s t a i n l e s s s t e e l f l u e s y s t e m s
Stainless Steel Flue Systems
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010page 2
jeremias
References special finish certifications
RAL coated
satin stainless steel
copper
mat
W a r r a n t y WE AS A SPECALIST COMPANY OFFER
10 YEARS WARRANTY
ON OUR EXHAUST PIPE SYSTEM ELEMENTS (MADE OF STAINLESS STEEL)
Pre-condition for the guaranteeing is an appropriate and professional installation under consideration
of the cross-sectional calculation according to EN 13384-1, the complete installation
of the single parts from the boiler and gas flue outlet to the end cap
in our quality of materials and the absolute avoidance of the impact of
chlorinated hydrocarbon.
The stainless steel pipe is to be cleaned with a plastic or stainless steel broom.
It has to be ruled out that the stainless steel mingles with ferritic or low-grade metal.
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010 page 3
double wall system - ( D W ) -
DW - eco 316 ...................................................................................................................... p. 10 DW - kl ................................................................................................................................ p. 11 DW - vision .......................................................................................................................... p. 12 DW - mammut ..................................................................................................................... p. 13
single wall system - ( S W ) -
EW - eco 316 ...................................................................................................................... p. 18 EW - eco 304 ...................................................................................................................... p. 19 EW - kl ................................................................................................................................. p. 20 EW - pps ............................................................................................................................. p. 21
Ferro-Lux - ( F E ) - „stovepipe“ Ferro-Lux ............................................................................................................................ p. 24 EW - connecting pipe .......................................................................................................... p. 25
SES by Jeremias - Free standing Industrial solutions SES - by jeremias: company profile..................................................................................... p. 26 Type FSA ............................................................................................................................ p. 28 Type FSA-X ......................................................................................................................... p. 29 Type FS-RM ........................................................................................................................ p. 30 Type FSB ............................................................................................................................ p. 31 Type FSC ............................................................................................................................ p. 32 Reference List ..................................................................................................................... p. 33
Index
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010 page 5
dry operation mode humid operation mode
no pressure positive pressure
positive pressure 5000 PA positive pressure200 PA
wall thickness 0,6 mm wall thickness 1,0 mm
double wall exhaust system Single-walled exhaust system
exhaust system for „indoor air independant“ operation mode
double wall,25 mm insulation
double wall, 32 mm insulation
connecting pipe for solid fuels
inside Stainless Steel / outside Stainless Steel inside Polypropylene / outside Stainless Steel
inside Polypropylene / outside painted oil, gas, solid fuels
oil, gas 10 years guarantee
xy 01 Item code
The part number for ordering is: Item code + thickness + Ø (for example xy1006130)
Item Description specific name of the article
Price The following prices are plus tax.
symbol description
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010page 6
System Overview
DW - eco DW - fu DW - kl SV - EI30
Furado - sqvare Furado - traingle EW - kl EW - twin - p
SEA SEE SET SED
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010 page 7
System Overview
DW - eco solid fuel DW - mammut DW - vision EW - eco
EW - pps EW - pps - flex EW - pps - Boiler cascade
EW-316 Pellet System connecting pipeSVC Wall bushing Ferrolux
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010page 8
Product description DW double wall system
a) Listing of surcharges:
Of course we are prepared to supply you with modified versions of our products.
1.) surcharges on demand
Type of material material thickness
- outer tube in copper - inner tube 0,8 mm
- outer tube brushed - inner tube 1,0 mm
- outer tube mat - inner tube 1,5 mm
- outer tube painted (not discountable) - insulation 50 mm
Special colors available upon request
special stainless steel
material 1.4828 permanent heat-resistant -1050 °C on request
material 1.4539 acid-resistant - 400 °C on request
2.) special elements
on request Diameters and special elements between Ø 80 and Ø 1100 mm are availableon request.
3.) terms of delivery
freight costs Public prices are on EX WORKS basis please ask your supplier for delivery terms
For appointments / delivery services, and supplies outside of the route we calculate freight charges.
4.) return of goods
We are prepared to take undamaged and package goods with a diameter of up to 250 mm back.
For taking back goods we will assess a charge of minimum 25 %. ( depends to the country)
Special parts will not be taken back.
Errors and technical changes excepted.
5.) discount overview
You can find the particular discount groups in our price or order forms.
Our General Terms and Conditions
6.) ordering processes
For quick and error-free processing of your order, we ask the to use the new order forms based on the new price list suche
Please take into account when placing your order, that some of our products have been provided during the transition to a new price list items code.
