© ABB Group August 8, 2015 | Slide 1 UMC100-FBP Technical Presentation Helmut Schönfelder, ABB...
-
Upload
bernadette-parsons -
Category
Documents
-
view
228 -
download
1
Transcript of © ABB Group August 8, 2015 | Slide 1 UMC100-FBP Technical Presentation Helmut Schönfelder, ABB...
© ABB Group April 19, 2023 | Slide 1
UMC100-FBPTechnical Presentation
Helmut Schönfelder, ABB Stotz-Kontakt, 27.08.2012
© ABB Group April 19, 2023 | Slide 2
UMC100Product Overview
UMC100Universal Motor Controller
UMC100 ATEX Universal Motor Controller
UMC100-PAN Control Panel
DX111/122 Expansion Modules Digital I/O
VI150/155 Expansion Modules Voltage
© ABB Group April 19, 2023 | Slide 3
UMC100Intelligent Motor Protection & Control System
Advanced Motor Protection
Flexible Motor Control
Diagnostics and Maintenance
Communication for all major fieldbusses
© ABB Group April 19, 2023 | Slide 5
UMC UsageWhere are UMCs used
© ABB Group April 19, 2023 | Slide 6
UMC100How are UMCs used
0V +24V Power supply
120 / 230 VAC
M
DI2
DI4
DI5
DI3
15 16 17 18
DI114
DI013
0V
24V
10 11 12
UMC100
DOC
87 9
DOC
5 6
CbCa
3 4
DO0
DO2
DO1
DO3
T2
T1
1 2
max. 1000 VAC
MM
N
Start Stop LocalFault
PTC
FieldBusPlug
CEM11Earth Fault Sensor
© ABB Group April 19, 2023 | Slide 7
UMC100 Motor ProtectionOverview
Comprehensive motor protection for 3-phase motors For motor voltages up to 1000 VAC 50 / 60 Hz
Sinus wave current no drive, no softstarter
For nominal motor currents
240 mA to 63 A without accessories
> 63 A with external current transformer
Protection against Overload according to EN/IEC 60947-4-1
tripclasses 5E, 10E, 20E, 30E, 40E
Rotor blocking
Phase loss / imbalance / sequence
Under- / Overcurrent
Under- / Overvoltage
Under- / Overload overload calculated or based on powerfactor
Hot motor Thermistor
Earth fault calculation or sensor CEM11
Too many starts per time
© ABB Group April 19, 2023 | Slide 8
UMC100 Motor ProtectionOverload Protection according to IEC60947-4-1
Protection based on calculated advanced thermal model
Current value
Thermal load value
Time to trip
Time to cool
Cooling after overload based on
Time or
Thermal load
Thermal overload pre-warning
Five trip classes:5E, 10E, 20E, 30E, 40E
Time
Current
Motor overload protection
Class 40EClass 30EClass 20EClass 10EClass 5E
© ABB Group April 19, 2023 | Slide 9
UMC100 Motor ProtectionLocked Rotor / Long Start Protection
Active during start-up
Extra fast protection when rotor locked
Reduces stress and protection on transmissions
Current level and delay timeto be set individually
start-up running
BlockingCurrent
DelayTime
MotorCurrent
© ABB Group April 19, 2023 | Slide 10
UMC100 Motor ProtectionHigh / Low Current Protection
Active after motor start-up
High Current Protection
Reduce stress and protection on transmissions
Early detection of overload situations
Low Current Protection
Detection of underload situations
E.g. detect a broken belt or a dry pump
Secure the process
Separate trip and warn threshold,each with individual delay timeCurrent levels and delay times
to be set individually
start-up running
Trip Level
Warn Level
Warn Level
Trip Level
MotorCurrent
© ABB Group April 19, 2023 | Slide 11
To avoid accidentsand damages
UMC100 Motor ProtectionPhase Monitoring
Phase loss
Avoid overheating of motor
Phase Imbalance
Detection of imbalanced currents due to voltage variations or motor problems etc.
Warning and trip threshold separately adjustable
Phase Sequence
Prevent wrong rotation – crusher, conveyor..
