BayTech
Management Tools for
Remote Locations and Data Centers
The Power to Control
![Page 2: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/2.jpg)
Session Objectives
• Identify Concerns and Objectives of Customers
• Explain Remote Management
• Identify Solutions
![Page 3: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/3.jpg)
Efficient
IT Management
Practices
![Page 4: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/4.jpg)
Identify Concerns of Customers . . .
• “Lights-Out” Initiatives -
Successful implementation of “lights-out facilities” requires the ability to perform tasks typically performed by on-site staff. Remote management tools allow a company to perform tasks remotely.
• Managing Remotely and not “Rolling a Truck” -The average “Truck Roll” costs $250 - $375. When remote management is in place, over 92% of problems are isolated and fixed within minutes – not hours or days.
• Reduction of IT Staff in the Data Center -Corporations are being forced through government and corporate initiatives to get the human error factor away from critical facilities. In order to maintain system integrity, remote management has to be put in place.
• Layoff Stories are Old News -Remote management can greatly enhance a corporation’s ability to monitor and to manage systems with reduced staff.
![Page 5: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/5.jpg)
Identify Objectives of Customers . . .
• Achievement of Higher ROI’s -Remote service capabilities diminish the time factors associated with wait, travel, diagnosis and repair due to system failure or human error.
• Convenience of Remote Communications -By managing power, data and the environment remotely, you reduce the likelihood of “rolling a truck.”
• Realization of a Sustainable Competitive Advantage -Diverse enterprises continually strive towards the best industry standards, including: IT integration, successful business continuity programs, “Five Nine” infrastructure systems and compliance with corporate and governmental regulations.
![Page 6: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/6.jpg)
Remote Management for IT Infrastructure
• Three critical areas for successful implementation
– Managed Power for IT Equipment • On, Off and Reboot
– Monitoring of Power and Physical Environment• Amps, Watts, Temp and Humidity
– Communication with IT Equipment • Console and KVM
![Page 7: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/7.jpg)
Managed Power for IT Equipment
• Practices used in the past include:
– Costly deployment of service personnel to reboot locked data and communication systems.
– Inefficient use of metering devices to test loads on a scheduled time frame.
![Page 8: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/8.jpg)
Managed Power for IT Equipment (On, Off, Reboot)
• Product solutions in use today include:
– Remote Power Control and Metering
– Power Metering and Environmental Sensors
• The essentials of managed power can range from simple monitoring to the wider range of control and detailed reporting.
![Page 9: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/9.jpg)
Managed Power for IT Equipment (On, Off, Reboot)
• Reboot Unresponsive Equipment
– The ability to control power to the receptacle level allows staff to remotely reboot locked equipment and turn off unused receptacles.
• Turn Off Unused Receptacles– Inadvertent tripping of breakers can
be eliminated by leaving unused receptacles in the off position.
• Make Informed Decisions– Circuits can be easily audited for
capacity prior to turning on receptacles. Additionally, part of this process is to document what is assigned to this receptacle.
(Screen Shot of GPM Software)
![Page 10: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/10.jpg)
Monitoring of Power & Physical Environment (Amps, Watts, Temp, Humidity)
• Environmental monitoring is key to maintaining the life expectancy of IT equipment.
• “An 18 degrees increase in temperature over 70 degrees can drop life expectancy as much as 50%.”
RES Remote Environmental Sensor Products
RPS-DE Power Metering and
Environmental Sensor Ability
![Page 11: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/11.jpg)
Monitoring of Power & Physical Environment (Amps, Watts, Temp, Humidity)
• Monitoring the Power Environment
– Managed Power provides continuous monitoring and reporting of current, voltage and power in watts and VA. High and low thresholds can be set for immediate notification via SNMP and E-mail.
– Watts can be directly converted to BTU for planning of the cooling infrastructure.
• Monitoring the Physical Environment
– High temperature reduces the life expectancy of IT equipment. Building automation typically reads the situation outside the cabinet. These solutions provide information regarding conditions inside the cabinet. (Screen Shot of GPM Software)
![Page 12: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/12.jpg)
Communication with IT Equipment
• Communication with IT equipment is integral for successful implementation of “lights-out”. IT staff must be able to remotely troubleshoot communication and data systems.
![Page 13: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/13.jpg)
• BayTech does not manufacture KVM. However, we partner with several KVM companies to bring together a united solution.
