08 Harmonics

download 08 Harmonics

of 113

Transcript of 08 Harmonics

  • 8/3/2019 08 Harmonics

    1/113

    631

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    8. Harmonics

  • 8/3/2019 08 Harmonics

    2/113

    632

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    8. HARMONICS

    The currents consumed by non-linear electrical equipment such as arc furnaces, lighting

    systems, convertors, rectifiers, etc., are non-sinusoidal, and flowing through the impedances of

    the power supply network they cause the sinusoidal supply voltage to become distorted. Thewaveform distortion is characterised by the appearance of voltages at harmonic frequencies.

    These harmonic voltages can disturb the operation of electrical devices on the network.

    This chapter deals with the different sources of harmonic disturbance, as well as the methods

    and techniques that can be applied to reduce it to an acceptable level.

    8.1. Basic concepts

    This paragraph gives the technical and theoretical fundamentals necessary for an investigation

    of harmonics.

    8.1.1. Fourier series periodic signal analysis

    The French mathematician Joseph Fourier showed that a periodic signal ( )s t , of period T, can

    be expressed as the sum of sinusoidal signal components plus a d.c. component:

    ( ) ( )s ta

    a p t b p t p

    p p= + +=

    01

    2cos sin

    where:

    =2

    T

    ( )aT

    s t dt T

    00

    2=

    ( ) ( )

    ( ) ( )

    aT

    s t p t dt

    bT

    s t p t dt

    pT

    p

    T

    =

    =

    2

    2

    0

    0

    cos

    sin

    where p is a whole number

    This analysis may also be expressed as follows:

    ( ) ( )s ta

    c p tp

    p p= + +=

    01

    2sin

    where: c a b p p p= +2 2

    pp

    p

    b

    a= arctan

  • 8/3/2019 08 Harmonics

    3/113

    633

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    8.1.2. Definitions

    A distorted voltage ( )v t of period T (T ms= 20 at f Hz= 50 ) can therefore be expressed in

    the following manner:

    ( ) ( )v t V V p t p

    p p= + +=

    01

    2 sin where

    =2

    T

    V0 : amplitude of the d.c. component, generally zero and taken to be so from now on .

    p : the initial phase ofVp , ( )t= 0 .

    Similarly, a distorted current ( )i t of period T can be expressed as:

    ( ) ( )i t I I p t p

    p p= + +=

    01

    2 sin

    I0 : amplitude of the d.c. component, generally zero and taken to be so from now on .

    p : the initial phase ofIp , ( )t= 0 .

    fundamental component, or fundamental

    V1 is the fundamental component of the signal ( )v t , that is to say the effective value of thesinusoid whose frequency is the same as that of the supply network.

    harmonic component, or harmonic

    For values of p 2 , Vp is the harmonic component of order p , of the signal ( )v t ; that is, the

    effective value of the sinusoidal voltage whose frequency is p times that of the supply

    network.

    order of harmonic

    The whole number equal to the ratio between the frequency of the harmonic and that of the

    fundamental.

    p is therefore the order of the harmonic.

    For example, V3 is the third harmonic voltage, or simply the 3rd harmonic.

  • 8/3/2019 08 Harmonics

    4/113

  • 8/3/2019 08 Harmonics

    5/113

    635

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    distortion factor according to IEC standard 1000-2-2

    - voltage distortion factor ( )V

    p

    p

    V

    V% = =

    100

    2

    2

    1

    - current distortion factor ( )I

    pp

    I

    I% =

    =

    100

    2

    2

    1

    The distortion factor as defined by the IEC standard represents the ratio between the r.m.s.

    value of the harmonics to that of the (undistorted) fundamental, and gives a good indication of

    the degree of harmonic disturbance on the network. This definition will be used throughout theremainder of the document.

    The DIN factor can be converted to the IEC factor as follows:

    1 11

    2 2D V V= +

    1 11

    2 2

    D I I

    = +

    As will be seen, IEC distortion factor values can be greater than 100 %.

    For low distortion factors the two definitions give nearly identical values. On the other hand, for

    high distortion factors the values turn out to be very different.

    For example, for I = 10 % we find DI = 9 95. %

    for I = 120% we find DI = 77 %

    individual harmonic rate

    The rate of the harmonic of order p is given by:

    ( )VV

    Vpp

    % = 1001

    ( )II

    Ipp

    % = 1001

  • 8/3/2019 08 Harmonics

    6/113

    636

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    power values for non-sinusoidal signals

    Definitions of power applying to sinusoidal signals are not appropriate to the treatment of non-

    sinusoidal signals.

    Consider a non-sinusoidal voltage and current whose Fourier series components are:

    ( ) ( )i t I p t pp

    p= +=

    1

    2 cos

    ( ) ( )v t V p t pp

    p= +=

    21

    cos

    By definition, active power is equal to mean power:

    ( ) ( )PT

    v t i t d t T

    = 1 0

    and after calculation, we obtain:

    ( ) P V I p pp

    p p= =

    1

    cos

    By definition, apparent power is equal to:

    S V Irms rms=

    The definition of reactive power applied to purely sinusoidal waveforms is wholly inappropriate

    to the treatment of non-sinusoidal signals.

    Certain documents do offer a definition, but since the reactive power of a non-sinusoidal signal

    has no practical relevance to an investigation of harmonics there is no need to refer to it in thisdocument.

  • 8/3/2019 08 Harmonics

    7/113

    637

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    power factor

    The power factor is defined as the ratio between active power and apparent power:

    F PSp

    =

    displacement factor(for the fundamental)

    The displacement factor is the ratio between active power and apparent power for the

    fundamental component:

    cos 1

    1

    1

    =P

    S

    It can also be defined as the cosine of the phase displacement between the fundamental

    voltage and current components : 1 = phase displacement ( )V I1 1, .

    Note: Taking the reference (in time) relative to U1 , we have 1 0= .

    harmonic factor

    This expresses the relationship between the power factor and the displacement factor:

    FF

    hp=

    cos1

    peak factor

    This is the ratio of peak current to r.m.s. current:

    F

    Ipk rms=

    interharmonics

    Interharmonics are sinusoidal components whose frequencies are not multiples of the

    fundamental frequency: 130 Hz, 170 Hz, 220 Hz, etc.

  • 8/3/2019 08 Harmonics

    8/113

    638

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    infraharmonics

    These are sinusoidal components whose frequencies are below that of the fundamental:

    10 Hz, 20 Hz...

    The presence of interharmonics or infraharmonics is due to periodic or random variation in the

    power consumed by certain electrical equipment. In this case, the signal is not periodic over

    time T (period of fundamental), a factor which explains the appearance of frequency

    components supplementary to those expressed by Fourier analysis.

    Common sources of the phenomena include:

    - arc furnaces- cycloconverters- speed variators.

    frequency spectrum

    A graphical representation of harmonics showing their individual amplitudes and orders.

    Usually, the level of each harmonic is represented by its value as a percentage of the

    fundamental (see fig. 8-1).

    1 3 5 7

    100

    n

    I1(%)

    Ip

    Figure 8-1: frequency spectrum of a non-sinusoidal current

  • 8/3/2019 08 Harmonics

    9/113

    639

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    linear and non-linear loads

    A load is said to be linear if its impedance is constant: the current input is therefore sinusoidal

    when the applied voltage is sinusoidal (see fig. 8-2).

    A load is said to be non-linear if its impedance varies over a given period: the current input is

    therefore non-sinusoidal for a sinusoidal supply voltage (see fig. 8-3).

    t

    v t

    i t

    Figure 8-2: linear load

    t

    v t

    i t

    Figure 8-3: non-linear load

  • 8/3/2019 08 Harmonics

    10/113

    640

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    8.1.3. The main sources of harmonics

    non-linear loads

    In this section we shall determine figures for the individual harmonic currents generated by

    common non-linear loads.

    The values given are approximate. They vary notably in relation to the upstream impedance

    (generally, when the upstream impedance increases, the harmonic current levels decrease).

    six-phase rectifier bridge (see fig. 8-4)

    This is a device to convert 3-phase alternating current into a single-phase direct current.

    T

    t

    t

    t

    T

    3T

    6

    i t

    i ta

    i tb

    i tc

    i tc

    i tb

    i ta

    Figure 8-4: six-phase rectifier bridge current waveforms.

    Theoretically, each of the currents I I I a b c, , has a rectangular waveform.

