Welcome DIN Rail product training ISOLATOR/MCB/RCD/RCBO

Post on 11-Jan-2016

29 views 2 download

description

Welcome DIN Rail product training ISOLATOR/MCB/RCD/RCBO. Load Disconnector Switch (Isolator). Rated current: 40, 63, 80, 100 & 125A Rated voltage: AC 230/400V Number of poles: 1p, 2p, 3p, 4p Module unit: 1 MU = 17.5 mm - PowerPoint PPT Presentation

Transcript of Welcome DIN Rail product training ISOLATOR/MCB/RCD/RCBO

© 2008 Eaton Corporation. All rights reserved.

This is a photographic template – your photograph should fit precisely within this rectangle.

Welcome DIN Rail product training

ISOLATOR/MCB/RCD/RCBO

2 2

Load Disconnector Switch (Isolator)

Rated current : 40, 63, 80, 100 & 125A

Rated voltage : AC 230/400V

Number of poles : 1p, 2p, 3p, 4p

Module unit : 1 MU = 17.5 mm

Terminals : Twin-purpose terminal, (lift/open mouthed) with

guide for secure connection

4 4

Miniature Circuit Breaker

Definition and benefit

Function

Product range

Technical data

Accessories

Summary

5 5

Miniature Circuit Breaker

Function of MCB

Protection against Overloads – a thermal delay (bi-metal) release initiates the disconnecting process and separates the contacts.

Protection against Short circuits - an electromagnetic instantaneous release (hammer- armature) performs the disconnecting process and separates the contacts.

6 6

Miniature Circuit Breaker

Tripping Characteristics

B – for line and cable protection in residential building installations (lighting and socket circuits)

C – for line and cable protection, particularly for electrical systems and equipment with higher making currents (groups of lamps)

D – for line and cable protection, particularly for electrical systems and equipment with very high making currents (welding transformers, motors)

8 8

Miniature Circuit Breaker

Installation and removal without removing the busbar

9 9

Miniature Circuit Breaker

Guide for secure terminal connection

Prevents missing the terminal when introducing the wire

10 10

Miniature Circuit Breaker

Contact position indicator red/green

11 11

Miniature Circuit Breaker STD series 2A-63A

Tested to : IEC/EN 60898

Rated breaking capacity : 10 kA; 6 kA; 4.5 kA

Rated current : 1 - 63 A

Rated voltage : AC 230/400V

: DC 48V per pole

Characteristic : B, C, D

Number of poles : 1p, 1+N, 2p, 3p, 3+N, 4p

Module unit : 1 MU = 17.5 mm

Terminals : Twin-purpose terminal (lift/open mouthed) with

guide for secure connection

Terminal capacity : 1 - 25 mm²

12 12

Miniature Circuit Breaker 125A

Tested to : EN 60947-2

Rated breaking capacity : 25 kA

Rated current : 80 – 125 A

Rated voltage : AC 240/415V AC

: DC 60 V per pole

Characteristic : B, C, D

Number of poles : 1p, 2p, 3p, 3+N, 4p

Module unit : 1.5 MU = 27mm

Terminals : lift terminal

Terminal capacity : 1 - 50 mm²

Device height : 90 mm

13 13

Miniature Circuit Breaker - accessories

Auxilliary Contact

Trip Contact

Undervoltage Release

230VAC

Shunt Trip

12-110VAC/12-60VDC

110-415VAC/110-220VDC

14 14

Miniature Circuit BreakerSummary of Features

• Installation and removal of MCB without removing the bus bar

• 80 mm device height – compatible with DIN rail products

• Twin-purpose terminal (lift/open mouthed) with guide for secure connection

• both releases work independent of each other.

• Wide range of accessories, most items in snap-on design

• Internal tripping is independent of the toggle position , guarantees proper tripping even in case the operating toggle is blocked or held by the operator

15 15

Definition & benefit

Function & Key Components

Product range

Features

Accessories

Applications

Summary

Residual Current Device

16 16

Product range

• Rated current: 25, 40, 63, 80, 100A

Number of poles: 2p, 4p•

• Rated tripping current: 30, 100, 300mA

• Voltage systems: AC 240/415V AC

• Frequency: 50Hz

Residual Current Device

17 17

Front printing

Standard ON/OFF

Nominal current

Short circuit strength

Nominal voltage

I∆N sensitivity

Contact position indicator

Terminal designation.

Test information

Residual Current Device

19 19

• Additional safety!

contact position indicator

red/green

Features

Residual Current Device

20 20

• Additional safety!

possibility to seal /

possibility to lock in

ON and OFF position

Features

Residual Current Device

21 21

Flexible and big room for connection!

Twin purpose terminal

(lift/open mouth on bottom and top)

35 mm2 capacity

both sides compatible to bus bars

Features

Residual Current Device

22 22

Combined Fault Current and Miniature Circuit Breaker (RCBO)

Definition and benefit

Specification

Place of installation

Application

Product line

Place of installation + features

Accessories

Summary

23 23

Combined Fault Current andMiniature Circuit Breaker

DEFINITION

Residual Current Device and Miniature Circuit Breaker in one (RCBO)

ADVANTAGE

Protection against O/L, S/C and E/L in one unit.

24 24

Combined Fault Current andMiniature Circuit Breaker

Single Module RCBO

-Electronic residual current device & MCB combination in one

-1p + N in only one 1 module

-Design IEC/EN 61009

-Breaking capacity 10kA

-Type B, C & D.

25 25

Combined Fault Current andMiniature Circuit Breaker

Contact positon indicator red/green

Contact positon indicator red/green

Can be sealed with leads in the ON or OFF position

Can be sealed with leads in the ON or OFF position

Twin-purpose terminal (lift/open mouthed) above and below

Twin-purpose terminal (lift/open mouthed) above and below

Lift terminalLift terminal

Benefits & Features

• single module, compact 17.5mm Width.• Height 120mm.• Frame size 45mm compatible with other

modular components.• Contact position indicator red/green.• Can be sealed with leads in the ON or OFF

position. • open mouthed/lift terminals top & bottom.• Fixed connected neutral length 950mm.• Can be connected in a STD pan assembly• Terminal capacity 25mm

27 27