE NOTED AND THE WORK OF OTHER TRADES PRIOR TO SUBMITTING BIDS. ANY THEMSELVES WITH ALL EXISTING CONDITIONS RELATED TO THEIR WORK G. THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE LOCATION OF ALL WALL MOUNTED DEVICES. WHERE THE ARCHITECT HAS DRAWN SUCH ELEVATIONS, FOR THE F. REFER TO ARCHITECTURAL INTERIOR ELEVATION DRAWINGS. ENTERING THE DUCT OR PIPE SHALL BE TEMPORARILY CAPPED TO PREVENT CONSRUCTION DEBRIS FROM DUCTWORK/PIPING IS NOT IMMEDIATELY CONNECTED TO TAP LOCATION E. ALL DUCT OR PIPE TAPS/PENETRATIONS IN WHICH THE DOWNSTREAM SUBMITTALS, RECORD DRAWINGS AND MAINTENANCE MANUAL D. REFER TO SPECIFICTION FOR REQUIREMENTS RELATED TO SHOP DRAWING MECHANICAL CONSTRUCTION. C. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR FEDERAL, STATE AND LOCAL CODES, REGULATIONS AND STANDARDS B. ALL MECHANICAL CONSTRUCTION SHALL COMPLY WITH ALL APPLICABLE AND WORKING MECHANICAL SYSTEM. APPURTENANCES REQUIRED FOR A COMPLETE, COORDINATED A. FURNISH ALL LABOR, MATERIALS, EQUIPMENT, APPARTUS AND M501 M20B M10B M000 MECHANICAL DETAILS MECHANICAL RENOVATION PLAN MECHANICAL DEMOLITION PLAN MECHANICAL SYMBOLS AND ABBREVIATIONS SHEET: Original drawing is 42 x 30 Do not scale contents of this drawing SHEET TITLE: PROJECT NO. (MDACC) PROFESSIONAL SEALS All reproduction & intellectual property rights reserved © 2011 REVISION/ISSUE NO. YYYY-MM-DD Houston, TX 77027 USA t +1 713 407 7700 f +1 713 407 7809 3200 Southwest Freeway, Suite 900 HELLMUTH, OBATA & KASSABAUM, INC. PROJECT NO. (E&C) LOCATION DRAWN BY CHECKED BY A B C D 1 2 6 E 3 4 5 I :\ 3800 \ 3812 - MDACC Rec on f i gu r e Roo m GB. 3608 f o r Ra d On c \ M\ Mec h \ 3812 M SA 000 . dgn 3 / 1 / 2021 3 : 31 : 36 PM JS KJL UT M DA - RE CONF I GURE ROO M G B . 3608 F O R RAN ONC 190963 20.10205.00 (HOK) 3812 ISSUE 03-02-2021 FOR CONSTRUCTION E Engineers T XF i r mR e g i s t r a ti o n N o : F - 0 03 0 68 & Consultants C www.eceng.com F a x ( 71 3 ) 580 - 8888 T e l ( 713 ) 580 - 8 8 00 H o u s t on , T X7 7 002 1010 L a m a r , S u it e 6 50 E & CE n g i n e e r s &C on s u lt a n t s I n c . THE SEAL APPEARING ON THIS DRAWING WAS AUTHORIZED BY: E&C Engineers & Consultants Inc. Texas Firm Registration No: F-003068 L I C E N E S D 100166 KOREY J. LUST S T A T E O F T E X A S P R O F E S S I O N A L E N G I N E E R Digitally signed by Korey Lust Date: 2021.03.01 15:39:13-06'00'

Transcript of 1 2 6 3 4 5FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FD FIRE DAMPER, FLOOR DRAIN FCVA FLOOR...

Page 1: 1 2 6 3 4 5FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FD FIRE DAMPER, FLOOR DRAIN FCVA FLOOR CONTROL VALVE ASSEMBLY FCU FAN COIL UNIT FCS FLOOR CONTROL STATION FCO FLOOR ...

M000

MECHANICAL

SYMBOLS &

ABBREVIATIONS

aaa

aaaX X

PIPING SYMBOLS

D

G

M

X

X

FS

VS

1

1 R620

aaabb

RL

RS

RHG

HWR

HWS

CHR

CHS

CDR

CDS

T

H

F

DRA

F

abbb

cc/dd

aaabbb

ccc KW

UP

DN

M

B

FS

S

H

DUCTWORK

100 100

100100

X X X

X

X

X

X

X

"aaa" DENOTES TYPE

EXISTING PIPE,

"aaa" DENOTES TYPE

EXISTING PIPE TO BE REMOVED,

EQUIPMENT REFERENCE

OWNER OR CONTRACTOR FURNISHED

"cc/dd" DENOTES NECK SIZE

"a" DENOTES TYPE, "bbb" DENOTES CFM,

AIR DISTRIBUTION DEVICE REFERENCE.

APPLICABLE

"ccc KW" DENOTES HEATING KW WHERE

"aaa" DENOTES TYPE, "bbb" DENOTES CFM,

HVAC TERMINAL UNIT REFERENCE.

"bb" DENOTES NUMBER.

"aaa" DENOTES TYPE,

MECHANICAL EQUIPMENT REFERENCE.

SUPPLY AIR, "RA" DENOTES RETURN AIR

DUCT SMOKE DETECTOR. "SA" DENOTE

NEW, "R" DENOTES RELOCATED EXISTING.

SUPPLY AIR DIFFUSER, NO LETTER DENOTES

REMOVED AND REUSED AS APPLICABLE.

DENOTES TO REMAIN, "R" DENOTES TO BE

EXISTING SUPPLY AIR DIFFUSER, NO LETTER

EXISTING.

DENOTES NEW, "R" DENOTES RELOCATED

RETURN AIR OR EXHAUST GRILL, NO LETTER

TO BE REMOVED AND REUSED AS APPLICABLE.

NO LETTER DENOTES TO REMAIN, "R" DENOTES

EXISTING RETURN AIR OR EXHAUST GRILL,

"R" DENOTES RELOCATED EXISTING.

SUPPLY AIR SLOT, NO LETTER DENOTES NEW,

BE REMOVED AND REUSED AS APPLICABLE.

DENOTES TO REMAIN, "R" DENOTES TO

EXISTING SUPPLY AIR SLOT, NO LETTER

"R" DENOTES RELOCATED EXISTING.

RETURN AIR SLOT, NO LETTER DENOTES NEW,

BE REMOVED AND RELOCATED AS APPLICABLE.

DENOTES TO REMAIN, "R" DENOTES TO

EXISTING RETURN AIR SLOT, NO LETTER

AS APPLICABLE. NUMBER DENOTES CFM.

"R" DENOTES TO BE REMOVED AND REUSED

BOOTS, NO LETTER DENOTES TO REMAIN,

EXISTING LIGHT TROFFER SUPPLY AIR

RELOCATED EXISTING, NUMBER DENOTES CFM.