    The Fourier series analysis of the rectangular signal gives us the following harmonic currents

    of order p k= 6 1 ( that is: 5, 7, 11, 13, 17, 19...) and of amplitude II

    pp= 1

    I1 : amplitude of fundamental .

  • 8/3/2019 08 Harmonics

    11/113

    641

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    In reality, the current waveforms are not perfectly rectangular, with the result that the actual

    values of the harmonic current are less than their theoretical values. An empirical law exists

    (see IEC 146-1-2 3.6.2.1) enabling a calculation to be made of the approximate values of

    harmonic currents 5 to 31:

    II

    pp

    p =

    11

    5.2

    for 5 31 p

    From it we can obtain the individual values of harmonic current as a percentage of the

    fundamental (see table 8-1).

    I1 I5 I7 I11 I13 I17 I19 I23 I25 I29 I31

    100 % 18.9 % 11.0 % 5.9 % 4.8 % 3.4 % 3 % 2.3 % 2.1 % 1.8 % 1.6 %

    Table 8-1: values of the harmonic currents produced by a rectifier bridge

    The formula yields approximate values, especially when high thyristor delay angles, , are

    utilised. Moreover, the inductance of the d.c. circuit influences the harmonic content. A low

    value of inductance is conducive to high d.c. ripple, thereby increasing the 5th. harmonic

    (multiplied by 1.3 or greater ), as well as, but to a lesser degree, the 11th, 17th... ( )6 1k . The

    levels of harmonics 7, 13... ( )6 1k+ are usually lower. IEC standard 146-1-2, paragraphs 3.6.4

    and 3.6.5 gives a (very complicated) method of calculating the precise figure for each

    harmonic together with its phase angle.

    Generally speaking, a calculation of the precise theoretical value of each harmonic current is

    not essential for an investigation, indeed whenever possible, on-site measurement is the

    preferred method of obtaining the precise values.

  • 8/3/2019 08 Harmonics

    12/113

    642

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    computer switchmode power supplies (see fig. 8-5)

    t

    CR

    i t

    v t

    i t

    v t

    Figure 8-5: switchmode power supplies for computers, current waveform

    The harmonic currents produced by a switchmode power supply are more or less high in

    relation to the load and the upstream network impedance.

    A spread of values, in line with the two assumptions of high and low harmonic content, is given

    below (see table 8-2).

    I1 I3 I5 I7 I9 I11

    high 100 % 130 % 70 % 50 % 30 % 10 %

    low 100 % 65 % 35 % 25 % 15 % 5 %

    Table 8-2: values of harmonic currents for a computer switchmode power supply

    lighting loads (fluorescent tubes, discharge lamps)

    The values of harmonic currents supplied by fluorescent tubes and magnetic ballast discharge

    lamps are given in table 8-3.

    Electronic ballast discharge lamps supply harmonic currents having a value comparable to that

    of a computer switchmode power supply (see table 8-2: high).

    I1 I3 I5 I7 I9 I11 I13 I15

    100 % 35 % 27 % 10 % 2.5 % 3.5 % 1.5 % 1.5 %

    Table 8-3: fluorescent tube and magnetic ballast discharge lamp current harmonic values

  • 8/3/2019 08 Harmonics

    13/113

    643

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    uninterruptible power supplies (UPS)

    For example, the GALAXY model produces harmonic currents as shown in table 8-4.

    I1 I5 I7 I11 I13 I17 I19

    100 % 33 % 2.5 % 6.1 % 2.4 % 2.5 % 1.6 %

    Table 8-4: values of harmonic currents for the GALAXY model of UPS

    Note: the newer generation of "sine wave sampling" inverters do not generate harmonics(for example, the 0 to 4 kVA Pulsar models).

    speed variators

    Speed variators are used to vary the speed of an asynchronous motor.

    The harmonic currents they generate depend to a large extent on:

    - the ratio between the network short-circuit powerSsc and the apparent power of the variatorSn .

    - The variator load S (apparent power of the motor) as a percentage of the apparent powerof the variatorSn .

    Measurement results obtained are summarised in tables 8-5, 8-6, 8-7.

    S S sc n= 100% I1 I5 I7 I11 I13 I17 I19 I23 I25

    S S sc n= 250 100 % 85 % 72 % 41 % 27 % 8 % 5 % 6 % 5 %

    S S sc n= 100 100 % 73 % 52 % 16 % 7 % 7 % 5 % 3 % 3 %

    S S sc n= 50 100 % 63 % 35 % 6.2 % 1.3 % / / / /

    Table 8-5: speed variator with a load of 100% of its apparent power rating

  • 8/3/2019 08 Harmonics

    14/113

    644

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    S Sn= 50 % I1 I5 I7 I11 I13 I17 I19 I23 I25

    S S sc n= 250 100 % 90.5 % 82 % 59.5 % 48 % 25.5 % 16.5 % 6 % 4.5 %

    S S sc n= 100 100 % 82% 66.5 % 33 % 19.5 % 7 % 6.5 % 5 % 3.5 %

    S S sc n= 50 100 % 74.3 % 53.9 % 18.3 % 7.9 % 1.9 % 2.5 % / /

    Table 8-6: speed variator with a load of 50% of its apparent power rating

    S Sn= 25 % I1 I5 I7 I11 I13 I17 I19 I23 I25

    S S sc n= 250 100 % 94 % 89 % 74 % 66 % 47 % 38 % 22 % 15 %

    S S sc n= 100 100 % 89 % 78 % 53 % 40 % 17 % 9 % 5 % 6 %

    S S sc n= 50 100 % 84 % 68 % 38 % 24 % 6.1 % 2.1 % / /

    Table 8-7: speed variator with a load of 25% of its apparent power rating

    arc furnace

    Arc furnaces as used in iron and steel making can either be a.c. or d.c. supplied.

    the a.c. supplied arc furnace (see fig. 8-6)

    HV

    transformer

    cable

    furnace

    Figure 8-6: case of the a.c. supplied arc furnace

  • 8/3/2019 08 Harmonics

    15/113

    645

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    The arc produced is non-linear, dissymetric and unstable. It gives rise to odd and even

    harmonics, as well as to a continuous spectrum of currents (currents at all frequencies). The

    levels of harmonics produced together with the continuous spectrum values will depend on the

    type of furnace, its power, the duration of the process under consideration (casting, refining),

    etc.

    Therefore, the precise levels of harmonics can only be determined by measurement.

    Figure 8-7 is an example.

    1 3 5 7

    100

    10

    1

    0.1

    9

    4

    3.2

    1.3

    0.5

    100

    order

    continuous spectrum

    I1(%)

    Ip

    Figure 8-7: current spectrum of an a.c. supplied arc furnace

    the d.c. supplied arc furnace (see fig. 8-8)

    HV

    transformer

    cable

    furnace

    cable

    rectifier

    Figure 8-8: case of the d.c. supplied arc furnace

  • 8/3/2019 08 Harmonics

    16/113

    646

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    The d.c. supply is derived from a rectifier, the arc produced being more stable than for the a.c.

    supplied furnace.

    The current consumed comprises:

    - a spectrum of harmonic currents similar to that of a rectifier

    - a continuous spectrum with a lower overall value than for the a.c. supplied furnace.

    Figure 8-9 gives the harmonic current spectrum for a 144 MVA d.c. driven arc, fed from a dual

    bridge rectifier.

    The use of the latter explains the high values of 11th and 13th harmonics (see 8-4-6).

    order

    I1(%)

    Ip

    3.8%

    4.3% 2.5%

    3.4%

    1.5%1.2%

    2% 1.9%

    3.4%

    1.9% 1.9%

    9.1%

    7.7%

    3.2%3.5% 3.5%

    continuous spectrum

    Figure 8-9: harmonic current spectrum of a d.c. supplied arc furnace fed from a dual bridge rectifier

    magnetic circuit saturation in machines (transformers, motors, ...)

    Electrical machines are designed to work close to their magnetic saturation limits when

    operating under nominal supply voltage conditions.

    Should the supply voltage become abnormally high (greater than 1.1 times its nominal value),

    magnetic circuits will saturate and currents will become distorted. Henceforth, the machine

    becomes a source of odd order harmonic currents.

  • 8/3/2019 08 Harmonics

    17/113

    647

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    voltage sources

    Voltage sources (utility, alternator, UPS) possess pre-existing harmonic voltages which

    manifest even when the equipment is connected to perfectly linear loads.

    utilities

    Utilities possess pre-existing voltage harmonics due to other consumers (industrial and

    domestic) who create voltage harmonics on the distribution and transmission network.

