Post on 27-Jun-2020
Tel 877-214-6267 salesacromagcom wwwacromagcom 30765 Wixom Rd Wixom MI 48393 USA
Transmitters TT330 Series
Bulletin 8400-666K
DescriptionThe TT333 model is a space-saving four-wire transmitter that isolates and converts a millivolt or thermocouple sensor input to a proportional control signal DC current and voltage output are both supported on a single model An optional DIN rail bus can deliver primary or redundant power to multiple units without wiring
High-voltage isolation separates the input from the output circuit Isolation protects from surges reduces noise and eliminates ground loop errors
Setup and calibration are fast and easy with a convenient USB connection to your PC and Acromagrsquos Windows configuration software
Advanced signal processing capabilities variable range input and convenient USB programming make this instrument a very versatile temperature measurement device These transmitters can withstand harsh industrial environments and operate reliably across a wide temperature range with very low drift They feature RFI EMI ESD EFT and surge protection plus low radiated emissions
Key Features amp Benefits Easy setup and digital calibration via USB with
Windows configuration software
Universal thermocouple or millivolt input (TC Type J K T R S E B N or plusmn100mV)
Universal output connections support ranges up to plusmn21mA or plusmn105V DC without rewiring
Space-saving 175mm (07 inch) unit with pluggable terminals for convenient wiring
High accuracy linearity stability and reliability
User-selectable filtering (none low med high)
Adjustable response times (15ms to 850ms)
Supports reverse-acting (inverse) output
Selectable upscale or downscale operation for sensor faults and lead-break detection
Bus power local power or both
Redundant power ready (raillocal)
1500V isolation 3-way (power input output)
Shock (25g) and vibration (4g) resistant
Wide ambient operation (-40 to 80degC)
CE compliant ULcUL Class I Div 2 ATEXIECEx Zone 2 approvals
Universal thermocouplemillivolt input Universal currentvoltage output 12-32V DC localbus power
TT333 Thermocouplemillivolt input four-wire transmitterBOTTOM VIEW(INPUT SIDE)
TOP VIEW(OUTPUT amp POWER SIDE)
175 mm(069 in)990 mm
(390 in)
SIDE VIEW
OUTPUT
POWER
1145 mm(451 in)
TB1 TB3
TB4
+ndash
DC SUPPLY(12-32V DC)
EARTHGROUND
+
ndash12
11
987
10 ndash
121110
FUSE
++
ndashRndash
+9
8
7
SHIELDEDCABLE
ndash
ndash
++
ndashRndash
EARTHGROUND
I
CURRENTOUTPUT
VOLTAGEOUTPUT
OPTIONALGROUND
RAIL BUSPOWER
35mm DIN Rail
Rail Bus Connector1005-063
TT300Series
USB
TT300Series
USB
TT300Series
USB
TT300Series
USB
TT300Series
USB
TT300Series
USB
NC
SHIELDED CABLE
OPTIONALSHIELD
GROUND
THERMOCOUPLETYPE J K T E R S B OR NOR MILLIVOLT
INPUT
OPTIONALEARTH
GROUND3
1
2
TB121 3
+
ndash
TT330 Series Transmitter Configuration Software is downloadable (FREE) from wwwacromagcomWindowsreg XP Vista 7 and 8
USB Configured
TT333 Model software allows you to configure transmitters offline save the file and download into units later at your convenience
The Agilitytrade Config Tool is downloadable (FREE) at the Google Play StoreFor Android Devices only
Tel 877-214-6267 salesacromagcom wwwacromagcom 30765 Wixom Rd Wixom MI 48393 USA
All trademarks are property of their respective owners Copyright copy Acromag Inc 2019 Data subject to change without notice Printed in USA 102019
Transmitters TT330 SeriesTT333 Thermocouplemillivolt input four-wire transmitter
Performance Specifications
USB InterfaceUSB ConnectorType USB Mini-B type socket 5-pin Data rate 12Mbps USB v11 and 20 compatible Maximum cable length 50 metersUSB Transient ProtectionTransient voltage suppression on power and data linesDriverNot required Uses Windows HID drivers
InputDefault ConfigurationCalibrationInput TC J -210 to 760degC med filter break up Output 4 to 20mAInput Ranges and Accuracy
Input Range Accuracy TC J TC K TC T TC R TC S TC E TC B TC N mV
-210 to 760degC (-346 to 1400degF) -200 to 1372degC (-328 to 2502degF) -260 to 400degC (-436 to 752degF) -50 to 1768degC (-58 to 3214degF) -50 to 1768degC (-58 to 3214degF) -200 to 1000degC (-328 to 1832degF) 260 to 1820degC (500 to 3308degF) -230 to 1300degC (-382 to 2372degF) -100 to 100mV
