REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd March 07 4. EXTERNAL OPERATOR PROGRAM (HMI500) 4.1. Introduction .............................................................................. 4-3 4.2. Safety instructions ................................................................... 4-4 4.3. Installation................................................................................ 4-5 4.3.1. Minimum PC requirements ...................................................... 4-5 4.3.2. Set-up ...................................................................................... 4-5 4.3.2.1. Communication interface, off-line and simulation mode .......... 4-7 4.3.2.2. Mouse ...................................................................................... 4-8 4.3.2.3. Installation on a network .......................................................... 4-8 4.4. Starting HMI500 ....................................................................... 4-9 4.4.1. Window structure ................................................................... 4-11 4.4.2. Main window .......................................................................... 4-12 4.5. Operation ............................................................................... 4-15 4.5.1. File ......................................................................................... 4-15 4.5.1.1. File / Open ............................................................................. 4-15 4.5.1.2. File / Save as ......................................................................... 4-15 4.5.1.3. File / Upload from protection system...................................... 4-15 4.5.1.4. File / Download to protection system ..................................... 4-15 4.5.1.5. File / Compare….................................................................... 4-17 4.5.1.6. File / Exit ................................................................................ 4-19 4.5.2. View ....................................................................................... 4-20 4.5.2.1. View / Single-line diagram ..................................................... 4-20 4.5.2.2. View / Protection zone measurements................................... 4-22 4.5.2.3. View / Analog input measurements ....................................... 4-23 4.5.2.4. View / Binary input/output status............................................ 4-25 4.5.2.5. View / Switchgear objects ...................................................... 4-26 4.5.2.6. View / Protection zone circuit-breakers .................................. 4-27 4.5.2.7. View / Disturbance recorder................................................... 4-28 4.5.2.8. View / BP function monitoring (REB500sys only) .................. 4-32 4.5.2.9. View / Event list ..................................................................... 4-32 4.5.2.10. View / Reset latched tripping and signaling relays ................. 4-35 4.5.3. Settings .................................................................................. 4-36 4.5.3.1. Settings / System response ................................................... 4-36 4.5.3.2. Settings / Busbar protection ................................................... 4-36 4.5.3.3. Settings / Overcurrent release ............................................... 4-36 4.5.3.4. Settings / Voltage release ...................................................... 4-36 4.5.3.5. Settings / Voltage / external release ...................................... 4-36 4-1

Transcript of 04_1MRB520292-Uen-Reb500sys_Chap 4

Page 1: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

March 07

4. EXTERNAL OPERATOR PROGRAM (HMI500)

4.1. Introduction .............................................................................. 4-3

4.2. Safety instructions ................................................................... 4-4

4.3. Installation................................................................................ 4-5 4.3.1. Minimum PC requirements ...................................................... 4-5 4.3.2. Set-up ...................................................................................... 4-5 4.3.2.1. Communication interface, off-line and simulation mode .......... 4-7 4.3.2.2. Mouse...................................................................................... 4-8 4.3.2.3. Installation on a network .......................................................... 4-8

4.4. Starting HMI500....................................................................... 4-9 4.4.1. Window structure ................................................................... 4-11 4.4.2. Main window .......................................................................... 4-12

4.5. Operation ............................................................................... 4-15 4.5.1. File .........................................................................................4-15 4.5.1.1. File / Open ............................................................................. 4-15 4.5.1.2. File / Save as ......................................................................... 4-15 4.5.1.3. File / Upload from protection system...................................... 4-15 4.5.1.4. File / Download to protection system ..................................... 4-15 4.5.1.5. File / Compare…....................................................................4-17 4.5.1.6. File / Exit ................................................................................ 4-19 4.5.2. View.......................................................................................4-20 4.5.2.1. View / Single-line diagram ..................................................... 4-20 4.5.2.2. View / Protection zone measurements................................... 4-22 4.5.2.3. View / Analog input measurements ....................................... 4-23 4.5.2.4. View / Binary input/output status............................................ 4-25 4.5.2.5. View / Switchgear objects ...................................................... 4-26 4.5.2.6. View / Protection zone circuit-breakers.................................. 4-27 4.5.2.7. View / Disturbance recorder................................................... 4-28 4.5.2.8. View / BP function monitoring (REB500sys only) .................. 4-32 4.5.2.9. View / Event list ..................................................................... 4-32 4.5.2.10. View / Reset latched tripping and signaling relays................. 4-35 4.5.3. Settings.................................................................................. 4-36 4.5.3.1. Settings / System response ................................................... 4-36 4.5.3.2. Settings / Busbar protection................................................... 4-36 4.5.3.3. Settings / Overcurrent release ............................................... 4-36 4.5.3.4. Settings / Voltage release ...................................................... 4-36 4.5.3.5. Settings / Voltage / external release ...................................... 4-36