NO LETTER DENOTES NEW, "R" DENOTES

LIGHT TROFFER SUPPLY AIR BOOTS,

OR ROUND DUCTWORK

RELOCATED EXISTING RECTANGULAR

RELOCATED AS APPLICABLE

DUCTWORK TO BE REMOVED AND

EXISTING RECTANGULAR OR ROUND

HVAC TERMINAL UNIT

SINGLE DUCT FAN POWERED

BALANCING/STOP VALVE

GATE VALVE, HVAC

DIFFERENTIAL PRESSURE TAPS

BALANCING VALVE WITH

CONTROL VALVE

TWO-WAY MODULATING

CONTROL VALVE

THREE-WAY MODULATING

GAUGE COCK

PRESSURE GAUGE WITH

REFER TO

SHEET NUMBER

1RE:1MP100

MP100

DETAIL NUMBER

DRAWING/

ZV ZONE VALVE

Z ZONE

XP EXPLOSION ROOF

XFMR TRANSFORMER

WWF WELDED WIRE FABRIC

WT WATERTIGHT, WEIGHT

WS WATER SOFTENER

WPD WATER PRESSURE DROP

WP WEATHERPROOF

WM WATER METER

WH WATER HEATER, WALL HYDRANT

WCO WALL CLEANOUT

WC WATER CLOSET

WB WET BULB

W/O WITHOUT

W/ WITH

WIRE, WOMEN

W WATT, WIDTH, WASTE, WEST

VSZDT VERTICAL SINGLE ZONE DRAW THRU

VSZBT VERTICAL SINGLE ZONE BLOW THRU

VR VARIABLE AIR VOLUME REHEAT

VP VACUUM PUMP

VOL VOLUME

VFD VARIABLE FREQUENCY DRIVE

VEST VESTIBULE

VERT VERTICAL

VEL VELOCITY

VD VOLUME DAMPER

VB VACUUM BREAKER

VAV VARIABLE AIR VOLUME

VAC VACUUM, VOLTS AC

VA VOLT-AMPERE, VARIABLE

V/D VOICE/DATA

V VOLT, VENT

UPS UNINTERRUPTIBLE POWER SUPPLY

UON UNLESS OTHERWISE NOTED

LABORATORIES, INC.

UL UNDERWRITER'S

UH UNIT HEATER

UG UNDERGROUND

U/S UNDERSLAB

UF UNDERFLOOR

2S-2W TWO-SPEED, TWO WINDING

2S-1W TWO-SPEED, ONE WINDING

TYP TYPICAL

TXV THERMAL EXPANSION VALVE

TW TREATED WATER, TEMPERED WATER

TU TERMINAL UNIT

TS TAMPER SWITCH

TRD THREAD, THREADED

TR TRENCH

TP TRAP PRIMER, TOTAL PRESSURE

TOT TOTAL

TOS TOP OF SLAB

TOIL TOILET

TOF TOP OF FOOTING

TOC TOP OF CURB

TK TANK

THK THICK

TH BLK THRUST BLOCK

TEMP TEMPORARY

TF TRANSFER FAN

TDH TOTAL DYNAMIC HEAD

TD TRENCH DRAIN

COMPRESSOR

TCC TEMPERATURE CONTROL

TC TEMPERATURE CONTROL

T STAT THERMOSTAT/SENSOR

T&P TEMPERATURE & PRESSURE

SYS SYSTEM

SYM SYMMETRICAL

SWR SIDE WALL REGISTER

SWGR SWITCHGEAR

SWBD SWITCHBOARD

SW SWITCH, SOFTENED WATER

SV SANITARY VENT

SUSP SUSPENDED

SURF SURFACE

STRUC STRUCTURE, STRUCTURAL

STR STRAINER

STOR STORAGE

STM STEAM

STL STEEL

STD STANDARD

STC SOUND TRANSMISSION CLASS

STB STEAM BOILER

STAP SURGE TANK ALARM PANEL

STA STATION

SURGE TANK

ST SOUND TRAP, STEAM TRAP,

SST STAINLESS STEEL

SSD SUBSURFACE DRAIN

SSSC SOLID STATE SPEED CONTROL

STAINLESS STEEL

SS STOP-START PUSH-BUTTON,

SRF SMOKE REMOVAL FAN

SQ IN SQUARE INCHES

SQ SQUARE

SPKLK SPRINKLER

SPF STAIR PRESSURIZATION FAN

SPEC SPECIFICATION, SPECIFIED

SP STATIC PRESSURE, SUMP PUMP

SKW STARTING KW

SKVA STARTING KVA

SL SLOPE

SK SINK

SIM SIMILAR

SHWR SECONDARY HEATING WATER RETURN

SHWP SECONDARY HEATING WATER PUMP

SHT SHEET

SHR SHOWER

SH SHOWER

SFCS SPRINKLER FLOOR CONTROL STATION

SF SQUARE FEET

SERV SERVICE

SENS SENSIBLE

SECT SECTION

SEC SECONDARY

SE SEWAGE EJECTOR

SD SMOKE DETECTOR

SCW SOFTENED COLD WATER

SCR SILICON CONTROLLED RECTIFIER

SCHS SECONDARY CHILLED WATER SUPPLY

SCHR SECONDARY CHILLED WATER RETURN

SCHP SECONDARY CHILLED WATER PUMP

SCHED SCHEDULE(D)