Important for mobile units
Faults are detectedafter starting the motor
L1,L2 & L3L1,L3 & L2
L1/2/3
© ABB Group April 19, 2023 | Slide 12
UMC100 Motor ProtectionWith additional Voltage Module
With an additional Voltage Expansion Module VI 150 or VI155 UMC100 offers some more motor protection functions
High / Low power
Powerfactor (cosPhi)
Underload important for pump applications
Under / Overvoltage
All settings have warn / trip level and individual delay times
© ABB Group April 19, 2023 | Slide 13
Without Voltage module:
Phase faults can only be detected basedon current during motor operation
With Voltage Module:
Detect problems early –before starting the motor
Protection against
Phase loss
Phase imbalance
Phase sequence
Check for phase faults before starting the motor
UMC100 Motor Protection with Voltage ModulePhase Monitoring
© ABB Group April 19, 2023 | Slide 14
Recommended derating curve by NEMA.
Detection of problems in the supply network
Avoid reduced motor efficiency, overheating and reduction of insulation life -> reduction of life time of the motor
Motors operating with unbalance will benoisier in their operation
Available Functions
Overvoltage
Undervoltage
Voltage phase loss and imbalance
Harmonic distortion (THD)
Different warn - and trip levels
Balanced unbalanced
Protection of motor and equipment
UMC100 Motor Protection with Voltage ModulePhase Monitoring
© ABB Group April 19, 2023 | Slide 15
UMC100 Motor ProtectionPTC/Thermistor High Temperature Protection
For motors with integratedPTC elements
Detects obstructed cooling
Motors located in high temp areascan be exposed to high ambient temperatures
Can not be detected by an EOL
Cable short circuit and break detection
Fault or warning configurable
© ABB Group April 19, 2023 | Slide 16
Protection against earth fault due to damaged cable isolation etc.
4 different types available
8 threshold values for precise adjustment
Threshold range size
80 … 1.700 mA 20 mm Ø
100 … 3.400 mA 35 mm Ø
120 … 6.800 mA 60 mm Ø
240 … 13.600 mA 120 mm Ø
Can be used in all types of networks also with higher impedance to ground
also small ground fault currents can be detected
L1 L2 L3
24VDC
Protection of motorand equipment
UMC100 Motor ProtectionEarth Fault Protection with CEM11
© ABB Group April 19, 2023 | Slide 17
L1 L2 L3
Protection of motorand equipment
UMC100 Motor ProtectionEarth Fault Protection internal
Protection against earth fault due to damaged cable isolation, etc.
Trip and warn level
Active after startup or always
Preconditions Ground fault current must be
> 20% of Ie to be detected.
Only usable in networks with low impedance to ground
only higher ground fault currents can be detected
© ABB Group April 19, 2023 | Slide 18
UMC100 Motor ProtectionCheckback Supervision
Check supervision ensures that the motor is really running after a start command
Three options for checkback
Checkback current based (default)
Checkback via an auxiliary contact on the main contactor.Connect auxiliary signal to DI0 of UMC
Simulation: no checkback at all, for test purposes only
Checkback delay time is adjustable
© ABB Group April 19, 2023 | Slide 19
UMC100 Motor ProtectionLoad Shedding (Voltage DIP)
Application:
Stop motor in case of undervoltage
Automatic motor restart once voltage is back
Configuration:
Minimum time to detect undervoltage
Maximum time for automatic restart
Delay time for motor restart
Undervoltage detection by
External voltage monitor or
Voltage expansion module VI150 / VI155
© ABB Group April 19, 2023 | Slide 22
UMC100 Motor Control and ProtectionLimitation of Starts per Time
Application:
Protect the motor against too many starts in a short time
Limit the number of starts for a given time period
Enforce a pause time between two motor starts
Configurable fault / warning in case of one start left
© ABB Group April 19, 2023 | Slide 23
UMC100 Motor ControlOverview
Most common motor starters are integrated aseasy to parametrize control functions
Direct / Reverse / Star-Delta starter
Pole changing / Dahlander
Actuator mode (Open / close valve control)
Overload Relay
Transparent mode for feeders
Custom Application Editor for individual control functions
Support of different control stations
(DCS, Local bottons, Operation Panel ...)
