08 Harmonics
-
Upload
tarique-saifullah -
Category
Documents
-
view
229 -
download
0
Transcript of 08 Harmonics
-
8/3/2019 08 Harmonics
1/113
631
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
8. Harmonics
-
8/3/2019 08 Harmonics
2/113
632
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
8. HARMONICS
The currents consumed by non-linear electrical equipment such as arc furnaces, lighting
systems, convertors, rectifiers, etc., are non-sinusoidal, and flowing through the impedances of
the power supply network they cause the sinusoidal supply voltage to become distorted. Thewaveform distortion is characterised by the appearance of voltages at harmonic frequencies.
These harmonic voltages can disturb the operation of electrical devices on the network.
This chapter deals with the different sources of harmonic disturbance, as well as the methods
and techniques that can be applied to reduce it to an acceptable level.
8.1. Basic concepts
This paragraph gives the technical and theoretical fundamentals necessary for an investigation
of harmonics.
8.1.1. Fourier series periodic signal analysis
The French mathematician Joseph Fourier showed that a periodic signal ( )s t , of period T, can
be expressed as the sum of sinusoidal signal components plus a d.c. component:
( ) ( )s ta
a p t b p t p
p p= + +=
01
2cos sin
where:
=2
T
( )aT
s t dt T
00
2=
( ) ( )
( ) ( )
aT
s t p t dt
bT
s t p t dt
pT
p
T
=
=
2
2
0
0
cos
sin
where p is a whole number
This analysis may also be expressed as follows:
( ) ( )s ta
c p tp
p p= + +=
01
2sin
where: c a b p p p= +2 2
pp
p
b
a= arctan
-
8/3/2019 08 Harmonics
3/113
633
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
8.1.2. Definitions
A distorted voltage ( )v t of period T (T ms= 20 at f Hz= 50 ) can therefore be expressed in
the following manner:
( ) ( )v t V V p t p
p p= + +=
01
2 sin where
=2
T
V0 : amplitude of the d.c. component, generally zero and taken to be so from now on .
p : the initial phase ofVp , ( )t= 0 .
Similarly, a distorted current ( )i t of period T can be expressed as:
( ) ( )i t I I p t p
p p= + +=
01
2 sin
I0 : amplitude of the d.c. component, generally zero and taken to be so from now on .
p : the initial phase ofIp , ( )t= 0 .
fundamental component, or fundamental
V1 is the fundamental component of the signal ( )v t , that is to say the effective value of thesinusoid whose frequency is the same as that of the supply network.
harmonic component, or harmonic
For values of p 2 , Vp is the harmonic component of order p , of the signal ( )v t ; that is, the
effective value of the sinusoidal voltage whose frequency is p times that of the supply
network.
order of harmonic
The whole number equal to the ratio between the frequency of the harmonic and that of the
fundamental.
p is therefore the order of the harmonic.
For example, V3 is the third harmonic voltage, or simply the 3rd harmonic.
-
8/3/2019 08 Harmonics
4/113
-
8/3/2019 08 Harmonics
5/113
635
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
distortion factor according to IEC standard 1000-2-2
- voltage distortion factor ( )V
p
p
V
V% = =
100
2
2
1
- current distortion factor ( )I
pp
I
I% =
=
100
2
2
1
The distortion factor as defined by the IEC standard represents the ratio between the r.m.s.
value of the harmonics to that of the (undistorted) fundamental, and gives a good indication of
the degree of harmonic disturbance on the network. This definition will be used throughout theremainder of the document.
The DIN factor can be converted to the IEC factor as follows:
1 11
2 2D V V= +
1 11
2 2
D I I
= +
As will be seen, IEC distortion factor values can be greater than 100 %.
For low distortion factors the two definitions give nearly identical values. On the other hand, for
high distortion factors the values turn out to be very different.
For example, for I = 10 % we find DI = 9 95. %
for I = 120% we find DI = 77 %
individual harmonic rate
The rate of the harmonic of order p is given by:
( )VV
Vpp
% = 1001
( )II
Ipp
% = 1001
-
8/3/2019 08 Harmonics
6/113
636
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
power values for non-sinusoidal signals
Definitions of power applying to sinusoidal signals are not appropriate to the treatment of non-
sinusoidal signals.
Consider a non-sinusoidal voltage and current whose Fourier series components are:
( ) ( )i t I p t pp
p= +=
1
2 cos
( ) ( )v t V p t pp
p= +=
21
cos
By definition, active power is equal to mean power:
( ) ( )PT
v t i t d t T
= 1 0
and after calculation, we obtain:
( ) P V I p pp
p p= =
1
cos
By definition, apparent power is equal to:
S V Irms rms=
The definition of reactive power applied to purely sinusoidal waveforms is wholly inappropriate
to the treatment of non-sinusoidal signals.
Certain documents do offer a definition, but since the reactive power of a non-sinusoidal signal
has no practical relevance to an investigation of harmonics there is no need to refer to it in thisdocument.
-
8/3/2019 08 Harmonics
7/113
637
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
power factor
The power factor is defined as the ratio between active power and apparent power:
F PSp
=
displacement factor(for the fundamental)
The displacement factor is the ratio between active power and apparent power for the
fundamental component:
cos 1
1
1
=P
S
It can also be defined as the cosine of the phase displacement between the fundamental
voltage and current components : 1 = phase displacement ( )V I1 1, .
Note: Taking the reference (in time) relative to U1 , we have 1 0= .
harmonic factor
This expresses the relationship between the power factor and the displacement factor:
FF
hp=
cos1
peak factor
This is the ratio of peak current to r.m.s. current:
F
Ipk rms=
interharmonics
Interharmonics are sinusoidal components whose frequencies are not multiples of the
fundamental frequency: 130 Hz, 170 Hz, 220 Hz, etc.
-
8/3/2019 08 Harmonics
8/113
638
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
infraharmonics
These are sinusoidal components whose frequencies are below that of the fundamental:
10 Hz, 20 Hz...
The presence of interharmonics or infraharmonics is due to periodic or random variation in the
power consumed by certain electrical equipment. In this case, the signal is not periodic over
time T (period of fundamental), a factor which explains the appearance of frequency
components supplementary to those expressed by Fourier analysis.
Common sources of the phenomena include:
- arc furnaces- cycloconverters- speed variators.
frequency spectrum
A graphical representation of harmonics showing their individual amplitudes and orders.
Usually, the level of each harmonic is represented by its value as a percentage of the
fundamental (see fig. 8-1).
1 3 5 7
100
n
I1(%)
Ip
Figure 8-1: frequency spectrum of a non-sinusoidal current
-
8/3/2019 08 Harmonics
9/113
639
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
linear and non-linear loads
A load is said to be linear if its impedance is constant: the current input is therefore sinusoidal
when the applied voltage is sinusoidal (see fig. 8-2).
A load is said to be non-linear if its impedance varies over a given period: the current input is
therefore non-sinusoidal for a sinusoidal supply voltage (see fig. 8-3).
t
v t
i t
Figure 8-2: linear load
t
v t
i t
Figure 8-3: non-linear load
-
8/3/2019 08 Harmonics
10/113
640
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
8.1.3. The main sources of harmonics
non-linear loads
In this section we shall determine figures for the individual harmonic currents generated by
common non-linear loads.
The values given are approximate. They vary notably in relation to the upstream impedance
(generally, when the upstream impedance increases, the harmonic current levels decrease).
six-phase rectifier bridge (see fig. 8-4)
This is a device to convert 3-phase alternating current into a single-phase direct current.
T
t
t
t
T
3T
6
i t
i ta
i tb
i tc
i tc
i tb
i ta
Figure 8-4: six-phase rectifier bridge current waveforms.
Theoretically, each of the currents I I I a b c, , has a rectangular waveform.
The Fourier series analysis of the rectangular signal gives us the following harmonic currents
of order p k= 6 1 ( that is: 5, 7, 11, 13, 17, 19...) and of amplitude II
pp= 1
I1 : amplitude of fundamental .