4-1

Page 2: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.5.3.6. Settings / Bay protection (REB500sys only) .......................... 4-36 4.5.3.7. Settings / Breaker failure protection....................................... 4-36 4.5.3.8. Settings / Overcurrent protection ........................................... 4-36 4.5.3.9. Settings / End zone protection ............................................... 4-36 4.5.3.10. Settings / CB pole discrepancy .............................................. 4-37 4.5.3.11. Settings / Event memory........................................................ 4-37 4.5.3.12. Settings / Communication ...................................................... 4-37 4.5.4. Configuration ......................................................................... 4-37 4.5.4.1. Configuration / Activate/deactivate ........................................ 4-37 4.5.4.2. Configuration / Voltage transformers ..................................... 4-37 4.5.4.3. Configuration / BP licenses (REB500sys only) ...................... 4-37 4.5.4.4. Configuration / Device structure............................................. 4-38 4.5.4.5. Configuration / Isolators ......................................................... 4-38 4.5.4.6. Configuration / Disturbance recorder ..................................... 4-38 4.5.4.7. Configuration / CB inspection ................................................ 4-38 4.5.4.8. Configuration / Binary module................................................ 4-38 4.5.4.9. Configuration / Local HMI LEDs (LMI LEDs).......................... 4-38 4.5.4.10. Configuration / Circuit-breakers ............................................. 4-38 4.5.4.11. Configuration / Current transformers...................................... 4-39 4.5.4.12. Configuration / GPS time synchronization ............................. 4-39 4.5.5. Testing ................................................................................... 4-39 4.5.5.1. Testing / Test mode ............................................................... 4-39 4.5.5.2. Testing / Installation mode ..................................................... 4-42 4.5.6. Tools ...................................................................................... 4-44 4.5.6.1. Tools / Version....................................................................... 4-44 4.5.6.2. Tools / Reports ...................................................................... 4-45 4.5.6.3. Tools / Export SCS data ........................................................ 4-45 4.5.6.4. Tools / Change password ...................................................... 4-46 4.5.6.5. Tools / Settings ......................................................................4-46 4.5.6.6. Tools / Set system time.......................................................... 4-48 4.5.6.7. Tools / MMC session manager .............................................. 4-49 4.5.7. Window..................................................................................4-50 4.5.8. Help (?) .................................................................................. 4-50

4.6. Error messages .....................................................................4-51

4.7. Corrective action....................................................................4-51 4.7.1. Available system resources ................................................... 4-51

4.8. De-installation ........................................................................ 4-51

4-2

Page 3: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4. EXTERNAL OPERATOR PROGRAM (HMI500)

4.1. Introduction

HMI500 is the human/machine interface (HMI) for the protection systems REB500 and REB500sys. For brevity, these Operating Instructions refer simply to REB500 although the program applies to both systems. There are additional menu items, which only apply to REB500sys, and attention is explicitly drawn to these.

HMI500 is a convenient human-machine interface which permits the operator to view REB500 measurements and statuses, set REB500 protection functions and configure the system, download the latter data to REB500 and to control the disturbance recorder and event memory integrated in the system.

HMI500 runs on a standard PC (see Section 4.3.1. “Minimum PC requirements”) under Windows 98, Windows NT, Windows 2000 and Windows XP.

The data are transferred between the PC and REB500 via an optical reader attached to the front of either central or bay units and coupled to a serial interface on the PC.

NOTE: Any changes (e.g. settings, configuration etc.) made using HMI500 are stored in a specific customer database (MDB file) in the PC and not in the protection system. The database then has to be downloaded from the PC to the protection system (see Section 4.5.1.4.).

4-3

Page 4: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.2. Safety instructions

DANGER: HMI500 permits circuit-breakers and isolators to be operated. Every program operation and the possible consequences must be considered carefully beforehand. If switching operations have to be carried out, the same precautions must be taken as when performing them manually.

WARNING: Earlier HMI500 versions are incompatible with Version 7.30 of the protection system software.

WARNING: A password has to be entered to operate HMI500. Passwords may only be assigned to authorized operators. Change the standard passwords in the software as soon as the program is installed.

4-4

Page 5: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.3. Installation

The human-machine interface program HMI500 Version 7.40 is supplied on an installation CD in German, English, French and Spanish.

4.3.1. Minimum PC requirements

HMI500 runs on an IBM PC, compatible under Microsoft. Observe the information published by Microsoft on the PC hardware requirements in relation to the operating system installed.

The minimum PC hardware performance requirements are as follows:

• PC with a CPU operating at 300 MHz or higher

• mouse plus PS/2 interface (bus board) if the PC has only one serial interface

• 16 MByte RAM (64 MByte recommended) for Windows 98 and Windows NT 4.0; at least 64 MByte for Windows 2000 or Windows XP (256 MByte recommended)

• CD-ROM or DVD-ROM drive

• 1 serial interface (RS-232C) (COM1 or COM2)

• SVGA monitor (800 x 600)

• 1 parallel interface (LPT1) for a printer (recommended).

NOTE: The PC-operating program HMI500 runs under Microsoft®

Windows98® 1st Edition with Internet Explorer 4 SP2 or 2nd edition

Windows NT® V4.00 Service Pack 5

Windows 2000® Service Pack 4

Windows XP®

4.3.2. Set-up

Administrator access rights are required for the installation of HMI500 on PCs running the operating systems Windows NT, Windows 2000 or Windows XP. An attempt to install the program with lower access rights prompts an error message and the installation is aborted. Contact your system administrator in this case.

4-5

Page 6: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

Insert the CD-ROM in the drive. The installation program is then started automatically1.

Select the preferred language and confirm that the installation procedure should be continued.

You are now requested to read and confirm your acceptance of the license conditions.

The installation program proposes a target directory. Either confirm the proposed directory or enter a desired one. The program is installed automatically in the prescribed directory after clicking on “Next>”

1 Should the auto-start function on your PC be disabled, select and run the

program start.bat on the CD to start the installation program.

4-6

Page 7: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

A HMI500 directory and program icon 'HMI500 x.xx ss' are created in the Windows Start menu, x.xx signifying the program version and ss the language.

4.3.2.1. Communication interface, off-line and simulation mode

By default, the installation routine will select the first free inter-face (COM port). The communication settings can be changed subsequently by selecting 'Tools / Settings' (see Section 4.5.6.5.).

Aside from the interface a connection via TCP/IP is available as communication path.

The same menu item also provides a choice of operating mode by selecting either the radio button 'Off-line' (excludes the functions requiring a REB500 to be connected) or 'Simulated' (no REB500 connected, but with all the functions available for demonstration purposes and random generation of data) (see Section 4.5.6.5.).

NOTE: HMI500 automatically starts off-line, if an invalid COM port is entered or another application is using the port.

