Passwords

For CAPM controllers and WSOS4

Passwords for the CAPM controller and WSOS

CAPM Controller Switchgear Password Write Access Password

WSOS System Operator Protection Telecontrol

Password Protection

The Switchgear Password must be entered in order to change some settings via the panel.

If a password protected field is selected for change the user is prompted for the password.

Entering the Switchgear Password

The Switchgear Password can be up to five characters in length and is entered in the following way:

The <- -> keys are pressed until the first character of the password is displayed.

The SELECT key is then pressed. This sequence is repeated until the

complete password is displayed. The password is entered with the

ENTER or MENU key.

– The default password is CAPM

– Password remains active until panel shuts down.

Changing the Switchgear Password

The Switchgear Password can only be changed via WSOS while On-line.

Changing the Switchgear Password requires the WSOS ‘System’ password.

Previous Password System

System

Allows the user to connect to switchgear, look at the values, can trip or close, can change protection and operating settings. Can also change system parameters

Technician

connect to switchgear, look at the values, can trip or close, can change protection and operating settings.

Operator

Connect to switchgear, look at the values, can trip or close, can not change protection settings. Can change operating settings

Connect Connect to switchgear, look at the values, can

not trip or close, cannot change protection settings. Can not change operating settings.

New Password System CAPM Ver 28 WSOS 4.20

Write Access System

This is the highest level password in WSOS.

For a local connection, the System password is required to change the CAPM Write Access password

Operation Protection Telecontrol

Password Control

WSOS Passwords can be changed and time out options set via the Change Passwords dialogue box.

Time Out Options available are:

No Password Time Out - Once entered correctly that password will never expire.

Password Times Out After - Once entered correctly that password will expire after the entered number of minutes.

Require Password Every Time - The password is required to be entered every time.

Multiple Operator Passwords

This feature allows up to 10 unique operator passwords to be configured.

Each operator password has a unique user name.

The user name is a maximum of 20 characters.

The operator password is a maximum of 10 characters.

Only the ‘active’ passwords will be tested when an operator is entered.

Any of the ten passwords can be used.

Multiple Operator Password Selection

Multiple Operator Password Configuration

Active – Enables or disables this user name and password. User Name – Allows the user name to be configured.

Multiple Operator Password Configuration

Operator Password – Allows the operator password to be configured. Change Password – Allows the operator password to be configured.

Write Access Password – What is it?

Definition:

One secure password stored in the CAPM and used to control remote Write Access to the CAPM via WSOS through a remote port. (Normally P8 or P10)

Changing Switchgear Remote Access Passwords

The Switchgear Remote Access Password factory default is 000000 and can be changed remotely via WSOS.

The Switchgear Remote Access Password can be changed for an individual switchgear or multiple switchgears.

Q&A Once the Switchgear Password has been entered, how long will it remain

active? Until the panel shuts down ten minutes after the last button press.

The Switchgear Password can on be changed via …….. If the …………. Password is known.

WSOS System

How many levels of passwords are used by WSOS? 2 - System is the highest level, Protection, Operator and Telecontrol

are the same level. How many individual users can be configured to have unique passwords

when Multiple Operator Passwords is enabled? Ten

The Write Acces Password is stored in the CAPM and requested by WSOS when…..?

When a remote operator attempts to change a setting or operate the switchgear.