-
8/3/2019 08 Harmonics
11/113
641
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
In reality, the current waveforms are not perfectly rectangular, with the result that the actual
values of the harmonic current are less than their theoretical values. An empirical law exists
(see IEC 146-1-2 3.6.2.1) enabling a calculation to be made of the approximate values of
harmonic currents 5 to 31:
II
pp
p =
11
5.2
for 5 31 p
From it we can obtain the individual values of harmonic current as a percentage of the
fundamental (see table 8-1).
I1 I5 I7 I11 I13 I17 I19 I23 I25 I29 I31
100 % 18.9 % 11.0 % 5.9 % 4.8 % 3.4 % 3 % 2.3 % 2.1 % 1.8 % 1.6 %
Table 8-1: values of the harmonic currents produced by a rectifier bridge
The formula yields approximate values, especially when high thyristor delay angles, , are
utilised. Moreover, the inductance of the d.c. circuit influences the harmonic content. A low
value of inductance is conducive to high d.c. ripple, thereby increasing the 5th. harmonic
(multiplied by 1.3 or greater ), as well as, but to a lesser degree, the 11th, 17th... ( )6 1k . The
levels of harmonics 7, 13... ( )6 1k+ are usually lower. IEC standard 146-1-2, paragraphs 3.6.4
and 3.6.5 gives a (very complicated) method of calculating the precise figure for each
harmonic together with its phase angle.
Generally speaking, a calculation of the precise theoretical value of each harmonic current is
not essential for an investigation, indeed whenever possible, on-site measurement is the
preferred method of obtaining the precise values.
-
8/3/2019 08 Harmonics
12/113
642
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
computer switchmode power supplies (see fig. 8-5)
t
CR
i t
v t
i t
v t
Figure 8-5: switchmode power supplies for computers, current waveform
The harmonic currents produced by a switchmode power supply are more or less high in
relation to the load and the upstream network impedance.
A spread of values, in line with the two assumptions of high and low harmonic content, is given
below (see table 8-2).
I1 I3 I5 I7 I9 I11
high 100 % 130 % 70 % 50 % 30 % 10 %
low 100 % 65 % 35 % 25 % 15 % 5 %
Table 8-2: values of harmonic currents for a computer switchmode power supply
lighting loads (fluorescent tubes, discharge lamps)
The values of harmonic currents supplied by fluorescent tubes and magnetic ballast discharge
lamps are given in table 8-3.
Electronic ballast discharge lamps supply harmonic currents having a value comparable to that
of a computer switchmode power supply (see table 8-2: high).
I1 I3 I5 I7 I9 I11 I13 I15
100 % 35 % 27 % 10 % 2.5 % 3.5 % 1.5 % 1.5 %
Table 8-3: fluorescent tube and magnetic ballast discharge lamp current harmonic values
-
8/3/2019 08 Harmonics
13/113
643
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
uninterruptible power supplies (UPS)
For example, the GALAXY model produces harmonic currents as shown in table 8-4.
I1 I5 I7 I11 I13 I17 I19
100 % 33 % 2.5 % 6.1 % 2.4 % 2.5 % 1.6 %
Table 8-4: values of harmonic currents for the GALAXY model of UPS
Note: the newer generation of "sine wave sampling" inverters do not generate harmonics(for example, the 0 to 4 kVA Pulsar models).
speed variators
Speed variators are used to vary the speed of an asynchronous motor.
The harmonic currents they generate depend to a large extent on:
- the ratio between the network short-circuit powerSsc and the apparent power of the variatorSn .
- The variator load S (apparent power of the motor) as a percentage of the apparent powerof the variatorSn .
Measurement results obtained are summarised in tables 8-5, 8-6, 8-7.
S S sc n= 100% I1 I5 I7 I11 I13 I17 I19 I23 I25
S S sc n= 250 100 % 85 % 72 % 41 % 27 % 8 % 5 % 6 % 5 %
S S sc n= 100 100 % 73 % 52 % 16 % 7 % 7 % 5 % 3 % 3 %
S S sc n= 50 100 % 63 % 35 % 6.2 % 1.3 % / / / /
Table 8-5: speed variator with a load of 100% of its apparent power rating
-
8/3/2019 08 Harmonics
14/113
644
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
S Sn= 50 % I1 I5 I7 I11 I13 I17 I19 I23 I25
S S sc n= 250 100 % 90.5 % 82 % 59.5 % 48 % 25.5 % 16.5 % 6 % 4.5 %
S S sc n= 100 100 % 82% 66.5 % 33 % 19.5 % 7 % 6.5 % 5 % 3.5 %
S S sc n= 50 100 % 74.3 % 53.9 % 18.3 % 7.9 % 1.9 % 2.5 % / /
Table 8-6: speed variator with a load of 50% of its apparent power rating
S Sn= 25 % I1 I5 I7 I11 I13 I17 I19 I23 I25
S S sc n= 250 100 % 94 % 89 % 74 % 66 % 47 % 38 % 22 % 15 %
S S sc n= 100 100 % 89 % 78 % 53 % 40 % 17 % 9 % 5 % 6 %
S S sc n= 50 100 % 84 % 68 % 38 % 24 % 6.1 % 2.1 % / /
Table 8-7: speed variator with a load of 25% of its apparent power rating
arc furnace
Arc furnaces as used in iron and steel making can either be a.c. or d.c. supplied.
the a.c. supplied arc furnace (see fig. 8-6)
HV
transformer
cable
furnace
Figure 8-6: case of the a.c. supplied arc furnace
-
8/3/2019 08 Harmonics
15/113
645
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
The arc produced is non-linear, dissymetric and unstable. It gives rise to odd and even
harmonics, as well as to a continuous spectrum of currents (currents at all frequencies). The
levels of harmonics produced together with the continuous spectrum values will depend on the
type of furnace, its power, the duration of the process under consideration (casting, refining),
etc.
Therefore, the precise levels of harmonics can only be determined by measurement.
Figure 8-7 is an example.
1 3 5 7
100
10
1
0.1
9
4
3.2
1.3
0.5
100
order
continuous spectrum
I1(%)
Ip
Figure 8-7: current spectrum of an a.c. supplied arc furnace
the d.c. supplied arc furnace (see fig. 8-8)
HV
transformer
cable
furnace
cable
rectifier
Figure 8-8: case of the d.c. supplied arc furnace
-
8/3/2019 08 Harmonics
16/113
646
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
The d.c. supply is derived from a rectifier, the arc produced being more stable than for the a.c.
supplied furnace.
The current consumed comprises:
- a spectrum of harmonic currents similar to that of a rectifier
- a continuous spectrum with a lower overall value than for the a.c. supplied furnace.
Figure 8-9 gives the harmonic current spectrum for a 144 MVA d.c. driven arc, fed from a dual
bridge rectifier.
The use of the latter explains the high values of 11th and 13th harmonics (see 8-4-6).
order
I1(%)
Ip
3.8%
4.3% 2.5%
3.4%
1.5%1.2%
2% 1.9%
3.4%
1.9% 1.9%
9.1%
7.7%
3.2%3.5% 3.5%
continuous spectrum
Figure 8-9: harmonic current spectrum of a d.c. supplied arc furnace fed from a dual bridge rectifier
magnetic circuit saturation in machines (transformers, motors, ...)
Electrical machines are designed to work close to their magnetic saturation limits when
operating under nominal supply voltage conditions.
Should the supply voltage become abnormally high (greater than 1.1 times its nominal value),
magnetic circuits will saturate and currents will become distorted. Henceforth, the machine
becomes a source of odd order harmonic currents.
-
8/3/2019 08 Harmonics
17/113
647
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
voltage sources
Voltage sources (utility, alternator, UPS) possess pre-existing harmonic voltages which
manifest even when the equipment is connected to perfectly linear loads.
utilities
Utilities possess pre-existing voltage harmonics due to other consumers (industrial and
domestic) who create voltage harmonics on the distribution and transmission network.