4-7

Page 8: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.3.2.2. Mouse

A mouse is necessary to work with the HMI500 efficiently. It is possible to control it solely via the keyboard, but this can be a little cumbersome. The right mouse button is also used for some operations, and therefore it should not be configured to perform other functions (e.g. double click).

4.3.2.3. Installation on a network

Before attempting to install HMI500 on a network, ascertain that you are authorized to write in the corresponding Windows directory, otherwise the installation will fail.

4-8

Page 9: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4-9

4.4. Starting HMI500

NOTE: The program screens in this section are based on a typical application. Depending on the power system configura-tion and the options configured while engineering your system, certain menus may be missing or the display appears different.

The first screen to appear after starting the operator program is the 'System log-on' dialog:

Fig. 4.1 System log-on dialog

The program can be run in a read only mode by appropriately activating the 'Read only' check box, i.e. the data can be viewed but not changed. Users that want to run the program in a read/write mode (check box deactivated) must enter a password.

NOTE: To enable a start to be made, the password is set to 'System' when the program is supplied (case sensitive!).

HMI500 obtains the specific device data from a database in a file, which is stored both in the PC and the protection system. Database files on the PC have the extension '.mdb'.

Page 10: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4-10

Click on the 'OK' button to continue the start-up routine or on the 'Cancel' button to discontinue and close the program.

Communication with the protection system is tested after clicking on 'OK'.

Providing communication can be established, HMI500 starts in the on-line mode.

Should communication with the protection system fail, it starts either off-line or in the simulation mode (see Section 4.5.6.5.).

The main HMI500 window then appears.

Some of the dialogues used by the program are standard Windows dialogues. Should these not be in the same language as HMI500, than a different language is set for the Windows operating system.

NOTE: The database that was open during the last session opens automatically. If no database was open before, select 'Open' in the 'File' menu and then the desired file. An error message is displayed if an attempt is made to open an incompatible file. An existing file in the protection system can also be opened using the 'Upload' function in the 'File' menu.

Page 11: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4-11

Fig. 4.2 Main HMI500 window

4.4.1. Window structure

The structure and handling of the windows in the operator program is similar to other Windows applications.

Fig. 4.3 Dialogue buttons

The following buttons appear in many dialogues:

OK

The new settings are saved in the database on the PC and the dialogue closes.

Apply

The new settings are saved in the database on the PC and the dialogue stays open.

Page 12: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

Restore

The changes that have been made are ignored and the old settings restored. The dialogue stays open.

Cancel

The new settings are not saved and the dialogue closes.

Scroll (arrow) buttons

In windows permitting the selection of several bays (or isolators, circuit-breakers etc.), there are four scroll buttons at the bottom for scrolling through the bays.

Close

The window or dialogue is closed and a warning is displayed, if changes have been made which have not been saved.

In many dialogues with settings there is an overview tab for selecting one of a list of bays and a details tab showing the respective settings. Details can be viewed by either clicking on the tab or double-clicking on the bay in the overview list.

4.4.2. Main window

The title bar is at the top of the main program window and states the name of the program 'HMI500 (REBWIN)' and the project information entered by the ABB engineering department. The menu bar is located immediately below the title bar.

Fig. 4.4 Status bar

File

The menu item 'File' permits databases to be opened and saved and a database to be uploaded from the protection or downloaded to it.

4-12

Page 13: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

View

The menu item 'View' contains menu items for viewing the plant diagram, the measurements of each protection zone, inputs and outputs, switchgear statuses, the event list and any tripping that has taken place. For REB500sys, the application also provides facility for viewing the bay protection measurements.

Settings

By selecting the menu item 'Settings' it is possible to set the system parameters, the operating values for the various protection functions and the communication parameters.

Configuration

The menu item 'Configuration' concerns the definition of the various circuit-breakers, isolators and CTs, the activation/ deactivation (masking/unmasking) of items of plant, the configuration of system modules, tripping logics and the disturbance recorder and maintenance instances presented. Other items configured are the LEDs on the local HMI (REB500sys, bay unit type 500BU03) and the optional GPS synchronization system. In the case of REB500sys, an overview of the licensed bay protection functions is also provided.

Testing

The menu item 'Test' is for enabling/disabling either the test or installation mode.

Tools

Functions for editing data file versions, producing reports, exporting SCS communication data, changing passwords, selecting operator program options and setting the system time are available under the menu item 'Tools'.

Help

The online help system and information details of the software version are accessed by clicking on “Help”.

Status information is displayed on the bar at the bottom of the main window (Simulation/On-line/Off-line, Edit/Read only, Test mode, Installation mode, Database version, Setfile). These have the following significance:

Fig. 4.5 Status bar

4-13

Page 14: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

On-line/Off-line

If the program can successfully establish contact with the protection system, it is in the on-line mode. If no connection can be established or is not desired the program is in the off-line mode.

Simulation

The system is in the simulation mode when 'Simulation' is displayed on the status bar. All the functions can be executed without being connected to a protection device. Random values are generated when viewing protection unit data, e.g. event lists or measurements. Simulated faults can also be viewed.

Edit/Read only

'Edit' permits settings to be saved in a file or downloaded to the protection system. In the 'Read only' mode it is only possible to read data.

Test mode

'Test mode' is displayed on the status line whenever the test generator is activated.

Installation mode

'Installation mode' is displayed on the status line whenever the installation mode is activated.

Database version

The version of the database structure of the database that is open is displayed.

Setfile

The name and path of the setfile that is open are displayed at this location on the status bar.

4-14

Page 15: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.5. Operation

4.5.1. File

4.5.1.1. File / Open

After starting the program, select 'Open' from the 'File' menu. A dialogue opens which enables you to select the desired file. The dialogue provides facility for navigating through the various drives and directories. After making the corresponding choice, click on 'OK' to load the data into the program or on 'Cancel' to close the dialogue without making any changes.