Support of different operation modes
Remote, Local 1, Local 2
© ABB Group April 19, 2023 | Slide 24
UMC100 Motor ControlIntegrated Motor Starters
Motor starters
Direct Starter
Reversing Starter
Star-Delta Starter
Two-Speed Starter
Others
Different Actuators Open/Close Valve Control
Overload Relay Standalone applicationwithout fieldbus
Transparent Mode Feeder applications
© ABB Group April 19, 2023 | Slide 25
UMC100 Motor ControlIntegrated Motor Starters
Easy to configure – only 3 settings for overload protection
1. Select Starter type
2. Set nominal motor current
3. Set tripclass
Reduced engineering effort in the DCS
No further programming in the device required
Example DOL
© ABB Group April 19, 2023 | Slide 26
UMC100 Motor ControlCustom Application Editor
In most cases the built-in logic is flexible enough
but
for special requirements an individual starter application can be created
This is done with the “Custom Application Editor”, which is part of the PBDTM software package
Application Editor includes a library with function blocks for
UMC100 inputs / outputs
Logic functions
Basic functions
Control functions
Expansion modules
© ABB Group April 19, 2023 | Slide 27
UMC100 Motor ControlCustom Application Editor
2 ways how to set up a Custom Application Logic
Full flexibility
Start from zero
Build up logic step by step
result is an individual starter function
Easy way
Use the ABB standard starter and modify it as required
Advantage: use of ready and tested starter functions
In most cases only small modifications will be required
© ABB Group April 19, 2023 | Slide 28
UMC100 Motor ControlCustom Application Editor
Network View:All devices onthe fieldbus
UMC DTM
© ABB Group April 19, 2023 | Slide 29
UMC100 Motor ControlCustom Application Editor - The most basic application
Basic DI represents the digital inputs of UMC100 and the multifunction options
Fault Reset allows to acknowledge protection trips
Direct Starter handles all the logic to start a motor in one direction (check-back supervision …)
© ABB Group April 19, 2023 | Slide 30
UMC100 Motor ControlCustom Application Editor - Full application
Drawing Area
Function BlockLibrary
Tool Bar
© ABB Group April 19, 2023 | Slide 31
UMC100 Motor ControlHardware - Digital Inputs
Six digital inputs DI0 ... DI5
DI0 ... DI2: Configurable Multifunction inputs
Alarm / Warning / ...
Delay time
NO/NC
Autoreset, Fault text
DI3 ... DI5: Predefined inputs
Start Forward / Reverse / Stop
Jog / Inching mode
NO/NC
All inputs can be read by the DCS independent fromtheir setting
© ABB Group April 19, 2023 | Slide 32
UMC100 Motor ControlHardware - Multifunction Inputs
Easy to configure Separate settings for function and delay time Most functions selectable as NO or NC External Fault with configuration of
Individual text with 2 x 8 characters Autoreset Delay time
© ABB Group April 19, 2023 | Slide 33
UMC100 Motor ControlHardware - Multifunction Inputs
Off
Stop (NO/NC)
Ext. Fault always (NO/NC)
Ext. Fault Motor on (NO/NC)
Prep. emerg. Start (NO/NC)
Testposition (NC/NC)
Force local 2 (NO/NC)
Fault reset (NO/NC)
Voltage DIP (NO/NC)
CEM11 Warning always
CEM11 Warning after startup
CEM11 Fault always
CEM11 Fault after startup
Delay time configurable
© ABB Group April 19, 2023 | Slide 34
UMC100 Motor ControlHardware - Digital Outputs
3 x Relay Outputs DO0 ... DO2 Switching the motor contactors
Directly controlled by the control function in the UMC
Free outputs can be controlled by the DCSor the UMC100 Customer Application
DO2 can be configured as fault output
1 x 24V Transistor Output DO3 Configurable as fault output
or controlled by DCS
or controlled by Customer Application Logic
Fault Output: Configurable On / Off / Flashing in case of fault
© ABB Group April 19, 2023 | Slide 35
UMC100 Motor ControlControl Stations
Flexible definition where and when motor start/stop is allowed
4 Control Stations
Fieldbus (cyclic, acyclic)
Push buttons on DIs
LCD Operator Panel
3 modes: Local 1, Local 2, Auto
Individually to configure for each modewhich control station is allowed to start/stop
Depending on busfault, force local 2 and the autobit one of the 3 modes is active
© ABB Group April 19, 2023 | Slide 36
UMC100 Motor ControlFault Reset
Fault reset via Bus, LCD Panel or Digital Input
Manual reset of protection faults
Manual or automatic fault reset of faults coming from the multifunction inputs or inputs of the digital IO module
© ABB Group April 19, 2023 | Slide 37
UMC100 Motor Control Expansion Modules I/O DX111, DX122