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010 page 9
Product description DW double wall system
a) General description of our double wall systems
b) More detailed description of the double-walled systems:
application
dw-eco 316 Double wall stainless steel flue gas system for all standard heat appliances, all regular combustibles, in negative and positive pressure operation mode
dw-kl Double wall flue gas system for all standard heat appliances in negative and positive pressure, for dry and wet operation mode
dw-vision Double wall flue gas system for all standard heat appliances in negative pressure, for dry and wet operati-on mode, without locking bands
dw-mammut double wall chimney system with ceramic inner tube for all standard furnaces in negative pressure for dry and wet operation mode
quality characteristics
pipe fittings All fittings are welded condensate and gas proof
gaskets Use of high-quality sealing material (viton) => higher durability
order
diameter The following products are also available in bigger diameters on request.
locking bands
Locking bands are available for the following systems: dw-kl
oil gas sf temperature material wall thickness TIG NP/PP certification classifications
dw-eco 316 ■ ■ ■ ≤ 400 °C
inside: 1.4404 (316Ti) / 1.4571
(316L)outside: 1.4301
(304)
inside: 0,4 - 0,5 - 0,6 mmoutside: 0,4 - 0,5 - 0,6 mm
■ NP 0036 CPD 9174 030
T600 - N1 - D - V3 - L50040 - G70T450 - N1 - D - V3 - L50040 - G60 (HETAS)T400 - N1 - W - V2 - L50040 - O30T200 - P1 - W - V2 - L50040 - O00 (joint seal)
dw-kl ■ ■ ■ ≤ 600 °C inside: 1.4571outside: 1.4301
inside: 0,6 mmoutside: 0,6 mm ■ PP
5000 Pa 0036 CPD 9174 002
T400 - N1 - D - V3 - L50060 - G50T400 - N1 - W - V2 - L50060 - O20T400 - P1 - W - V2 - L50060 - O20T600 - N1 - D - V3 - L50060 - G50T600 - H1 - W - V2 - L50060 - O50
dw-vision ■ ■ ■ ≤ 200 °C≤ 400 °C
inside: 1.4571outside: 1.4301
inside: 0,6 mmoutside: 0,6 mm ■ NP 0036 CPD 9174 009 T400 - N1 - W - V2 - L50050 - O20
T400 - N1 - D - V2 - L50050 - G50
dw-mammut ■ ■ ■ ≤ 400 °C inside: Keramikoutside: 1.4301
inside: 8,0 mmoutside: 0,6 mm ■ NP Z - 7.1 - 3351
page 10 Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
System DW - eco 316
application Twin wall insulated stainless steel flue system suitable for all standard applications in negative and positive pressure, condensing (including gaskets)
combustible oil, gas and solid fuels
working ptemperature ≤ 600°C
material inside: 1.4404 (316Ti) / 1.4571 (316L)outside: 1.4301 (304)
wall thickness inside: 0,4 - 0,5 - 0,6 mmoutside: 0,4 - 0,5 - 0,6 mm
welding seam TIG continuous / laser
insulation mineral wool insulation with 25 mm wall thickness, bulk density 120 kg/m³
connection plug connector male / female coupler with locking band
admissible for pos. pressure
yes (including gaskets)
soot fire resistant yes
free standing extension from last wall bracket: 3m (Ø130-300mm)2,5m (Ø350-400mm), 1,5m (Ø450-500mm)
average roughness 1,0 mm
thermal resistance 0,26 m² K/W
buildup example CE mark number
0036 CPD 9174 030
CE classification EN 1856 - 1
T600 - N1 - D - V3 - L50040 - G70T450 - N1 - D - V3 - L50040 - G60 (HETAS)
T400 - N1 - W - V2 - L50040 - O30T200 - P1 - W - V2 - L50040 - O00 (joint seal)
End cap
Flashing
Ventilated fire Stop plate
straight length
Appliance adaptor
1
2
34
5
1
2
3
4
5
page 11Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
System DW - kl
application Twin wall insulated stainless steel pressuretight flue system for conbustion-engines and CHP´s applicable, in negative and positve pressure, for dry and wet operation mode
combustible oil, gas und solid fuels
working ptemperature ≤ 400°C / ≤ 600°C
material inside: 1.4571 (316Ti) / 1.4404 (316L)outside: 1.4301 (304)
wall thickness inside: 0,6 - 1,0 mmoutside: 0,6 - 1,0 mm
welding seam TIG continuous / laser
insulation mineral insulation with 32,5 or 50 mm wall thickness, bulk density 120 kg/m³
connection positive pressure by conical connection
admissible for pos. pressure
200 Pa / 5000 Pa
soot fire resistant yes
free standing extension 3 m up to last wall bracket to Ø 600 1,5 m up to last wall bracket > Ø 600 - 1000
average roughness 1,0 mm
thermal resistance 0,501 m² K/W
buildup example CE mark number
0036 CPD 9174 002
CE Classifiications EN 1856 - 1
T400 - N1 - D - V3 - L50060 - G50T400 - N1 - W - V2 - L50060 - O20T400 - P1 - W - V2 - L50060 - O20T600 - N1 - D - V3 - L50060 - G50T600 - H1 - W - V2 - L50060 - G50
End cap
flashing kit
Adjustable rafter brace
straight length
tee 87°
Base plate
Adjustable wall brackets
Support
adaptor
Rigid pipe bend with clean-out opening
1
2
3
45
6
7
8
9
10
1
2
3
4
5
6
8
9
7
10
page 12 Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application double wall flue system (SS) for all standard furnaces in negative pressure, for dry and wet operation mode.Striaght finish design, without locking band.