4.5.1.2. File / Save as

The current data in the PC database can be saved in a file by opening the 'File' menu and clicking on 'Save as'. As was the case with 'Open', the dialogue that appears gives full access to the PC file system.

4.5.1.3. File / Upload from protection system

This menu item enables data stored in the protection system to be uploaded to a file in the PC.

Fig. 4.6 Upload from protection system

4.5.1.4. File / Download to protection system

Open the 'File' menu and select 'Download to protection system' to download the current data from the PC database to the protection system.

The versions are compared before downloading proceeds and the result is displayed. An index and a comment may also be entered beforehand by selecting Tools/Version (see Section 4.5.6.). For safety reasons, the new data is only saved if it is different. Data will only be saved if they are different or the version index is different.

4-15

Page 16: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

NOTE: Data can be correctly downloaded as soon as the central unit has started.

After the downloading procedure is complete, the protection system is restarted and the valid version can then be verified on the HMI.

Fig. 4.7 Download to protection system and comparison of versions

Fig. 4.8 Warning: Download to protection system and comparison of versions

The progress of the downloading procedure is shown on the screen. The correct time format must be set via the control panel on the PC for the procedure to be presented correctly. The procedure can be interrupted by the user as far as 'Archive data in the protection system'.

4-16

Page 17: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Fig. 4.9 Download to protection system

Various check sums are calculated to establish the integrity of the data in the database and these are examined after the transfer of data has been completed.

Only after all the data have been successfully transferred are they saved in the non-volatile memory. The auxiliary supply of the central unit must not be interrupted during this part of the procedure.

4.5.1.5. File / Compare…

This menu item provides facility for comparing the PC database loaded by HMI500 and the database stored in the protection system or a second database file in the PC.

4-17

Page 18: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

Fig. 4.10 Comparison of system databases

Second database is stored at PC

Activating this radio button compares the system database loaded by HMI500 and another database in the PC. The latter is chosen by clicking on the button 'Select file…'.

Second database is at target

Activating this radio button compares the system database loaded by HMI500 and the database already stored in the protection system. The degree of detail is determined with the aid of the button 'Only compare checksum'.

Show only differences

Checking the 'Show only differences' box enables the scope of the report to be limited to the differences actually found.

Limit number of differences

The number entered here determines the number of differences that can be found before the current comparison operation is aborted.

4-18

Page 19: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Show pre-engineering changes only for feeders, modules and switchgear objects

When this box is checked (default setting), the comparison is restricted to determining whether changes have taken place in relation to the pre-engineering data for bays, modules and switchgear. Generally, the default settings should be retained as otherwise the number of differences that will be discovered increases considerably (events, signals etc., are then also taken into account).

Write log file

Check the box 'Write log file' to store the results of the comparison in a file.

Compare…

The button 'Compare... ' starts the comparison operation.

4.5.1.6. File / Exit

To terminate the program, open the 'File' menu and select 'Exit'. A warning is displayed if there are changes that have not been saved. You then have the choice of saving or discarding them.

4-19

Page 20: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.5.2. View

4.5.2.1. View / Single-line diagram

Opening the 'View' menu and selecting 'Single-line diagram' displays a diagram of the plant corresponding to the layout and wiring diagrams created for the project by the ABB engineering department.

The screen below shows a typical single-line diagram:

Fig. 4.11 Single-line diagram

The name of every item of plant can be changed by pointing at its label and clicking the right mouse button. This opens a menu with the operation 'Change label'. Clicking the right mouse button again on this command opens a dialogue called 'New label'. After entering the new name, click on 'OK' to confirm it.

The names can also be changed via the 'Configuration' menu.

The primary system shown above is only an example.

Providing the items of plant have been configured, updating once or cyclically shows their actual status and the feeder currents.

Using the right mouse button, it is also possible to display the differential currents of the selected busbar zone. A busbar zone is selected by clicking the right mouse button on its label, e.g. BZ1.

4-20

Page 21: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Fig. 4.12 Updated single-line diagram

Click the right mouse button in an empty field in the single-line diagram to view a dialogue with a list of the symbols used. The buttons on the right provide facility for changing the default colors for open, closed or invalid objects to suit your needs.

4-21

Page 22: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.5.2.2. View / Protection zone measurements

This dialogue displays the actual values of measured variables for each protection zone (restrained differential current of the busbar protection function). The protection zones are determined by the positions of the isolators and the bus-tie breakers (busbar image).

Overview

Fig. 4.13 Overview dialogue for protection zone measurements

The currently active protection zones are listed in order showing the associated sections of busbar and the differential current per phase or in the neutral. The overview is not updated auto-matically, it is necessary to click on the 'Refresh' button. A protection zone to which no measurement has been assigned (not a single bay unit current is processed by the busbar protection algorithm) is shown as being invalid.

Protection zones that have been connected (e.g. via a pair of feeder isolators or a longitudinal isolator) are also presented.

4-22

Page 23: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Detailed view

Fig. 4.14 Detailed view of measurements per zone

The feeders assigned to individual protection zones are listed in the detailed views of the relevant zones.

The differential current, the restraint current and the stability factor are also displayed.

4.5.2.3. View / Analog input measurements

The bay units and their labels and slots are listed in the overview dialogue.

Fig. 4.15 Overview dialogue for protection zone measurements

4-23

Page 24: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

To display the values of measured variables, first select a module (becomes highlighted) and click on the 'Open measurements window' button or alternatively double click on the module. Up to eight measurement windows can be open at the same time.

The windows can be arranged under each other by clicking on the 'Arrange windows' button.

The display can be updated either manually by clicking on the 'Update measurement' button or automatically by clicking on the 'Update cyclically' button. This updates all the measurement windows, which are open at the same time.