8 galvanic isolated DIs
4 relay outputs
1 Analog output (0/4-20mA, 0-10V)to drive current meter or to a DCS
2 separate roots for the relay outputs and the DI
Flexible mounting:Up to 3m distance between UMC100 and DX1xx
2 Types
DX111 DIs 24 V DC
DX122 DIs 110 / 230 V AC
© ABB Group April 19, 2023 | Slide 38
UMC100 Motor Control Using the Digital I/O Expansion
Usable without programming
Options
Disabled, Fault, or Warning
Autoreset
Delay
Fault text
Fault message displayed on the LCD
DI always available in the DCS
© ABB Group April 19, 2023 | Slide 39
UMC100 Motor Control Expansion Modules Voltage VI150, VI155
3 voltage inputs L1, L2, L3
150 – 690 V AC
1 relay output
Flexible mounting:Up to 3m distance between UMC100 and VI15x
2 Types
VI150 grounded networks
VI155 grounded networksungrounded netw.altitudes >2000 m
For use with UMC100 R0101
© ABB Group April 19, 2023 | Slide 40
UMC100 Motor ControlExpansion Modules Voltage VI150, VI155
Additional features with Voltage module Protection
Under / Overvoltage protection
Under / Overload protection
Power factor (cos Phi)
Voltage based phase loss / imbalance / sequence
Diagnostics 3 Phase voltages
Powerfactor
Voltage imbalance
Active power
Apparent power
Energy
THD Total harmonic distortion
© ABB Group April 19, 2023 | Slide 41
UMC100 DiagnosticsGeneral
Comprehensive information via fieldbus and LCD operator panel
Motor data
Status
Current
3 Phase Voltages
Active Power
Powerfactor
Thermal Load
Start-up time and max. current
Time to trip, Time to cool
© ABB Group April 19, 2023 | Slide 42
UMC100 DiagnosticsGeneral
Faults and Warnings
Shown as text on the display
Maintenance counters
Operating hours of motor
Number of starts
Number of overload trips
Energy
Event memory for the last 16 events
© ABB Group April 19, 2023 | Slide 43
UMC100 DiagnosticsControl Panel UMC100-PAN
Monitor DIO
Current (A, %)
Alarms
Display user defined values
Operate Start
Stop
Fault Acknowledge
Configure All parameters can be set
Optional Password Protection
Copy parameters and / or logic
Contextdependenthot-key 1
Contextdependenthot-key 2
Scroll up-and downbuttons
StartStop
© ABB Group April 19, 2023 | Slide 44
UMC100 DiagnosticsControl Panel UMC100-PAN
Graphical display
Shows up to 4 lines
Text instead of cryptical codes
Backlight
Multilanguage
English, French, German
Italian, Portuguese, Spanish, Russian
5 User defined displays on top menue
Customer defined fault texts
2 x 8 characters
Customer defined tag name
© ABB Group April 19, 2023 | Slide 45
UMC100 DiagnosticsControl Panel - Top Level Menu
… …
© ABB Group April 19, 2023 | Slide 46
UMC100 Diagnostics Control Panel – Operation Mode
From any top level menu via left soft-key Direction: For/FFor/Rev/FRev
(depending on control function) Key-Up/Down changes the direction
selection Dedicated keys for Start / Stop Icons in the bottom line show current
output status Rem / Loc is shown in the bottom line
depending on mode Option: password protection
© ABB Group April 19, 2023 | Slide 47
UMC100 DiagnosticsControl Panel – Set Parameters
Press the right context menu button to enter the parameter menus
From there you can enter the different submenus
Submenues can contain further sub-menus
At the end one ore more parameters can be adjusted
© ABB Group April 19, 2023 | Slide 48
UMC100 Diagnostics Control Panel - Acknowledge Faults
In the event of an error the left hotkeycan be used to enter the error menu
Errors are shown there
Errors can be acknowledged there
© ABB Group April 19, 2023 | Slide 49
UMC100 Communication Fieldbuses and Networks
UMC100 can be connected via FieldBusPlug to
Modbus TCP new
PROFIBUS DP
DeviceNet
Modbus RTU
CANopen
Only one version of UMC100 for all fieldbuses and networks
Full motor protection and control in case of a bus failure
Fieldbus interface and UMC can be mounted separately - perfect for withdrawable MCC applications
Parameterization via device description files (GSD, EDS) or Operator Panel or PC Configuration Tool
© ABB Group April 19, 2023 | Slide 50
UMC100 Communication Fieldbuses and Networks
Example with PROFIBUS
Support of all relevant fieldbusses and networks
PROFIBUS DP V0/V1 PDP22, PDQ22
Modbus RTU MRP21
Ethernet Modbus TCP MTQ22 new
DeviceNet DNP21
CANopen COP21
© ABB Group April 19, 2023 | Slide 51
UMC100 Communication Separation of Busnode and Device
FBP InterfaceCable
LCD Control Panela) Drawer mountedb) or remote mounting
UMC100
Panel ExtensionCable
Fits in very space limited installations!