Communication with IT Equipment (Console and KVM)
• Console Access via IP• Console Access via embedded modem• Per port username and password• Secure Shell or Telnet connections• Multi and Single User Solution
– With remote management in place IT staff can:• Connect to a server or router• Determine it is locked• Reboot it• Watch it come alive from thousands of
miles away.
![Page 14: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/14.jpg)
Remote Management Provides . . .
Continuous Return on Investment
• Unresponsive equipment is rebooted remotely.
• Response time to network and server problems
is instantaneous.
• Equipment is monitored and controlled from anywhere
and at anytime.
• Environmental problems are isolated sooner.
• Monitoring of power is proactive and continuous.
![Page 15: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/15.jpg)
Managed Power
Identifying the Opportunity, Building the Solution
![Page 16: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/16.jpg)
Building the Managed Power Solution
• Identify the Functions Required
• Establish the Voltage and Current Requirements
• Select the Mounting Method(s)
• Determine the Method of Connectivity
• Select the Features and Management Method
![Page 17: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/17.jpg)
Identify the Functions Required
Product Features Power Distribution
Current/ Voltage/ Power Metering
Receptacle On/Off Reboot
PDU
Power Distribution Unit
RPS
Remote Power Sensor
RPC
Remote Power Control
![Page 18: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/18.jpg)
Control Receptacles and Monitor Power
• RPC (Remote Power Control)
– Control individual receptacles
– Turn and leave off unused receptacles
– Monitor Power (Amps, Voltage, Watts)
– Power Distribution
8 NEMA 5-15R receptacles
15 or 20 Amp Input
NetworkInterface
RS-232Interface
Status LED’s
![Page 19: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/19.jpg)
• RPS (Remote Power Sensor)
– Monitor Power (Amps, Voltage, Watts)
– Power Distribution
Control Receptacles and Monitor Power
![Page 20: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/20.jpg)
Power Distribution
• PDU (Power Distribution Unit)
– Rack mount
– Vertical (Zero-U)
![Page 21: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/21.jpg)
Establish the Voltage and Current Requirements
Voltage and
Current
Single Phase
10 Amp
Single Phase
15 Amp
Single Phase
20 Amp
Single Phase
30 Amp
Three Phase
20 Amp
Three Phase
30 Amp
100-120VAC
NA 1500-1800 Max
Watts
2000-2400 Max
Watts
3000-3600 Max
Watts
5760 Max
Watts
7620 Max
Watts
208-250 VAC
2080-2500 Max
Watts
NA 4160-5000 Max
Watts
6240-7500 Max
Watts
5760 Max
Watts
7620 Max
Watts
• Most customers have already established these standards. As seen in the table above, higher voltage offers more power capacity per circuit.
![Page 22: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/22.jpg)
• Determine the Input and Output Cords and Receptacles
– Input power cords can be either locking or non-locking.
– RPC’s and RPS’s ship with a standard 7’ power cord; required customized lengths may be requested also.
– Output power receptacles are either the NEMA or IEC style.
Establish the Voltage and Current Requirements
• Power cord and receptacle type are typically the most problematic aspects of the product selection stage.
![Page 23: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/23.jpg)
Establish the Voltage and Current Requirements
• Determine the density of the build.
– Low Density: 4 - 8 devices
– Medium Density: 9 - 16 devices
– High Density: 16+ devices
• Consider the number of power cords incorporated into each device. With today’s N+1 standard most equipment is dual corded.
![Page 24: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/24.jpg)
Establish the Voltage and Current Requirements
Rack Mount Solutions
Low density Low Density High Density
Medium Density
![Page 25: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/25.jpg)
Establish the Voltage and Current Requirements
Zero-U Applications
12 Single Corded Devices
20 Single Corded Devices
20 Dual Corded
Devices
12 Dual Corded Devices
![Page 26: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/26.jpg)
Redundancy for Single Corded Devices
16 Single Corded
Devices
8 Single Corded Devices
18 Single Corded Devices
Establish the Voltage and Current Requirements
![Page 27: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/27.jpg)
Select the Mounting Method(s)
• When choosing mounting options, several aspects should be considered.
Vertical Zero-U
Mounting
Horizontal 1- 2-U
Mounting
![Page 28: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/28.jpg)
• Retrofitting existing enclosures can be quite challenging. The majority of older enclosures were shallow rather than wide.