combustible oil, gas and solid fuels
working ptemperature ≤ 400°C
material inside: 1.4571 (316Ti) / 1.4404 (316L)outside: 1.4301 (304) (finishing satin stainless teel; not coatable)
wall thickness inside: 0,6 mmoutside: 0,6 mm
welding seam TIG continuous / laser
insulation mineral insulation with 32,5 mm wall thickness, bulk density 120 kg/m³
connection threaded slip joint (outer tube)
admissible for pos. pressure
no
soot fire resistant yes
free standing extension 3 m up to last wall bracket
average roughness 1,0 mm
thermal resistance 0,501 m² K/W
buildup example CE mark number
0036 CPD 9174 009
CE Classifiications EN 1856 - 1
T400 - N1 - W - V2 - L50050 - O20T400 - N1 - D - V3 - L50050 - G50
Characteristic
double wall flue system (SS) for all standard furnaces in negative pressure, for dry and wet operation mode.Striaght finish design, without locking band.
Length
The straight pipe elements can be cut to length.
End cap
straight length
wall bracket
tee 87°
pipe length with clean-out opening
adjustable support
System DW - vision
12
3
4
5
6
1
2
3
4
5
6
page 13Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application double wall flue gas system with internal isostatic pressed ceramic pipe and external stainless steel pipe for all standard furnaces in negative pressure mode
combustible pellets, cereal, oil, gas, solid fuels
working ptemperature ≤ 400°C
material inside: isostatic ceramic tubeoutside: 1.4301 (304)
wall thickness inside: 8,0 mmoutside: 0,6 mm
welding seam TIG continuous / laser (outside)
insulation mineral insulation with 32,5 mm wall thickness, bulk density 120 kg/m³
connection inside: plug-and-socket connection with acid-proof cementoutside: plug-and-socket connection with locking band
admissible for pos. pressure
no
soot fire resistant yes
free standing extension 3 m up to last wall bracket
average roughness 1,5 mm
thermal resistance > 0,322 m² K/W
buildup example CE approval number
Z - 7.1 - 3351 (only in Germany W3G)
CE mark number
0036 CPD 9174 0390036 CPD 9174 040
CE Classifiications
T400 - N1 - D - 3 - G50 --> DIN EN 13063 - 1T400 - N1 - W - 2 - O20 --> DIN EN 13063 - 2
End cap
wall bracket
Locking band
straight length
tee 87°
pipe length with clean-out opening
System DW - mammut
12
34
5
6
1
2
3
4
5
6
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010page 14
product description EW single wall exhaust system
Please take into account when placing your order, that some of our products have been provided during the transition to a new price list items code.
Of course we are prepared to supply you with modified versions of our products.
1.) surcharges on demand
type of material material thicknesses
- oval - 0,8 mm
- brushed - 1,25 mm
- reinforced version of fittings - 1,50 mm
special stainless steel
material 1.4539 acid resistant up to 400°C on request
material 1.4828 heat resistant up to 1050°C on request
2.) special elements
freight costs On request we can also produce special parts and diameters from 60 – 1000 mm
3.) terms of delivery
freight costs Public prices are on EX WORKS basis please ask your supplier for delivery terms
Extra freight costs could be allso charged for express and special deliveries.
4.) return of goods
We are prepared to take back undamaged and packaged goods until Ø 250 mm.
For taking back goods we will assess a charge of minimum 25 %. (depends on the country)
Special parts will not be taken back.
Errors and technical changes excepted.
5.) discount overview
You can find the particular discount groups in our price lists or in order forms.
Basically our general terms and conditions apply.
6.) ordering processes
For quick and error-free processing of your order, we kindly ask you to use ther new order forms based on the new price list.
a) Listing of surcharges:
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010 page 15
product description EW
application
ew-eco 316 single wall stainless steel flue system for the renovation of existing chimneys, connecting pipes and (exhaust) ventilation
ew-eco 304 single wall stainless steel flue system for the renovation of existing chimneys, connecting pipes and (exhaust) ventilation
ew-kl single wall stainless steel flue gas system for all standart furnaces and internal combustion engines application outside of chimney ducts possible
ew-pps single wall plasic flue gas system for condensing boilers
quality characteristics
pipe fittings All fittings are welded condensate and gas proof
gaskets Use of high quality sealing materials (Viton) => higher durability
order
diameter The following products are also available in bigger diameters on request.
oil gas sf Operation temp.