    Measurements taken on the French electricity authority EDF's MV distribution network have

    given the results provided in table 8-8:

    V1 V5 V7

    high 100 % 9 % 3 %

    medium 100 % 6 % 2 %

    low 100 % 3 % 1 %

    Table 8-8: harmonic voltages pre-existing on the French electricity authority EDF's M.V. network

    Note: the 3rd harmonic currents, and multiples of them, which exist at high levels on the industrialand domestic low-voltage network, are eliminated by the delta-star connection of MV/LVtransformers. This is why 3rd harmonic voltages, and multiples of them, do not appear on theM.V. network.

    Uninterruptible power supplies (UPS)

    The sinusoidal voltage supplied by an inverter will not be perfect even for a linear load.

    A UPS will therefore possess pre-existing harmonic voltages (see table 8-9).

    Hardware model EPS 5000 EPS 2000 ALPES 1000 GALAXY

    Overall distortion factor 5 % 4 % 5 % 2 %

    Table 8-9: pre-existing harmonic voltages of UPS

  • 8/3/2019 08 Harmonics

    18/113

    648

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    alternators

    The sinusoidal voltage supplied by an alternator will not be perfect even for a linear load.

    An alternator therefore possesses pre-existing harmonic voltages. Taking the example ofLeroy-Somer 10 kVA to 5000 kVA alternators, the voltage distortion factor is around the 4 %

    mark, with 2 to 3 % of 5th harmonics and some 3rd harmonics.

    V 4 %

    I

    Ito5

    1

    2 3= %

    Note: the more unbalanced the load, the more 3rd harmonic an alternator will generate.

  • 8/3/2019 08 Harmonics

    19/113

    649

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    8.1.4. Method of determining harmonic currents and voltages on a supply network

    non-linear loads model

    For calculation purposes, non-linear loads are considered to be harmonic current generators

    (for harmonics p 2 ). They are modelled as currents injected into the network (see fig. 8-10).

    Note: this model is valid for a discrete spectrum. In the case of a continuous spectrum (arc furnace) amore complex model must be devised. Such models are not dealt with in this document.

    source

    Vp Ip

    Z

    Ip : harmonic current of orderp

    ( )Z : impedance of network at angular frequency = =p 0 0( angular frequency at 50 Hz or 60 Hz).

    Figure 8-10: model for current harmonics generated by non-linear loads

    Each non-linear load will thus be modelled by its impedance at 50 Hz (or 60 Hz) and by current

    sources corresponding to the harmonic currents generated by the load.

    A harmonic current Ip , flowing across the network to the source through the impedance

    ( )Z , gives rise to a harmonic voltage Vp , such that:

    ( )V Z p I p p= 0

    The voltage distortion factor resulting from a spectrum of harmonic currents I I I 2 3 4, , ... is then:

    ( )

    Vp

    p Z p I

    V=

    =

    2

    02 2

    1

  • 8/3/2019 08 Harmonics

    20/113

    650

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    Where a network comprises inductances and capacitances the impedance spectrum ( )Z

    may vary significantly, as the curve below shows (see fig. 8-11).

    0 2 0 4 0 6 0 8 0 p 0

    Z( )

    Figure 8-11: impedance spectrum

    Harmonic voltages created on the network disturb the operation of electrical equipment. One

    element of any investigation into harmonic content must therefore be to limit the values of

    ( )Z for values ofcorresponding to the harmonic currents with the highest values.

  • 8/3/2019 08 Harmonics

    21/113

    651

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    modelling of sources polluted by pre-existing harmonic voltages

    For the sake of calculation, pre-existing harmonic voltages are considered to be harmonic

    voltage sources (see fig. 8-12).

    Z

    Vp load

    Vp : p order of harmonic voltage

    ( )Z : impedance of the supply network at angular frequency = =p 0 0( angular frequency at 50 Hz).

    Figure 8-12: pre-existing harmonic voltage model

    A voltage source polluted by pre-existing harmonic voltages will therefore be modelled by its

    nominal value at 50 Hz plus harmonic voltage sources.

    impedance of network elements

    utility

    The impedance of the utility is generally taken to be a pure reactance. Nevertheless, the

    capacitor banks found at HV/MV substations may provoke resonances at undesired

    frequencies.

    This should be taken into consideration during an investigation of harmonics where the

    installation comprises non-linear loads drawing large amounts of power (for example, an arc

    furnace).

    cables, power lines and transformers

    These are considered as resistances of constant value and reactances proportional to the

    order of the harmonic:

    ( ) Z p R jpX 0 = +

    p : order of the harmonic

    X : reactance at 50 Hz.

  • 8/3/2019 08 Harmonics

    22/113

    652

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    capacitor banks

    These are treated as capacitors whose impedance is inversely proportional to the order of the

    harmonic:

    ( )Z pCp

    00

    1=

    alternator

    It will be explained further on why the reactance of an alternator is not proportional to the order

    of the harmonic. An alternator is considered to have negligible resistance.

    at the supply network frequency

    The field created by the three stator currents rotates at the speed of the rotor and is therefore

    fixed in relation to it.

    When the stator current increases, the voltage decreases. The impedance of the alternator is

    equal to the synchronous reactance Xd which is of the order of 200 to 300 %.

    at frequencies other than that of the network

    The field created by the three stator currents does not rotate at the speed of the rotor and is

    not therefore fixed in relation to it.

    This rotating field causes harmonic currents to flow in the rotor, thereby producing a drop in

    voltage.

    For harmonic currents of order 3 1k , the alternator's impedance is a function of the sub-

    transient impedance:

    ( ) X k X k d3 1 3 1 = "

    Xd"

    is of the order of 10 to 20 %.

    For 3 k order harmonics, if the neutral is not distributed the impedance is infinite. Indeed, 3rd

    order harmonics, and multiples of the 3rd, flowing in the neutral are in phase. However, if the

    neutral is not distributed they cannot flow, with the result that the impedance is considered to

    be infinite.

  • 8/3/2019 08 Harmonics

    23/113

    653

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    If the neutral is distributed, 3rd order harmonic currents and multiples of them flow in it, the

    alternator impedance then being a function of the zero-sequence impedance. Indeed, the field

    created by harmonics which are multiples of 3 does not rotate, as in a zero-sequence current

    system.

    X k X k3 03=

    X0 is roughly equal to half Xd"

    , or of the order of 5 to 10 %

    asynchronous motor

    The reactance of an asynchronous motor is not proportional to the order of the harmonic. Its

    resistance is considered negligible.

    At the supply network frequency the motors impedance ZM depends on the load.

    Indeed, ZV

    IMn=

    Vn : single-phase voltage

    I : current consumed by the motor, which depends on its load.

    For harmonic voltages of order 3 k, the impedance is infinite because generally the neutral of

    the motor is not distributed.

    For 3 1k order harmonics, the motor's impedance is a function of the locked rotor impedance

    (or starting impedance if there is no starting current limiting system):

    ( )X kI

    IXk

    n

    bn3 1 3 1 =

    ( )X kV

    Ikn

    lr

    3 1 3 1 =

    Xn : motor impedance at rated load, XV

    Inn

    n=

    Ilr : locked rotor current (or start up current if there is no starting current limiting system).

  • 8/3/2019 08 Harmonics

    24/113

    654

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    inverters

    The output impedance is vastly different according to whether the machine is of the older type

    (EPS 5000) or one of the newer generation (GALAXY or COMET).

    older type inverters (EPS 5000)

    The output impedance is equal to impedance of the output filter. The equivalent circuit as seen

    from the output is that of figure 8-13.

    V

    Zs ( )

    Figure 8-13: older type inverter output impedance

    Output impedance is therefore frequency dependant (see fig. 8-14).

    At low frequencies the output impedance is close to L .

    At high frequencies the output impedance is close to1

    C.

    At the resonance frequency fL C

    r =1

    2 , the filter's impedance is very high, having an order

    of magnitude equal to the nominal load impedance, that is ( )Z fout r 2 100 % .

    In practice, the resonance frequency is chosen to be far from that of the most common

    harmonic currents.

    For example, 210 Hz might be selected since 4th order harmonics are virtually non-existent.

  • 8/3/2019 08 Harmonics

    25/113

    655

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    newer generation inverters with phase-neutral voltage regulation (GALAXY, COMET)

    This type of equipment uses a very high switching frequency (several kHz) and an extremely

    fast voltage regulator, enabling output voltage quality to be maintained even with a high

    current distortion factor. As a consequence, the output impedance is very low and virtuallyconstant for all orders of harmonic (see fig. 8-14).