Measurements taken on the French electricity authority EDF's MV distribution network have
given the results provided in table 8-8:
V1 V5 V7
high 100 % 9 % 3 %
medium 100 % 6 % 2 %
low 100 % 3 % 1 %
Table 8-8: harmonic voltages pre-existing on the French electricity authority EDF's M.V. network
Note: the 3rd harmonic currents, and multiples of them, which exist at high levels on the industrialand domestic low-voltage network, are eliminated by the delta-star connection of MV/LVtransformers. This is why 3rd harmonic voltages, and multiples of them, do not appear on theM.V. network.
Uninterruptible power supplies (UPS)
The sinusoidal voltage supplied by an inverter will not be perfect even for a linear load.
A UPS will therefore possess pre-existing harmonic voltages (see table 8-9).
Hardware model EPS 5000 EPS 2000 ALPES 1000 GALAXY
Overall distortion factor 5 % 4 % 5 % 2 %
Table 8-9: pre-existing harmonic voltages of UPS
-
8/3/2019 08 Harmonics
18/113
648
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
alternators
The sinusoidal voltage supplied by an alternator will not be perfect even for a linear load.
An alternator therefore possesses pre-existing harmonic voltages. Taking the example ofLeroy-Somer 10 kVA to 5000 kVA alternators, the voltage distortion factor is around the 4 %
mark, with 2 to 3 % of 5th harmonics and some 3rd harmonics.
V 4 %
I
Ito5
1
2 3= %
Note: the more unbalanced the load, the more 3rd harmonic an alternator will generate.
-
8/3/2019 08 Harmonics
19/113
649
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
8.1.4. Method of determining harmonic currents and voltages on a supply network
non-linear loads model
For calculation purposes, non-linear loads are considered to be harmonic current generators
(for harmonics p 2 ). They are modelled as currents injected into the network (see fig. 8-10).
Note: this model is valid for a discrete spectrum. In the case of a continuous spectrum (arc furnace) amore complex model must be devised. Such models are not dealt with in this document.
source
Vp Ip
Z
Ip : harmonic current of orderp
( )Z : impedance of network at angular frequency = =p 0 0( angular frequency at 50 Hz or 60 Hz).
Figure 8-10: model for current harmonics generated by non-linear loads
Each non-linear load will thus be modelled by its impedance at 50 Hz (or 60 Hz) and by current
sources corresponding to the harmonic currents generated by the load.
A harmonic current Ip , flowing across the network to the source through the impedance
( )Z , gives rise to a harmonic voltage Vp , such that:
( )V Z p I p p= 0
The voltage distortion factor resulting from a spectrum of harmonic currents I I I 2 3 4, , ... is then:
( )
Vp
p Z p I
V=
=
2
02 2
1
-
8/3/2019 08 Harmonics
20/113
650
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
Where a network comprises inductances and capacitances the impedance spectrum ( )Z
may vary significantly, as the curve below shows (see fig. 8-11).
0 2 0 4 0 6 0 8 0 p 0
Z( )
Figure 8-11: impedance spectrum
Harmonic voltages created on the network disturb the operation of electrical equipment. One
element of any investigation into harmonic content must therefore be to limit the values of
( )Z for values ofcorresponding to the harmonic currents with the highest values.
-
8/3/2019 08 Harmonics
21/113
651
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
modelling of sources polluted by pre-existing harmonic voltages
For the sake of calculation, pre-existing harmonic voltages are considered to be harmonic
voltage sources (see fig. 8-12).
Z
Vp load
Vp : p order of harmonic voltage
( )Z : impedance of the supply network at angular frequency = =p 0 0( angular frequency at 50 Hz).
Figure 8-12: pre-existing harmonic voltage model
A voltage source polluted by pre-existing harmonic voltages will therefore be modelled by its
nominal value at 50 Hz plus harmonic voltage sources.
impedance of network elements
utility
The impedance of the utility is generally taken to be a pure reactance. Nevertheless, the
capacitor banks found at HV/MV substations may provoke resonances at undesired
frequencies.
This should be taken into consideration during an investigation of harmonics where the
installation comprises non-linear loads drawing large amounts of power (for example, an arc
furnace).
cables, power lines and transformers
These are considered as resistances of constant value and reactances proportional to the
order of the harmonic:
( ) Z p R jpX 0 = +
p : order of the harmonic
X : reactance at 50 Hz.
-
8/3/2019 08 Harmonics
22/113
652
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
capacitor banks
These are treated as capacitors whose impedance is inversely proportional to the order of the
harmonic:
( )Z pCp
00
1=
alternator
It will be explained further on why the reactance of an alternator is not proportional to the order
of the harmonic. An alternator is considered to have negligible resistance.
at the supply network frequency
The field created by the three stator currents rotates at the speed of the rotor and is therefore
fixed in relation to it.
When the stator current increases, the voltage decreases. The impedance of the alternator is
equal to the synchronous reactance Xd which is of the order of 200 to 300 %.
at frequencies other than that of the network
The field created by the three stator currents does not rotate at the speed of the rotor and is
not therefore fixed in relation to it.
This rotating field causes harmonic currents to flow in the rotor, thereby producing a drop in
voltage.
For harmonic currents of order 3 1k , the alternator's impedance is a function of the sub-
transient impedance:
( ) X k X k d3 1 3 1 = "
Xd"
is of the order of 10 to 20 %.
For 3 k order harmonics, if the neutral is not distributed the impedance is infinite. Indeed, 3rd
order harmonics, and multiples of the 3rd, flowing in the neutral are in phase. However, if the
neutral is not distributed they cannot flow, with the result that the impedance is considered to
be infinite.
-
8/3/2019 08 Harmonics
23/113
653
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
If the neutral is distributed, 3rd order harmonic currents and multiples of them flow in it, the
alternator impedance then being a function of the zero-sequence impedance. Indeed, the field
created by harmonics which are multiples of 3 does not rotate, as in a zero-sequence current
system.
X k X k3 03=
X0 is roughly equal to half Xd"
, or of the order of 5 to 10 %
asynchronous motor
The reactance of an asynchronous motor is not proportional to the order of the harmonic. Its
resistance is considered negligible.
At the supply network frequency the motors impedance ZM depends on the load.
Indeed, ZV
IMn=
Vn : single-phase voltage
I : current consumed by the motor, which depends on its load.
For harmonic voltages of order 3 k, the impedance is infinite because generally the neutral of
the motor is not distributed.
For 3 1k order harmonics, the motor's impedance is a function of the locked rotor impedance
(or starting impedance if there is no starting current limiting system):
( )X kI
IXk
n
bn3 1 3 1 =
( )X kV
Ikn
lr
3 1 3 1 =
Xn : motor impedance at rated load, XV
Inn
n=
Ilr : locked rotor current (or start up current if there is no starting current limiting system).
-
8/3/2019 08 Harmonics
24/113
654
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
inverters
The output impedance is vastly different according to whether the machine is of the older type
(EPS 5000) or one of the newer generation (GALAXY or COMET).
older type inverters (EPS 5000)
The output impedance is equal to impedance of the output filter. The equivalent circuit as seen
from the output is that of figure 8-13.
V
Zs ( )
Figure 8-13: older type inverter output impedance
Output impedance is therefore frequency dependant (see fig. 8-14).
At low frequencies the output impedance is close to L .
At high frequencies the output impedance is close to1
C.
At the resonance frequency fL C
r =1
2 , the filter's impedance is very high, having an order
of magnitude equal to the nominal load impedance, that is ( )Z fout r 2 100 % .
In practice, the resonance frequency is chosen to be far from that of the most common
harmonic currents.
For example, 210 Hz might be selected since 4th order harmonics are virtually non-existent.