material wall thickness TIG NP/PP certification classifiications
ew-eco 316 ■ ■ ■ ≤ 200° C≤ 600° C
standard: 1.4571 (316Ti) /1.4404 (316L)
surcharge: 1.4539 (904L) /1.4878 (321)
0,4 - 0,5 - 0,6 mm ■ PP0036 CPD 9174 029
T200 - P1 - W - V2 - L50040 - O00 (joint seal) T400 - N1 - W - V2 - L50040 - O50T600 - N1 - D - V2 - L50040 - G100
ew-eco 304 ■ ■ ≤ 200° C≤ 600° C
1.4301 (AISI 304) 0,4 - 0,5 - 0,6 mm ■ PP 0036 CPD 9174 029
T200 - P1 - W - V2 - L20040 - O00 (joint seal) T400 - N1 - W - V2 - L20040 - O50T600 - N1 - D - V2 - L20040 - G100
ew-kl ■ ■ ■≤ 200° C≤ 400° C≤ 600° C
1.4571/1.4404 0,6 mm ■ PP - 5000 Pa 0036 CPD 9174 004
T200 - P1 - W - V2 - L50060 - O00T400 - N1 - D - V2 - L50060 - G50T400 - N1 - W - V2 - L50060 - O50T400 - P1 - W - V2 - L50060 - O50T600 - N1 - D - V2 - L50060 - G100T600 - P1 - W - V2 - L50060 - O100T600 - H1 - W - V2 - L50060 - G50** with 32 mm insulation
ew-pps ■ ■ ≤ 120° C Polypropylene 2,0 mm PP - 200 Pa 0036 CPD 91264 005 T120 - P1 - O - W - 2 - O20 - I - E
b) technical overview of our single wall systems:
a) General description of our single wall systems
page 16 Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application single wall stainless steel flue system for the renovation of existing chimneys, connecting pipes and (exhaust) ventilation
combustible oil, gas, solid fuels
working ptemperature ≤ 200 °C / ≤ 600 °C
material standard: 1.4571 (316Ti) / 1.4404 (316L) surcharge: 1.4539 (904L) / 1.4878 (321)
wall thickness 0,4 - 0,5 - 0,6 mm
welding seam TIG continuous / laser
insulation optional
connection plug-and socket connection
admissible for pos. pressure
no
soot fire resistant yes
average roughness 1,0 mm
buildup example CE mark number
0036 CPD 9174 029
CE Classifiications
T200 - P1 - W - V2 - L50040 - O00 (joint seal)
T400 - N1 - W - V2 - L50040 - O50T600 - N1 - D - V2 - L50040 - G100
Combination
The following basic components can be combined with components of the- positive pressure tight system- system EW-Line flex- system EW-las and/orthe additional elements of system EW.
Applicability
The system Jeremias-EW ECO 316 is applicable for the reduction of the cross-sectional area of chimneys for the adaption to modern furnaces (oil, gas, solid fuel, pellets).
Positive pressure & condensing
The system Jeremias - EW ECO 316 can be used for condensing applications by inserting a silicone gasket in the female socket.
Rain cap
End cap with storm collar
Assembly clamp distancer
straight length 1000 mm
Rigid pipe bend 30°
straight length 500 mm
Locking band
Rigid pipe bend 90°
tee 87°
straight length 250 mm
Rigid pipe bend 87°
pipe length with clean-out opening
Condensate collector with outlet
System EW - eco 316
1
2
3
4
5
6
78
910
11 12
13
1
2
34
5
6
78
9
10
11
12
13
page 17Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application single wall stainless steel flue system for the renovation of existing chimneys, connecting pipes and (exhaust) ventilation
combustible oil, gas
working ptemperature ≤ 200 °C / ≤ 600 °C
material 1.4301 (AISI 304)
wall thickness 0,4 - 0,5 - 0,6 mm
welding seam TIG continuous / laser
insulation optional
connection plug-and socket connection
admissible for pos. pressure
no
soot fire resistant yes
average roughness 1,0 mm
buildup example CE mark number
0036 CPD 9174 029
CE classifications
T200 - P1 - W - V2 - L20040 - O00 (joint seal)
T400 - N1 - W - V2 - L20040 - O50T600 - N1 - D - V2 - L20040 - G100
Combination
The following basic components can be combined with components of the- positive pressure tight system- system EW-Line flex- system EW-las and/orthe additional elements of system EW.
Applicability
The system Jeremias-EW ECO 304 is applicable for the reduction of the cross-sectional area of chimneys for the adaption to modern furnaces (oil, gas).
Positive pressure
The system Jeremias - EW ECO 304 can be used for positve applications by inserting a silicone gasket in the female socket.