A warning appears in the measurement window if measurements cannot be correctly performed. Closing the overview window closes all the measurement windows as well.

If a type 500BU03 bay unit is selected, the phase-angles are displayed as well as the analog measurements (see Fig. 4.15 'Overview dialogue for protection zone measurements'). The currently valid reference channel, i.e. reference point for displaying phase-angles, is highlighted yellow. The user can change the reference channel by double-clicking on the desired one. The phase-angle display is not available on the other types of bay unit.

4-24

Page 25: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.5.2.4. View / Binary input/output status

Fig. 4.16 Binary input/output status

The binary inputs and outputs are listed in the overview dialogue together with their bay labels and slot numbers.

To view a signal status, select the corresponding module and click on the 'Open status window' button or alternatively double click on the module. Up to eight status windows can be open at the same time. They can be arranged under each other by clicking on the 'Arrange windows' button.

The display can be updated either manually by clicking on the 'Update status' button or automatically by clicking on the 'Update cyclically' button. This updates all the status windows, which are open at the same time.

A status window shows either the inputs or the outputs. A '1' in a field indicates that the respective input or output is set and a '0' that it is reset. The statuses of all valid values are green (gray on a monochrome screen).

Two windows can be opened to view the inputs and outputs of a bay at the same time.

4-25

Page 26: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

A status of an input or output that has been impressed is yellow (white on a monochrome screen) (see Section 4.5.5.). The statuses of inputs, which the supervision function has tagged as being invalid, are red. This can also occur briefly when the window is opened.

The signals assigned to each physical channel while configuring the binary module are displayed in the status window. Channels to which no signals were assigned are marked 'No signal assigned'.

Closing the overview window closes all the status windows as well.

NOTE: Further details of the signals assigned to the various binary inputs and outputs can be viewed by opening the 'Configuration' menu and selecting 'Binary modules' (see Section 4.5.4.8. 'Configuration / Binary module').

4.5.2.5. View / Switchgear objects

The detailed view shows the statuses of circuit-breakers and isolators.

Fig. 4.17 Switchgear objects

If neither a closed nor an open position is defined, a status of 'invalid' is displayed.

4-26

Page 27: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.5.2.6. View / Protection zone circuit-breakers

The detailed view shows all the circuit-breakers belonging to the respective protection zone.

Fig. 4.18 Protection zone circuit-breakers, detailed view

These circuit-breakers are intertripped, for example, in the event of a busbar fault in the respective protection zone.

4-27

Page 28: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.5.2.7. View / Disturbance recorder

Overview

The number of records and the current status is displayed for every bay unit:

• Ready: The disturbance recorder is ready to make records.

• Not ready: The disturbance recorder has to be restarted in the detailed view of the bay (e.g. when the 'fix' mode of recording is set and the memory is full, see Section 5.3.9.2.).

• Recording: A record procedure is in progress.

Fig. 4.19 Disturbance recorder overview

Press 'Shift' and click on the desired fields to select several fields at once.

• Detailed views of all the bay units selected can be opened.

• Recording can be initiated for each of the bay units selected.

• The records of each of the bay units selected can be transferred (see Fig. 4.20 'Transferring disturbance recorder records')

• The records of each of the bay units can be deleted.

4-28

Page 29: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Transferring disturbance recorder records (together)

The records of the bay units selected can be transferred together in a single operation.

Fig. 4.20 Transferring disturbance recorder records

This dialogue provides the following facilities:

• Select a directory for storing the records

• Deleting the records transferred in the protection system

• Manual transfer of records using the ComTrade standard

• Automatic transfer (only if 'Delete disturbance recorder data' is selected): the user has the possibility of setting the transfer interval and selecting the ComTrade format.

4-29

Page 30: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

Detailed view

Dialogue for viewing individual bay units and processing records.

Fig. 4.21 Disturbance recorder detailed view

The following data are displayed:

• Status (defined in the overview)

• Number of records available

• Number of free memory addresses

• Sampling rate (see Section 5.3.9. ' Configuration / Disturbance recorder')

• Type of trigger

• Duration of recording

• Record number (see Disturbance recorder file).

The dialogue provides the following facilities:

• Stop disturbance recording

• Start disturbance recording

• Deleting records manually (only the oldest record is accessible)

• Selection of ComTrade format, i.e. saving according to standard 91 or 99

• Manual transfer of the 'ComTrade' record (only the oldest record is accessible).

4-30

Page 31: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Disturbance recorder file

COMTRADE format

Saving records in the COMTRADE format involves the automatic creation of three files.

1. dddsssnn.CFG

2. A file with the extension .DAT

3. A file with the extension .HDR

Record file name

The disturbance recorder records are saved in files with the following standard names in the PC:

dddsssnn.CFG

where ddd Day of the year (1...365)

sss Disturbance recorder station number

nn Consecutive disturbance recorder number.

The name of the file can be changed providing the records are transferred manually.

4-31

Page 32: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.5.2.8. View / BP function monitoring (REB500sys only)

The menu item 'BP function monitoring' is only provided with REB500sys.

Fig. 4.22 Bay protection measurements

The bay units licensed to include bay protection are listed in the overview dialogue.

To view the measurements, select a bay unit (highlighted) and click on the 'Continue' button or more directly, simply double click on the desired bay unit using the left mouse button.

The 'Select function' dialogue with a list of bay protection functions and measurements available in the particular bay unit appears. Select the desired function either by double clicking on it or selection and clicking on the 'Open function' button.

The protection function measurement is automatically refreshed. Close the dialogue either by clicking on 'OK' or 'Cancel'.

4.5.2.9. View / Event list

Protection system events are shown in chronological order. By correspondingly setting the event filter, just protection events, system events or test events can be viewed separately. Events with an invalid time tag can be excluded from the display. You can choose between 'User-defined' and 'System-defined' event texts.