-
8/3/2019 08 Harmonics
25/113
655
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
newer generation inverters with phase-neutral voltage regulation (GALAXY, COMET)
This type of equipment uses a very high switching frequency (several kHz) and an extremely
fast voltage regulator, enabling output voltage quality to be maintained even with a high
current distortion factor. As a consequence, the output impedance is very low and virtuallyconstant for all orders of harmonic (see fig. 8-14).
150
100
50
0 50 250 500 750
new type of inverter(GALAXY, COMET)
old type of inverter (EPS 5000)
ratio of the output impedance
to the nominal load impedanceZn
%Zs
f Hz( )
Figure 8-14: inverter output impedance
-
8/3/2019 08 Harmonics
26/113
656
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
particular case of 3rd harmonics and multiples of the 3rd
3rd harmonic currents are in phase, with a current equal to their sum flowing in the neutral
when distributed (see fig. 8-15). If the neutral is not distributed, 3rd harmonics and multiples of
them cannot flow, and thus cannot exist.
I3
I3
I3
3 3I neutral
Figure 8-15: 3rd harmonic currents, and multiples of them, flowing in the neutral
why 3rd harmonics, and multiples of the 3rd, are in phase
Take 3 equal currents I ta ( ) , I tb ( ) and I tc ( ) with phase displacements of 1/3 of a period:
( )
( )
( )
i t t
i t t T
i t t T
a
b
c
=
= +
= +
cos
cos
cos
32
3
where T=2
period of signal
Note !: the currents are phase shifted in time and must therefore be expressed as above.
The 3rd harmonics of these currents are obtained by replacing by 3 :
( )i t t a3 3 3= cos
( ) ( )i t t T t t b3 3 3 33 3 2 3= + = + =cos ( ) cos cos
( ) ( )i t t T t t c3 3 3 33 2 3 4 3= + = + =cos ( ) cos cos
giving i t i t i t t a b c3 3 3 33 3( ) ( ) ( ) cos+ + =
-
8/3/2019 08 Harmonics
27/113
657
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
The in-phase relationship can also be shown graphically (see fig. 8-16). The same is true for
all harmonics that are multiples of the 3rd.
I3
I2
I1
t
t
t
3rd harmonic
t
Ineutral
3rd harmonic
3rd harmonic
Figure 8-16: the 3rd harmonics of a 3-phase system are in phase
-
8/3/2019 08 Harmonics
28/113
658
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
superposition theorem
Consider the case of a network with the following characteristics:
- a voltage source with pre-existing harmonics V V V2 3 4, , , ...
- a transformer whose impedance is R LT T, , feeding a busbar
- various non-linear loads grouped together to form an equivalent load generating the
harmonic currents I I I2 3 4, , , ...
The loads are supplied from the busbar through an impedance R L1 1,
- various linear loads grouped together to form an equivalent load fed from the busbar
through an impedance R L2 2,
- the equivalent capacitorC representing the reactive energy compensating capacitors.
Each voltage and current source is considered to act in independently on the network.
The theorem of superposition states: for a linear network, the current (or voltage) generated in
a branch by several independent sources acting simultaneously, is equal to the currents (or
voltages) produced in the same branch by the different sources acting in isolation.
Figure 8-17 illustrates the application of this theorem.
-
8/3/2019 08 Harmonics
29/113
659
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
R LT T,
V source
non-linearloads
linearloads
CR1 R2
L2L1
equivalent
non-linear
loads
linear
loads
V1
oC
1
R LT T o,
R1 R2L o1 L o2 +
non-linearloads
linearloads
Vp
R pLT T o,
pL o1
R1 R2pL o2
1
pC o +
linearloadsIp
R1pL o1
R2pL o2
1
pC o
R pLT T o,
network at 50 Hz + p harmonic networks of orders
1 2, ,..., p supplied by voltagesources V V Vp1 2, ,...,
+ p harmonic networks of orders
1 2, ,..., p supplied by currentsources I I Ip1 2, ,... ,
Figure 8-17: superposition theorem as applied to harmonics
-
8/3/2019 08 Harmonics
30/113
660
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
addition of equal order harmonics arising from different non-linear loads
The harmonic currents of the same order generated by several non-linear loads are not
necessarily in phase. The resultant current is obtained by vector addition (see fig. 8-18).
r
Ip,1
r
Ip, 2
r
Ip sum,
Figure 8-18: vector addition of two 2 harmonic currents of the same order
Take the two extreme situations.
their phase relationship is perfectly random
The modulus of the sum of two p order harmonics is, on average:
I p mean,2
( ) ( )[ ]= + +12 1 22
22
0
2
I I I d p p p, , ,cos sin
( )= + +12 202
12
22
1 2
I I I I d p p p p, , , , cos
= +I Ip p, ,12 22
I p mean, = +I Ip p, ,12
22
By extension, for a number k of non-linear loads supplying harmonics of order p , the
modulus of their sum is, on average: I I p sum p
k
, ,= 2
-
8/3/2019 08 Harmonics
31/113
661
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
the harmonics are perfectly in phase
In this case, the harmonics add together algebraically, giving :
I I p sum p ii
k
, ,==
1
Practical instances fall somewhere between the two extremes, with phase correlation
depending to a greater or lesser degree on: diversity of harmonic sources, transformer vector
group, etc. Consequently, an empirical law has been defined to estimate the modulus of the
sum of equal order harmonics, expressed by the following relationship:
( )I I p sum p ik
, ,
/
=
1
where 1 2
= 1 : the harmonics are perfectly in phase= 2 : harmonic phases are perfectly random.
It can be seen that I p sum,
decreases as increases,
I p sum,
r eqZ
C,
1.
-
8/3/2019 08 Harmonics
40/113
Publication, traduction, et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos servicesThe publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
670
Figure 8-23 illustrates the variations in Zeq as a function of .
N
M
K
R
r
Zeq
Figure 8-23: variations in Zeq as a function of angular frequency
n definition of amplification factor FA
FA is the ratio of the network impedances with and without capacitors, at the resonant frequency.
FKN
KMA= (see fig. 8-22)
i.e. FR
LA sc r =
hence
F R
C
LA sc=
now Q C Un= 02
and LU
Sscn
sc0
2
=
henceF
Q S
PAsc=
-
8/3/2019 08 Harmonics
41/113
Publication, traduction, et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos servicesThe publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
671
definition of the order of resonance pr
The order of resonance is defined as the ratio pr of the angular frequency of resonance to the angular
frequency of the network:
prr=
0
now rccL C
= 1
hencep
S
Qrcc=
determining the network behaviour in the presence of harmonic current the order of
which is equal to pr
For = =r eqZ R,
hence V R Ir r=
V F L I r A cc r r =
Vr : harmonic voltage of orderr appearing on the busbar
The harmonic voltage Vr on the busbar is therefore multiplied by FA compared to the case
where there are no capacitors (V L Ir cc r r = ).
Let IC r, be the harmonic current of order r flowing in the capacitors,
I C V C L C
R IC r r r cc
r, = =1
I F I C r A r , =
Let IL r, be the harmonic current of order r flowing in the upstream network,
IV
L
Lcc C
LccR IL r
r
cc rr, = =
I F I L r A r , =
-
8/3/2019 08 Harmonics
42/113
672
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
The currents and voltages at resonance are those shown in figure 8-24.
R
Ir
IrC
I F I L, r A r I F IC, r A r
V F L I r A sc r r Lsc
Figure 8-24: currents and voltages appearing at resonance
The following paragraphs will demonstrate that the value of FA could be very high on an
industrial network (in general anything from 2 to 5, and as much as 20).
As the diagram shows, harmonic currents flowing in the capacitors and upstream network are
each amplified by a factor ofFA .
Therefore, compared to the case where there are no capacitors, the harmonic voltage of order
r produced on the busbar is amplified by a factor of FA . Compensating capacitors will then
more than likely pose significant problems when large, non-linear loads are connected to the
network.
example
Let us consider a 20 kV / 400 V transformer of S kVAT = 1250 , and Usc = 5 5. % , supplying :
- day and night, a bridge rectifier whose powerS kVAB = 500 and power factorFp B, .= 0 8 .