    150

    100

    50

    0 50 250 500 750

    new type of inverter(GALAXY, COMET)

    old type of inverter (EPS 5000)

    ratio of the output impedance

    to the nominal load impedanceZn

    %Zs

    f Hz( )

    Figure 8-14: inverter output impedance

  • 8/3/2019 08 Harmonics

    26/113

    656

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    particular case of 3rd harmonics and multiples of the 3rd

    3rd harmonic currents are in phase, with a current equal to their sum flowing in the neutral

    when distributed (see fig. 8-15). If the neutral is not distributed, 3rd harmonics and multiples of

    them cannot flow, and thus cannot exist.

    I3

    I3

    I3

    3 3I neutral

    Figure 8-15: 3rd harmonic currents, and multiples of them, flowing in the neutral

    why 3rd harmonics, and multiples of the 3rd, are in phase

    Take 3 equal currents I ta ( ) , I tb ( ) and I tc ( ) with phase displacements of 1/3 of a period:

    ( )

    ( )

    ( )

    i t t

    i t t T

    i t t T

    a

    b

    c

    =

    = +

    = +

    cos

    cos

    cos

    32

    3

    where T=2

    period of signal

    Note !: the currents are phase shifted in time and must therefore be expressed as above.

    The 3rd harmonics of these currents are obtained by replacing by 3 :

    ( )i t t a3 3 3= cos

    ( ) ( )i t t T t t b3 3 3 33 3 2 3= + = + =cos ( ) cos cos

    ( ) ( )i t t T t t c3 3 3 33 2 3 4 3= + = + =cos ( ) cos cos

    giving i t i t i t t a b c3 3 3 33 3( ) ( ) ( ) cos+ + =

  • 8/3/2019 08 Harmonics

    27/113

    657

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    The in-phase relationship can also be shown graphically (see fig. 8-16). The same is true for

    all harmonics that are multiples of the 3rd.

    I3

    I2

    I1

    t

    t

    t

    3rd harmonic

    t

    Ineutral

    3rd harmonic

    3rd harmonic

    Figure 8-16: the 3rd harmonics of a 3-phase system are in phase

  • 8/3/2019 08 Harmonics

    28/113

    658

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    superposition theorem

    Consider the case of a network with the following characteristics:

    - a voltage source with pre-existing harmonics V V V2 3 4, , , ...

    - a transformer whose impedance is R LT T, , feeding a busbar

    - various non-linear loads grouped together to form an equivalent load generating the

    harmonic currents I I I2 3 4, , , ...

    The loads are supplied from the busbar through an impedance R L1 1,

    - various linear loads grouped together to form an equivalent load fed from the busbar

    through an impedance R L2 2,

    - the equivalent capacitorC representing the reactive energy compensating capacitors.

    Each voltage and current source is considered to act in independently on the network.

    The theorem of superposition states: for a linear network, the current (or voltage) generated in

    a branch by several independent sources acting simultaneously, is equal to the currents (or

    voltages) produced in the same branch by the different sources acting in isolation.

    Figure 8-17 illustrates the application of this theorem.

  • 8/3/2019 08 Harmonics

    29/113

    659

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    R LT T,

    V source

    non-linearloads

    linearloads

    CR1 R2

    L2L1

    equivalent

    non-linear

    loads

    linear

    loads

    V1

    oC

    1

    R LT T o,

    R1 R2L o1 L o2 +

    non-linearloads

    linearloads

    Vp

    R pLT T o,

    pL o1

    R1 R2pL o2

    1

    pC o +

    linearloadsIp

    R1pL o1

    R2pL o2

    1

    pC o

    R pLT T o,

    network at 50 Hz + p harmonic networks of orders

    1 2, ,..., p supplied by voltagesources V V Vp1 2, ,...,

    + p harmonic networks of orders

    1 2, ,..., p supplied by currentsources I I Ip1 2, ,... ,

    Figure 8-17: superposition theorem as applied to harmonics

  • 8/3/2019 08 Harmonics

    30/113

    660

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    addition of equal order harmonics arising from different non-linear loads

    The harmonic currents of the same order generated by several non-linear loads are not

    necessarily in phase. The resultant current is obtained by vector addition (see fig. 8-18).

    r

    Ip,1

    r

    Ip, 2

    r

    Ip sum,

    Figure 8-18: vector addition of two 2 harmonic currents of the same order

    Take the two extreme situations.

    their phase relationship is perfectly random

    The modulus of the sum of two p order harmonics is, on average:

    I p mean,2

    ( ) ( )[ ]= + +12 1 22

    22

    0

    2

    I I I d p p p, , ,cos sin

    ( )= + +12 202

    12

    22

    1 2

    I I I I d p p p p, , , , cos

    = +I Ip p, ,12 22

    I p mean, = +I Ip p, ,12

    22

    By extension, for a number k of non-linear loads supplying harmonics of order p , the

    modulus of their sum is, on average: I I p sum p

    k

    , ,= 2

  • 8/3/2019 08 Harmonics

    31/113

    661

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    the harmonics are perfectly in phase

    In this case, the harmonics add together algebraically, giving :

    I I p sum p ii

    k

    , ,==

    1

    Practical instances fall somewhere between the two extremes, with phase correlation

    depending to a greater or lesser degree on: diversity of harmonic sources, transformer vector

    group, etc. Consequently, an empirical law has been defined to estimate the modulus of the

    sum of equal order harmonics, expressed by the following relationship:

    ( )I I p sum p ik

    , ,

    /

    =

    1

    where 1 2

    = 1 : the harmonics are perfectly in phase= 2 : harmonic phases are perfectly random.

    It can be seen that I p sum,

    decreases as increases,

    I p sum,

    r eqZ

    C,

    1.

  • 8/3/2019 08 Harmonics

    40/113

    Publication, traduction, et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos servicesThe publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    670

    Figure 8-23 illustrates the variations in Zeq as a function of .

    N

    M

    K

    R

    r

    Zeq

    Figure 8-23: variations in Zeq as a function of angular frequency

    n definition of amplification factor FA

    FA is the ratio of the network impedances with and without capacitors, at the resonant frequency.

    FKN

    KMA= (see fig. 8-22)

    i.e. FR

    LA sc r =

    hence

    F R

    C

    LA sc=

    now Q C Un= 02

    and LU

    Sscn

    sc0

    2

    =

    henceF

    Q S

    PAsc=

  • 8/3/2019 08 Harmonics

    41/113

    Publication, traduction, et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos servicesThe publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    671

    definition of the order of resonance pr

    The order of resonance is defined as the ratio pr of the angular frequency of resonance to the angular

    frequency of the network:

    prr=

    0

    now rccL C

    = 1

    hencep

    S

    Qrcc=

    determining the network behaviour in the presence of harmonic current the order of

    which is equal to pr

    For = =r eqZ R,

    hence V R Ir r=

    V F L I r A cc r r =

    Vr : harmonic voltage of orderr appearing on the busbar

    The harmonic voltage Vr on the busbar is therefore multiplied by FA compared to the case

    where there are no capacitors (V L Ir cc r r = ).

    Let IC r, be the harmonic current of order r flowing in the capacitors,

    I C V C L C

    R IC r r r cc

    r, = =1

    I F I C r A r , =

    Let IL r, be the harmonic current of order r flowing in the upstream network,

    IV

    L

    Lcc C

    LccR IL r

    r

    cc rr, = =

    I F I L r A r , =

  • 8/3/2019 08 Harmonics

    42/113

    672

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    The currents and voltages at resonance are those shown in figure 8-24.

    R

    Ir

    IrC

    I F I L, r A r I F IC, r A r

    V F L I r A sc r r Lsc

    Figure 8-24: currents and voltages appearing at resonance

    The following paragraphs will demonstrate that the value of FA could be very high on an

    industrial network (in general anything from 2 to 5, and as much as 20).

    As the diagram shows, harmonic currents flowing in the capacitors and upstream network are

    each amplified by a factor ofFA .

    Therefore, compared to the case where there are no capacitors, the harmonic voltage of order

    r produced on the busbar is amplified by a factor of FA . Compensating capacitors will then

    more than likely pose significant problems when large, non-linear loads are connected to the

    network.

    example

    Let us consider a 20 kV / 400 V transformer of S kVAT = 1250 , and Usc = 5 5. % , supplying :

    - day and night, a bridge rectifier whose powerS kVAB = 500 and power factorFp B, .= 0 8 .

