Nottingham Royal Concert Hall

Background◦ Project Scope

Replace existing Tungsten light source with LED Retain the existing lighting points Recreate exactly the same lighting feel Compatible with existing DMX control system Seamless dimming to zero Viable ROI

Nottingham Royal Concert Hall

A program of works where the capital cost is recovered through energy savings which are guaranteed by E.ON

£

£

£

£

£

£

£

£

£

Imp

lem

en

tati

on

costs

(in

cl.

fi

nan

cin

g)

Ongoing

savings

Guaranteed savings period

Guaranteed savings

p.a.

Savings in the early

years repay the

initial capital

investment thereby limiting

client risk

Client net

benefit

Energy Performance Contracting

Nottingham Energy Performance Contract • E.ON secured a contract under the RE:FIT Framework

to deliver an EPC for Nottingham City Council.

• £1.2M Investment to deliver a 26% energy saving

across 8 buildings, including Leisure Centres, Care

Homes and a Sports Stadium.

• All savings guaranteed for 7 years in order to pay back

the original investment.

• One of the 8 Buildings is the Royal Concert Hall.

Design Challenges (DES)◦ The issues that needed to be resolved

Sourcing suitable product Existing light fittings

Consistent and effective dimming Control interface The building Emergency Lighting Commissioning

Nottingham Royal Concert Hall

Design Challenges (DES)

Nottingham Royal Concert Hall

Existing Fittings (High Level) 300W Par Lamps

Design Challenges (DES)

Nottingham Royal Concert Hall

The Building

Project Hardware – AlphaLED

Nottingham Royal Concert Hall

◦ High Level Lighting (20m+ Height)

60 x Bespoke fittings created Mechanical Interface

2700 CCT – To match tungsten “feel”

3000Lm 28° Beam For punch and penetration. Replaced 300W R95 lamps

Project Hardware – AlphaLED

Nottingham Royal Concert Hall

◦ Low Level Lighting

458 Down lighters Across 4 levels.

2700 CCT Match tungsten feel 700lm @ 11.5 TCW. Replaced 75W Lamps

AlphaLED Attributes◦ Initial Colour Consistency

1 x 2 step SDCM specification. Consistent wall washing

◦ Colour Consistency Guaranteed No colour shift over life (5 years, 50,000 hrs)

◦ Low Lumen Depreciation L95 50,000 hrs capability

Nottingham Royal Concert Hall

Control Gear◦ DMX Capable – Dim to Zero Light level

EldoLED Powerdrive.

Nottingham Royal Concert Hall

Nottingham Royal Concert Hall• Outcome – Theatre Prospective

• LED/energy saving houselights and dimming, the bottom 10%

• Maintenance and consumable savings (700 bulb changes a year previously)

• Audience reaction to the change

Facts and Figures

Nottingham Royal Concert Hall

Nottingham Royal Concert Hall - Energy Usage          

                   

      Power (W) Qty Total W Total kW

Existing Fittings / Lamps Removed            

300W Par 56     300   60   18000 18

75W R95        75   458   34350 34.35

Total                 52.35

New AlphaLED Product Installed            

Bespoke Atrium 28 Deg Beam              

3000lm CRI80+ 2700K   46.1   60   2766 2.766Atrium with astral bezel              

700lm CRI80+ 2700K     11.5   458   5267 5.267

                  8.033

KW Saving     85% saving         44.317

Facts and Figures◦ The comparison is made assuming the lighting is

used in the same way as the existing lighting.

Nottingham Royal Concert Hall

In Use Energy Consumption   kW   Hrs / Day   No Days Total Kwh

Existing       52.35   14   345 252850.5

New Lighting     8.033   14   345 38799.39

Kwh Saving               214051.11

Use control for further energy savings◦ Tungsten to LED – saves 85% energy

Further energy Savings are possible:◦ LED with DMX allows for various dimming profiles◦ Set 100% for Theatre Customer use◦ Set 65% for cleaning◦ Set 50% at other times

◦ These are examples only

Nottingham Royal Concert Hall

Possible to double the saving

◦ Don’t forget to consider use and control

Nottingham Royal Concert Hall

In Use Energy Consumption   kW   Hrs / Day   No Days Total Kwh

Existing       52.35   14   345 252850.5

New Lighting 100% Level   8.033   4   345 11085.54

New Lighting 65% Level   8.033   5   345 9007.00

New Lighting 50% Level   8.033   5   345 6928.46

Total           14     27021.00

Kwh Saving               225829.50

Additional Saving with dimming profile           187030.11

Original Saving               214051.11

Total saving               401081.22

Conclusions◦ Substantial Energy Savings are possible◦ Light Quality can be matched◦ Day to day maintenance eliminated◦ Further substantial savings with controls◦ Hardware guaranteed 5 years 50,000hrs

Nottingham Royal Concert Hall

Any questions ?Thank You