SC STEAM CONVERTER

SAF SUPPLY AIR FAN

SAD SUPPLY SIR DIFFUSER

SOUND ATTENUATOR

SA SUPPLY AIR, SHOP AIR

S SOUTH, SUPPLY, SINK

RVS REVERSE

NON-REVERSING

RVNR REDUCED-VOLTAGE,

RV RELIEF VALVE

RTU ROOFTOP UNIT

RTAH ROOFTOP AIR HANDLING UNIT

RS REFRIGERANT SUCTION

RPM REVOLUTIONS PER MINUTE

ROW RIGHT OF WAY

RO ROUGH OPENING, REVERSE OSMOSIS

RND,~ ROUND

RM REFRIGERATION MACHINE, ROOM

RLA RUNNING LOAD AMPS

RL REFRIGERANT LIQUID

RKW RUNNING KW

RKVA RUNNING KVA

RIO ROUGH-IN ONLY

RIC ROUGH-IN AND CONNECT

RHG REFRIGERANT HOT GAS

RH RELATIVE HUMIDITY

REV REVISION, REVISED

REQD REQUIRED

REINF REINFORCED, REINFORCING

REG REGISTER

REFR REFRIGERATOR

RED REDUCER

RECPT RECEPTACLE

RECIRC RECIRCULATE, RECIRCULATING

REC RECESSED

RE: REFERENCE, REFER

RD ROOF DRAIN

RCP REFLECTED CEILING PLAN

RAG RETURN AIR GRILLE

RAF RETURN AIR FAN

RAD REFRIGERATED AIR DRYER

RA RETURN AIR

R&D REMOVE & DISPOSE

(R) RELOCATE

R RISER

QTY QUANTITY

PWR POWER

PW PRESSURED COLD WATER

PVMT PAVEMENT

PVDF POLYVINYLIDENE FLUORIDE

PVC POLYVINYL CHLORIDE

PV PLUG VALVE

PT PLUMBING TRIM

PSIG POUNDS PER SQUARE INCH GAUGE

PSI POUNDS PER SQUARE INCH

PSF POUNDS PER SQUARE FOOT

PS PRESSURE SWITCH

PRV PRESSURE REDUCING VALVE

PRS PRESSURE REDUCING STATION

PROP PROPERTY

PROJ PROJECT

PRI PRIMARY

PRES PRESSURE

PR PAIR, PRINTER

PPM PARTS PER MILLION

PP POLY PROPYLENE

PNTH PENTHOUSE

PNL PANEL

PNEU PNEUMATIC

PLUMB PLUMBING

PL PILOT LIGHT

PKG PACKAGE, PARKING

PIV POST INDICATOR VALVE

PHWS PRIMARY HEATING WATER SUPPLY

PHWR PRIMARY HEATING WATER RETURN

PHWP PRIMARY HEATING WATER PUMP

PH PHASE

PERF PERFORATED

PEND PENDANT

PD PRESSURE DROP

PCW PUMPED COLD WATER

PCHS PRIMARY CHILLED WATER SUPPLY

PCHR PRIMARY CHILLED WATER RETURN

PCHP PRIMARY CHILLED WATER PUMP

PCR PUMPED CONDENSATE RETURN

PERSONAL COMPUTER

PC PLUMBING CONTRACTOR,

PB PUSH BUTTON

EQUIPMENT

P PUMP, POLE, PLUMBING

OZ OUNCE

OS&Y OUTSIDE STEM & YOLK

OPP OPPOSITE

OPNG OPENING

OPH OPPOSITE HAND

OH OVERHEAD

OFF OFFICE

OD OUTSIDE DIAMETER

OCEW ON CENTER EACH WAY

OC ON CENTER

OBD OPPOSED BLADE DAMPER

OAF OUTSIDE AIR FAN

OA OUTSIDE AIR

O OXYGEN

NTS NOT TO SCALE

NOM NOMINAL

N.O. NORMALLY OPEN

NO NUMBER

NIC NOT IN CONTRACT

NFS NON-FUSED SWITCH

NF NON-FUSED

ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

MANUFACTURER'S ASSOCIATION

NEMA NATIONAL ELECTRICAL

NEC NATIONAL ELECTRICAL CODE

N.C. NORMALY CLOSED

NC NOISE CRITERIA

NAT NATURAL

NA NOT ACCEPTABLE

(N) NEW

N NORTH, NITROGEN

MZU MULTI-ZONE UNIT

MVP MEDICAL VACUUM PUMP

MVD MANUAL VOLUME DAMPER

MVA MEGA VOLT-AMPS

MV MEDICAL VACUUM

MU MAKE-UP

MTG MOUNTING

MTD MOUNTED

MSTM MEDIUM PRESSURE STEAM

MSGR MAIN SWITCHGEAR

MSB MAIN SWITCHBOARD

MS MONITOR SWITCH

MPT MALE PIPE THREAD

MP MEDIUM PRESSURE

MON MONITOR SWITCH

ML MATCH LINE

MISC MISCELLANEOUS

MIN MINIMUM

MI MALLEABLE IRON

MH MANHOLE

MG MEDICAL GAS OUTLET

MFGR MANUFACTURER

MEZZ MEZZANINE

M/E/P MECHANICAL/ELECTRICAL/PLUMBING

MEMB MEMBRANE

MED MEDIUM

MECH MECHANICAL

MDP MAIN DISTRIBUTION PANEL

MCC MOTOR CONTROL CENTER

MCB MAIN CIRCUIT BREAKER

MC MECHANICAL CONTRACTOR

MBH THOUSANDS OF BTU'S

MAX MAXIMUM

MAP MASTER ALARM PANEL

MAC MEDICAL AIR COMPRESSOR

MA MEDICAL AIR

M METER, MALE, MEN

LWT LEAVING WATER TEMPERATURE

LWCO LOW WATER CUT OFF

LWB LEAVING WET BULB

LW LAUNDRY LINT WASTE

LVP LABORATORY VACUUM PUMP

LVL LEVEL

LV LAB VACUUM

LTG LIGHTING

LSTM LOW PRESSURE STEAM

LRA LOCKED ROTOR AMPS

LPT LOW POINT

LP LOW PRESSURE

CONSTRUCTION

LOC LOCATION, LIMIT OF

LH LEFT HAND

LG LAB GAS OUTLET

LF LINEAR FEET

LED LIGHT EMITTING DIODE

LDB LEAVING DRY BULB

LD LINEAR DIFFUSER

LCS LIQUID CRYSTAL DISPLAY

LB(S) POUND(S)