Rain cap
End cap with storm collar
Assembly clamp distancer
straight length 1000 mm
Rigid pipe bend 30°
straight length 500 mm
Locking band
Rigid pipe bend 90°
tee 87°
straight length 250 mm
Rigid pipe bend 87°
pipe length with clean-out opening
Condensate collector with outlet
System EW - eco 304
1
2
3
4
5
6
78
910
11 12
13
1
2
3
4
5
6
7
8
9
10
11
12
13
page 18 Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application Twin wall insulated stainless steel pressuretight flue system for conbustion-engines and CHP´s applicable, in negative and positve pressure, for dry and wet operation mode
combustible oil, gas und solid fuels
working ptemperature ≤ 200 °C / ≤ 400 °C / ≤ 600 °C
material standard: 1.4571 (316Ti) / 1.4404 (316L) surcharge: 1.4539 (904L)
wall thickness 0,6 mm
welding seam TIG continuous / laser
connection metallic - conical finishing seal plug-and-socket and locking band (optional)
admissible for pos. pressure
up to 200 Pa without locking band up to 5.000 Pa with locking band
soot fire resistant yes
average roughness 1,0 mm
buildup example CE mark number
0036 CPD 9174 004
CE Classifiications EN 1856 - 1
T200 - P1 - W - V2 - L50060 - O00T400 - N1 - D - V2 - L50060 - G50T400 - N1 - W - V2 - L50060 - O50T400 - P1 - W - V2 - L50060 - O50T600 - N1 - D - V2 - L50060 - G100T600 - P1 - W - V2 - L50060 - O100T600 - H1 - W - V2 - L50060 - G50 ** with 32 mm insulation
End cap with storm collar
straight length
Assembly clamp distancer
pipe length with clean-out opening
straight length
tee 87°
Rigid pipe bend with clean-out opening
pipe length with clean-out opening
Condensate collector
System EW - kl
1
2
3
4
5
6
7
8
9
1
2
3
4
5
67
8
9
page 19Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application single wall plastic flue gas system for condensing boilers
combustible oil, gas
working ptemperature ≤ 120°C
material PP - polypropylene
wall thickness 2,0 mm
welding seam hot-plate welding according to DVS 2207 T11
connection plug-and-socket connection plug-and-socket with EPDM-interior gasket
admissible for pos. pressure
200 Pa
soot fire resistant no
average roughness 1,0 mm
buildup example CE mark number
0036 CPD 91264 005
CE classification EN 14471
T120 - P1 - O - W - 2 - O20 - I - E
Application
The system EW – pps can be used for the evacuation of exhaust gases of oil- and gas-fired furnacesin positive and negative pressure operation mode with a maximum temperature of 120°C.
The custom-fit boiler connections allow the system EW – pps to be connected to allcurrent boiler types.
multi-use end cap incl. end pipe INOX and storm collar
straight length
pipe bend 87° with support leg and support rail
1
2
3
System EW - pps
1
2
3
page 20 Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application connection pipe made of sheet steel DC01 (St 12) with threaded plug-in connection, for application in the living area for detached chimneys.according to DIN 1298
combustible solid fuels
working ptemperature ≤ 400°C≤ 600°C
material sheet steel
wall thickness 2,0 mm
welding seam TIG without additive
colours black 702.284cast-grey 702.288
on request:black-metallic 702.310 cast-grey hell 800.820
finishing coated with heat resistant Senotherm-paint
average roughness 1 mm
CE mark number 0036 CPD 9174 017
CE-classificationDIN EN 1956-2
T600 - N1 - D - Vm - L01200 - G400with radiation protection
System Ferro - Lux
page 21Release: January 2010®
s t a i n l e s s s t e e l f l u e s y s t e m s
application connection piping of stainless steel 1.4404 with plug-and-socket connector and inner seal for use in the residential area and viewing area for free-stan-ding stoves in the room according to DIN 1298
combustible solid fuels
working temperature ≤ 200°C
material 1.4404 (316L)
Surface painted black / cast-grey /polished stainless steel
Connection plug-and socket connection with Special inner seal
buildup example
stom collor (ZUWA.4C1500.676)
pip bend 90° with inspection openning (EWEC.6C15AL.019)
straight length 1000 mm(EWEC.6C15AL.013)
tee 90° with detachable condensate collector (EWEC.6C15AL.557)
System EW connecting pipe
1
2
3
4
EWEC.6C15AL.725
EWEC.6C15AL.019
EWEC.6C15AL.557
12
3
4
Release: January 2010page 22
phone: +49 (0) 98 32 / 68 69 - 0Fax: +49 (0) 98 32 / 68 69 - 64E-Mail: info@ses-web.deInternet: www.ses-web.de
Engelhardt GmbHOpfenrieder Str. 12D - 91717 Wassertrüdingen
STEEL CHIMNEYS AND VENTILATION TOWERS ACCORDING TO DIN 4113 / EN 13084
HIGH-PRESSURE-TIGHT SYSTEMS
MANUFACTURER’S QUALIFICATION CLASS E ACCORDING TO DIN 18800-7
ENGELHARDT GMBHSTEEL FOR EXHAUST AND AIR TECHNOLOGY
Release: January 2010 page 23
Industrial Solutions
SES Company profileThe company Engelhardt GmbH, in short “SES” was founded in 1992. As a powerful partner in free-standing chimney systems, flue gas systems and ventilation towers we have established ourseves among the leading manufacturers in the European market. Our core business is in industrial chimneys as well as ventilation towers in accordance with the static demands EN 13084 / DIN 4133
Each project is designed and manufactured to meet exhaust gas requirements of specific fuel types in given situations. To aid selection SES offer a full range of technical services.
