Cabling a Rackmounted9910-P33 UPS

i5 or p5 with one PDU or two (redundant) PDUs

How to Connect the Power and Interface (Communication) Cables

World Trade (WT)

Page 2: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

2

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Receiving the Rack

UPS will be installed in rack If selected “Rack Install” features in the configurator

Connections that need to be completed Power

• UPS to utility (mains)

• UPS to PDU / Devices

Interface (communications)• UPS to server(s)

Page 3: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

3

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Getting Acquainted with the P33

Location of UPS• Installed at bottom of rack

• Connections make @ rear of rack

What a P33 UPS looks like from the rear

Page 4: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

4

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Line cords & connectors

C13 connector- 10A rated (female)Rack, HD & E PDU outletsMating connector to server used onP33 and PDU Outlets

C14 connector- 10A rated (male)The inlet on most servers & optionsRack jumper cords

C19 connector- 16A rated (female)P33 Outlet

C20 connector- 16A rated (male)P33 inlet and Part of BladeCenter line

cord

Lower number is female. Power flows from female to male.

Page 5: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

5

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

PDU line cord #6656

UPS outputline cord PN

53P1968(1/2 of #9855)

Customersupplied

receptaclevaries

PDU #7188 or#9188

Power Cabling with one PDU & #9855 to 16A Plug

520 or 550 withRedundant Powersupplies #5158 or #7889 being fed

by non-redundantpower source

Server power cablesto one PDU - non- redundant

UPS inputline cord PN

varies

This example showsa server with redundantpower supplies beingpowered by one PDU.Therefore, this installationis classified as non- redundant

POWER CORD TABLEFC Description9866 CEE7 VII Type 189867 SABS 164 Type 229868 CEI 23-16 Type 259871 IEC309 P+N+G 16A Type 469872 SII 32-1971 Type 329874 SAA-AS 3112 Type 549875 IEC 60083-A5 Type 64

Page 6: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

6

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

PDU line cord #6656

UPS outputline cord PN

53P1968(1/2 of #9855)

PDU line cord #1449

PN 21H7693

Customersupplied

receptacleIEC309

P+N+G 32A

PDU #7188 or#9188

Power Cabling with one PDU & #9855 to 32A Plug

520 or 550 withRedundant Powersupplies #5158 or #7889 being fed

by non-redundantpower source

Server power cablesto one PDU - non- redundant

UPS inputline cord PN

53P1969(1/2 of #9855)

This example showsa server with redundantpower supplies beingpowered by one PDU.Therefore, this installationis classified as non- redundant

Page 7: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

7

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

PDU line cord #6656

UPS outputline cord

PN 53P1968(1/2 of #9855)

PDU line cord #1449

PN 21H7693

Customersupplied

receptacleIEC309

P+N+G 32A

PDU #7188 or#9188

Power Cabling with two PDUs

520 or 550 withRedundant Power

supplies #5158 or #7889 being fed by redundant

power sourceUPS inputline cord

PN 53P1969RedundantPDU line

cord #6656

Customersupplied

receptacleIEC309

P+N+G 32A

2nd or redundant PDU

Server power cablesto two redundant PDUs

UPS input line cordshown using 30/32Aplugs as an exampleonly.

Page 8: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

8

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface Cabling i5 to P33

520 or 550UPS port

P1-T1

Install i5 UPS Interface

Cable #1827(included with i5)

Install X-Slot Relay Card

#2936

Install UPS to #1827Interface CablePN 05142494

(included with #2936)Follow Relay Card Quick Start Guide directions to set UPS

monitoring functions in i5 OS

Page 9: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

9

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface Cabling iSeries to P33

8xx Series UPS port

“J14” or ”UPS”

Install X-Slot Relay Card

#2936

Install UPS Interface CablePN 05142494

(included with #2936)

Follow Relay Card Quick Start Guide directions to set UPS

monitoring functions in OS/400 OS

Page 10: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

10

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface Cabling i5 & serial to P33

520, 550 or 570UPS port

P1-T1

Install i5 UPS Interface

Cable #1827(included with

i5)

Install X-Slot Relay / SerialCard #2939

Install UPS to #1827

Interface CablePN 124902074-030

(included with #2939) Follow Relay / Serial Card Quick

Start Guide directions to set UPS monitoring functions in i5 OS and

serial (TTY) server.

Serial (TTY)server

Install UPS to serial Interface

Cable PN 124102022-

003(with #2939)

Install LanSafe Software (contained on CD)

onto server

Page 11: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

11

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface - p5 Options

Serial (Non-LPAR) One to three serial

connections possible

LPAR (Logical PARtitions of the p5 Operating System)

Requires a p5 Ethernet connection

Must use #2934 Web/SNMP card

Page 12: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

12

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface (Serial) p5

p5 520 or 550 NOTE: Must have 2-port Asynchronous

EIA - 232 PCI Adapter #5723

Install UPS serial Interface CablePN 124102022-002

(contained in P33 AccessoryKit PN 21P7229)

Follow Multi-ServerUser’s Guide to set

UPS monitoring functions

NOTE: Obtain 5200-05 Maintenancepackage (APAR IY66260) for AIX 5.2L V5.2

and the 5300-01 maint. Pkg. For AIX 5.3L V5.3(APAR IY62267) from IBM

Multi-Serial Card shown.Your P33 may have asingle serial port card.

Install LanSafe Software (contained on CD)

onto p5

Page 13: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

13

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Interface for LPARs (Ethernet) p5

p5 520 or 550 NOTE: Must have Ethernet Port

Follow ConnectUPSWeb/SMMP User’s Guide

to set UPS monitoring functions

Install ConnectUPS Web/SNMP Card

#2934

Install EthernetCable - customer

supplied

Install NetWatch Software (contained on CD)onto each LPAR

Page 14: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power.

14

i5 & p5 Training WT

Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005

Completing Start-Up

You have finished the power and connectivity installation process

Continue with Start-up instructions in User’s Manuals

Questions? Contact: The local IBM office supporting your account Eaton Power Quality Global Services