Post on 03-Feb-2022
Wireless High Level Analog Input Transmitter Series XYR 6000, Model STIW600 Specifications 34-XY-03-30 February 2010
Introduction
Building upon the tremendously successful ST 3000
series transmitter line; Honeywell brings simple, safe, and
secure wireless technology to its measurement portfolio
in the XYR 6000 Series Wireless Transmitters.
The XYR 6000 series measurements are part of the
Honeywell OneWireless system and are ISA100.11a
Compliant.
Measurement and information without wires! The XYR
6000 wireless transmitter series enable customers to
obtain data and create information from remote and
hazardous measurement locations without the need to
run wires, where running wire is cost prohibitive and/or
the measurement is in a hazardous location. Without
wires, transmitters can be installed and operational in
minutes, quickly providing information back to your
system.
XYR 6000 wireless transmitters send information to an
ISA100.11a compliant MESH infrastructure. Wireless
Data Managers (WDM) provides the path to bring that
information into Experion PKS or any other control
system wirelessly via OPC client or Modbus-TCP.
Transmitter power is supplied by two “D” size lithium
batteries in an intrinsic safe module with an expected
lifetime of up to ten years or by an external 24 Vdc power
pupply. Transmitter range with the integral antenna is
1000’ (305 m) under ideal conditions.
The HLAI Transmitter can be used to convert any
measurement device with a 4-20mA/1-5 V output into a
wireless sensor; for example, analytical, flow, or level
measurements. The HLAI can be used with measurement
devices that have Intrinsic Safety approval to make a
wireless measurement while retaining the Intrinsic Safety
rating.
Model STIW600: (0 to 5 Volts, 1 to 5 Volts, 0 to 20 mA 4 to 20 mA)
Figure 1 — XYR6000 High Level Analog Input Transmitters
Only 0/4 to 20 mA inputs are certified as Intrinsically
Safe. 0/1 to 5 V inputs are not certified as Intrinsically
Safe.
Implement the value of wireless technology today:
Measure remote access points simply, safe and
securely
Obtain and utilize previously inaccessible
information due to high wiring cost or hazardous
locations.
Easily meet Regulatory Requirements
Improve process efficiency
Enhance Flexibility to monitor applications:
- that have no access to power
- that are remote or difficult to reach
- that may require frequent reconfiguration
- where manual readings have been required
previously
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 2
Specifications
Operating Conditions
Parameter Reference Condition
(at zero static)
Rated Condition Operative Limits Transportation and Storage
°C °F °C °F °C °F °C °F
Ambient Temperature** 25 ±1 77 ±2 -40 to 85* -40 to 185* -40 to 85* -40 to 185* -40 to 85 -40 to 185
Humidity %RH 10 to 55 0 to 100 0 to 100 0 to 100
Ambient Temperature LCD Display visible range
25 ±1 77 ±2 -40 to 85°C -40 to 185°F
Vibration Maximum of 4g over 15 to 200Hz.
Shock Maximum of 40g.
Battery powered 3.6V Lithium thionyl chloride (LiSOCl2) batteries non rechargeable, size D
Power 24VDC Wired Power (option) - For I.S. Application: 21 V to 25 Vdc Operated with MTL7728P+ barrier (252 Ohms Max. end to end resistance), Max input current 26mA. For Non I.S. application: 11 V to 30 Vdc Input range, Max input current 100mA.
*24V power option rated 80°C (176°F)
** The Ambient Limits shown are for Ordinary Non-Hazardous locations only. Refer to the appropriate Control Drawing, FM/CSA, ATEX, or
IECEx for the Ambient Limits when installed in Hazardous Locations.
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 3
Wireless Specifications
Parameter Description
Wireless Communication
2,400 to 2,483.5 MHz (2.4 GHz) Industrial, Scientific and Medical (ISM) band
FHSS Selection – Frequency Hopping Spread Spectrum
DSSS Selection – Direct Sequential Spread Spectrum per FCC 15.247 / IEEE 802.15.4–
2006.
ISA100.11a Compliant (2.4 GHz Direct Sequence Spread Spectrum 802.15.4 DSSS-FH)
Every data packet transmitted in either direction is verified (CRC check) and acknowledged by the receiving device.
USA – FCC Certified
Canada – IC Certified
European Union – RTTE/ETSI Conformity
Japan – Ministry of Internal Affairs and Communications Certified (DSSS Selection only)
ISA100.11a RF
Transmitter Power
(Optional)
NA Selection – 125 mW (20.9 dBm) maximum transmit power not including antenna per FCC/IC, or 400 mW (26.0 dBm) maximum EIRP including antenna for USA and Canadian locations.
EU Selection – 10 mW (10.0 dBm) maximum EIRP including antenna per RTTE/ETSI for EU locations.
FHSS RF Transmitter Power (Optional)
NA Selection – 125 mW (20.9 dBm) maximum transmit power not including antenna per FCC/IC, or 400 mW (26.0 dBm) maximum EIRP including antenna for USA and Canadian locations.
EU Selection – 100 mW (20.0 dBm) maximum EIRP including antenna per RTTE/ETSI for EU locations.
DSSS RF Transmitter Power (Optional)
NA Selection – 125 mW (20.9 dBm) maximum transmit power not including antenna per
FCC/IC, or 400 mW (26.0 dBm) maximum EIRP including antenna for USA and Canadian locations.
EU Selection – 10 mW (10.0 dBm) maximum EIRP including antenna per RTTE/ETSI for EU locations.
JP Selection – 12.14 dBm/MHz [32mW (15.14 dbm)] maximum EIRP including antenna for Japanese locations.