Our services cover the following specifications
•Site surveying•Product selection of flue gas pipes on the basis of the structural and heating requirements.•Selection of the ventilation towers regarding the ventilation technical requirements•Preparation of static calculations in consideration of the geographical and static specifications on site•Preparation of CAD drawings for page on site•Preparation of workshop drawings•Delivery according construction schedule •Coordination of installation with site management•Ready for use installation•Maintenance monitoring EN 13084 / DIN 4133
State of the art machinery, a permanent product control by our own welding specialist engineers, high quality standards as well as flexibility distinguish our strengths
A complete range of different finish options, RAL colour, brushed stainless steel, satined…We offer different options for ladders and platforms for inspection and maintenance.We think in every single detail in order to reduce the installing time at site.
in accordance withEN 13084-7
FSA FSB
FS-RM FSC
Release: January 2010page 24
application
• the line FSA is a universal and compact solution for steel chimneys and exhaust systems without fixation to a building.• the outer supporting tube allows great erection heights.
structure
• a roller bearing-supported and insulated flue gas pipe is fixed in a static supporting outer tube with room for vertical expansion.• the dimensions of the supporting tube are based on static calculations (dead weight) and in case of need on the dynamic load (lateral oscillation, wind load).
insulation
• slip-proof fixation to flue gas pipe• ideal vapor barrier due to outer aluminium lamination
back ventilation
• an annular gap between insulated flue gas pipe and supporting outer tube allows the back ventilation of the multi-layer system structure.• an evacuation of the outlet air from the heating room is also possible.
pedestals / safety-ladder
• if a regular sweeping from on top of the chimney is required, a safety-ladder is installed on the supporting tube (usually on the outside) according to the safety prevention regulations.• optional available are sweeping platform or circumferential (up to 360°) working platform.
accessories
• if necessary accelerator nozzles, deflector bonnets or silencers can be added to the chimney.
Type FSAstatic system anchor bolt ring or fixation to
buildingsupporting element outer tube structure multi-layer inner tube 316 / 304 / 904L / Corteninsulation inner tube yes, alum. laminated (vapor
barrier) back ventilation yesouter tube 304 or St 37-2 no. of inner tubes 1finishing painted
galvanized steelgrinded stainl. steelblasted stainl. steel(cladding)
fitted system -application standard furnaces
co-generatorsemergency gener.special furnaces
Type FSA
FSA
Release: January 2010 page 25
application
• the line FSA-X is a universal and compact solution for steel chimneys and exhaust systems without fixation to a building.• the outer supporting tube allows great erection heights.
structure
• a roller bearing-supported and insulated flue gas pipe is fixed in a static supporting outer tube with room for vertical expansion.• the dimensions of the supporting tube are based on static calculations (dead weight) and in case of need on the dynamic load (lateral oscillation, wind load).
insulation
• slip-proof fixation to flue gas pipe• ideal vapor barrier due to outer aluminium lamination
back ventilation
• an annular gap between insulated flue gas pipe and supporting outer tube allows the back ventilation of the multi-layer system structure.• an evacuation of the outlet air from the heating room is also possible.
pedestals / safety-ladder
• if a regular sweeping from on top of the chimney is required, a safety-ladder is installed on the supporting tube (usually on the outside) according to the safety prevention regulations.• optional available are sweeping platform or circumferential (up to 360°) working platform.
accessories
• if necessary accelerator nozzles, defl ector bonnets or silencers can be added to the chimney.
Type FSA-Xstatic system anchor bolt ring or fixation to
buildingsupporting element outer tube structure multi-layer inner tube 316 / 304 / 904L / Corteninsulation inner tube yes, alum. laminated (vapor
barrier) back ventilation yesouter tube 304 or St 37-2 no. of inner tubes ≥ 2finishing painted
galvanized steelgrinded stainl. steelblasted stainl. steel(cladding)
fitted system -application standard furnaces
co-generatorsemergency gener.special furnaces
Type FSA-X
FSA-X
Release: January 2010page 26
application
• the FS-RM combines a compact construction with stainless steel system elements, which can be erected to up to 40 meters due to the central support pipe tower.• combines the advantages of all class F types
structure
• one or more roller bearing-supported and insulated flue gas pipes (wall thickness stainless steel ≥ 1.0 mm) are in a support pipe tower with room for vertical expansion.• one or more element systems are installed on the outside of the support pipe tower (satellite: product type dw-fu, dw-al, dw-kl, dw-vision, dw-eco or system FSB)
insulation
• slip-proof fixation to flue gas pipe• ideal vapor barrier due to outer aluminium lamination
back ventilation
• an annular gap between insulated flue gas pipe and supporting outer tube allows the back ventilation of the multi-layer system structure.• an evacuation of the outlet air from the heating room is also possible.
pedestals / safety-ladder
• if a regular sweeping from on top of the chimney is required, a safety-ladder is installed on the supporting tube (usually on the outside) according to the safety prevention regulations.• optional available are sweeping platform or circumferential (up to 360°) working platform.