LATENT

LAT LEAVING AIR TEMPERATURE,

LAV LAVATORY

LAB LABORATORY

LAC LAB AIR COMPRESSOR

LA LAB AIR COMPRESSOR

L LENGTH, LONG, LAVATORY

KWH KILOWATT-HOUR

KW KILOWATTS

KVA KILOVOLT-AMPS

KO KNOCKOUT

KIT KITCHEN

KEC KITCHEN EQUIPMENT CONTRACTOR

JT JOINT

JST JOIST

JS JANITOR SINK

JPC JOCKEY PUMP CONTROLLER

JP JOCKEY PUMP

JB JUNCTION BOX

JAN JANITOR

IW ICE WATER

IPS IRON PIPE SIZE

INV INVERT

INT INTERNAL, INTERIOR

INSUL INSULATE, INSULATION

INC INCLUDE, INCLUSIVE

INCAND INCANDESCENT

IN INCH

IF INTERMITTENT FAN VAV

IG IRRIGATION

IE INVERT ELEVATION

ID INSIDE DIAMETER

HZ HERTZ

HWS HOT WATER SUPPLY

HWR HOT WATER RETURN

HWP HEATING WATER PUMP

HWC HOT WATER CIRCULATOR

HWB HOT WATER BOILER

HW HOT WATER

HVU HEATING AND VENTILATING UNIT

CONDITIONING

HVAC HEATING, VENTILATING & AIR

HUH HOT WATER/GAS UNIT HEATER

HTR HEATER

HTG HEATING

HT HEIGHT

DRAW-THRU

HSZDT HORIZONTAL, SINGLE-ZONE,

BLOW-THRU

HSZBT HORIZONTAL, SINGLE-ZONE,

HSTM HIGH PRESSURE STEAM

HSC HORIZONTAL SPLIT CASE

HS HOT WATER SUPPLY

HR HOUR, HOT WATER RETURN

HPT HIGH POINT

HP HORSEPOWER, HIGH PRESSURE

HORIZ HORIZONTAL

HND D HAND DRYER

HKP HOUSEKEEPING PAD

HGR HANGER

HE HEAT EXCHANGER

DETECTOR

HD HEAD, HUB DRAIN, HEAT

HC HEATING COIL

HB HOSE BIBB

H STAT HUMIDISTAT/SENSOR

H-O-A HAND-OFF-AUTOMATIC

H HIGH, HEIGHT, HUMIDIFIER

GW GREASE WASTE

GV GATE VALVE

GTH GRAND TOTAL HEAT

GSH GRAND SENSIBLE HEAT

GRV GRAVITY ROOF VENT

GRD GRADE

GR GRILLE

GPM GALLONS PER MINUTE

GPH GALLONS PER HOUR

GPD GALLONS PER DAY

GOVT GOVERNMENT

GND GROUND

GLV GLOBE VALVE

GL GLASS

GKT GASKET

GEN GENERATOR

GCO GRADE CLEAN OUT

GC GENERAL CONTRACTOR

GB GRADE BEAM

GALV GALVANIZED

GAL GALLON

GA GAGE

G GAS

FVR FULL-VOLTAGE, REVERSING

FVNR FULL-VOLTAGE, NON-REVERSING

FVC FIRE VALVE CABINET

FUT FUTURE

FURND FURNISHED

FURN FURNITURE

FTR FINNED TUBE RADIATION

FTG FOOTING

FT FOOT, FEET

PANEL

FSCP FIRE SUPPRESSION CONTROL

FIRE SPRINKLER, FLOOR SINK

FS FUSED SWITCH, FLOW SWITCH,

FRZR FREEZER

FRM FRAME

FR FLOOR REGISTER

FPT FEMALE PIPE THREAD

FPC FIRE PUMP CONTROLLER

FIRE PUMP

FP FAN POWERED MIXING BOX,

FOV FUEL OIL VALVE

FOS FUEL OIL SUPPLY

FOR FUEL OIL RETURN

FOP FUEL OIL PUMP

FO FUEL OIL

FM FACTORY MUTUAL

FLR FLOOR

FLEX FLEXIBLE

FLA FULL LOAD AMPERES

FL FLOW LINE

FIXT FIXTURE

FIN FINISH

FHV FIRE HOSE VALVE

FHR FIRE HOSE RACK

FHC FIRE HOSE CABINET

FH FIRE HYDRANT

FG FINISHED GRADE

FFE FINISHED FLOOR ELEVATION

FF FINAL FILTER, FINISHED FLOOR

FEC FIRE EXTINGUISHER CABINET

FE FIRE EXTINGUISHER

FDV FIRE DEPARTMENT VALVE

FDS FIRE DEPARTMENT SIAMESE

FDN FOUNDATION

FDC FIRE DEPARTMENT CONNECTION

FD FIRE DAMPER, FLOOR DRAIN

FCVA FLOOR CONTROL VALVE ASSEMBLY

FCU FAN COIL UNIT

FCS FLOOR CONTROL STATION

FCO FLOOR CLEAN OUT

FBO FURNISHED BY OTHERS

FACP FIRE ALARM CONTROL PANEL

FAB(D) FABRICATE (D)

FA FIRE ALARM

F & E FURNITURE & EQUIPMENT

F to F FACE TO FACE

F FAHRENHEIT, FAN, FIRE, FEMALE

EXT EXTERNAL

EXPD EXPOSED

EXP EXPANSION

EXIST EXISTING

EXH EXHAUST

EXCV EXCAVATE, EXCAVATION

EX EXPLOSION PROOF

EWT ENTERING WATER TEMPERATURE

EWC ELECTRIC WATER COOLER

EWB ENTERING WET BULB

EW EACH WAY

EVAP EVAPORATOR

EUH ELECTRIC UNIT HEATER

EVAC EVACUATION PUMP

ETR EXISTING TO REMAIN

ET EXPANSION TANK

ES END SUCTION

EQUIV EQUIVALENT

EQUIP EQUIPMENT

EQ EQUAL

AGENCY

EPA ENVIRONMENTAL PROTECTION

ENGR ENGINEER

ENCL ENCLOSURE

EMER EMERGENCY

ELEV ELEVATOR

ELEC ELECTRIC, ELECTRICAL

EL ELEVATION, EXPANSION LOOP

EJ EXPANSION JOINT

EF EXHAUST FAN

EDB ENTERING DRY BULB

ECC ECCENTRIC

EC ELECTRICAL CONTRACTOR

EAT ENTERING AIR TEMPERATURE

EA EACH

(E) EXISTING

E EAST

COIL UNIT

DXFC DIRECT EXPANSION FAN

DX DIRECT EXPANSION

DWS DRINKING WATER SUPPLY

DWR DRINKING WATER RETURN

DWP DOMESTIC WATER PUMP

DWH DOMESTIC WATER HEATER

DWG DRAWING

DWC DRINKING WATER COOLER

DW DISHWASHER, DISTILLED WATER

DV DOUBLE DUCT VAV

DS DOUBLE SUCTION, DOWN SPOUT

DPR DAMPER

DP DIFFERENTIAL PRESSURE

DN DOWN

DMH DRAIN MANHOLE

DL DOOR LOUVER

DIV DIVISION

DIST DISTRIBUTION

DISC DISCONNECT

DIS DEIONIZED WATER SUPPLY

DIR DEIONIZED WATER RETURN

DIM DIMENSION

DIFF DIFFUSER

DIA DIAMETER

DEIONIZED WATER

DI DUCTILE IRON, DRAIN INLET,

DF DRINKING FOUNTAIN

DET DETAIL

DESIG DESIGNATION

DEPT DEPARTMENT

DEP DEIONIZED WATER PUMP

DEG DEGREE

DDC DIRECT DIGITAL CONTROL

DD DECK DRAIN, DOUBLE DUCT

CONSTANT VOLUME

DC DIRECT CURRENT, DOUBLE DUCT

DBL DOUBLE

DB DRY BULB

Db DECIBEL

D DEPTH, DRAIN

CVRH CONSTANT VOLUME REHEAT

CW COLD WATER

CV CONTROL VALVE, CHECK VALVE

Cv CAPACITY INDEX

CU FT CUBIC FEET

CU COPPER

CTR CENTER

CT COOLING TOWER

CSS CLINICAL SERVICE SINK

CRU CONDENSATE RETURN UNIT

CRT CATHODE RAY TUBE

CRAC COMPUTER ROOM A/C UNIT

CONDENSTAE RETURN

CR CONSTANT VOLUME REHEAT,

CPUC CPU CHILLER

CHLORIDE

CPVC CHLORINATED POLYVINYL

CPI CAST IRON PIPE INSTITUTE

CO2 CARBON DIOXIDE

CORR CORRIDOR

CONV CONVERTER

CONTR CONTRACTOR

CONTINUATION

CONT CONTINUOUS, CONTROLLER

CONST CONSTRUCTION

CONN CONNECTION

COND CONDENSER, CONDENSATE

CONC CONCRETE, CONCENTRIC

COMP COMPRESSOR

COMB COMBINATION

COL COLUMN

CHR CHILLED WATER RETURN

CO CLEANOUT

CMU CONCRETE MASONRY UNIT

CMP CORRUGATED METAL PIPE

CLG CEILING

CL CENTER LINE

CIRC CIRCULATING

CIP CAST IN PLACE

CI CAST IRON

CHV CHECK VALVE

CHS CHILLED WATER SUPPLY

CHP CHILLED WATER PUMP

CH CHILLER

CG CEILING GRILL

CFS CUBIC FEET PER SECOND

CFM CUBIC FEET PER MINUTE

CFH CUBIC FEET PER HOUR

CDS CONDENSER WATER SUPPLY

CDR CONDENSER WATER RETURN

CDP CONDENSER WATER PUMP

CD CEILING DIFFUSER

CC CENTER TO CENTER

CB CATCH BASIN

CAB CABINET

CA CONTROL AIR, COMPRESSED AIR

C CELSIUS, CONDUIT

BWV BACKWATER VALVE

BALANCING VALVE

BV BUTTERFLY VALVE, BALL VALVE,

BT BATH TUB, BREAK TANK

BSMT BASEMENT

BS BLACK STEEL

BKT BRACKET

BOT BOTTOM

BOS BOTTOM OF STRUCTURE

BOP BOTTOM OF PIPE

BOH BOTTOM OF HUB

BOF BOTTOM OF FOOTING

BOB BOTTOM OF BEAM

BM BEAM, BENCH MARK

BLDG BUILDING

BH BOX HYDRANT

BFW BOILER FEED WATER

BFV BOILER FEED VALVE

PREVENTER

BFP BOILER FEED PUMP, BACKFLOW

BFD BOILER FEED DEAERATOR

BC BELOW COUNTER

ASSOCIATION

AWWA AMERICAN WATER WORKS

AWS AMERICAN WELDING SOCIETY

AW ACID WASTE

AVTR ACID VENT THRU ROOF

AVG AVERAGE

AV AREA VALVE, ACID VENT

AUX AUXILIARY

AUTO AUTOMATIC

ATT(S) ATTENUATOR(S)