- a linear load whose power consumption S kVAld = 600 during the daytime period, andS kVAln = 100 during the night-time period, with a power factorFp l, .= 0 9 .
The upstream network short-circuit powerS MVAup = 130 .
The requirement is to compensate the reactive energy of the fundamental during the day so as
to obtain tan .1 0 4= , where tan 11
1
=P
Q.
P1 : active power of the fundamental component
Q1 : reactive power of the fundamental component.
-
8/3/2019 08 Harmonics
43/113
673
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
determining the reactive power of the capacitors to be installed
Using the manufacturers' assumption (see 8.1.5), we can calculate the fundamental
component values for the bridge rectifier:
P P F S B B p B B1 0 8 500 400, , .= = = =
From the example of paragraph 8.1.5, Q kVAB1 277, = .
The daytime period linear load is S kVAld = 600 where Fp l, .= 0 9 .
Calculating the active and reactive powers of a linear load is straightforward:
P S F kW ld ld p l = =, 540
Q S P k ld ld ld = =2 2
262 var
We can also calculate the installation's tan 1 value:
tan .,
,
11
1
277 262
400 5400 57=
+
+=
++
=Q Q
P P
B ld
B ld
To compensate the reactive energy of the fundamental, the necessary capacitor bank power
rating is thus given by:
( ) ( )Q P P k B ld = + = =1 1 0 940 0 17 159 8, tan .4 . . va
The choice would be to install a standard value capacitor bank with a rated power value ofQ kC = 160 var.
-
8/3/2019 08 Harmonics
44/113
674
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
calculation of the harmonic voltages and distortion factor in the absence of capacitors
Firstly, the equivalent impedance for the transformer and upstream network is calculated.
Using the approximation that the transformer and upstream network are composed of purereactance (see 4.2.1.4 - Protection Guide), we have:
XU
Supn
up=
2
and XU
SUT
n
Tsc=
2
hence ( )X UU
S Sm sc n
sc
T up= +
=
+
=2 2
3 6
1400
0055
1250 10
1
130 108 27
..
X Xup T, : are the reactance of the upstream network and the transformer respectivelyXsc : is the equivalent reactance of the transformer and upstream network (short-circuit impedance).
We can now calculate the harmonic voltages (see table 8-12) and the distortion factor.
Order of harmonic 5 7 11 13 17 19 23 25 29 31
( )Ip % 18.9 11.0 5.9 4.8 3.4 3 2.3 2.1 1.8 1.6
( )I Ap
132.7 77.3 41.4 33.7 23.9 21.1 16.2 14.7 12.6 11.2
( )V pX I V p sc p= 5.49 4.47 3.77 3.62 3.36 3.32 3.08 3.04 3.02 2.87
( )V
Vp
1
%2.39 1.95 1.64 1.58 1.46 1.44 1.34 1.32 1.31 1.25
Table 8-12: harmonic voltages in the absence of capacitors
From here, the voltage distortion factor is:
V = 5 07. %
This is an acceptable value, both for the operation of the bridge rectifier and for the rest of the
installation (see 8.2).
-
8/3/2019 08 Harmonics
45/113
675
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
calculation of the harmonic voltages and distortion factor for the daytime period with
the compensating capacitors in service
Calculating the order of resonance:
pS
Qrsc=
where SU
XMVAsc
n
sc= =
2
19 35.
Q k= 160 var
hence pr
= 1100.
The order of resonance is the same as the order of a high value harmonic current generated
by the bridge rectifier.
Calculating the amplification factor:
FQ S
PAsc=
P is the active power of the linear loads, giving P P kW
ld= =540
hence FA = 3 26.
Calculating the equivalent impedance Zeq :
1 1 10
0Z Rj p C
p Leq ld sc= +
Z
RpC
p L
eq
ld sc
=+
1
1 12 0
0
where RU
Pmld
n
ld= =
2
2963.
CQ
Un0 2 100= = .
L X m sc sc
0
8 27= = .
-
8/3/2019 08 Harmonics
46/113
676
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
Figure 8-25 shows the curve of the Zeq ( ) impedance spectrum.
We can go on to calculate the harmonic voltages (see table 8-13)
Order of harmonic 5 7 11 13 17 19 23 25 29 31
( )I Ap 132.7 77.3 41.4 33.7 23.9 21.1 16.2 14.7 12.6 11.2
Z meq ( ) 51.3 92.5 296.3 199.7 95.7 76.5 55.4 48.9 39.9 36.6
( )V Z I V p eq p= 6.81 7.15 12.27 6.73 2.29 1.61 0.90 0.72 0.50 0.41
( )V
Vp
1
%2.96 3.11 5.33 2.93 0.99 0.70 0.39 0.31 0.22 0.18
( )I AC p, 34.1 50.1 135 87.5 38.9 30.6 20.7 18.0 14.5 12.7
Table 8-13: harmonic voltages during the daytime period with capacitors in service
From here, the voltage distortion factor is :
V = 7 5. %
The harmonic currents flowing in the capacitor bank are obtained from:
I pC V C p p, = 0 (see table 8-14).
The r.m.s. current in the capacitor bank is :
I IC rms C , ,=
2
IC, 1 is the fundamental current in the capacitors, that is the nominal current, which gives
I I C V AC C n n, ,1 0
230= = = .
hence I AC rms, .= 2930
and I
I
C rms
C n
,
,
.= 1 27
Next, we can calculate Vrms = 230 64. .
-
8/3/2019 08 Harmonics
47/113
677
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
It can be seen that despite the high values of some of the harmonic currents, the r.m.s. voltage
is virtually identical to the nominal voltage. The manufacturers' assumption is thus justified:
U Urms = 1 .
The r.m.s. current in the capacitor bank is close to the limit of 1.3 IC n, , there is thus a risk of
the capacitors overheating.
The voltage distortion factor is only just acceptable, and certain loads may well be disturbed
(see 8.2). The bridge rectifier will be able to operate normally (see 8.2).
calculation of harmonic voltages and distortion factor for the night-time period with
the compensating capacitors in service
Calculating the amplification factor:
FQ S
PAsc=
P is the active power of the linear loads during the night-time period, giving P P S kW = = =ln ln 0 9 90.
hence FA =160 19 350
90
FA = 19 6.
Z
RpC
p L
eq
sc
=
+
1
1 12 0
0ln
where RU
Pmn
ln ln= =
2
1778.
CQ
Un0 2 1 00= = .
L X m sc sc0 8 27= = .
Figure 8-25 shows the curve of the Zeq ( ) impedance spectrum
-
8/3/2019 08 Harmonics
48/113
678
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
We can go on to calculate the harmonic voltages (see table 8-14)
Order of harmonic 5 7 11 13 17 19 23 25 29 31
( )I Ap 132.7 77.3 41.4 33.7 23.9 21.1 16.2 14.7 12.6 11.2
Z meq ( ) 52.1 97.2 1778 267.3 101.1 79.1 56.3 49.6 40.3 36.9
( )V Z I V p eq p= 6.91 7.51 73.61 9.01 2.41 1.67 0.91 0.73 0.51 0.41
( )V
Vp
1
%3.01 3.27 32.0 3.92 1.05 0.73 0.40 0.32 0.22 0.18
( )I AC p, 34.6 52.6 809.7 117.1 41.0 31.7 20.9 18.3 14.8 12.7
Table 8-14: harmonic voltages during night-time period with capacitors in service
From here, the voltage distortion factor is :
V = 32 6. %
This figure is unacceptable to the majority of equipment, which will not operate properly and
may be damaged as a result (see 8.2). The bridge rectifier itself will malfunction, the
distortion factor being well above the permitted threshold (see 8.2).
The harmonic currents flowing in the capacitor bank are given by:
I pC V C p p, = 0 (see table 8-15).