Type FS-RMstatic system anchor bolt ring or fixation to
buildingsupporting element support pipe towerstructure multi-layer inner tube 316 / 304 / 904L / Corteninsulation inner tube yes, alum. laminated (vapor
barrier) back ventilation yesouter tube /finishing
paintedstainl. steel claddinggrinded, mat, high-gloss
Rohrmast 304 or S235JRno. of inner tubes ≥ 1 application
standard furnaces steam/hot water boil. co-generator unitsemergency generatorsspecial furnacesbiomass boilers
Type FS-RM
FS-RM
Release: January 2010 page 27
application
• the FSB is a self-supporting steel chimney which statically is mostly realised with a fixation on a building.• the erection height depends on the number of possible wall fixations and the free-standing cantilever above the last wall fixation.
structure
• generally the inner tube is the supporting and at the same time the medium leading system element.• the minimum wall thickness for stainless steel (standard material 316) is 1,5-3 mm, for a steel tube (S235JR) it is 3-8 mm.• dimensions are determined on the basis of the necessary corrosion allowance, the static (dead weight) and if needed the dynamic load (lateral oscillation).
insulation
• one- or multi-layer, offset, butt-jointed and slip-proof fixation to inner tube• cladded with visible sheet-metal
pedestals / safety-ladder
• retrofitting possible in particular cases• safety-ladder and working platform optional available
accessories
• if necessary accelerator nozzles, deflector bonnets or silencers can be added to the chimney.
Type FSBstatic system fixation to buildingsupporting element inner tubestructure multi-layer inner tube 316 / S235JRinsulation inner tube yes, alum. laminated
(vapor barrier) back ventilation -outer tube /finishing
cladding versions:copper, aluminium, stainless steel (mat, brushed,high-gloss)
support pipe tower -no. of inner tubes 1 (one-draught)application
standard furnaces steam/hot water boil. co-generator unitsemergency generatorsspecial furnacesbiomass boilers
Type FSB
FSB
Release: January 2010page 28
application
• the line FSC is used in the air conditioning and heating sector.
structure
• the visible tube is the supporting and medium leading pipe at the same time, and is normally not insulated.• the dimensions of the supporting tube are determined and calculated according to the given air volumetric flow rate, the static (dead weight) and if needed the dynamic load (lateral oscillation).• depending on the application stainless steel with a wall thickness of ≥ 1.5 mm or black steel with ≥ 4 mm is used.
bonnets
• finned bonnets, air outlet bends or accelerator nozzles can optionally be attached to the support tube. Retrofitting is also possible in particular cases.
accessories
• optionally a from the outside not visible S E S water trap can be installed. The advantage is that it has the same function like the deflector bonnet, but a lower resistance value.
Type FSCstatic system acnchor bolt ring or
fixation to buildingsupporting element self-supportingstructure single-layerinner tube -insulation inner tube -back ventilation -outer tube - supporting tube
304 or St 37-2no. of inner tubes -finishing painted, high-gloss,
galvanised steel, stainless steel brushed, stainless steel blasted (cladding)
fitted system -application supply- /
outlet air
Type FSC
FSC
Release: January 2010 page 29
list of references
contractor installation location system Aø height year
Dantherm, Tonsberg NO NO - Oslo FSA-2 1420 mm 21 m 2006
Dantherm, Tonsberg NO NO - Bodo 2 FSA 559 mm 11 m 2006
Astebo, Marchtrenk AT SY - Syrien FSA 1420 mm 35 m 2007
Dantherm, Tonsberg NO NL - Kvalsund FSA 660 mm 11 m 2007
Loos GmbH, Gunzenhausen DE EG - Egypt FSA 610 mm 10 m 2008
Jeremias, Timisoara RO RO - Drobeta Turnu Severin 2 FSA 1420 mm 16 m 2008
Dantherm, Tonsberg NO NO - Larvik 4 FSA 559 mm 16 m 2008
Dantherm, Tonsberg NO NO - Egersund FSA 610 mm 20 m 2008
Viessmann Werke, Berlin DE Palm Jumeirah FSA 914 mm 15 m 2008
Bautechnik, Bozen IT IT - Vahm 2 FSB 1016 mm 18,50 m 2008
Energ-g Zrt., Budapest HU HU - Csepel FSA-6 2020 mm 28 m 2009
Herhof GmbH, Solms DE CY - Zypern FSA 1800 mm 18 m 2009
Krones AG, Neutraubling DE AO - Angola 3 FSA + VBL 1016 mm 20 m 2009