Establish the Voltage and Current Requirements
• Vertical Mounting Considerations Inside Enclosures
– Is there enough depth and width in the enclosure?
(4”- 6” clearance from the back of the mounting rails is recommended)
– What are the height restrictions for the enclosure?
– Are there horizontal guide rails in the way?
– Will there be enough room for power cord management?
![Page 29: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/29.jpg)
• U-Space is “real-estate” to data center managers. Careful consideration should be given to vertical mounting options.
Establish the Voltage and Current Requirements
• Horizontal Mounting Considerations
– Is “U-Space” available?
– How will power cords be managed?
– Based on the number of receptacles required, how many “U’s”
will be used?
– Taking power cord and data cable management into
consideration, where will the units be mounted?
![Page 30: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/30.jpg)
Determine the Method of Connectivity
Monitoring and Control Local RS232
AccessDial-up IP
Number Network Ports Per Strip
RPC’s with Ethernet Port 1
RES Product connected to the RS232 port of the
RPS/RPC 1 for every two strips
F-Series Multi-Session RS-232 Controller 1 for every 32 strips
DS-Series Single-Session RS232 Controllers 1 for every 32 strips
• There are 4 primary methods of connectivity for the RPC’s and RPS’s. The size and scope of the solution should dictate which method is used.
• There are considerable cost considerations in this phase of the selection process.
![Page 31: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/31.jpg)
• The more Ethernet connections - the higher the cost.
• Consider using the DS / F- Series controllers when the solution contains more than 6 RPC’s or RPS’s.
• Remote locations with less then 6 strips should consider.
– RPC’s with Ethernet Ports– Connecting RPC’s or RPS’s to the RES (EMW) controllers
• An Ethernet port on a network switch typically cost $150 - $200. RPC’s with Ethernet ports cost more. When the two are combined, the application cost can rise an average of 28%.
Determine the Method of Connectivity
![Page 32: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/32.jpg)
• RPC’s with Ethernet connections can directly connect to network ports on switches and hubs.
• This method is best suited for smaller “stand alone” solutions.
Determine the Method of Connectivity
![Page 33: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/33.jpg)
• RPC’s and RPS’s with RS-232 ports can be connected to the RES products.
• This method is best suited for smaller “stand alone” solutions.
Determine the Method of Connectivity
![Page 34: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/34.jpg)
• RPC’s and RPS’s can be connected to the RS-232 Ports of the DS-Series or F-Series products.
• This method is best suited for larger enterprise solutions.
Determine the Method of Connectivity
![Page 35: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/35.jpg)
RS-232 connections
Dial-up Connection
Ethernet Connection
TCP/IP SNMP –or Telnet
• The RPC’s or RPS’s are connected via RS-232 from the RPC to the DS / F- Series.
Determine the Method of Connectivity
![Page 36: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/36.jpg)
Select the Management Method
Features Telnet
SSH WEBS
SL
SNMP
NT Domain & Active Directory Security
Outlet Groups
Historical Logging of Events and
Alarms
Graphing of Power
Email Alarm
Notification
RES with RPC’s and
RPS’s
DS-Series with RPC’s and
RPS’s
F-Series with RPC’s and
RPS’s
Global Power Management
(GPM)
![Page 37: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/37.jpg)
• WEB interface
• Optional External Sensor Support
• SNMP Support
• E-mail Alarm Notification
• On-Board Graphing
• Supports up to 4 RPC’s or RPS’s
Select the Management Method
![Page 38: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/38.jpg)
• Telnet • Secure SSH • WEB with secure SSL• SNMP • Dial-up with internal or
external modem• Single Session Support
DS- Series• Multi Session Support
F- Series• Capacity level of 32 strips
per DS or F- Series
Select the Management Method
![Page 39: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/39.jpg)
• Screen shot of the F62 Web Interface
Select the Management Method
![Page 40: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/40.jpg)
Select the Management Method
• Global Power Management (GPM) provides an Enterprise Level Approach to Managed Power in the Data Center.
– Discovers BayTech devices on existing subnet– Builds Logical and Functional Views of RPC’s
in Remote Locations– Supports Equipment with Single or Redundant Power – Provides easy “Click Through” control of RPC’s anywhere– Displays Alerts for All or Individual RPC’s– Notification of Alert via E-mail– Graphically Displays Power Environment per RPC
![Page 41: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/41.jpg)
• Discover controllers on the same subnet, or enter in the IP address of remote controllers.