Data PV Publish Cycle Time: Configurable as 1, 5, 10 or 30 seconds
Rate: 250 Kbps
Antennas Integral – 2 dBi omnidirectional monopole
Integral – 4 dBi omnidirectional monopole
Remote – 8 dBi omnidirectional monopole with up to 20 m cable and lightning surge arrester.
Remote – 14 dBi directional parabolic with up to 20 m cable and lightning surge arrester.
Signal Range Nominal 305 m (1,000 feet) between Field Transmitter and Infrastructure Unit (Multinode) or Gateway Unit when using 2 dBi Integral antenna with a clear line of sight.*
Routing vs Non-Routing Unit can be set as a Field Routing or non-Field Routing device; the number of routing devices is set by the system manager.
Using the device as a routing device will impact battery life, the more messages routed through a device, the greater the impact on battery life.
* Actual range will vary depending on antennas, cables and site topography.
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 5
Remote Antennas
4 dBi Omnidirectional Antenna 8 dBi Omnidirectional Antenna 14 dBi Directional Antenna
Performance under Rated Conditions
Parameter Description
Accuracy ±0.10% of range at reference conditions for linear inputs
Temperature Effects ±0.10% of range per °C
Stability ±0.10% of URL per year
Stray Rejection Common Mode (50 or 60 Hz): 120 dB
Normal Mode (50 or 60 Hz): 40 dB
Loop Resistance 0-20/4-20 mA input
24.9 Ohms
Lightning Surge Arrester (Remote antenna only)
Frequency range: 0 – 3 GHz, 50 Ohms, VSWR = 1:1.3 Max, Insertion Loss = 0.4 dB Connectors Type N Female, Max, Gas Tube Element: 90 V ± 20%, Impulse Breakdown Voltage = 1,000 V ± 20%, Maximum Withstand Current = 5 KA.
CE Conformity These transmitters conform with the protection requirements of European Council Directives: 89/336/EEC, the EMC Directive and 1999/5/EC, the Telecommunications Directive per EN 300 328, V1.6.1 (2004-11), EN 300 489-1, V1.6.1 (2005-09), EN 300 489-3, V1.4.1 (2002-08) and EN 61326-1997+A1+A2, Electrical Equipment for Measurement, Control and Laboratory Use – EMC Requirements.
Hazardous Location Certifications See the Model Selection Guide on page 9.
Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, and 10 to 55% RH.
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 6
Physical Specifications
Parameter Description
Mounting Bracket Carbon Steel (Zinc-plated) or Stainless Steel angle bracket or Carbon Steel flat bracket available (standard options).
Terminal Assembly wiring gauge range
28 to 16
Electronic Housing
Stainless Steel Housing (option)
Epoxy-Polyester hybrid paint. Low Copper-Aluminum. Meets NEMA 4X (hosedown and corrosion resistant), IP 66/67 (hosedown and submersible to 1m).
316 SS Electronics Housing - with M20 Conduit Connections
316 SS Housing with 1/2" NPT Conduit Connection
316 SS or Grade CF8M, the casting equivalent of 316 SS with M20 or 1/2" NPT Conduit Connection.
If ordered with the Remote Antenna options, the antenna parts are not SS or Marine type cables; the integral antenna uses SS parts.
Mounting Can be mounted in virtually any position using the standard mounting bracket. Mounting should result in the antenna being vertically oriented. Bracket is designed to mount on 2-inch (50 mm) vertical or horizontal pipe. See Figure 3.
Dimensions See Figure 4.
Net Weight Approximately 9 pounds (4.1 Kg)
Wiring
1
2
3
5
4
6
+
-
0-5V1-5V
+
-
1
2
3
5
4
6
+
-
0-5V1-5V
+
-
1
2
3
5
4
6
+
-
0-20 mA4-20mA
+
-
1
2
3
5
4
6
+
-
0-20 mA4-20mA
1
2
3
5
4
6
+
-
0-20 mA4-20mA
+
-
Figure 2 - Wiring: voltage (left), current (right)
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 7
Mounting
Figure 3 — Examples of typical mounting positions
Figure 4 — Typical mounting dimensions for reference.
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 8
Options
Mounting Bracket
The angle mounting bracket is available in either zinc-plated carbon steel or stainless steel and is suitable for horizontal or vertical mounting on a two inch (50 millimeter) pipe, as well as wall mounting. An optional flat mounting bracket is also available in carbon steel for two inch (50 millimeter) pipe mounting.
Tagging (Option TG)
Up to 30 characters can be added on the stainless steel nameplate mounted on the transmitter’s electronics housing at no extra cost.
A stainless steel wired on tag with additional data of up to 4 lines of 28 characters is also available. The number of characters for tagging includes spaces.
Transmitter Configuration
All configurable parameters are accessible via the
OneWireless network via READ/WRITE transactions.
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 9
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at:
http://hpsweb.honeywell.com/Cultures/en-US/Products/Instrumentation/ProductModelSelectionGuides/default.htm
Model Selection Guide (34-XY-16-47)
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 12
Specifications are subject to change without notice.
OneWireless and XYR are trademarks and Experion is a registered trademark of Honeywell International Inc.
XYR 6000 STIW600 Wireless High Level Analog Input Transmitter 13
For More Information
Learn more about how Honeywell’s Wireless High
Level Analog Input Transmitter can provide simple,
safe, and secure wireless technology, visit our website
www.honeywell.com/ps/hfs or contact your Honeywell
account manager.
Honeywell Process Solutions
1860 West Rose Garden Lane
Phoenix, Arizona 85027
Tel: 1-800-423-9883 or 1-800-343-0228
www.honeywell.com/ps
34-XY-03-30 November 2010 © 2011 Honeywell International Inc.