plusmn05degC plusmn05degC plusmn05degC plusmn10degC plusmn10degC plusmn05degC plusmn10degC plusmn10degC plusmn01mV
Error includes the effects of repeatability terminal point conformity and linearization (but not CJC error)Thermocouple Reference (Cold Junction Compensation)plusmn02degC typical plusmn05degC maximum at 25degCAmbient Temperature EffectBetter than plusmn80ppmdegC (plusmn0008degC)Scaling AdjustZero 0 to 95 of range typical Full scale 5 to 100 of full scale range typicalLead Break (Sensor Burnout) DetectionUpscaledownscale plusmn5 full scale range typicalInput Over-Voltage ProtectionBipolar Transient Voltage Suppressers (TVS) 56V clamp level typicalInput ResolutionMillivolt input 00025 (1 part in 40000) Thermocouple input 01degC
Input ImpedanceCurrent input 249 ohms Voltage input 15M ohmsInput FilterSelectable digital filtering settings (none low medium and high)Noise RejectionNormal mode 60Hz gt05dB (no filter) gt80dB (high filter) Common mode 60Hz gt100dB (no filter) gt130dB (high filter)
OutputOutput Range
Range Over-Range Resolutionplusmn10V plusmn5V 0 to 10V 0 to 5V plusmn20mA 0 to 20mA 4 to 20mA
plusmn105V plusmn525V ndash05527 to +105V ndash027634 to +525V plusmn21mA ndash11054 to 21mA ndash11054 to 21mA
1 part in 62415 1 part in 31208 1 part in 59240 1 part in 60262 1 part in 62259 1 part in 58596 1 part in 46877
Output LoadVoltage output 1K ohms minimum Current output 0-550 ohmsOutput Response Time (for step input change)
Time to reach 98 of final output value (typical)No filter Low filter
15 milliseconds 40 milliseconds
Medium filter 120 millisecondsHigh filter 850 milliseconds
Output RippleLess than plusmn01 of output spanOutput Ambient Temperature DriftBetter than plusmn80ppmdegC (plusmn00080degC
EnvironmentalOperating temperature-40 to 80degC (-40deg to 176degF)Storage temperature-40 to 85degC (-40 to 185degF)Relative humidity5 to 95 non-condensingPower Requirement12-32V DC SELV (Safety Extra Low Voltage) 24mA maxIsolation1500V AC peak 250V AC (354V DC) continuous isolation between input output and power (3-way)Shock and Vibration ImmunityVibration 4g per IEC 60068-2-6 Shock 25g per IEC 60068-2-27ApprovalsCE compliant ULcUL listed Class I Division 2 Groups ABCD ATEX IECEx certified Zone 2
II 3 G Ex nA IIC T4 Gc -40degC lt Ta lt +80degC
Electromagnetic Compatibility (EMC) ComplianceRadiated Emissions BS EN 61000-6-4 CISPR 16 RFI BS EN 61000-6-2 IEC 61000-4-3 Conducted RFI BS EN 61000-6-2 IEC 61000-4-6 ESD BS EN 61000-6-2 IEC 61000-4-2 EFT BS EN 61000-6-2 IEC 61000-4-4 Surge Immunity BS EN 61000-6-2 IEC 61000-4-5
PhysicalGeneralGeneral-purpose enclosure designed for mounting on 35mm ldquoT-typerdquo DIN railCase MaterialSelf-extinguishing polyamide UL94 V-0 rated color light gray General-purpose NEMA Type 1 enclosureIO ConnectorsRemovable plug-in terminal blocks rated for 12A250V AWG 26-12 stranded or solid copper wireDimensions175 x 1145 x 990 mm (07 x 451 x 390 inches)Shipping Weight022 kg (05 pounds) packed
Ordering Information
ModelsTT333-0700Four-wire transmitter thermocouplemillivolt input
ServicesTT330-ConfigCalFactory custom configurationcalibration service Specify input type inputoutput zero and full-scale values filtering and sensor fault settings on order
SoftwareTTC-SIP (recommend one kit per customer)Software Interface Package for Acromag TT Series transmitters Includes configuration software CD-ROM (5040-944) isolator (USB-ISOLATOR) and two USB cables (4001-112 4001-113)
AccessoriesSee wwwacromagcom for more informationUSB-ISOLATORUSB-to-USB isolator includes USB cable (4001-112)TT BUS-KITDIN rail bus power connector and leftright terminal blocks One kit supports multiple transmitters
IMPORTANT To prevent damage or errors from grounded PCs and surges Acromag
strongly recommends use of their USB-ISOLATOR when configuring a TT330 Series transmitter
Tel 877-214-6267 salesacromagcom wwwacromagcom 30765 Wixom Rd Wixom MI 48393 USA
Transmitters TT Series
Bulletin 8400-836b