Select the Management Method
![Page 42: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/42.jpg)
• Build Logical and Functional Views of RPC’s in Remote Locations.
Select the Management Method
![Page 43: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/43.jpg)
• View power readings as a group or individual circuit.
Select the Management Method
![Page 44: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/44.jpg)
• View power trends over time.
Select the Management Method
![Page 45: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/45.jpg)
Building the Managed Power Solution
• Identify the Functions Required
• Establish the Voltage and Current Requirements
• Select the Mounting Method(s)
• Determine the Method of Connectivity
• Select the Features and Management Method
![Page 46: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/46.jpg)
Remote Console Management
Communicating with Equipment
![Page 47: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/47.jpg)
Console Management
• BayTech provides . . .– A way to remotely manage
serial devices through modem or Ethernet.
– The ability to upgrade equipment and troubleshoot hardware from anywhere.
– Used as a switch for BayTech’s RPC products, the console servers eliminate the need for IP resources for each RPC.
![Page 48: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/48.jpg)
Features DS-Series F-Series
TELNET SSH
SNMP WEB/SSL
Expandable Per Port Security
Multi-Session
• The only difference between the DS and F- Series is multi-session support and cost.
Console Management
![Page 49: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/49.jpg)
# PortsDS-Series with
DS62F-Series with F62
4 $ 152.00 $ 219.50
8 $ 88.38 $ 138.38
12 $ 70.50 $ 117.17
16 $ 59.06 $ 102.19
20 $ 52.20 $ 93.20
24 $ 51.79 $ 90.58
28 $ 47.93 $ 85.82
32 $ 45.03 $ 82.25
• The cost per port lowers as the port density rises. This is typical with an expandable system.
Console Management
![Page 50: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/50.jpg)
Environmental Monitoring
Understand the Physical Environment
![Page 51: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/51.jpg)
Environmental Monitoring
FeaturesRPC/RPS with ENV Ports
RES – Series
(EMW)
GPM Software with
DS/F-Series
Stand Alone Operation Web HTTP
Support Historical Graphing
Email Alarm Notification
Secure Authentication
SNMP SupportWith DS/F
Series
RPC Support
![Page 52: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/52.jpg)
• RES Series
Environmental Monitoring
![Page 53: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/53.jpg)
• Simplicity by Design– Easy to install - navigate - sell– No software, no downloads, no hassles– No support calls for setups
• Quick and Easy Setup– Device has 100% of software built-in– Uncluttered and intuitive navigation– “Plug and Play” sensors
• Flexibility and Versatility– “Mix and Match” sensors and RPC’s– E-mail notifications– SNMP polling– “On-board” graphing– Compliant with all operating systems– Zero-U rack mountable
Environmental Monitoring
![Page 54: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/54.jpg)
• RPC/RPS Environmental
– Sensor ports integrated with power management solution
– SNMP management support with DS and F- Series products
– Integration with GPM for graphing
• BayTech’s integrated approach to managing the power and physical environment eliminates the need to have two different products.
Environmental Monitoring
![Page 55: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/55.jpg)
BayTech = 27 Years of Quality Manufacturing
• Bay Technical Associates was founded in 1976.
• BayTech has been developing Data Communication products from the beginning and continues to provide its customers with the equipment necessary to manage a successful network.
![Page 56: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/56.jpg)
Sampling of BayTech’s Customers
• Telecommunications/ InternetMotorola C&W(Exodus)Sprint VerioAT&T YahooMCI GoogleGEACCESS Quest
• FederalU.S. Department of EnergyU.S. Department of DefenseNOAANASAUSAF, USN, & USMCNOA
• Corporate Retail/ ManufacturingWalmart CiscoKmart AdtranTarget AventisBest Buy RamBus
• Financial/Banking
HiberniaWells FargoCargillBank of AmericaEdward D. JonesGMACCSFBLouis Dreyfus
• MedicalChildren’s Hospital Philadelphia Mt. SinaiQuest Diagnostics
• PharmaceuticalsJohnson and JohnsonPfizerGlaxoAmgen
![Page 57: ® BayTech Management Tools for Remote Locations and Data Centers The Power to Control.](https://reader036.fdocuments.net/reader036/viewer/2022062807/56649d435503460f94a1f9d7/html5/thumbnails/57.jpg)