    - a linear load whose power consumption S kVAld = 600 during the daytime period, andS kVAln = 100 during the night-time period, with a power factorFp l, .= 0 9 .

    The upstream network short-circuit powerS MVAup = 130 .

    The requirement is to compensate the reactive energy of the fundamental during the day so as

    to obtain tan .1 0 4= , where tan 11

    1

    =P

    Q.

    P1 : active power of the fundamental component

    Q1 : reactive power of the fundamental component.

  • 8/3/2019 08 Harmonics

    43/113

    673

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    determining the reactive power of the capacitors to be installed

    Using the manufacturers' assumption (see 8.1.5), we can calculate the fundamental

    component values for the bridge rectifier:

    P P F S B B p B B1 0 8 500 400, , .= = = =

    From the example of paragraph 8.1.5, Q kVAB1 277, = .

    The daytime period linear load is S kVAld = 600 where Fp l, .= 0 9 .

    Calculating the active and reactive powers of a linear load is straightforward:

    P S F kW ld ld p l = =, 540

    Q S P k ld ld ld = =2 2

    262 var

    We can also calculate the installation's tan 1 value:

    tan .,

    ,

    11

    1

    277 262

    400 5400 57=

    +

    +=

    ++

    =Q Q

    P P

    B ld

    B ld

    To compensate the reactive energy of the fundamental, the necessary capacitor bank power

    rating is thus given by:

    ( ) ( )Q P P k B ld = + = =1 1 0 940 0 17 159 8, tan .4 . . va

    The choice would be to install a standard value capacitor bank with a rated power value ofQ kC = 160 var.

  • 8/3/2019 08 Harmonics

    44/113

    674

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    calculation of the harmonic voltages and distortion factor in the absence of capacitors

    Firstly, the equivalent impedance for the transformer and upstream network is calculated.

    Using the approximation that the transformer and upstream network are composed of purereactance (see 4.2.1.4 - Protection Guide), we have:

    XU

    Supn

    up=

    2

    and XU

    SUT

    n

    Tsc=

    2

    hence ( )X UU

    S Sm sc n

    sc

    T up= +

    =

    +

    =2 2

    3 6

    1400

    0055

    1250 10

    1

    130 108 27

    ..

    X Xup T, : are the reactance of the upstream network and the transformer respectivelyXsc : is the equivalent reactance of the transformer and upstream network (short-circuit impedance).

    We can now calculate the harmonic voltages (see table 8-12) and the distortion factor.

    Order of harmonic 5 7 11 13 17 19 23 25 29 31

    ( )Ip % 18.9 11.0 5.9 4.8 3.4 3 2.3 2.1 1.8 1.6

    ( )I Ap

    132.7 77.3 41.4 33.7 23.9 21.1 16.2 14.7 12.6 11.2

    ( )V pX I V p sc p= 5.49 4.47 3.77 3.62 3.36 3.32 3.08 3.04 3.02 2.87

    ( )V

    Vp

    1

    %2.39 1.95 1.64 1.58 1.46 1.44 1.34 1.32 1.31 1.25

    Table 8-12: harmonic voltages in the absence of capacitors

    From here, the voltage distortion factor is:

    V = 5 07. %

    This is an acceptable value, both for the operation of the bridge rectifier and for the rest of the

    installation (see 8.2).

  • 8/3/2019 08 Harmonics

    45/113

    675

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    calculation of the harmonic voltages and distortion factor for the daytime period with

    the compensating capacitors in service

    Calculating the order of resonance:

    pS

    Qrsc=

    where SU

    XMVAsc

    n

    sc= =

    2

    19 35.

    Q k= 160 var

    hence pr

    = 1100.

    The order of resonance is the same as the order of a high value harmonic current generated

    by the bridge rectifier.

    Calculating the amplification factor:

    FQ S

    PAsc=

    P is the active power of the linear loads, giving P P kW

    ld= =540

    hence FA = 3 26.

    Calculating the equivalent impedance Zeq :

    1 1 10

    0Z Rj p C

    p Leq ld sc= +

    Z

    RpC

    p L

    eq

    ld sc

    =+

    1

    1 12 0

    0

    where RU

    Pmld

    n

    ld= =

    2

    2963.

    CQ

    Un0 2 100= = .

    L X m sc sc

    0

    8 27= = .

  • 8/3/2019 08 Harmonics

    46/113

    676

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    Figure 8-25 shows the curve of the Zeq ( ) impedance spectrum.

    We can go on to calculate the harmonic voltages (see table 8-13)

    Order of harmonic 5 7 11 13 17 19 23 25 29 31

    ( )I Ap 132.7 77.3 41.4 33.7 23.9 21.1 16.2 14.7 12.6 11.2

    Z meq ( ) 51.3 92.5 296.3 199.7 95.7 76.5 55.4 48.9 39.9 36.6

    ( )V Z I V p eq p= 6.81 7.15 12.27 6.73 2.29 1.61 0.90 0.72 0.50 0.41

    ( )V

    Vp

    1

    %2.96 3.11 5.33 2.93 0.99 0.70 0.39 0.31 0.22 0.18

    ( )I AC p, 34.1 50.1 135 87.5 38.9 30.6 20.7 18.0 14.5 12.7

    Table 8-13: harmonic voltages during the daytime period with capacitors in service

    From here, the voltage distortion factor is :

    V = 7 5. %

    The harmonic currents flowing in the capacitor bank are obtained from:

    I pC V C p p, = 0 (see table 8-14).

    The r.m.s. current in the capacitor bank is :

    I IC rms C , ,=

    2

    IC, 1 is the fundamental current in the capacitors, that is the nominal current, which gives

    I I C V AC C n n, ,1 0

    230= = = .

    hence I AC rms, .= 2930

    and I

    I

    C rms

    C n

    ,

    ,

    .= 1 27

    Next, we can calculate Vrms = 230 64. .

  • 8/3/2019 08 Harmonics

    47/113

    677

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    It can be seen that despite the high values of some of the harmonic currents, the r.m.s. voltage

    is virtually identical to the nominal voltage. The manufacturers' assumption is thus justified:

    U Urms = 1 .

    The r.m.s. current in the capacitor bank is close to the limit of 1.3 IC n, , there is thus a risk of

    the capacitors overheating.

    The voltage distortion factor is only just acceptable, and certain loads may well be disturbed

    (see 8.2). The bridge rectifier will be able to operate normally (see 8.2).

    calculation of harmonic voltages and distortion factor for the night-time period with

    the compensating capacitors in service

    Calculating the amplification factor:

    FQ S

    PAsc=

    P is the active power of the linear loads during the night-time period, giving P P S kW = = =ln ln 0 9 90.

    hence FA =160 19 350

    90

    FA = 19 6.

    Z

    RpC

    p L

    eq

    sc

    =

    +

    1

    1 12 0

    0ln

    where RU

    Pmn

    ln ln= =

    2

    1778.

    CQ

    Un0 2 1 00= = .

    L X m sc sc0 8 27= = .

    Figure 8-25 shows the curve of the Zeq ( ) impedance spectrum

  • 8/3/2019 08 Harmonics

    48/113

    678

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    We can go on to calculate the harmonic voltages (see table 8-14)

    Order of harmonic 5 7 11 13 17 19 23 25 29 31

    ( )I Ap 132.7 77.3 41.4 33.7 23.9 21.1 16.2 14.7 12.6 11.2

    Z meq ( ) 52.1 97.2 1778 267.3 101.1 79.1 56.3 49.6 40.3 36.9

    ( )V Z I V p eq p= 6.91 7.51 73.61 9.01 2.41 1.67 0.91 0.73 0.51 0.41

    ( )V

    Vp

    1

    %3.01 3.27 32.0 3.92 1.05 0.73 0.40 0.32 0.22 0.18

    ( )I AC p, 34.6 52.6 809.7 117.1 41.0 31.7 20.9 18.3 14.8 12.7

    Table 8-14: harmonic voltages during night-time period with capacitors in service

    From here, the voltage distortion factor is :

    V = 32 6. %

    This figure is unacceptable to the majority of equipment, which will not operate properly and

    may be damaged as a result (see 8.2). The bridge rectifier itself will malfunction, the

    distortion factor being well above the permitted threshold (see 8.2).

    The harmonic currents flowing in the capacitor bank are given by:

    I pC V C p p, = 0 (see table 8-15).