The Agilitytrade Config Tool is a mobile application that allows easy setup and configuration of Acromag TT Series transmitters via a tethered mobile device
This free app is available for Android devices at the Google Play store at Acromag Agilitytrade Config Tool
Demo the software no need for a module To enter demo mode simply tap the icon in the upper left corner 8 times
Acromag Agilitytrade Config Tool Mobile Application
Key Features amp Benefits Connects to Acromag TT Series transmitters
(except models TT231)
Requires the use of USB OTG Cable (Acromag part 5028-565) and USB A to Mini B Cable (Acromag part 4001-113)
Configures and calibrates TT Series products via phone or tablet running Android 43 ICS (Ice Cream Sandwich) or later
View wiring diagrams even without an internet connection
Perform quick and easy field diagnostics and troubleshooting
Ideal for field techniciansWith a couple of taps quickly configure input output unit and scaling options
Quick and easy access to the wiring diagram even offline without internet access
Tel 877-214-6267 salesacromagcom wwwacromagcom 30765 Wixom Rd Wixom MI 48393 USA
All trademarks are property of their respective owners Copyright copy Acromag Inc 2019 Data subject to change without notice Printed in USA 102019
Transmitters TT330 SeriesTT333 Thermocouplemillivolt input four-wire transmitter
Performance Specifications
USB InterfaceUSB ConnectorType USB Mini-B type socket 5-pin Data rate 12Mbps USB v11 and 20 compatible Maximum cable length 50 metersUSB Transient ProtectionTransient voltage suppression on power and data linesDriverNot required Uses Windows HID drivers
InputDefault ConfigurationCalibrationInput TC J -210 to 760degC med filter break up Output 4 to 20mAInput Ranges and Accuracy
Input Range Accuracy TC J TC K TC T TC R TC S TC E TC B TC N mV
-210 to 760degC (-346 to 1400degF) -200 to 1372degC (-328 to 2502degF) -260 to 400degC (-436 to 752degF) -50 to 1768degC (-58 to 3214degF) -50 to 1768degC (-58 to 3214degF) -200 to 1000degC (-328 to 1832degF) 260 to 1820degC (500 to 3308degF) -230 to 1300degC (-382 to 2372degF) -100 to 100mV
plusmn05degC plusmn05degC plusmn05degC plusmn10degC plusmn10degC plusmn05degC plusmn10degC plusmn10degC plusmn01mV
Error includes the effects of repeatability terminal point conformity and linearization (but not CJC error)Thermocouple Reference (Cold Junction Compensation)plusmn02degC typical plusmn05degC maximum at 25degCAmbient Temperature EffectBetter than plusmn80ppmdegC (plusmn0008degC)Scaling AdjustZero 0 to 95 of range typical Full scale 5 to 100 of full scale range typicalLead Break (Sensor Burnout) DetectionUpscaledownscale plusmn5 full scale range typicalInput Over-Voltage ProtectionBipolar Transient Voltage Suppressers (TVS) 56V clamp level typicalInput ResolutionMillivolt input 00025 (1 part in 40000) Thermocouple input 01degC
Input ImpedanceCurrent input 249 ohms Voltage input 15M ohmsInput FilterSelectable digital filtering settings (none low medium and high)Noise RejectionNormal mode 60Hz gt05dB (no filter) gt80dB (high filter) Common mode 60Hz gt100dB (no filter) gt130dB (high filter)
OutputOutput Range
Range Over-Range Resolutionplusmn10V plusmn5V 0 to 10V 0 to 5V plusmn20mA 0 to 20mA 4 to 20mA
plusmn105V plusmn525V ndash05527 to +105V ndash027634 to +525V plusmn21mA ndash11054 to 21mA ndash11054 to 21mA
1 part in 62415 1 part in 31208 1 part in 59240 1 part in 60262 1 part in 62259 1 part in 58596 1 part in 46877
Output LoadVoltage output 1K ohms minimum Current output 0-550 ohmsOutput Response Time (for step input change)
Time to reach 98 of final output value (typical)No filter Low filter
15 milliseconds 40 milliseconds
Medium filter 120 millisecondsHigh filter 850 milliseconds
Output RippleLess than plusmn01 of output spanOutput Ambient Temperature DriftBetter than plusmn80ppmdegC (plusmn00080degC
EnvironmentalOperating temperature-40 to 80degC (-40deg to 176degF)Storage temperature-40 to 85degC (-40 to 185degF)Relative humidity5 to 95 non-condensingPower Requirement12-32V DC SELV (Safety Extra Low Voltage) 24mA maxIsolation1500V AC peak 250V AC (354V DC) continuous isolation between input output and power (3-way)Shock and Vibration ImmunityVibration 4g per IEC 60068-2-6 Shock 25g per IEC 60068-2-27ApprovalsCE compliant ULcUL listed Class I Division 2 Groups ABCD ATEX IECEx certified Zone 2