The r.m.s. current in the capacitor bank is :
I IC rms C , ,=
2
IC, 1 is the fundamental current in the capacitors, that is, the nominal current. We have then I I C V AC C n n, ,1 0 230= = = .
hence I AC rms, .4= 854
and I
I
C rms
C n
,
,
.= 3 71
-
8/3/2019 08 Harmonics
49/113
679
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
The r.m.s. current in the capacitor bank is much greater than the permitted maximum, with the
result that the protection system will disconnect them.
Next, we can calculate the r.m.s. voltage: V Vrms = 242 .
Being 5 % above nominal voltage, this is an acceptable value in terms of the capacitors.
conclusion
The installation of reactive energy compensating capacitors increases the voltage distortion
factor, especially when harmonic currents exist close to the resonance frequency. When the
power consumed by any linear loads is reduced, voltage distortion increases resulting in higher
levels of disturbance.
For large, non-linear loads, the installation of capacitors should go hand in hand with an
investigation of the harmonics. This will enable calculations to be made for the equipment
necessary (see 8.4) to overcome the problem cited above.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31
1700
1500
1300
1100
900
700
500
400
300
200
100
with capacitors, night-time
with capacitors, day-time
frequency
(p x 50 Hz)
without capacitors
Z meq
Figure 8-25: the different impedance spectrum curves
-
8/3/2019 08 Harmonics
50/113
680
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
8.2. Effects of harmonics on electrical apparatus, and working guidelines
Harmonics may well cause electrical equipment to malfunction, or to overheat, or to produce
mechanical vibrations which could lead to irreparable damage.
capacitors
Capacitors should conform to the IEC standard 871-1 for M.V. and to IEC standard 831-1 for
L.V. These standards stipulate:
- the ability to permanently pass a current of 1.3 times rated value, corresponding to a current
distortion factor ofI = 83 % . In fact, I
pp
pp rms
I I I I2
2
2
2
12 2
1
2
2
21= =
+
= +=
=
I1 : rated current of the bank
hence ( )I = 1 3 12
.
- the ability to withstand 1.1 times rated voltage 12 h / day for M.V. use, and 8 h / day in a
L.V. application, allowing their operating voltage to be 10% above rated value.
working guidelines
The above specifications are not cumulative, therefore the following condition should be
observed:
3 1 3 I V Qrms rms n .
Qn : nominal or rated power of the bank.
Should this condition not be met, techniques to limit harmonics could be implemented
(see 8.4). Otherwise, one approach might be to install, if this is adequate, over-insulatedcapacitors (class H) able to permanently pass 1.5 times their rated current, a figurecorresponding to a current distortion factor of I = 112% .
-
8/3/2019 08 Harmonics
51/113
681
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
example
A capacitor bank of standard value 200 400k Vvar, is supplied from a busbar whose voltage
characteristics are:
- daytime period VV
d1400
3=
- night-time period VV
t1420
3=
- measured harmonic voltages, identical for day and night-time periods, of:
V V V5 7 113 5 7V V V1 1 1
= = =%, %, % andV13 4V1
= % .
calculating the r.m.s. current in the capacitors during the daytime period
For the fundamental component (at 50 Hz):
I C V d1 0 1=
where V Vd n1 = : rated voltage of capacitor bankI In1 = : rated current of capacitor bank 0 2 50= : angular frequency of the supply network .
For the harmonics:
I pC V p p= 0
henceI
Ip
V
Vp p
d1 1=
I I pV
Vpp
d
212 2
1
2
=
( ) ( ) ( ) ( )( ) I I I pV
VIrms
p
dp
212
12 2
1
2
12 2 2 2 2 2 2 2 2
2
1 0 03 5 0 05 7 0 07 11 0 04 13= +
= + + + +
=
. . . .
I Irms = 1 1.42
hence I Irms n= 1 42.
The capacitors will overheat and deteriorate prematurely if the protection system does not
disconnect them.
-
8/3/2019 08 Harmonics
52/113
682
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
calculating the r.m.s. current in the capacitors during the night-time period
For the fundamental component (at 50 Hz):
I C V C V VV
C Vt nt
nn1 0 1 0
10
420400
= =
=
hence I In1 1 05= .
For the harmonics :
I pC V p p= 0
henceI
I
pV
V
p p
t1 1
=
I I pV
Vpp
t
212 2
1
2
=
I I I pV
Vrmsp
t
212
12 2
1
= +
=
I I I rms n= = 1 42 1 42 1 051. . .
hence I Irms n= 1 49.
The r.m.s. value of current is higher during the night-time period because the voltage is higher.
As a result the capacitors will overheat all the more.
-
8/3/2019 08 Harmonics
53/113
683
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
transformers
When subjected to harmonic currents a transformer will suffer supplementary losses and
possible disturbance to its magnetic circuit. Moreover, it will tend to generate noise due to the
vibrations caused by the harmonics.
Joule losses
These are proportional to the square of the r.m.s. current : loss = R I rms2
.
Harmonic currents therefore increase Joule losses.
iron loss
This comprises eddy current losses and magnetic induction hysteresis losses.
Eddy current loss is proportional to the square of the frequency, whereas hysteresis loss is
proportional to the frequency. The higher frequency harmonic currents will therefore generate
significant iron losses.
disturbance of the magnetic circuit
Harmonic currents generate an extra magnetic flux proportional to the impedance of the
upstream network. This is superimposed on the flux produced in the transformer by the
fundamental.
The peak value of flux is thereby increased, which can lead to saturation and an increase in
magnetising current and iron losses. The transformer itself may also generate harmonics.
-
8/3/2019 08 Harmonics
54/113
684
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
transformer de-rating formula, and working guidelines
To take account of the extra heat developed, transformers should be de-rated. The formula
commonly used is:
kI
Ip
p
p
=
+
=
1
1 0 11
21
2
..
p : order of harmonic
I1 : transformer rated current.
A transformer of rated powerSn is therefore limited to supplying a load of k Sn .
Another solution consists in obtaining the manufacturer's agreement to construct a transformer
specially designed to feed equipment that produces harmonics.
example 1
It is required to feed a 800 kVA, bridge rectifier from a transformer.
Using table 8-1, the de-rating factor is:
11 0 1
2
k
= + . ( ) ( ) ( ) ( ) ( )[ 0 189 5 0 11 7 0 059 11 0 048 13 0 034 172 1 6 2 1 6 2 1 6 2 1 6 2 1 6. . . . .. . . . . + + + +
( ) ( ) ( ) ( ) ( ) ]+ + + + + 0 03 19 0 023 23 0 021 25 0 018 29 0 016 312 1 6 2 1 6 2 1 6 2 1 6 2 1 6. . . . .. . . . .
hence k= 0931.
The bridge rectifier should therefore be supplied from a transformer whose rated power is at
least equal to 859 kVA.
example 2
It is required to feed a 250 kVA load in the shape of switchmode power supply from atransformer.
Using the high harmonic level assumption of table 8-2, the de-rating factor is:
( ) ( ) ( ) ( ) ( )[ ]1
1 0 1 1 3 3 0 7 5 0 5 7 0 3 9 0 1 112
2 1 6 2 1 6 2 1 6 2 1 6 2 1 6
k= + + + + + . . . . . .. . . . .
hence k= 0532.
A transformer of at least 470 kVA should therefore be installed.
-
8/3/2019 08 Harmonics
55/113
685
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
motors
When harmonic voltages are present, motors are subject to supplementary losses and
pulsating torques.
Joule losses
Joule loss is proportional to the square of the r.m.s. value of current : loss = R I rms2
.
Harmonic currents generated by the harmonic voltages present in the supply will thus increase
Joule losses.
iron loss
This comprises Foucault current (eddy current) losses and magnetic induction hysteresislosses.