    The r.m.s. current in the capacitor bank is :

    I IC rms C , ,=

    2

    IC, 1 is the fundamental current in the capacitors, that is, the nominal current. We have then I I C V AC C n n, ,1 0 230= = = .

    hence I AC rms, .4= 854

    and I

    I

    C rms

    C n

    ,

    ,

    .= 3 71

  • 8/3/2019 08 Harmonics

    49/113

    679

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    The r.m.s. current in the capacitor bank is much greater than the permitted maximum, with the

    result that the protection system will disconnect them.

    Next, we can calculate the r.m.s. voltage: V Vrms = 242 .

    Being 5 % above nominal voltage, this is an acceptable value in terms of the capacitors.

    conclusion

    The installation of reactive energy compensating capacitors increases the voltage distortion

    factor, especially when harmonic currents exist close to the resonance frequency. When the

    power consumed by any linear loads is reduced, voltage distortion increases resulting in higher

    levels of disturbance.

    For large, non-linear loads, the installation of capacitors should go hand in hand with an

    investigation of the harmonics. This will enable calculations to be made for the equipment

    necessary (see 8.4) to overcome the problem cited above.

    1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31

    1700

    1500

    1300

    1100

    900

    700

    500

    400

    300

    200

    100

    with capacitors, night-time

    with capacitors, day-time

    frequency

    (p x 50 Hz)

    without capacitors

    Z meq

    Figure 8-25: the different impedance spectrum curves

  • 8/3/2019 08 Harmonics

    50/113

    680

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    8.2. Effects of harmonics on electrical apparatus, and working guidelines

    Harmonics may well cause electrical equipment to malfunction, or to overheat, or to produce

    mechanical vibrations which could lead to irreparable damage.

    capacitors

    Capacitors should conform to the IEC standard 871-1 for M.V. and to IEC standard 831-1 for

    L.V. These standards stipulate:

    - the ability to permanently pass a current of 1.3 times rated value, corresponding to a current

    distortion factor ofI = 83 % . In fact, I

    pp

    pp rms

    I I I I2

    2

    2

    2

    12 2

    1

    2

    2

    21= =

    +

    = +=

    =

    I1 : rated current of the bank

    hence ( )I = 1 3 12

    .

    - the ability to withstand 1.1 times rated voltage 12 h / day for M.V. use, and 8 h / day in a

    L.V. application, allowing their operating voltage to be 10% above rated value.

    working guidelines

    The above specifications are not cumulative, therefore the following condition should be

    observed:

    3 1 3 I V Qrms rms n .

    Qn : nominal or rated power of the bank.

    Should this condition not be met, techniques to limit harmonics could be implemented

    (see 8.4). Otherwise, one approach might be to install, if this is adequate, over-insulatedcapacitors (class H) able to permanently pass 1.5 times their rated current, a figurecorresponding to a current distortion factor of I = 112% .

  • 8/3/2019 08 Harmonics

    51/113

    681

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    example

    A capacitor bank of standard value 200 400k Vvar, is supplied from a busbar whose voltage

    characteristics are:

    - daytime period VV

    d1400

    3=

    - night-time period VV

    t1420

    3=

    - measured harmonic voltages, identical for day and night-time periods, of:

    V V V5 7 113 5 7V V V1 1 1

    = = =%, %, % andV13 4V1

    = % .

    calculating the r.m.s. current in the capacitors during the daytime period

    For the fundamental component (at 50 Hz):

    I C V d1 0 1=

    where V Vd n1 = : rated voltage of capacitor bankI In1 = : rated current of capacitor bank 0 2 50= : angular frequency of the supply network .

    For the harmonics:

    I pC V p p= 0

    henceI

    Ip

    V

    Vp p

    d1 1=

    I I pV

    Vpp

    d

    212 2

    1

    2

    =

    ( ) ( ) ( ) ( )( ) I I I pV

    VIrms

    p

    dp

    212

    12 2

    1

    2

    12 2 2 2 2 2 2 2 2

    2

    1 0 03 5 0 05 7 0 07 11 0 04 13= +

    = + + + +

    =

    . . . .

    I Irms = 1 1.42

    hence I Irms n= 1 42.

    The capacitors will overheat and deteriorate prematurely if the protection system does not

    disconnect them.

  • 8/3/2019 08 Harmonics

    52/113

    682

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    calculating the r.m.s. current in the capacitors during the night-time period

    For the fundamental component (at 50 Hz):

    I C V C V VV

    C Vt nt

    nn1 0 1 0

    10

    420400

    = =

    =

    hence I In1 1 05= .

    For the harmonics :

    I pC V p p= 0

    henceI

    I

    pV

    V

    p p

    t1 1

    =

    I I pV

    Vpp

    t

    212 2

    1

    2

    =

    I I I pV

    Vrmsp

    t

    212

    12 2

    1

    = +

    =

    I I I rms n= = 1 42 1 42 1 051. . .

    hence I Irms n= 1 49.

    The r.m.s. value of current is higher during the night-time period because the voltage is higher.

    As a result the capacitors will overheat all the more.

  • 8/3/2019 08 Harmonics

    53/113

    683

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    transformers

    When subjected to harmonic currents a transformer will suffer supplementary losses and

    possible disturbance to its magnetic circuit. Moreover, it will tend to generate noise due to the

    vibrations caused by the harmonics.

    Joule losses

    These are proportional to the square of the r.m.s. current : loss = R I rms2

    .

    Harmonic currents therefore increase Joule losses.

    iron loss

    This comprises eddy current losses and magnetic induction hysteresis losses.

    Eddy current loss is proportional to the square of the frequency, whereas hysteresis loss is

    proportional to the frequency. The higher frequency harmonic currents will therefore generate

    significant iron losses.

    disturbance of the magnetic circuit

    Harmonic currents generate an extra magnetic flux proportional to the impedance of the

    upstream network. This is superimposed on the flux produced in the transformer by the

    fundamental.

    The peak value of flux is thereby increased, which can lead to saturation and an increase in

    magnetising current and iron losses. The transformer itself may also generate harmonics.

  • 8/3/2019 08 Harmonics

    54/113

    684

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    transformer de-rating formula, and working guidelines

    To take account of the extra heat developed, transformers should be de-rated. The formula

    commonly used is:

    kI

    Ip

    p

    p

    =

    +

    =

    1

    1 0 11

    21

    2

    ..

    p : order of harmonic

    I1 : transformer rated current.

    A transformer of rated powerSn is therefore limited to supplying a load of k Sn .

    Another solution consists in obtaining the manufacturer's agreement to construct a transformer

    specially designed to feed equipment that produces harmonics.

    example 1

    It is required to feed a 800 kVA, bridge rectifier from a transformer.

    Using table 8-1, the de-rating factor is:

    11 0 1

    2

    k

    = + . ( ) ( ) ( ) ( ) ( )[ 0 189 5 0 11 7 0 059 11 0 048 13 0 034 172 1 6 2 1 6 2 1 6 2 1 6 2 1 6. . . . .. . . . . + + + +

    ( ) ( ) ( ) ( ) ( ) ]+ + + + + 0 03 19 0 023 23 0 021 25 0 018 29 0 016 312 1 6 2 1 6 2 1 6 2 1 6 2 1 6. . . . .. . . . .

    hence k= 0931.

    The bridge rectifier should therefore be supplied from a transformer whose rated power is at

    least equal to 859 kVA.

    example 2

    It is required to feed a 250 kVA load in the shape of switchmode power supply from atransformer.

    Using the high harmonic level assumption of table 8-2, the de-rating factor is:

    ( ) ( ) ( ) ( ) ( )[ ]1

    1 0 1 1 3 3 0 7 5 0 5 7 0 3 9 0 1 112

    2 1 6 2 1 6 2 1 6 2 1 6 2 1 6

    k= + + + + + . . . . . .. . . . .

    hence k= 0532.

    A transformer of at least 470 kVA should therefore be installed.

  • 8/3/2019 08 Harmonics

    55/113

    685

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    motors

    When harmonic voltages are present, motors are subject to supplementary losses and

    pulsating torques.

    Joule losses

    Joule loss is proportional to the square of the r.m.s. value of current : loss = R I rms2

    .

    Harmonic currents generated by the harmonic voltages present in the supply will thus increase

    Joule losses.

    iron loss

    This comprises Foucault current (eddy current) losses and magnetic induction hysteresislosses.