ATS AUTOMATIC TRANSFER SWITCH

ATP AUTOMATIC TRAP PRIMER

AND MATERIALS

ASTM AMERICAN SOCIETY FOR TESTING

MECHANICAL ENGINEERS

ASME AMERICAN SOCIETY OF

CONDITIONING ENGINEERS

AND REFRIGERATION AND AIR

ASHRAE AMERICAN SOCIETY OF HEATING

AS AIR SEPARATOR

INSTITUTE

ARI AMERICAN REFRIGERATION

ARCH ARCHITECT, ARCHITECTURAL

APD AIR PRESSURE DROP

AP ACCESS PANEL, ALARM PANEL

INSTITUTE

ANSI AMERICAN NATIONAL STANDARDS

ANOD ANODIZED

AMB AMBIENT

ALT ALTERNATE

AL ALUMINUM

CAPACITY

AIC AMPERES INTERRUPTING

AHU AIR HANDLING UNIT

AFG ABOVE FINISHED GRADE

AFF ABOVE FINISHED FLOOR

AFC ABOVE FINISHED CEILING

AF AIR FILTER

ADJ ADJUSTABLE

AD ACCESS DOOR, AIR DRYER

ACCU AIR COOLED CONDENSING UNIT

ACC AIR COOLED CHILLER

A/C AIR CONDITIONING

AIR COMPRESSOR

AC ALTERNATING CURRENT,

ABV ABOVE

AAP AREA ALARM PANEL

A AMPS, AIR (COMPRESSED)

ABBREVIATIONS MECHANICAL SYMBOLS

PIPING TYPES MISCELLANEOUS

(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS) GENERAL NOTES

DRAIN LINE

REFRIGERANT LIQUID LINE

REFRIGERANT SUCTION LINE

REFRIGERANT HOT GAS LINE

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

FLOOR DRAIN

DRAWING NOTE REFERENCE

FLOW SWITCH

VALVE SUPERVISORY SWITCH

THERMOSTAT

HUMIDISTAT

FIRESTAT

FLOW SWITCH

PNEUMATIC TUBING OR CONTROL WIRING

EXISTING

POINT OF NEW CONNECTION TO

ELBOW UP

ELBOW DOWN

VALVE IN DROP

VALVE IN RISE

DIRECTION OF FLOW

DIRECTION OF SLOPE DOWN

CONCENTRIC REDUCER

ECCENTRIC REDUCER

TEE OUTLET UP

TEE OUTLET DOWN

UNION

PIPE ANCHOR

EXPANSION JOINT

STRAINER WITH BLOWDOWN VALVE

GLOBE VALVE

BALL VALVE

OS&Y VALVE

CHECK VALVE

PRESSURE REDUCING VALVE

MANUAL AIR VENT

AUTOMATIC AIR VENT

T&P RELIEF VALVE

VACUUM BREAKER

LINE CLEANOUT

THERMOMETER

WATER METER

FLEXIBLE CONNECTION

TWO POSITION CONTROL VALVE

PRESSURE AND TEMPERATURE TAP

FLOW VENTURI

EXISTING DUCTWORK

SUPPLY OR OUTSIDE AIR DUCT

RETURN, RELIEF, OR EXHAUST AIR DUCT

FLEXIBLE DUCT CONNECTION

INCLINED RISE IN DUCT

INCLINED DROP IN DUCT

TURNING VANES

DUCT EXTRACTOR

SPLITTER DAMPER

DUCT MOUNTED HEATING COIL

DUCT MOUNTED FILTER

DUCT MOUNTED HUMIDIFIER

DOUBLE DUCT HVAC TERMINAL UNIT

SINGLE DUCT HVAC TERMINAL UNIT

FIRE DAMPER

SMOKE DAMPER

FIRE|SMOKE DAMPER

MANUAL BALANCING DAMPER

GRAVITY BACKDRAFT DAMPER

MOTORIZED DAMPER

EXISTING FLEXIBLE DUCT TO BE REMOVED

NEW FLEXIBLE DUCT

NEW RECTANGULAR OR ROUND DUCTWORK

EXISTING FLEXIBLE DUCT

DRAWING LIST

DRAWING/DETAIL REFERENCE KEY

FOR TAB REQUIREMENTS.

ENGINEER AND OWNER UPON PROJECT COMPLETION. RE: SPECIFICATIONS

W. TEST AND BALANCE REPORT SHALL BE SUBMITTED FOR APPROVAL BY THE

FLOOR NUMBER.

V. ASTERISK (*) IN EQUIPMENT DESIGNATIONS CORRESPONDS TO THE

GENERAL CONTRACTOR PRIOR TO EACH CONCRETE POUR.

U. COORDINATE ALL SLAB PENETRATIONS AND SLEEVES WITH THE

PRIOR TO FABRICATION.

ARCHITECTURAL DRAWINGS. LENGTHS SHALL BE FIELD COORDINATED

ARE APPROXIMATE. EXACT LENGTHS SHALL BE AS SHOWN ON THE

T. LENGTHS OF SUPPLY AND RETURN AIR SLOT DIFFUSERS SHOWN

AIR METHOD IS SHOWN ON THIS DRAWINGS.

AS THE RETURN AIR PATH TO THE PLENUM, UNLESS ANOTHER RETURN

PROJECT. IN GENERAL, RETURN AIR LIGHT FIXTURES WILL BE USED

S. THE CEILING PLENUM IS USED AS A RETURN AIR PATH ON THIS

AND PARTITION SUPPORT SYSTEMS.

R. CONDUIT, PIPING AND DUCTWORK SHALL BE INDEPENDENT OF CEILING

FLAT BLACK.

ABOVE CEILING ITEMS WHICH ARE VISIBLE THROUGH AIR SLOTS OF GRILLS

Q. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PAINTING ANY

EXTENDING 12 INCHES ON EITHER SIDE OF PARTITION.

PENETRATES A PARTITION TO DECK, PROVIDE INSULATED RIGID DUCT

PARTITIONS SHALL BE INSTALLED AS DETAILED. WHERE FLEXIBLE DUCTWORK

EXTEND TO DECK. EACH DUCT AND PIPE PENETRATION THROUGH THESE

P. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF PARTITIONS WHICH

MECHANICAL DRAWINGS.

SHALL BE PROVIDED BY CODE, EVEN IF THEY ARE NOT SHOWN ON THE

ARCHITECTURAL DRAWINGS. FIRE, SMOKE AND FIRE/SMOKE DAMPERS

FIRE, SMOKE AND FIRE/SMOKE PARTITIONS SHOWN ON THE

COORDINATING THE DUCTWORK FABRICATION DRAWINGS WITH THE

O. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR

THE DRAWINGS

BY APPLICABLE CODES,REGARDLESS OF WHETHER A DAMPER IS SHOWN ON

BE PROVIDED WITH A FIRE, FIRE/SMOKE OR SMOKE DAMPER AS REQUIRED

SPECIFIED. EACH DUCT PENETRATION THROUGH THESE PARTITIONS SHALL

PARTITIONSSHALL BE INSTALLED AND FIRESTOPPPED AS DETAILED AND

RATED PARTITIONS TO DECK. EACH PIPE PENETRATION THROUGH THESE

N. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF FIRE AND SMOKE

CONCEALED MECHANICAL EQUIPMENT, VALVES, CONTROLS AND OTHER DEVICES.

CONTRACTOR IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO

M. FURNISH ACCESS DOORS FOR INSTALLATION BY THE GENERAL

LIGHT FIXTURES AND OTHER CEILING MOUNTED DEVICES.