© ABB Group April 19, 2023 | Slide 52
UMC100 Communication Separation of Busnode and Device
Application with FBPin a Drawer System
© ABB Group April 19, 2023 | Slide 53
UMC100 Communication Separation of Busnode and Device
Robust solution to connect fieldbus with motor controller inside a drawer: No trunklines!
Busnode stays alive while drawer gets exchanged All required accessories available: control panel extension,
inside and outside passive cable and fixing bracket
© ABB Group April 19, 2023 | Slide 54
UMC100 Communication Separation of Busnode and Device
Application with PDQ22in a Drawer System
© ABB Group April 19, 2023 | Slide 55
UMC100 CommunicationEthernet – Modbus TCP with MTQ22 new
Ethernet connectivity forup to four UMC100
Modbus TCP protocol
Supports differentnetwork topologies
Star
Bus
Ring with redundancy
Easy to use
Easy to setup
No special Ethernet connectorsrequried in MCCs
UMC100 Communication Ethernet – Network topologies new
© ABB Group April 19, 2023 | Slide 56
The ring topology offers cable redundancy on Ethernet side
A managed switch supporting MRP and acting as MRP manager must be used in this case
The implemented media redundancy protocol (MRP) is according to EN/IEC 62439-2
© ABBMarch 2012 | Slide 57
UMC100 Communication Ethernet – Redundant ring topology new
In ring or line setup the devices arenot reachable if just two drawersare withdrawn
Complex and expensive Ethernet connectors are required to short-cut Ethernet lines when drawers are withdrawn to overcome the above mentioned problem
Problems with long timeouts canoccure because of missing devices
General problem: 10/100MBit communication inside a drawer
UMC100 Communication Ethernet – Competitor’s solution new
© ABB Group April 19, 2023 | Slide 58
UMC100 Communication Ethernet – Solution with MTQ22 new
© ABB Group April 19, 2023 | Slide 59
Other UMCs / MTQs are always reachable
If drawer withdrawn
If MTQ not reachable becauseof a cable break
No special Ethernet connectorsfor drawers needed
No need to link 100MBit into drawers
UMC100 CommunicationEthernet – Modbus TCP with MTQ22
To drawer4x
2x
Network – SwitchSupply for switch,MTQ22
Network – SwitchSupply for switch,MTQ22
For a ring goback to switchFor a ring goback to switch
24 V DC
MTQ22 Supply
To next MTQ22
To drawers
To switch
Simple connection fromMTQ22 to drawers
Ready made cables available
Or make own cables
Terminal blocks available separately
© ABB Group April 19, 2023 | Slide 60
UMC100 Communication Ethernet – Modbus TCP with MTQ22 new
Advantages
Multimaster functionality – up to 4 masters supported
Supports MRP protocol EN/IEC 62439-2 for redundancy
No Ethernet inside a drawer – no need to bring in 100 Mbit/s
Simple connection between MTQ22 and UMC100 –No special Ethernet connectors required
Redundancy even works with several drawers taken out
All types of UMCs are supported – easy system upgrade
Micro USB port for configuration via PC
© ABB Group April 19, 2023 | Slide 61
© ABB Group April 19, 2023 | Slide 62
Fast installation through ready made cables
CDP18, CDP19
No issues in withdrawable systems
Ethernet not inside the drawer!