4-32

Page 33: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Fig. 4.23 Event list

The central unit event list has a maximum length of 1000 and the bay units 100 records.

In the event of a supply failure, the events stored in the REB500 central unit remain intact for at least 24 hours.

Load events

The protection system has an event memory for every unit (central unit and bay units).

To upload the latest events to the PC, open the 'View' menu and select 'Event list'. This opens the 'Event list' dialogue (HMI500 must be in the on-line mode). Click on the 'Refresh' button to upload the events. The protection system stores the events until they are explicitly deleted.

The list viewed on the PC is refreshed either on command or cyclically. To specify the refreshing interval, select 'Tools / Settings' (see Section 4.5.6.5.).

4-33

Page 34: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

There is no indication should the event memory overflow before the events have been uploaded. The events are updated as determined by the system response setting (see Section 4.5.3.11. 'Settings / Event memory').

The following information is shown for every event:

• Type of event P = Protection function event S = System event T = Test generator event

• Date event occurred

• Time event occurred

• Time tag valid (yes / no)

• Source of event with application, node and device ID FFFSSAAAA (e.g. BPD010004) FFF: English function designation (e.g. PDP =

Bay protection device) SS: No. of the bus section AAAA: Address of the hardware unit that

generated the event.

NOTE: The source data are important for locating hardware defects.

• Text as entered via 'Configuration/Binary module' (user defined) or alternatively, the name assigned by the system (system defined)

• Value, e.g. ON or OFF.

The width of the columns can be adjusted by dragging the border with the mouse in the table header.

Providing a printer is connected to the PC, you can print the event list by clicking on the “Print” button.

The event list can be saved in a text file on the PC with the aid of 'ASCII export'.

Deleting events

An event is marked (becomes highlighted) by clicking on it, with the mouse and several events by holding the mouse button pressed and moving the pointer over them.

4-34

Page 35: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Clicking in the blank field at the top left of the window (next to ‘Type’) marks all the events in the list.

Deleting the PC list

Mark events you wish to delete and click on the 'Delete PC list' button. Deleting can take several seconds and single events, groups of events or all events can be deleted.

Deleting the system list

All the events stored in the protection system are deleted.

Deleting events that have been viewed

All the protection events viewed since opening the window are deleted.

System events when starting

A number of system signals that are generated when starting the system are recorded as events. Up to the instant that system clocks are automatically synchronized, events may have an incorrect date and time. These events are not displayed if 'Only events with a valid time tag' was selected.

4.5.2.10. View / Reset latched tripping and signaling relays

Fig. 4.24 Resetting latched tripping and signaling relays

All latched signals are reset and the corresponding display on the local control unit deleted.

4-35

Page 36: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.5.3. Settings

4.5.3.1. Settings / System response

See Section 5.4.2. “Settings / System response”.

4.5.3.2. Settings / Busbar protection

See Section 5.4.3. “Busbar protection” (settings and calcula-tions).

4.5.3.3. Settings / Overcurrent release

See Section 11.10.1 “Overcurrent release of the trip command (option)”.

4.5.3.4. Settings / Voltage release

The setting dialogue for the voltage release is only available providing the function is part of the scope of supply.

See Section 11.10.2. “Release logic / matrix”.

4.5.3.5. Settings / Voltage / external release

See Section 11.10.2. “Release logic / matrix”.

4.5.3.6. Settings / Bay protection (REB500sys only)

The setting dialogue for the bay protection is only available providing the function is part of the scope of supply.

See Section 12. “Bay protection”.

4.5.3.7. Settings / Breaker failure protection

The setting dialogue for the breaker failure protection is only available providing the function is part of the scope of supply.

See Section 11.1. “Breaker failure protection (option)”.

4.5.3.8. Settings / Overcurrent protection

The setting dialogue for the time-overcurrent protection is only available providing the function is part of the scope of supply.

See Section 11.3. “Overcurrent protection (def. time) (option)”.

4.5.3.9. Settings / End zone protection

The setting dialogue for the end zone protection is only available providing the function is part of the scope of supply.

See Section 11.2. “End fault protection (option)”.

4-36

Page 37: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.5.3.10. Settings / CB pole discrepancy

The setting dialogue for the CB pole discrepancy function is only available providing it is part of the scope of supply.

See Section 11.4. 'Breaker pole discrepancy protection (option)'

4.5.3.11. Settings / Event memory

See Section 5.4.12. 'Event memory'.

4.5.3.12. Settings / Communication

Providing the corresponding hardware has been fitted, the busbar protection can communicate with a station automation system (SCS) or station monitoring system (SMS) via the interbay bus connector.

See Section 11.13. 'Interbay bus (IBB) connection'.

4.5.4. Configuration

4.5.4.1. Configuration / Activate/deactivate

Entire bay units or individual items of plant can be activated or deactivated, i.e. included in or excluded from the protection system.

See Section 7.6. 'Configuring REB500 to match the layout of the primary plant'.

4.5.4.2. Configuration / Voltage transformers

This menu item only appears if the protection system includes VTs.

See Section 11.8. 'Configuration - voltage transformer (REB500 option)'.

4.5.4.3. Configuration / BP licenses (REB500sys only)

This menu item only appears if the protection system includes the bay protection function.

See Chapter 12 'Bay protection'.

An overview of licensed and configured protection function groups for each bay unit is shown. A help text appears when the mouse pointer is over a licensed group listing the protection functions it contains.

4-37

Page 38: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

Fig. 4.25 Licensed bay protection functions

4.5.4.4. Configuration / Device structure

See Section 5.3.6. 'Configuration / Device structure'.

4.5.4.5. Configuration / Isolators

This menu item permits the isolator labels to be changed.

See Section 5.3.2. 'Configuration / Isolators'.

4.5.4.6. Configuration / Disturbance recorder

See Section 5.3.9. 'Configuration / Disturbance recorder'.