VALVES AND OTHER DEVICES REQUIRING ACCESS WITH THE LOCATIONS OF

L. COORDINATE THE LOCATION OF NEW ABOVE CEILING MECHANICAL EQUIPMENT,

REQUIRED FOR COORDINATED INSTALLATION.

DIVISIONSAND EXISITING CONDITIONS AND PROVIDING OFFSETS AS

THE LOCATION OF DUCTWORK AND PIPING WITH THE WORK OF OTHER

K. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING

CONDUIT AND LIGHTING FIXTURES.

8 INCHES ABOVE FINISHED CEILING TO PROVIDE CLEARANCE FOR ELECTRIAL

THE ARCHITECTURAL DRAWINGS,ALL DUCTWORK/PIPING SHALL BE INSTALLED

CONSTRUCTION, HEIGHTS AND LIGHT FIXTURE LOCATIONS TO BE AS SHOWN IN

J. IT IS THE INTENT OF THESE DOCUMENTS TO ALLOW THE CEILING

I. ALL SUPPLY AIR DEVICES SHALL BE 4-WAY THROW, UNLESS NOTED OTHERWISE.

H. ALL DUCTWORK SIZES SHOWN ARE FREE AIR STREAM DIMENSIONS.

ARCHITECT/ENGINEER PRIOR TO SUBMITTING BIDS

DURING THE VISIT SHALL BE BROUGHT TO THE ATTENTION OF THE

DISCREPANCIES IN THE CONSTRUCTION DOCUMENTS WHICH ARE NOTED

AND THE WORK OF OTHER TRADES PRIOR TO SUBMITTING BIDS. ANY

THEMSELVES WITH ALL EXISTING CONDITIONS RELATED TO THEIR WORK

G. THE MECHANICAL CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE

LOCATION OF ALL WALL MOUNTED DEVICES.

WHERE THE ARCHITECT HAS DRAWN SUCH ELEVATIONS, FOR THE

F. REFER TO ARCHITECTURAL INTERIOR ELEVATION DRAWINGS.

ENTERING THE DUCT OR PIPE

SHALL BE TEMPORARILY CAPPED TO PREVENT CONSRUCTION DEBRIS FROM

DUCTWORK/PIPING IS NOT IMMEDIATELY CONNECTED TO TAP LOCATION

E. ALL DUCT OR PIPE TAPS/PENETRATIONS IN WHICH THE DOWNSTREAM

SUBMITTALS, RECORD DRAWINGS AND MAINTENANCE MANUAL

D. REFER TO SPECIFICTION FOR REQUIREMENTS RELATED TO SHOP DRAWING

MECHANICAL CONSTRUCTION.

C. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR

FEDERAL, STATE AND LOCAL CODES, REGULATIONS AND STANDARDS

B. ALL MECHANICAL CONSTRUCTION SHALL COMPLY WITH ALL APPLICABLE

AND WORKING MECHANICAL SYSTEM.

APPURTENANCES REQUIRED FOR A COMPLETE, COORDINATED

A. FURNISH ALL LABOR, MATERIALS, EQUIPMENT, APPARTUS AND

M501

M20B

M10B

M000

MECHANICAL DETAILS

MECHANICAL RENOVATION PLAN

MECHANICAL DEMOLITION PLAN

MECHANICAL SYMBOLS AND ABBREVIATIONS

SHEET:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET TITLE:

PROJECT NO.

(MDACC)

PROFESSIONAL SEALS

All reproduction & intellectual property rights reserved © 2011

REVISION/ISSUE NO. YYYY-MM-DD

Houston, TX 77027 USA

t +1 713 407 7700 f +1 713 407 7809

3200 Southwest Freeway, Suite 900

HELLMUTH, OBATA & KASSABAUM, INC.

PROJECT NO.

(E&C)

LOCATION

DRAWN BY

CHECKED BY

A

B

C

D

1 2 6

E

3 4 5I:\3

800\3

812 - M

DA

CC R

econfigure R

oo

m G

B.3

608 for

Rad

Onc\M\M

ech\3

812 M S

A 0

00.d

gn

3/1/2

021

3:3

1:3

6 P

M

JS

KJL

UT

MD

A - R

EC

ON

FIG

UR

E R

OO

M G

B.3

608 F

OR R

AN O

NC

190963

20.10205.00

95% CD 01-18-2021

(HOK)

3812

95% CD 02-11-2021

ISSUE 03-02-2021FOR CONSTRUCTION

EEngineers

TX Firm Registration No: F-003068

&

Consultants

C www.eceng.com

Fax (713) 580-8888

Tel (713) 580-8800

Houston, TX 77002

1010 Lamar, Suite 650

E&C Engineers & Consultants Inc.

THE SEAL APPEARING ON THIS DRAWING WAS AUTHORIZED BY:

E&C Engineers & Consultants Inc.Texas Firm Registration No: F-003068

LIC E N ES

D

100166

KOREY J. LUST

STATE OF TEX

A

S

PROF

ESSIONAL EN

GIN

EER

Digitally signed by Korey LustDate: 2021.03.01 15:39:13-06'00'

Page 2: 1 2 6 3 4 5FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FD FIRE DAMPER, FLOOR DRAIN FCVA FLOOR CONTROL VALVE ASSEMBLY FCU FAN COIL UNIT FCS FLOOR CONTROL STATION FCO FLOOR ...

50

GB.3783

636

GB.3603

158

GB.3698

95

GB.3694

90

GB.3601

127

GB.3796

294

GB.3798129

GB.3794

93

GB.3607B

621

GB.3605

32

GB.3611

60

GB.3613

773

GB.3609

510

GB.3691

234

GB.3606

609

GB.3604

113

GB.3603A

113

GB.3605A

246

GB.3607A

697

GB.3607

T10/10

8/6

18/10 16|10

18"~

18"~

16"~

18/

12

540

280

270

270

12/10

12/

10

33"

~1

9/

16

OV

AL

220110 110

100

1570

14/10

DD-PB-28

GENERAL THERAPY

EQUIP. CLEANING RM.

GB.3608

CORRIDOR

GB.3604

PE.46PE.47PE.48PE.49PE.64

PE.44

PE.43

PE.44PE.44

M10B

1

2

1

1

MECHANICAL

DEMOLITION

FLOOR PLAN

BASEMENT - MECHANICAL DEMOLITION PLAN SCALE: 1/4"=1'-0"01

3

3

3

X

X

X

XX

X

X

XX

XX

XX

XX

XX

X

4

XX

XX

X

REBALANCE SYSTEM AS REQUIRED.

EQUIPMENT. CAP AND SEAL DUCT AT MAIN AIR TIGHT.

5 EXHAUST DUCT TO BE REMOVED FROM OLD PROCESSOR

COORDINATE FINAL LOCATION WITH ARCHITECT.

4 EXISTING THERMOSTAT TO BE REMOVED AND RELOCATED.

GRILLE LOCATION.

EXISTING DUCTWORK AS REQUIRED TO ACCOMODATE NEW

BALANCED TO PRETAB VALUE UPON FINAL BALANCE. MODIFY

SHALL BE TAKEN AT GRILLE AND AIR DEVICE SHALL BE

NEW AIR DEVICE TO MATCH EXISTING. PRETAB READINGS

3 EXISTING AIR DEVICE TO BE REMOVED AND REPLACED WITH

REBALANCED.

2 EXISTING TERMINAL UNIT TO BE REMAIN AND BE

1 EXISTING AIR DEVICE TO REMAIN TO BE REBALANCED.

DRAWING NOTES:

HINDER FINAL TAB REQUIREMENTS.