    Eddy current loss is proportional to the square of the frequency, whereas hysteresis loss is

    proportional to the frequency. The higher frequency harmonic voltages will therefore generate

    significant iron losses.

    pulsating torques, opposing or motor

    Harmonic voltages produce harmonic currents, creating rotating fields whose speeds differ

    from that of the 50 Hz field. Such fields will produce either motor or opposing torques at

    frequencies other than 50 Hz. These torques, and the vibrations they cause, may lead to

    mechanical damage, extraneous noise, supplementary Joule loss in the rotor and a reduction

    in motor efficiency.

    working guidelines

    IEC standard 34-1 lays down that a.c. current motors must be able to operate correctly with a

    supply voltage whose harmonic voltage factor ( HVF ) is as follows:

    HVF 2 %

    The HVF value is calculated from the following formula:

    HVFV

    V pp

    p

    =

    =

    1

    2

    2

    1

    According to the standard only harmonics of order 13 need generally be considered.

  • 8/3/2019 08 Harmonics

    56/113

    686

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    example

    Using the example of paragraph 8.6.1:

    without capacitors

    From table 8-12, calculation gives HVF= 162. % (whereas V = 5 07. % ). This value isacceptable for motors conforming to IEC standard 34-1.

    with capacitors during the day time period

    From table 8-13, calculation gives HVF= 2 50. % . This higher value is the figure laid down bythe standard. Any motor installation must therefore involve specific calculations, or testing at

    the manufacturers to check motor thermal withstand or to establish the de-rating figure that

    may need to be applied to the machines.

    with capacitors during the night time period

    From table 8-14, calculation gives HVF= 9 89. % . This is a value far greater than that definedby IEC standard 34-1, the strong resonance at the 11th harmonic producing intolerably high

    harmonic voltages.

  • 8/3/2019 08 Harmonics

    57/113

    687

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    alternators

    When supplying non-linear loads, an alternator will suffer supplementary losses and pulsating

    torques due to the harmonic currents produced.

    iron loss

    This comprises Foucault current (eddy current) loss and magnetic induction hysteresis loss.

    Eddy current loss is proportional to the square of the frequency, whereas hysteresis loss is

    proportional to the frequency. The higher frequency harmonic currents will therefore generate

    significant iron losses.

    pulsating torques, opposing or motor

    Harmonic currents create rotating fields whose speeds differ from that of the 50 Hz field. Such

    fields will produce either motor or opposing torques at frequencies other than 50 Hz. These

    torques, and the vibrations they cause, may lead to mechanical damage, extraneous noise,

    supplementary Joule loss in the rotor and a reduction in alternator efficiency.

    working guidelines

    Alternators supplying less than 20% of non-linear loads will not generally have any difficulties.Between 20 and 30 % certain manufacturers de-rate their machines by 10 %. Above 30%, the

    the harmonic current spectrum must be shown to the manufacturer so that he can provide the

    derating coefficient. For example, for an uninterruptible power supply manufacturers

    recommend choosing an alternator with a power of 1.5 to 1.9 times that of the UPS.

  • 8/3/2019 08 Harmonics

    58/113

    688

    Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation crite de nos services.

    The publication, translation or reproduction either wholly or in part of this document is not allowed without our written consent.

    Industrial electrical network design guide T & D 6 883 427/AE

    neutral conductor heat problem

    3rd harmonic currents, and multiples of the 3rd, are in phase and flow in the neutral conductor

    when it exists, and when the transformer vector group makes it possible (e.g. a delta-star

    transformer, which is the most common case).

    The r.m.s. current in the neutral conductor is given by:

    I Ineutral k k

    ==

    3 321

    This current may be greater than that flowing in the phase conductors, and as a result the

    neutral conductor must be oversized.

    working guideline

    The cross-section of the neutral conductor must take into account the existence of 3rd

    harmonic currents and multiples of the 3rd.

    example 1

    Consider a lighting load whose current spectrum is that of table 8-15.

    I1 I3 I5 I7 I9 I11 I13 I15

    100 % 35 % 27 % 10 % 2.5 % 3.5 % 1.5 % 1.5 %

    Table 8-15: lighting load current spectrum

    We can derive:

    I Irms = 110 1.

    ( ) ( ) I I I neutral = + =3 0 35 0 025 1 0512 2

    1. . .

    The neutral current value is more or less equal to that flowing in a phase conductor, and as

    such all cables can have similar cross-sections.

    .

  • 8/3/2019 08 Harmonics

    59/113

    689

    Industrial electrical network design guide T & D 6 883 427/AE

    example 2

    Consider computer type loads that have a spectrum as shown in table 8-16.

    I1 I3 I5 I7 I9 I11

    100 % 65 % 35 % 25 % 15 % 5 %

    Table 8-16: current spectrum for computer loads

    We can derive:

    I Irms = 1 28 1.

    ( ) ( ) I I I neutral = + =3 0 65 0 15 2 0012 2

    1. . .

    andI

    Ineutral

    rms= 1 56.

    The current in the neutral is much larger than that flowing in a phase conductor. This demands

    the use of a protection device (circuit-breaker with 4-pole protection) plus a neutral conductor

    of sufficient cross-section.

    electromagnetic disturbances in a TNC earthing system

    Currents due to the 3rd harmonic, and multiples of the 3rd, flow in the neutral conductor. In a

    TNC earthing system the neutral conductor and circuit protection conductor are one and the

    same.

    Now, since the circuit protection conductor connects together all exposed conductive parts,

    including elements of the building's infrastructure, 3rd harmonic currents and multiples of them

    flowing in these circuits will produce local variations in potential.

    This phenomenon may cause problems such as :

    - corrosion of metal parts

    - overcurrent on a telecommunication link connecting the exposed conductive parts of two

    loads (for example, between a microcomputer and a printer)

    - electromagnetic radiation affecting computer screens.

    Where 3rd harmonics or multiples of them are present the TNC earthing system must be

    avoided.

  • 8/3/2019 08 Harmonics

    60/113

    690

    Industrial electrical network design guide T & D 6 883 427/AE

    inverters

    The level of harmonic disturbance created by an inverter will depend on the technique used to

    generate the sine wave voltage, that is, either PWM (Pulse Width Modulation) or non-PWM.

    non-PWM inverters

    The output current of non-PWM inverters is limited to its rated value, giving an instantaneous

    value of current no higher than 2 In .

    Manufacturers apply a de-rating factor that is a function of the peak factor F

    Ipk n=

    This de-rating factor is given by :

    dFpk

    = 2

    PWM inverters

    The output current of Merlin Gerin PWM inverters is limited to 2.35 times the r.m.s. value ofrated current, giving an instantaneous value no higher than 2 35. In .

    - if In

    2 35. de-rating is not applied- if In> 2 35. the de-rating factor is given by:

    dI

    n=

    2 35.

    hence dFpk

    =2 35.

    example

    Table 8-17a gives the de-rating coefficients for inverters feeding computer type loads.

    Type of load IBM 4381 IBM AS400 IBM PCXT IBM site *

    Peak Factor 2.14 2.53 5.54 2.21

    Non-PWM de-rating 0.66 0.56 0.26 0.64

    PWM de-rating / 0.93 0.42 /

    Table 8-17a: inverter de-rating when feeding computer loads

    * Example of an IBM site with a large number of terminals.

  • 8/3/2019 08 Harmonics

    61/113

    691

    Industrial electrical network design guide T & D 6 883 427/AE

    semiconductor convertors

    IEC standard 146-1-1, 2.5.4.1 lays down the operating limits, without performance loss, for

    convertors, defining them according to the machine's immunity class (see table 8-17b):

    - class A: limits are applicable to convertors used on highly (harmonically) disturbed

    networks.

    - class B: limits are applicable to convertors used on networks where there is an average

    level of disturbance

    - class C: limits are applicable to convertors used on networks where the disturbance is low.

    If the immunity class is not specified, class B is deemed to apply.

    Immunity class

    A B C

    Individual even harmonics (%) 2 2 1

    Individual odd harmonics (%) 12.5 5 2.5

    Total harmonic distortion (%) 25 10 5

    Table 8-17b: operating limits without performance loss, for convertors

  • 8/3/2019 08 Harmonics

    62/113

    692

    Industrial electrical network design guide T & D 6 883 427/AE

    special case of the uninterruptible power supply

    The IEC standard 146-4, 5.1 lays down the guaranteed operating limits for a UPS:

    - voltage distortion factor less than 10 %

    - harmonic voltage components less than those defined by the curve shown in figure 8-26.