Eddy current loss is proportional to the square of the frequency, whereas hysteresis loss is
proportional to the frequency. The higher frequency harmonic voltages will therefore generate
significant iron losses.
pulsating torques, opposing or motor
Harmonic voltages produce harmonic currents, creating rotating fields whose speeds differ
from that of the 50 Hz field. Such fields will produce either motor or opposing torques at
frequencies other than 50 Hz. These torques, and the vibrations they cause, may lead to
mechanical damage, extraneous noise, supplementary Joule loss in the rotor and a reduction
in motor efficiency.
working guidelines
IEC standard 34-1 lays down that a.c. current motors must be able to operate correctly with a
supply voltage whose harmonic voltage factor ( HVF ) is as follows:
HVF 2 %
The HVF value is calculated from the following formula:
HVFV
V pp
p
=
=
1
2
2
1
According to the standard only harmonics of order 13 need generally be considered.
-
8/3/2019 08 Harmonics
56/113
686
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
example
Using the example of paragraph 8.6.1:
without capacitors
From table 8-12, calculation gives HVF= 162. % (whereas V = 5 07. % ). This value isacceptable for motors conforming to IEC standard 34-1.
with capacitors during the day time period
From table 8-13, calculation gives HVF= 2 50. % . This higher value is the figure laid down bythe standard. Any motor installation must therefore involve specific calculations, or testing at
the manufacturers to check motor thermal withstand or to establish the de-rating figure that
may need to be applied to the machines.
with capacitors during the night time period
From table 8-14, calculation gives HVF= 9 89. % . This is a value far greater than that definedby IEC standard 34-1, the strong resonance at the 11th harmonic producing intolerably high
harmonic voltages.
-
8/3/2019 08 Harmonics
57/113
687
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
alternators
When supplying non-linear loads, an alternator will suffer supplementary losses and pulsating
torques due to the harmonic currents produced.
iron loss
This comprises Foucault current (eddy current) loss and magnetic induction hysteresis loss.
Eddy current loss is proportional to the square of the frequency, whereas hysteresis loss is
proportional to the frequency. The higher frequency harmonic currents will therefore generate
significant iron losses.
pulsating torques, opposing or motor
Harmonic currents create rotating fields whose speeds differ from that of the 50 Hz field. Such
fields will produce either motor or opposing torques at frequencies other than 50 Hz. These
torques, and the vibrations they cause, may lead to mechanical damage, extraneous noise,
supplementary Joule loss in the rotor and a reduction in alternator efficiency.
working guidelines
Alternators supplying less than 20% of non-linear loads will not generally have any difficulties.Between 20 and 30 % certain manufacturers de-rate their machines by 10 %. Above 30%, the
the harmonic current spectrum must be shown to the manufacturer so that he can provide the
derating coefficient. For example, for an uninterruptible power supply manufacturers
recommend choosing an alternator with a power of 1.5 to 1.9 times that of the UPS.
-
8/3/2019 08 Harmonics
58/113
688
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.
The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.
Industrial electrical network design guide T & D 6 883 427/AE
neutral conductor heat problem
3rd harmonic currents, and multiples of the 3rd, are in phase and flow in the neutral conductor
when it exists, and when the transformer vector group makes it possible (e.g. a delta-star
transformer, which is the most common case).
The r.m.s. current in the neutral conductor is given by:
I Ineutral k k
==
3 321
This current may be greater than that flowing in the phase conductors, and as a result the
neutral conductor must be oversized.
working guideline
The cross-section of the neutral conductor must take into account the existence of 3rd
harmonic currents and multiples of the 3rd.
example 1
Consider a lighting load whose current spectrum is that of table 8-15.
I1 I3 I5 I7 I9 I11 I13 I15
100 % 35 % 27 % 10 % 2.5 % 3.5 % 1.5 % 1.5 %
Table 8-15: lighting load current spectrum
We can derive:
I Irms = 110 1.
( ) ( ) I I I neutral = + =3 0 35 0 025 1 0512 2
1. . .
The neutral current value is more or less equal to that flowing in a phase conductor, and as
such all cables can have similar cross-sections.
.
-
8/3/2019 08 Harmonics
59/113
689
Industrial electrical network design guide T & D 6 883 427/AE
example 2
Consider computer type loads that have a spectrum as shown in table 8-16.
I1 I3 I5 I7 I9 I11
100 % 65 % 35 % 25 % 15 % 5 %
Table 8-16: current spectrum for computer loads
We can derive:
I Irms = 1 28 1.
( ) ( ) I I I neutral = + =3 0 65 0 15 2 0012 2
1. . .
andI
Ineutral
rms= 1 56.
The current in the neutral is much larger than that flowing in a phase conductor. This demands
the use of a protection device (circuit-breaker with 4-pole protection) plus a neutral conductor
of sufficient cross-section.
electromagnetic disturbances in a TNC earthing system
Currents due to the 3rd harmonic, and multiples of the 3rd, flow in the neutral conductor. In a
TNC earthing system the neutral conductor and circuit protection conductor are one and the
same.
Now, since the circuit protection conductor connects together all exposed conductive parts,
including elements of the building's infrastructure, 3rd harmonic currents and multiples of them
flowing in these circuits will produce local variations in potential.
This phenomenon may cause problems such as :
- corrosion of metal parts
- overcurrent on a telecommunication link connecting the exposed conductive parts of two
loads (for example, between a microcomputer and a printer)
- electromagnetic radiation affecting computer screens.
Where 3rd harmonics or multiples of them are present the TNC earthing system must be
avoided.
-
8/3/2019 08 Harmonics
60/113
690
Industrial electrical network design guide T & D 6 883 427/AE
inverters
The level of harmonic disturbance created by an inverter will depend on the technique used to
generate the sine wave voltage, that is, either PWM (Pulse Width Modulation) or non-PWM.
non-PWM inverters
The output current of non-PWM inverters is limited to its rated value, giving an instantaneous
value of current no higher than 2 In .
Manufacturers apply a de-rating factor that is a function of the peak factor F
Ipk n=
This de-rating factor is given by :
dFpk
= 2
PWM inverters
The output current of Merlin Gerin PWM inverters is limited to 2.35 times the r.m.s. value ofrated current, giving an instantaneous value no higher than 2 35. In .
- if In
2 35. de-rating is not applied- if In> 2 35. the de-rating factor is given by:
dI
n=
2 35.
hence dFpk
=2 35.
example
Table 8-17a gives the de-rating coefficients for inverters feeding computer type loads.
Type of load IBM 4381 IBM AS400 IBM PCXT IBM site *
Peak Factor 2.14 2.53 5.54 2.21
Non-PWM de-rating 0.66 0.56 0.26 0.64
PWM de-rating / 0.93 0.42 /
Table 8-17a: inverter de-rating when feeding computer loads
* Example of an IBM site with a large number of terminals.
-
8/3/2019 08 Harmonics
61/113
691
Industrial electrical network design guide T & D 6 883 427/AE
semiconductor convertors
IEC standard 146-1-1, 2.5.4.1 lays down the operating limits, without performance loss, for
convertors, defining them according to the machine's immunity class (see table 8-17b):
- class A: limits are applicable to convertors used on highly (harmonically) disturbed
networks.
- class B: limits are applicable to convertors used on networks where there is an average
level of disturbance
- class C: limits are applicable to convertors used on networks where the disturbance is low.
If the immunity class is not specified, class B is deemed to apply.
Immunity class
A B C
Individual even harmonics (%) 2 2 1
Individual odd harmonics (%) 12.5 5 2.5
Total harmonic distortion (%) 25 10 5
Table 8-17b: operating limits without performance loss, for convertors
-
8/3/2019 08 Harmonics
62/113
692
Industrial electrical network design guide T & D 6 883 427/AE
special case of the uninterruptible power supply
The IEC standard 146-4, 5.1 lays down the guaranteed operating limits for a UPS:
- voltage distortion factor less than 10 %
- harmonic voltage components less than those defined by the curve shown in figure 8-26.