4.5.4.7. Configuration / CB inspection

See Section 5.3.11. 'Configuration / CB inspection'.

4.5.4.8. Configuration / Binary module

See Section 5.3.7. 'Configuration / Binary module'.

4.5.4.9. Configuration / Local HMI LEDs (LMI LEDs)

See Section 5.3.10. 'Configuration / HMI LEDs'.

4.5.4.10. Configuration / Circuit-breakers

This menu item permits the circuit-breaker labels and the recovery time to be changed.

See Section 5.3.3. 'Configuration / Circuit-breaker'.

4-38

Page 39: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.5.4.11. Configuration / Current transformers

This menu item permits the CT labels and ratios to be changed.

See Section 5.3.4. 'Configuration / Current transformers'.

4.5.4.12. Configuration / GPS time synchronization

This menu permits the GPS synchronization to be configured.

See Section 11.15. 'Synchronizing using GPS (option)'.

4.5.5. Testing

4.5.5.1. Testing / Test mode

WARNING: Switching to the test mode while the protection is in operation should only be undertaken by especially trained personnel. Incorrect manipulations can cause false tripping, for example, by inadvertently operating a tripping relay, simulating an incorrect isolator or circuit-breaker status or activating a tripping output (e.g. External TRIP). The test generator is activated by opening the 'Testing' menu, selecting 'Test mode' and entering a valid password. A tick appears next to the menu item, 'Test mode' is added to the status line at the bottom of the screen and the 'Test mode' dialogue opens.

NOTE: To enable a start to be made, the password is set to 'Test' when the program is supplied.

The test generator is used in conjunction with the 'Status of binary inputs/outputs' dialogue (has to be opened by the operator), see Section 4.5.2.4. 'View / Binary input/output status'.

When the test generator is active, the statuses of the tripping commands cannot change.

Where bay protection is installed, a test sequencer can be activated in the test mode which checks the protection functions (see Section 12.1.4.).

4-39

Page 40: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

Fig. 4.26 Test mode

Unblock all relays

Clicking on the 'Unblock all relays' button restores the relays to normal operation and their statuses can change again.

WARNING: An output relay can now be set or reset either directly (e.g. by setting an output relay) or indirectly (e.g. via an input or by a protection function). The greatest care must be taken when using the test mode, especially when the protection system is in operation. Block all relays

Clicking on the “Block all relays” button prevents the statuses of all relays for which outputs have been configured from being changed.

Block all tripping relays

Clicking on the 'Block all tripping relays' button prevents the statuses of all tripping relays from being changed with the exception of '41810_In service', '41835_Test generator active' and '41410_Output relays blocked'.

Reset all overridden relays

Clicking on the 'Reset all overridden signals' button returns all inputs and outputs which had statuses impressed on them for test purposes to their original states.

4-40

Page 41: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

NOTE: Blocking hierarchy • Blocking by the test generator takes precedence over all

other functions, i.e. neither a protection function nor an External TRIP signal can initiate a trip.

• Unblocking by the test generator takes precedence over all other functions, i.e. blocking by an isolator or differential current alarm or a signal applied to an opto-coupler input is cancelled.

Using the test generator

Fig. 4.27 Statuses of binary inputs and outputs in the test mode

In order to set or reset binary inputs and outputs using the test generator, it is necessary to open the 'Status of binary inputs/outputs' dialogue. Providing the test mode is active, the status of an input or output can be changed by simply double-clicking on it.

Regardless of whether they are logical '0' or logical '1', inputs and outputs are normally green, those with impressed statuses yellow and invalid ones red. Impressed statuses are green after the display is refreshed.

4-41

Page 42: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

Shutting down the test generator

The test generator is deactivated by clicking on the menu item 'Test mode' a second time. All the relays are then restored to their original statuses, any latching is reset and blocking by the test generator is cancelled.

4.5.5.2. Testing / Installation mode

This mode is activated by opening the 'Testing' menu, selecting 'Installation mode' and entering a valid password.

A tick appears next to the menu item, 'Installation mode' is displayed on the status line at the bottom of the screen and the 'Installation mode' dialogue opens.

Click on 'Installation mode' in the 'Testing' menu to reset the installation mode. The tick in the menu item is reset.

NOTE: To enable a start to be made, the password is set to 'Install' when the program is supplied.

Fig. 4.28 Restart the protection system

4-42

Page 43: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

Fig. 4.29 Delete database in the protection system

Delete data base in the protection system

All the data in the protection system are deleted, i.e. the project database (MDB file) in the protection system is deleted.

Restart the protection system

Clicking on the 'Restart the protection system' button reinitializes the protection.

Debug mode

In the debug mode, the protection system generates additional internal program events. As a rule, the debug mode is only used by the ABB engineering department for test purposes. In seldom cases should the corrective action suggested in Chapter 9 not prove successful, it is possible that a solution can be found using the debug mode.

Read trace ability information

The hardware data (type, serial number, revision index, date of manufacture etc.) and software data (version) are uploaded from the protection equipment and stored in the database to enable previous history to be retraced.

4-43

Page 44: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

4.5.6. Tools

4.5.6.1. Tools / Version

This menu item is for administering the database for the specific protection system, which contains information such as settings, event texts, configuration of the binary inputs and outputs etc. Parts of the database can be edited on the PC using HMI500 and then downloaded to the protection. The database has a version number and index that are displayed in the HMI main menu.

Version: X.YY, date of the last change, description

The version is purely numerical, i.e. X {0...9} and Y {0...9}. It is assigned by ABB while processing the contract and determined at the time the system is accepted by the user. The user cannot change it subsequently.

Index: XX, date of the last change, description

The index only comprises letters, i.e. X {A...Z}. The user must change the index and its description if he changes the REB500 settings in order to document and distinguish different sets of settings. When a new index is assigned, the current date on the PC is recorded as the date of the last change.