    5%

    1%

    0.5%

    0.4%

    0.3%

    3 5 7 9 11 13 25 100

    Vp

    V1(%)

    Figure 8-26: maximum permitted harmonic voltage content on a UPS a.c. supply input

  • 8/3/2019 08 Harmonics

    63/113

    693

    Industrial electrical network design guide T & D 6 883 427/AE

    permanent insulation monitors (PIM)

    Such devices apply a d.c. or low-frequency voltage between the protection conductor and the

    neutral (or phase if the neutral is not accessible), and measure the current.

    PIMs using a d.c. voltage are not affected by harmonics since they measure a highly filtered

    d.c. current.

    On the other hand, the older type of PIM (before 1993), such as the XM100, will be affected.

    These inject a 10 Hz voltage and filter the 50 Hz signal. However, the filter becomes ineffective

    from, and including, the 3rd harmonic upwards. Thus, any 3rd harmonic currents or multiples

    of them or unbalanced harmonic currents of monophased loads flowing in the neutral may be

    "seen" by the PIM causing it to alarm in error.

    Where an installation has in-circuit fault location core-balance current transformers on its

    outgoing feeders, harmonic currents flowing in the neutral will disrupt the fault location system.

    No permitted voltage distortion limits have been defined for PIMs, since any likely disruption

    will depend on the characteristics of the network and loads.

    The newer generation PIMs (post 1993), which use a 2.5 Hz voltage and filters which are

    effective above 4 Hz, are immune to harmonics.

    circuit-breakers with electronically tripping relay

    The thermal or magnetic detection of older model circuit-breakers (still on sale today) aresensitive to peak values of current.

    High current distortion factors can mean high peak currents (see the values for computer

    equipment, table 8-18) leading in turn to spurious opening of the circuit-breakers. The thermal

    detection threshold must then be increased when this is possible or the harmonics filtered out.

    Newer generation devices - compact or masterpact - sample the current and calculate its r.m.s.

    value, and are therefore immune.

    computer loads

    The recommended threshold for reliable operation is:

    V

    Vp

    p 1

    2

    1

    5

    21 0.2/ * 0.2/ * 10 0.5 0.2/0.5*

    19 1.5 1 12 0.2/0.5* 0.2/0.5*

    23 1.5 0.7 14 0.2/0.5* 0.2/0.5*

    25 1.5 0.7 16 0.2/0.5* 0.2/0.5*

    > 25 0 212 5

    ..

    +n

    *

    0 112 5

    ..

    +n

    *

    18 0.2/0.5* 0.2/0.5*

    20 0.2/0.5* 0.2/0.5*

    22 0.2/0.5* 0.2/0.5*

    24 0.2/0.5* 0.2/0.5*

    > 24 0.2/ * 0.2/ *

    Total harmonic distortion

    8 % on MV networks 3 % on HV networks

    * : values specific to the EDF "Emeraude" contract : no value has been specified

    Table 8-19: compatibility levels for harmonic voltages on medium and high-voltage public networks

    (taken from Electra, n123 March 1989, and the EDF's Emeraude contract)

  • 8/3/2019 08 Harmonics

    69/113

    699

    Industrial electrical network design guide T & D 6 883 427/AE

    on industrials networks

    IEC standard 1000-2-4 lays down the compatibility levels for harmonic and interharmonic

    voltages existing on industrial networks (see tables 8-20 and 8-21).

    They apply to low and medium-voltage networks .The compatibility levels are given for different classes of environment:

    Class 1:

    Environments in this class are essentially protected networks, with compatibility levels lower

    than for public networks, where equipment particularly sensitive to supply network disturbance

    is used: laboratory instruments, certain automatic and protective installations, certain

    computers, etc.

    Equipment in this type of environment is, of necessity, generally supplied from an

    uninterruptible power supply. Only low-voltage networks are included in this class.

    Class 2:

    This class concerns the utility's take-over point and the internal network.

    The compatibility levels are identical to those applying to public supply networks.

    Class 3:

    This class applies only to internal networks. Compatibility levels are higher than for class 2

    environments.

  • 8/3/2019 08 Harmonics

    70/113

    700

    Industrial electrical network design guide T & D 6 883 427/AE

    Odd harmonics not

    multiples of 3

    Odd harmonics

    multiples of 3

    Even harmonics

    Order of

    harmonicn

    Harmonic voltage

    %

    Order of

    harmonicn

    Harmonic voltage

    %

    Order of

    harmonicn

    Harmonic voltage

    %

    class

    1

    class

    2

    class

    3

    class

    1

    class

    2

    class

    3

    class

    1

    class

    2

    class

    3

    5 3 6 8 3 3 5 6 2 2 2 3

    7 3 5 7 9 1.5 1.5 2;5 4 1 1 1.5

    11 3 3.5 5 15 0.3 0.3 2 6 0.5 0.5 1

    13 3 3 4.5 21 0.2 0.2 1.7

    5

    8 0.5 0.5 1

    17 2 2 4 > 21 0.2 0.2 1 10 0.5 0.5 1

    19 1.5 1.5 4 > 10 0.2 0.2 1

    23 1.5 1.5 3.5

    25 1.5 1.5 3.5

    > 25 212 5

    +.

    n2

    12 5+

    .

    n 511

    n

    Total harmonic distortion

    5 % for class 1 8 % for class 2 10 % for class 3

    Table 8-20: compatibility levels for harmonic voltages existing on industrial networks

    Order

    h

    Class 1

    ( )Up %Class 2

    ( )Up %Class 3

    ( )Up %

    < 11 0.2 0.2 2.5

    11 to 13 inclusive 0.2 0.2 2.25

    13 to 17 inclusive 0.2 0.2 2

    17 to 19 inclusive 0.2 0.2 2

    19 to 23 inclusive 0.2 0.2 1.75

    23 to 25 inclusive 0.2 0.2 1.5

    > 25 0.2 0.2 1

    Table 8-21: compatibility levels for inter-harmonic voltages on industrial networks

  • 8/3/2019 08 Harmonics

    71/113

    701

    Industrial electrical network design guide T & D 6 883 427/AE

    8.3.2.2. Emission levels

    Harmonic currents emitted by customer installations and equipment must be limited in order

    avoid harmonic disturbance attaining the maximum levels of compatibility defined previously

    (see tables 8-18, 8-19, 8-20 and 8-21).

    emission limits applied to low voltage apparatus drawing less than 16 A per phase

    It would be extremely difficult to check the harmonic current emissions of each customer

    connected to a low-voltage network. Besides, IEC 1000-3-4 was drawn up by standards bodies

    to define emission limits for low-voltage apparatus drawing less than 16 A per phase, and

    destined to be connected to the public low-voltage distribution networks. Table 8-22 defines

    the emission limits for class A equipment: i.e. apparatus other than portable tools, lighting and

    equipment drawing an input current with a "special waveform" whose active power

    consumption is less than 600 W (for equipment of this type see IEC 1000-3-2, 7).

    These limits do not apply to professional equipment with a power rating greater than 1 kW.

    Order of harmonic

    n

    Maximum permissible harmonic current

    ( )A

    Odd harmonics

    3 2.30

    5 1.14

    7 0.77

    9 0.40

    11 0.33

    13 0.21

    15 39 n015

    15.

    n

    Even harmonics

    2 1.084 0.43

    6 0.30

    8 40 n0 23

    8.

    n

    table 8-22: harmonic current emission limits for class A, low-voltage apparatus

    drawing less than 16 A per phase

  • 8/3/2019 08 Harmonics

    72/113

    702

    Industrial electrical network design guide T & D 6 883 427/AE

    emission limits applied to industrial consumers

    Precisely limiting the harmonic voltages generated by industrial users would penalise those

    connected to a low short-circuit power network (highly impedant).

    An equitable solution consists in permitting the level of disturbance generated to be

    proportional to the customer's subscribed demand, as applied to each class of voltage ( LV,

    MV, HV)

    There is no international standard laying down the emission limits applying to industrial users.

    case of France

    In France, the EDF's new "Emeraude" contract gives the following tolerances applying to its

    MV and HV networks for information only. At present, the limits shown are not obligatory

    although customers are advised to conform since values more or less equivalent to them will

    no doubt become statutory between now and 1998.

    In the contract, the customer is obliged to take steps to limit the individual harmonic currents

    introduced onto the EDF network. Such limits are calculated on a pro-rata basis according to

    each customer's subscribed demand ( Ssubscribed ).

    A limiting coefficient, kp , is applied to each harmonic current of order p . The customer must

    limit harmonics to a level given by:

    I kS

    Up p

    subscribed

    C=

    3

    where UC is the contract voltage.

    Table 8-23 gives the values for kp as a function of the harmonic order p .