EXISTING DEFICIENCIES IN THE SYSTEM WHICH MAY

SHALL BE DONE AS SOON AS POSSIBLE TO IDENTIFY ANY

EQUIPMENT TO REMAIN IN SCOPE OF PROJECT. PRETAB

B. PRETAB READINGS SHALL BE TAKEN AT ALL MECHANICAL

A. REFER TO M000 FOR ADDITIONAL GENERAL NOTES.

GENERAL NOTES:

5

SHEET:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET TITLE:

PROJECT NO.

(MDACC)

PROFESSIONAL SEALS

All reproduction & intellectual property rights reserved © 2011

REVISION/ISSUE NO. YYYY-MM-DD

Houston, TX 77027 USA

t +1 713 407 7700 f +1 713 407 7809

3200 Southwest Freeway, Suite 900

HELLMUTH, OBATA & KASSABAUM, INC.

PROJECT NO.

(E&C)

LOCATION

DRAWN BY

CHECKED BY

A

B

C

D

1 2 6

E

3 4 5I:\3

800\3

812 - M

DA

CC R

econfigure R

oo

m G

B.3

608 for

Rad

Onc\M\M

ech\3

812 M D

EM

O 1

0B.d

gn

3/1/2

021

3:3

3:2

8 P

M

JS

KJL

UT

MD

A - R

EC

ON

FIG

UR

E R

OO

M G

B.3

608 F

OR R

AN O

NC

190963

20.10205.00

95% CD 01-18-2021

(HOK)

3812

95% CD 02-11-2021

ISSUE 03-02-2021FOR CONSTRUCTION

EEngineers

TX Firm Registration No: F-003068

&

Consultants

C www.eceng.com

Fax (713) 580-8888

Tel (713) 580-8800

Houston, TX 77002

1010 Lamar, Suite 650

E&C Engineers & Consultants Inc.

CC

THE SEAL APPEARING ON THIS DRAWING WAS AUTHORIZED BY:

E&C Engineers & Consultants Inc.Texas Firm Registration No: F-003068

LIC E N ES

D

100166

KOREY J. LUST

STATE OF TEX

A

S

PROF

ESSIONAL EN

GIN

EER

Digitally signed by Korey LustDate: 2021.03.01 15:39:13-06'00'

Page 3: 1 2 6 3 4 5FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FD FIRE DAMPER, FLOOR DRAIN FCVA FLOOR CONTROL VALVE ASSEMBLY FCU FAN COIL UNIT FCS FLOOR CONTROL STATION FCO FLOOR ...

GENERAL THERAPY

EQUIP. CLEANING RM.

GB.3608

CORRIDOR

GB.3604

GB.3783

50

GB.3603

636

GB.3698

158

GB.3694

GB.3601

90

GB.3796

127 GB.3798

294

GB.3794

129

GB.3607B

93

GB.3605

621

GB.3611

32

GB.3613

60 GB.3609

773GB.3691

510

GB.3606

234

GB.3604

609

GB.3603A

113

GB.3605A

113

GB.3607A

246

GB.3607

697

10/108/6

18/10 16|10

18"~

18"~

16"~

18/

12

540

270

270

12/10

12/

10

33"

~1

9/

16

OV

AL

110 110

100

1570

14/10

DD-PB-28

4

9' - 0"

PE.46PE.47PE.48PE.49PE.64

PE.44

PE.43

PE.44PE.44

M20B

MECHANICAL

3

3

3

1

11

2

RENOVATION

FLOOR PLAN

BASEMENT - MECHANICAL HVAC PLAN SCALE: 1/4"=1'-0"01

T

4

FS

5 PROVIDE NEW FS DAMPER IN EXISTING TRANSFER BOOT.

CALIBRATED PRIOR TO FINAL TAB.

REQUIRED. ENSURE THERMOSTAT IS WORKING AND

4 EXISTING RELOCATED THERMOSTAT. EXTEND WIRING AS

NEW DAMPER AS REQUIRED.

TO PRETAB VALUES. EXTEND FLEX AS REQUIRED. PROVIDE

3 NEW AIR DEVICE TO MATCH EXISTING AIR DEVICE. BALANCE

2 EXISTING TERMINAL UNIT TO REMAIN AND REBALANCED.

1 EXISTING AIR DEVICE TO REMAIN AND REBALANCED.

DRAWING NOTES:

HINDER FINAL TAB REQUIREMENTS.

EXISTING DEFICIENCIES IN THE SYSTEM WHICH MAY

SHALL BE DONE AS SOON AS POSSIBLE TO IDENTIFY ANY

EQUIPMENT TO REMAIN IN SCOPE OF PROJECT. PRETAB

B. PRETAB READINGS SHALL BE TAKEN AT ALL MECHANICAL

A. REFER TO M000 FOR ADDITIONAL GENERAL NOTES.

GENERAL NOTES:

5

CFM

280

CFM

220

SHEET:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET TITLE:

PROJECT NO.

(MDACC)

PROFESSIONAL SEALS

All reproduction & intellectual property rights reserved © 2011

REVISION/ISSUE NO. YYYY-MM-DD

Houston, TX 77027 USA

t +1 713 407 7700 f +1 713 407 7809

3200 Southwest Freeway, Suite 900

HELLMUTH, OBATA & KASSABAUM, INC.

PROJECT NO.

(E&C)

LOCATION

DRAWN BY

CHECKED BY

A

B

C

D

1 2 6

E

3 4 5I:\3

800\3

812 - M

DA

CC R

econfigure R

oo

m G

B.3

608 for

Rad

Onc\M\M

ech\3

812 M

H 2

0B.d

gn

3/1/2

021

3:3

4:5

4 P

M

JS

KJL

UT

MD

A - R

EC

ON

FIG

UR

E R

OO

M G

B.3

608 F

OR R

AN O

NC

190963

20.10205.00

95% CD 01-18-2021

(HOK)

3812

95% CD 02-11-2021

ISSUE 03-02-2021FOR CONSTRUCTION

EEngineers

TX Firm Registration No: F-003068

&

Consultants

C www.eceng.com

Fax (713) 580-8888

Tel (713) 580-8800

Houston, TX 77002

1010 Lamar, Suite 650

E&C Engineers & Consultants Inc.

THE SEAL APPEARING ON THIS DRAWING WAS AUTHORIZED BY:

E&C Engineers & Consultants Inc.Texas Firm Registration No: F-003068

LIC E N ES

D

100166

KOREY J. LUST

STATE OF TEX

A

S

PROF

ESSIONAL EN

GIN

EER

Digitally signed by Korey LustDate: 2021.03.01 15:39:13-06'00'

Page 4: 1 2 6 3 4 5FDN FOUNDATION FDC FIRE DEPARTMENT CONNECTION FD FIRE DAMPER, FLOOR DRAIN FCVA FLOOR CONTROL VALVE ASSEMBLY FCU FAN COIL UNIT FCS FLOOR CONTROL STATION FCO FLOOR ...

MECHANICAL

M501

DETAILS AND

SCHEDULES

EXISTING AIR TERMINAL UNITS SCHEDULE

UNIT NO. TEC NAME SERVICE

COLD DECK HOT DECK

REMARKS

FLOW MAX

EXT.CLG.

FLOW MAX

NEW CLG.

FLOW MIN

EXT.CLG

FLOW MIN

NEW CLG.

FLOW MAX

EXT.HTG.