No special Ethernet connectors required when using in a MCC
UMC100 Communication Ethernet – MTQ22 and withdrawable solution
© ABB Group April 19, 2023 | Slide 63
Fast installation
Communication via ready made cable
CDP17
No special Ethernet connectors required
UMC100 Communication Ethernet – MTQ22 and fixed setup
© ABB Group April 19, 2023 | Slide 64
PC tool for configuration
Standard Micro USB interface
Online / Offline
UMC100 Communication Ethernet – MTQ22 setup
© ABB Group April 19, 2023 | Slide 65
UMC100 Communication Monitoring Data: UMC100 -> Control System
© ABB Group April 19, 2023 | Slide 66
UMC100 Communication Command Data: Control System -> UMC100
© ABB Group April 19, 2023 | Slide 67
UMC100 Communication Diagnosis Data: UMC100 -> Control System
© ABB Group April 19, 2023 | Slide 68
UMC100 CommunicationEngineering Workflow
Configure UMC100 with
LCD Panel
GSD, EDS
HWD
DTM
No Programming
Customer Requirements
Predefined logicsufficient 80% / 20%
Predefined logicnot sufficient
Change control logic with function block editor
Download / test application
Change function block parameters and protection parameters simply via configuration (like left side)
© ABB Group April 19, 2023 | Slide 69
UMC100 CommunicationConfiguration via Device Description Files (GSD, EDS)
Table based configuration within the control system. Download of parameters during bus start / engineering time.
Custom applications can’t be changed
PROFIBUS:
Separate GSD files for PDP22 and PDQ22
CANopen / DeviceNet
EDS files for each bus
Latest GSD and EDS files are always available on the internet side
PROFIBUS Example
© ABB Group April 19, 2023 | Slide 70
UMC100 CommunicationConfiguration via Device Type Manager (DTM)
Very comfortable way to configure all parameters and functions of the UMC
Explanation of parameters through images …
Custom applications can be created and downloaded into the UMC100
Offline engineering of devices and whole bus lines
Online monitoring and diagnosis on PROFIBUS
Same tool and PC communication adapter as used by ABB Instrumentation
© ABB Group April 19, 2023 | Slide 71
UMC100 Communication Configuration via PC-Adapters
Using the open FDT/DTM standard
Point to point connection via UTF21
Profibus connectionvia UTP22
© ABB Group April 19, 2023 | Slide 73
UMC100 Product Assortment
UMC100-FBP Universal Motor Controller
UMC100-FBP Universal Motor Controller ATEX
DX111 I/O Expansion module Inputs 24 V DC
DX122 I/O Expansion module Inputs 110 / 230 V AC
VI150 Voltage Expansion module Grounded networks
VI155 Voltage Expansion module Un-/Grounded networks
UMC100-PAN Operating panel
UMCIO Cable UMC100 – expansion module
IOIO Cable expansion module – exp. module
PBDTM DTM software packageIncludes the Custom Application Logic Editor
© ABB Group April 19, 2023 | Slide 74
UMC100 Product AssortmentEthernet communication new
MTQ22-FBP.0 Ethernet Modbus TCP Interface
CDP17-FBP.150 Cable MTQ22 – UMC100 Length 1,5 m
CDP18-FBP.150 Cable MTQ22 – drawer outside Length 1,5 m
CDP19-FBP.100 Cable UMC100 – drawer inside Length 1 m
CDP11-FBP.0 Passive cable fixing bracket 50 pcs
CDP11-FBP.4 Passive cable fixing bracket 4 pcs
ETHTB-FBP.4 Terminal blocks 4 pcs
ETHTB-FBP.50 Terminal blocks 50 pcs
© ABB Group April 19, 2023 | Slide 75
UMC100Summary
UMC100 integrates
Advanced Motor Protection
Flexible Motor Control
Diagnostics and Maintenance Data
Fieldbus Communication for all major busses
Perfect solution for Motor Control Centers
Can be adapted to almost all customer requirements
Built-in logic -> just configure
Customer specific logic -> logic editor
Powerful LCD panel for monitoring, parameterization and control