Naturwärme-montafon, Schruns DE AT - Schrunz 2 FSA 2320 mm1120 mm 20 m 2009
RK-Technology GmbH, Dortmund DE PL - Lublin FSA 1420 mm 20 m 2009
MAWERA GmbH, Hard am Bodensee DE FR - Betschdorf FSA 762 mm 18 m 2009
Astebo, Marchtrenk AT HU - Gönyü FSB + VBL 1016 mm 45 m 2009
Jeremias, Amorebieta ES ES - Madrid FSA 1016 mm 25 m 2009
Bigwood School, Nottingham US GB - Nottingham FSA-RM 711 mm 16 m 2009
Jeremias, Amorebieta ES ES - Cambrils FSC 2760 mm 18 m 2009
Viessmann GmbH, Allendorf DETM - Turkmenistan 239 FSB
von ø 350 mm -
650 mm
10 m 2010
Astebo, Marchtrenk AT NL - Amsterdam 2 FSA + 2 VBL 1220 mm 25 m 2010
Alfred Kuhse GmbH, Winsen / Luhe DE GB - Nottingham FSA-RM 711 mm 13 m 2010
Kraftszer Kft., Budapest HU HU - Ungarn 2 FSA + VBL 3000 mm 40 m 2010
Release: January 2010page 30
contractor installation location system Aø height year
Continental Reifenwerke Korbach FSC 1800 21 m 2007
Kronos Titan GmbH / Werk Nordenham Nordenham FSC 1016 23 m 2007
Milupa GmbH Fulda VBL 504 6 m 2007
Rexroth Bosch Group Witten FSC 500 10 m 2007
Loos Deutschland GmbH Gunzenhausen FSC 704 15 m 2008
Telekom Trier FSA 1220 25 m 2008
Saxonia Edelmetalle GmbH Halsbrücke FSA 1016 17 m 2008
DeTelmmobilien Trier FSA 700 17 m 2008
Schiffsdieseltechnik Kiel GmbH Rendsburg FSB 500 9 m 2008
CINCOMPLEX BORZESTI SA Onesti, Rumänien FSA 2300 8 m 2008
Klausner Holz Türingen GmbH BHKB Frisau Ebersdorf / Frisau FSA 2200 54 m 2008
IVA Berlin, Wolfferts Berlin 3 x FSA 610 20 m 20 m 20 m
2009
HKW Eisenhüttenstadt KAB-Takuma Eisenhüttenstadt FSA 1420 55 m 2009
Siemens SK-Malzenice FSB 1000 42 m 2009
Gefahrenstoffzentrum Jäger Kunststofftechnik Kaiserslautern FSA 1220 27 m 2009
Stahlwerk Breitenfeld AT-Mitterdorf 3 x FSC 2 x 6501 x 600
12 m 25 m 2009
Chantier Müller Cheminées CH-Genf 4 x FSC 1806 6 m 2009
Geovol Unterföhring 2 x FSA 12201016
25 m 25 m 2009
Nürburgring Nürburg / Eifel 5 x FSC 2250 5 m 2009
MAN – Diesel Augsburg VBL 2009
Maschinenfabrik Alfing Kessler Aalen-Wasseralfing FSA 1400 22 m 2009
Friedrich Löffler Institut Riems VBL 2009
AFK Geothermie Aschheim 2 x FSA 1220 19 m 2009
Vivantes Klinikum Hellersdorf / Berlin FSA-4 1220 21 m 2009
Holzwärme Grindelwald / Schweiz 2 FSA 914 24 m 15 m 2009
list of references
®
s t a i n l e s s s t e e l f l u e s y s t e m sRelease: January 2010 page 31
Warranty
W a r r a n t y WE AS A SPECALIST COMPANY OFFER
10 YEARS WARRANTY
ON OUR EXHAUST PIPE SYSTEM ELEMENTS (MADE OF STAINLESS STEEL)
Pre-condition for the guaranteeing is an appropriate and professional installation under consideration
of the cross-sectional calculation according to EN 13384-1, the complete installation
of the single parts from the boiler and gas flue outlet to the end cap
in our quality of materials and the absolute avoidance of the impact of
chlorinated hydrocarbon.
The stainless steel pipe is to be cleaned with a plastic or stainless steel broom.
It has to be ruled out that the stainless steel mingles with ferritic or low-grade metal.
Release: January 2010
jeremias high quality products are only installed by chosen experts.
The experts in your area:
Locations
Jeremias UK LtdBasepoint Business CentreBromsgrove Technology ParkIsidore RoadBromsgroveB60 3ET
Tel +44 (0) 1527 888914Fax +44 (0) 1527 888915Internet: www.jeremias-fluesystems.co.ukE-Mail: info@jeremias-fluesystems.co.uk
GermanyJeremias GmbH Opfenrieder Str. 11 - 14
D - 91717 Wassertrüdingen
• Tel.: +49 (0) 9832 - 68 68 50 • Fax: +49 (0) 9832 - 68 68 68 • eMail: info@jeremias.de
Czech RepublicJeremias CZ s.r.o. Školni 22/6
CZ - 434 01 Most Rudolice
• Tel.: +420 476 701238 • Fax: +420 476 704296 • eMail: info@jeremias.cz
Spain Jeremias España S. A. P.l. Zubieta 3
ES - 48340 Amorebieta
• Tel.: +34 94 630 10 10• Fax: +34 94 630 10 06• eMail: info@jeremias.com.es
PolandJeremias Sp. zoo ul. Kokoszki 6
PL - 62200 Gniezno
• Tel.: +48/ 61 428 46 20 • Fax: +48/ 61 424 17 10 • eMail: jeremias@jeremias.pl
RussiaOOO Jeremias Rus Krasnobogatirskaja ul., 2/str.2, office 30
RU - 107564 Moskwa
• Tel.: +7 (495) 737 72 89• Fax: +7 (495) 737 72 89• eMail: info@jeremias.ru
Hevac LimitedMuirfield Drive,Naas Road,Dublin 12,Ireland.Tel: 00353 1 419 1919Fax: 00353 1 458 4806Email: infor@hevac.ieWeb: www.hevac.ie