5%
1%
0.5%
0.4%
0.3%
3 5 7 9 11 13 25 100
Vp
V1(%)
Figure 8-26: maximum permitted harmonic voltage content on a UPS a.c. supply input
-
8/3/2019 08 Harmonics
63/113
693
Industrial electrical network design guide T & D 6 883 427/AE
permanent insulation monitors (PIM)
Such devices apply a d.c. or low-frequency voltage between the protection conductor and the
neutral (or phase if the neutral is not accessible), and measure the current.
PIMs using a d.c. voltage are not affected by harmonics since they measure a highly filtered
d.c. current.
On the other hand, the older type of PIM (before 1993), such as the XM100, will be affected.
These inject a 10 Hz voltage and filter the 50 Hz signal. However, the filter becomes ineffective
from, and including, the 3rd harmonic upwards. Thus, any 3rd harmonic currents or multiples
of them or unbalanced harmonic currents of monophased loads flowing in the neutral may be
"seen" by the PIM causing it to alarm in error.
Where an installation has in-circuit fault location core-balance current transformers on its
outgoing feeders, harmonic currents flowing in the neutral will disrupt the fault location system.
No permitted voltage distortion limits have been defined for PIMs, since any likely disruption
will depend on the characteristics of the network and loads.
The newer generation PIMs (post 1993), which use a 2.5 Hz voltage and filters which are
effective above 4 Hz, are immune to harmonics.
circuit-breakers with electronically tripping relay
The thermal or magnetic detection of older model circuit-breakers (still on sale today) aresensitive to peak values of current.
High current distortion factors can mean high peak currents (see the values for computer
equipment, table 8-18) leading in turn to spurious opening of the circuit-breakers. The thermal
detection threshold must then be increased when this is possible or the harmonics filtered out.
Newer generation devices - compact or masterpact - sample the current and calculate its r.m.s.
value, and are therefore immune.
computer loads
The recommended threshold for reliable operation is:
V
Vp
p 1
2
1
5
21 0.2/ * 0.2/ * 10 0.5 0.2/0.5*
19 1.5 1 12 0.2/0.5* 0.2/0.5*
23 1.5 0.7 14 0.2/0.5* 0.2/0.5*
25 1.5 0.7 16 0.2/0.5* 0.2/0.5*
> 25 0 212 5
..
+n
*
0 112 5
..
+n
*
18 0.2/0.5* 0.2/0.5*
20 0.2/0.5* 0.2/0.5*
22 0.2/0.5* 0.2/0.5*
24 0.2/0.5* 0.2/0.5*
> 24 0.2/ * 0.2/ *
Total harmonic distortion
8 % on MV networks 3 % on HV networks
* : values specific to the EDF "Emeraude" contract : no value has been specified
Table 8-19: compatibility levels for harmonic voltages on medium and high-voltage public networks
(taken from Electra, n123 March 1989, and the EDF's Emeraude contract)
-
8/3/2019 08 Harmonics
69/113
699
Industrial electrical network design guide T & D 6 883 427/AE
on industrials networks
IEC standard 1000-2-4 lays down the compatibility levels for harmonic and interharmonic
voltages existing on industrial networks (see tables 8-20 and 8-21).
They apply to low and medium-voltage networks .The compatibility levels are given for different classes of environment:
Class 1:
Environments in this class are essentially protected networks, with compatibility levels lower
than for public networks, where equipment particularly sensitive to supply network disturbance
is used: laboratory instruments, certain automatic and protective installations, certain
computers, etc.
Equipment in this type of environment is, of necessity, generally supplied from an
uninterruptible power supply. Only low-voltage networks are included in this class.
Class 2:
This class concerns the utility's take-over point and the internal network.
The compatibility levels are identical to those applying to public supply networks.
Class 3:
This class applies only to internal networks. Compatibility levels are higher than for class 2
environments.
-
8/3/2019 08 Harmonics
70/113
700
Industrial electrical network design guide T & D 6 883 427/AE
Odd harmonics not
multiples of 3
Odd harmonics
multiples of 3
Even harmonics
Order of
harmonicn
Harmonic voltage
%
Order of
harmonicn
Harmonic voltage
%
Order of
harmonicn
Harmonic voltage
%
class
1
class
2
class
3
class
1
class
2
class
3
class
1
class
2
class
3
5 3 6 8 3 3 5 6 2 2 2 3
7 3 5 7 9 1.5 1.5 2;5 4 1 1 1.5
11 3 3.5 5 15 0.3 0.3 2 6 0.5 0.5 1
13 3 3 4.5 21 0.2 0.2 1.7
5
8 0.5 0.5 1
17 2 2 4 > 21 0.2 0.2 1 10 0.5 0.5 1
19 1.5 1.5 4 > 10 0.2 0.2 1
23 1.5 1.5 3.5
25 1.5 1.5 3.5
> 25 212 5
+.
n2
12 5+
.
n 511
n
Total harmonic distortion
5 % for class 1 8 % for class 2 10 % for class 3
Table 8-20: compatibility levels for harmonic voltages existing on industrial networks
Order
h
Class 1
( )Up %Class 2
( )Up %Class 3
( )Up %
< 11 0.2 0.2 2.5
11 to 13 inclusive 0.2 0.2 2.25
13 to 17 inclusive 0.2 0.2 2
17 to 19 inclusive 0.2 0.2 2
19 to 23 inclusive 0.2 0.2 1.75
23 to 25 inclusive 0.2 0.2 1.5
> 25 0.2 0.2 1
Table 8-21: compatibility levels for inter-harmonic voltages on industrial networks
-
8/3/2019 08 Harmonics
71/113
701
Industrial electrical network design guide T & D 6 883 427/AE
8.3.2.2. Emission levels
Harmonic currents emitted by customer installations and equipment must be limited in order
avoid harmonic disturbance attaining the maximum levels of compatibility defined previously
(see tables 8-18, 8-19, 8-20 and 8-21).
emission limits applied to low voltage apparatus drawing less than 16 A per phase
It would be extremely difficult to check the harmonic current emissions of each customer
connected to a low-voltage network. Besides, IEC 1000-3-4 was drawn up by standards bodies
to define emission limits for low-voltage apparatus drawing less than 16 A per phase, and
destined to be connected to the public low-voltage distribution networks. Table 8-22 defines
the emission limits for class A equipment: i.e. apparatus other than portable tools, lighting and
equipment drawing an input current with a "special waveform" whose active power
consumption is less than 600 W (for equipment of this type see IEC 1000-3-2, 7).
These limits do not apply to professional equipment with a power rating greater than 1 kW.
Order of harmonic
n
Maximum permissible harmonic current
( )A
Odd harmonics
3 2.30
5 1.14
7 0.77
9 0.40
11 0.33
13 0.21
15 39 n015
15.
n
Even harmonics
2 1.084 0.43
6 0.30
8 40 n0 23
8.
n
table 8-22: harmonic current emission limits for class A, low-voltage apparatus
drawing less than 16 A per phase
-
8/3/2019 08 Harmonics
72/113
702
Industrial electrical network design guide T & D 6 883 427/AE
emission limits applied to industrial consumers
Precisely limiting the harmonic voltages generated by industrial users would penalise those
connected to a low short-circuit power network (highly impedant).
An equitable solution consists in permitting the level of disturbance generated to be
proportional to the customer's subscribed demand, as applied to each class of voltage ( LV,
MV, HV)
There is no international standard laying down the emission limits applying to industrial users.
case of France
In France, the EDF's new "Emeraude" contract gives the following tolerances applying to its
MV and HV networks for information only. At present, the limits shown are not obligatory
although customers are advised to conform since values more or less equivalent to them will
no doubt become statutory between now and 1998.
In the contract, the customer is obliged to take steps to limit the individual harmonic currents
introduced onto the EDF network. Such limits are calculated on a pro-rata basis according to
each customer's subscribed demand ( Ssubscribed ).
A limiting coefficient, kp , is applied to each harmonic current of order p . The customer must
limit harmonics to a level given by:
I kS
Up p
subscribed
C=
3
where UC is the contract voltage.
Table 8-23 gives the values for kp as a function of the harmonic order p .