Fig. 4.30 Version

4-44

Page 45: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.5.6.2. Tools / Reports

Fig. 4.31 Reports

The 'Reports' dialogue is opened by selecting 'Reports' in the 'Tools' menu. It contains a list of the various kinds of reports.

Either a desired report can be printed on its own or all the reports can be printed by activating the 'Print all reports' check box.

The difference between the options in the 'Printing quality' field is that the data are presented in tabular form if the 'Normal' radio button is active.

Unless a printer is actually installed on the PC, the 'Reports' menu item is grey and inactive. A printer does not, however, have to be connected.

4.5.6.3. Tools / Export SCS data

This menu item exports any communication data contained in the database.

Fig. 4.32 Export SCS data

4-45

Page 46: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

In the case of the optional IEC 61850-8-1, LON and IEC 60870-5-103 communication protocols, the 'Export' button creates files that can be used to configure the communication interface at the remote end.

4.5.6.4. Tools / Change password

This menu item provides facility for changing the passwords giving access to various protected functions (changing settings and activating the test mode or installation mode). Passwords apply to HMI500 on the PC and not for the protection system.

4.5.6.5. Tools / Settings

HMI500 settings

Some of the operator program functions can be customized:

Fig. 4.33 HMI500 settings

Communication

Communication can be established with a REB500 or REB500sys system either via a serial interface or the TCP/IP protocol. The input fields for the communication parameters presented by the program depend on which of the two is chosen.

Serial interface:

In addition to defining the serial interface (COM port), there is also a setting for the Baud rate.

4-46

Page 47: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

TCP/IP winsock:

Settings are provided for the TCP/IP address and the TCP/IP port of the REB system to which communication is being established.

It is possible to change between the communication modes On-line, Off-line and Simulation. Clicking on the 'Check Online' button causes HMI500 to check whether communication with REB500 system is active or can be established (see Section 4.3.2.1.).

Write DB download/upload log file

If these checkboxes are active, a log file is saved every time the database is downloaded to, respectively uploaded from the protection system.

Parameters for reading and exporting event data

Settings are provided for the period for cyclically reading events and the separator for an ASCII file when exporting events.

Database locations

HMI500 creates a number of configuration databases. The following dialogue provides facility for defining the directories where the databases are located and changing the database names. Default directories are created during the installation of HMI500 and it is recommended that these not be changed.

Fig. 4.34 Settings / Database locations

4-47

Page 48: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

PSM support (option)

HMI500 automatically displays this directory when E_wineve is installed on the PC. The directory enables you to verify the response of E_wineve after disturbance recorder data have been transferred.

• Check the box 'Send notification after automatically uploading data' to obtain notification as to which disturbance recorder data have been sent. For this purpose, E_wineve has to have been started in the batch mode.

• Check the box 'Evaluate after manually uploading data from the protection system' to be offered the possibility of evaluating disturbance recorder data using E_wineve after they have been manually transferred.

• The button 'Select PSM' provides facility for locating the E_wineve installation to be used for evaluating disturbance recorder data.

Fig. 4.35 PSM support settings

4.5.6.6. Tools / Set system time

The system clock in the protection system is equipped with a standby battery and if not synchronized periodically by an external reference, runs independently with an accuracy of 150 ppm (13 s per day). The date and time are set by opening the 'Tools' menu and selecting 'Set system time'. The date and time displayed are those effective on the PC.

4-48

Page 49: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

The settings in the fields can be incremented or decremented by clicking on the appropriate arrow to the right of the value. After making the necessary changes, click on the 'Set time' button to automatically download the new date and time to the protection system.

Fig. 4.36 Setting the system time

4.5.6.7. Tools / MMC session manager

Fig. 4.37 MMC session manager

As a rule, this function runs entirely automatically and requires no intervention by the operator. Only if after something untoward happens and an error message is displayed is it necessary to manually close sessions (e.g. if the PC is switched off without correctly shutting down the program).

Every transaction involving communication between the operator program and the protection system (e.g. reading the event list or

4-49

Page 50: 04_1MRB520292-Uen-Reb500sys_Chap 4

ABB Switzerland Ltd REB500/REB500sys 1MRB520292-Uen/Rev. E

setting inputs and outputs using the test generator) is managed as a (DAC) session. Open the 'Tools' menu and select 'MMC session manager' to open a dialogue with a list of open sessions.

Mark the sessions to be closed and then click on the 'Close session' button. Take care when doing so that no other PC is connected to any other part of the protection system as its communication may also be terminated.

The session 'TGR_Read EMI' refers to the main communication between the operator PC and the protection system and must remain open. HMI500 has to be restarted should the 'TGR_Read EMI' session be closed by mistake.

Refer also to Section 9.2.4. 'HMI500 faults'.

4.5.7. Window

When several windows are in use, this menu provides facility for arranging them to overlap, under each other or next to each other.

4.5.8. Help (?)

About

This provides information on the program version and the PC system (available memory etc.).

4-50

Page 51: 04_1MRB520292-Uen-Reb500sys_Chap 4

REB500/REB500sys 1MRB520292-Uen/Rev. E ABB Switzerland Ltd

4.6. Error messages

Refer also to Section 9.2.4. 'HMI500 faults'.

4.7. Corrective action Refer also to Section 9.2.4. 'HMI500 faults'.

4.7.1. Available system resources

Should your PC’s system resources fall below 20% after starting HMI500 (select “About” in the 'Help' menu and click on 'System info'), HMI500 may not function correctly. In this case, close all other Windows applications.

4.8. De-installation

To de-install HMI500 open the Windows control panel and then 'Add/remove programs'. Find the entry for HMI500 in the list of programs presented and select it and then click on OK to remove the program.

4-51