FLOW MAX

NEW HTG.

FLOW MIN

EXT.HTG

FLOW MIN

NEW HTG.

EXISTING UNIT

NOTES

1. SCHEDULE PROVIDED FOR REBALANCING PURPOSES.

2. VERIFY EXISTING EQUIPMENT LOCATIONS ARE IDENTIFIED ON THE CEILING GRID PER MDACC ID STANDARDS.

3. VERIFY EXISTING THERMOSTATS ARE CALIBRATED AND WORKING PROPERLY.

4. VERIFY EXISTING DDC GRAPHICS ARE UPDATED ACCORDINGLY.

R=1.5 x W

R

TYPICAL DUCT FITTINGS

W

RADIUS ELBOW SQUARE ELBOW DETAIL OF TURNING VANE

NOT TO SCALE

EXPANDED DUCT TAP SPLIT DUCT TAP

EQUAL SPLIT SQUARE TEE UNEQUAL SPLIT SQUARE TEE

Q=45!

W

L

TYP. SPLITTER

DAMPER, WHERE

SHOWN ON DWGS.BALL JOINT

BRACKET (TYP)

TYP. MANUAL

VOLUME DAMPER,

WHERE SHOWN

ON DRAWINGS.

2" O.C.

45!

45!

2"

L=W/4,4" MIN

01

12"

MA

X

1|2"

STIFFEN AS

REQUIRED

TYPICAL ROUND

DUCT DAMPER

REGULATOR

RE: TYPICAL

DETAIL

CONTINUOUS ROD ON ALL DUCT

OVER 12" DIA AND ON ALL DUCT

2" WG AND ABOVE

SINGLE BLADE BALANCING DAMPERS MAY BE USED IN ROUND DUCT AND

IN RECTANGULAR DUCT UP TO A MAXIMUM DUCT SIZE OF 12" H x 48" W

22 GA BLADEDUCT

3|8" REGULATOR

RE: TYP DETAIL

1|8" CLEARANCE ALL

AROUND UP TO 18"

12"

MA

X

TYPICAL RECTANGULAR DUCT DAMPER

DUCT

12"

MA

X

1|2" REGULATOR

RE: TYP DETAIL

1|8" CLEARANCE ALL

AROUND UP TO 19"-48"

3|8" CDS ROD 1|2" CDS ROD

16 GA BLADE

ROD END BEARING. PROVIDE OUTSIDE END BEARING

AT PRESSURE UP TO 2"WG. PROVIDE INSIDE ROD

BEARING AT PRESSURES 3"WG AND ABOVE (TYP)

ELEVATION OF TYPICAL

RECTANGULAR DUCT DAMPER

02 NOT TO SCALE

TYPICAL DUCT MOUNTED SINGLE

BLADE BALANCING DAMPERS

03NOT TO SCALE

SPRING LOCK

LIGHT

TYPICAL AIR DEVICES

AS SCHEDULED

RE: DETAILS

SPECIFIED DUCT WITH LINER

ON DUCTWORK AS SPECIFIED

SPIN-IN COLLAR WITH MANUAL

VOLUME DAMPER. ORIENT DAMPER

SHAFT PARALLEL TO DUCT AIR

FLOW. PROVIDE ACCESS DOOR IF

DAMPER IS LOCATED IN AN

INACCESSIBLE LOCATION.

INSULATED RIGID ROUND DUCT

EXTENSION AS REQUIRED

TYPICAL AIR DEVICE

FLEXIBLE CONNECTION

FLEXIBLE DUCT (8' MAXIMUM)

SUPPORT FLEXIBLE DUCT

RUNS OVER 36" ON 36"

CENTERS.

SEAL FLEXIBLE DUCT

LINER WITH DRAWBAND

AND SEAL VAPOR

BARRIER WITH DUCT

TAPE (TYP)

04 NOT TO SCALE

TYPICAL BALANCING

DAMPER OPERATORS

'L' HANDLE

BALL JOINT

BRACKET

DUCT

CONTROL ROD

SPLITTER

DAMPER

BLADE

BALL JOINT

BRACKET

TYPICAL SPLITTER DAMPER CONTROL ROD

CONCEALED REGULATOR

(NOTE 2)

EXTENDED DAMPER

ROD (NOTE 2)

UNIVERSAL JOINT

(NOTE 2)

DAMPER REGULATOR

(NOTE 1)

RAISED INSULATION

BASE

DUCT

NOTES:

1. LEVER TYPE LOCKING QUADRANT FOR

CONCEALED DAMPERS IN ACCESSIBLE

AND IN INACCESSIBLE LOCATIONS

WHERE ACCESS DOORS ARE PROVIDED.

2. EXTENDED DAMPER ROD WITH UNIVERSAL

JOINT(S) OR ANGLE GEARBOX TO FLUSH

MOUNTED CONCEALED REGULATOR WHERE

NOTED FOR CONCEALED, NON-ACCESSIBLE

DAMPERS, UNLESS NOTED OTHERWISE.

LOCKING NUT TYPE REGULATOR WITHOUT

LEVER FOR EXPOSED DUCTWORK IN

OCCUPIED SPACES.

SINGLE BLADE OR

OPPOSED BLADE

DAMPER

DUCT

LOCATIONS, IN MECHANICAL SPACES

TYPICAL DAMPER CONTROL REGULATOR

DUCTWRAP

LINER

DD-PB-28 GBM.3606.DDPB28 GB.3608

APPLICATION

540 540 320 320 220 220 0 02237-CV

5. VALUES BASED ON EXISTING PROGRAMMED TEC VALUES PROVIDED BY MDACC. THE INTENT IS THE BOX IS TO REMAIN WITH THE SAME SETTINGS.

SHEET:

Original drawing is 42 x 30 Do not scale contents of this drawing

SHEET TITLE:

PROJECT NO.

(MDACC)

PROFESSIONAL SEALS

All reproduction & intellectual property rights reserved © 2011

REVISION/ISSUE NO. YYYY-MM-DD

Houston, TX 77027 USA

t +1 713 407 7700 f +1 713 407 7809

3200 Southwest Freeway, Suite 900

HELLMUTH, OBATA & KASSABAUM, INC.

PROJECT NO.

(E&C)

LOCATION

DRAWN BY

CHECKED BY

A

B

C

D

1 2 6

E

3 4 5I:\3

800\3

812 - M

DA

CC R

econfigure R

oo

m G

B.3

608 for

Rad

Onc\M\M

ech\3

812 M D

T 5

01.d

gn

3/1/2

021

3:3

5:4

7 P

M

JS

KJL

UT

MD

A - R

EC

ON

FIG

UR

E R

OO

M G

B.3

608 F

OR R

AN O

NC

190963

20.10205.00

95% CD 01-18-2021

(HOK)

3812

95% CD 02-11-2021

ISSUE 03-02-2021FOR CONSTRUCTION

EEngineers

TX Firm Registration No: F-003068

&

Consultants

C www.eceng.com

Fax (713) 580-8888

Tel (713) 580-8800

Houston, TX 77002

1010 Lamar, Suite 650

E&C Engineers & Consultants Inc.

THE SEAL APPEARING ON THIS DRAWING WAS AUTHORIZED BY:

E&C Engineers & Consultants Inc.Texas Firm Registration No: F-003068

LIC E N ES

D

100166

KOREY J. LUST

STATE OF TEX

A

S

PROF

ESSIONAL EN

GIN

EER

Digitally signed by Korey LustDate: 2021.03.01 15:39:13-06'00'