II 3 G Ex nA IIC T4 Gc -40degC lt Ta lt +80degC
Electromagnetic Compatibility (EMC) ComplianceRadiated Emissions BS EN 61000-6-4 CISPR 16 RFI BS EN 61000-6-2 IEC 61000-4-3 Conducted RFI BS EN 61000-6-2 IEC 61000-4-6 ESD BS EN 61000-6-2 IEC 61000-4-2 EFT BS EN 61000-6-2 IEC 61000-4-4 Surge Immunity BS EN 61000-6-2 IEC 61000-4-5
PhysicalGeneralGeneral-purpose enclosure designed for mounting on 35mm ldquoT-typerdquo DIN railCase MaterialSelf-extinguishing polyamide UL94 V-0 rated color light gray General-purpose NEMA Type 1 enclosureIO ConnectorsRemovable plug-in terminal blocks rated for 12A250V AWG 26-12 stranded or solid copper wireDimensions175 x 1145 x 990 mm (07 x 451 x 390 inches)Shipping Weight022 kg (05 pounds) packed
Ordering Information
ModelsTT333-0700Four-wire transmitter thermocouplemillivolt input
ServicesTT330-ConfigCalFactory custom configurationcalibration service Specify input type inputoutput zero and full-scale values filtering and sensor fault settings on order
SoftwareTTC-SIP (recommend one kit per customer)Software Interface Package for Acromag TT Series transmitters Includes configuration software CD-ROM (5040-944) isolator (USB-ISOLATOR) and two USB cables (4001-112 4001-113)
AccessoriesSee wwwacromagcom for more informationUSB-ISOLATORUSB-to-USB isolator includes USB cable (4001-112)TT BUS-KITDIN rail bus power connector and leftright terminal blocks One kit supports multiple transmitters
IMPORTANT To prevent damage or errors from grounded PCs and surges Acromag
strongly recommends use of their USB-ISOLATOR when configuring a TT330 Series transmitter
Tel 877-214-6267 salesacromagcom wwwacromagcom 30765 Wixom Rd Wixom MI 48393 USA
Transmitters TT Series
Bulletin 8400-836b
The Agilitytrade Config Tool is a mobile application that allows easy setup and configuration of Acromag TT Series transmitters via a tethered mobile device
This free app is available for Android devices at the Google Play store at Acromag Agilitytrade Config Tool
Demo the software no need for a module To enter demo mode simply tap the icon in the upper left corner 8 times
Acromag Agilitytrade Config Tool Mobile Application
Key Features amp Benefits Connects to Acromag TT Series transmitters
(except models TT231)
Requires the use of USB OTG Cable (Acromag part 5028-565) and USB A to Mini B Cable (Acromag part 4001-113)
Configures and calibrates TT Series products via phone or tablet running Android 43 ICS (Ice Cream Sandwich) or later
View wiring diagrams even without an internet connection
Perform quick and easy field diagnostics and troubleshooting
Ideal for field techniciansWith a couple of taps quickly configure input output unit and scaling options
Quick and easy access to the wiring diagram even offline without internet access
Tel 877-214-6267 salesacromagcom wwwacromagcom 30765 Wixom Rd Wixom MI 48393 USA
Transmitters TT Series
Bulletin 8400-836b
The Agilitytrade Config Tool is a mobile application that allows easy setup and configuration of Acromag TT Series transmitters via a tethered mobile device
This free app is available for Android devices at the Google Play store at Acromag Agilitytrade Config Tool
Demo the software no need for a module To enter demo mode simply tap the icon in the upper left corner 8 times
Acromag Agilitytrade Config Tool Mobile Application
Key Features amp Benefits Connects to Acromag TT Series transmitters
(except models TT231)
Requires the use of USB OTG Cable (Acromag part 5028-565) and USB A to Mini B Cable (Acromag part 4001-113)
Configures and calibrates TT Series products via phone or tablet running Android 43 ICS (Ice Cream Sandwich) or later
View wiring diagrams even without an internet connection
Perform quick and easy field diagnostics and troubleshooting
Ideal for field techniciansWith a couple of taps quickly configure input output unit and scaling options
Quick and easy access to the wiring diagram even offline without internet access