Post on 12-Feb-2017
Thermo Scientific Polar Series Cooling/Heating Recirculating Chillers
Product Cat. No.
Accel 250 LC Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force Pump with USB & Low Level Switch 223312800 223312600 223312100 223312900
Force / Suction Pump with USB & Low Level Switch 223412800 223412600 223412100 223412900
Accel 500 LC Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force Pump with USB & Low Level Switch 223322800 223322600 223322100 223322900
Force / Suction Pump with USB & Low Level Switch 223422800 223422600 223422100 223422900
Accel 500 LT Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force / Suction Pump with USB & Low Level Switch 223432800 223432600 223432100 223432900
Accel 500 LT/HT Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force / Suction Pump with USB & Low Level Switch 223432801 –– 223432101 ––
Accessories
USB Interface Cable (1.8 m) 1600033
Trolley with Locking Casters 1600122
Magnetic Condenser Air Filter 096270
Supply and Return Tubing - Non-Insulated 1600146
Supply and Return Tubing - Insulated 1600147
Insulated Flex SS Tubing w/M16x1 Threaded Fittings (0.5 m) 3330292
Insulated Flex SS Tubing w/M16x1 Threaded Fittings (1.0 m) 3330293
Insulated Flex SS Tubing w/M16x1 Threaded Fittings (1.5 m) 3330294
Dynamic, reliable, efficient
As an innovative leader in temperature control, we have the expertise to enable you to optimize your liquid cooling and heating applications while increasing productivity and reducing operating costs. With over 50 years of industry leading service and countless successful installations around the world, we collaborate with you to provide product and applications expertise to meet the most demanding temperature control requirements. From bio-tech and pharmaceutical to printing and semiconductor applications, world class companies and industry leaders continue to make Thermo Scientific temperature control products their first choice.
Select the product that is right for your application from the most comprehensive portfolio of temperature control solutions that deliver scalable product offerings ranging from bench top research to large process manufacturing. Our new and innovative products – developed from customer feedback – represent a giant leap forward in performance, configurability and technology and provide unparalleled advantages including:
A Flexible Choice: We have options to help you configure a flexible, cost-effective temperature control system that suits your specific requirements.
Innovation: Our research and development team is focused on designing innovative products based on your feedback.
Global Service and Support: With our extensive global footprint, as well as, service and support capabilities, we can support you anywhere in the world.
The Ideal FitTemperature control products for a wide range of applications
trim
4
Thermo Scientific Accel 250 LC and Accel 500 LC Designed with you in mind
Dynamic: Designed to provide temperature control with the flexibility needed for demanding applications and performance requirements, while fitting into your laboratory with minimal requirements for energy.
Reliable: Built for the high quality and reliability you demand, using proven refrigeration components and manufacturing methods to ensure a robustproduct that you can depend on for years of operation.
Efficient: Compact, powerful cooling/heating recirculating chillers not only perform to specifications but do so with minimal footprint, efficient use of energy,and little disruption to your quiet laboratory, with less than a 58 dBA rating.
The Polar series is ideal for closed-and open-looped applications up to 500 watts. Each easy-to-use chiller offers a wide range of cooling for quick ramp-up and cool-down of your application. Set your desired temperature with models featuring custom temperature control capabilities.
Typical Applications:
• Chemical Reaction Control
• Separations
• Life Science Instrumentation
• Mass Spectroscopy
• Molecular Spectroscopy
• Atomic Spectroscopy
• Surface Science
• Materials Characterization
• Laboratory Automation
• General Laboratory Instrumentation
5
• Intuitive HMI interface with digital control and readout for easy navigation.
• Small internal reservoir and high cooling capacities translate into fast temperature ramp times.
• Ergonomic design fill, drain and control from the front. No need to reposition the machine to fill or drain.
• Small footprint allows you to place multiple units right next to each otherother.
• Additional Features: • Overflow tube • Extremely quiet operation – less than 58 dBA
• Available Options: • Pump options available for increased pressure and flow for demanding applications • USB port for serial communication • Low liquid level warning and alarm
Thermo Scientific Polar Series Cooling/Heating Recirculating Chillers
All user interface pointsare located on the frontof the unit for quick andeasy handling.
Cover protects againstinadvertent dislodging of the fill tube.
All units include funnelaccessory for easy filling.
Site tube on the front of the unit allows for quick indication of the fluid level.
Flexible fill tube on the frontpanel enables unit to be drained quickly.
Front Panel System ControlAll user interface points are located on the front of the unit for quick and easy handling.
Hea
t Lo
ad (W
atts
)H
eat
Load
(Wat
ts)
-20 0 20 40 60 80 100
700
600
500
400
300
200
100
300
250
200
150
100
50
Temperature °C
Temperature °C
A = WaterB = 50/50 Water/EG
A
B
-20 0 20 40 60 80
1. Accel 500 specifications obtained at sea level at a 20°C process setpoint, 20°C ambient condition, at nominal operating voltage. Other fluids, process temperatures, ambient temperatures, altitude or operating voltage will affect performance.2. LT/HT chiller results obtained using medium pump speed.
Cooling Capacity Accel 500 Heat Load Capacity1, 2
Hea
t Lo
ad (W
atts
)H
eat
Load
(Wat
ts)
-20 0 20 40 60 80 100
700
600
500
400
300
200
100
300
250
200
150
100
50
Temperature °C
Temperature °C
A = WaterB = 50/50 Water/EG
A
B
-20 0 20 40 60 80
3. Accel 250 specifications obtained at sea level using water (above 5°C) and 50/50 Water/EG (<5°C) as the recirculating fluid at a 20°C process setpoint, 20°C ambient condition, at nominal operating voltage. Other fluids, process temperatures, ambient temperatures, altitude or operating voltage will affect performance.
Cooling Capacity Accel 250 Heat Load Capacity3
Performance Curves
trim
Specifications
Accel 250 LC Accel 500 LC Accel 500 LT Accel 500 LT/HT
Working Temperature Range -10°C to +80°C (+14°F to +176°F)
-10°C to + 80°C(+ 14°F to + 176°F)
-25°C to +80°C(-13°F to +176°F)
-25°C to +95°C-13°F to +203°F
Cooling Capacity at 20° C 250 W / 853 BTU 500 W / 1706 BTU
Force PumpMaximum FlowMaximum Pressure
15 lpm (3.96 gpm)805 mbar (11.7 psi)
––––––
Force-Suction PumpMaximum FlowMaximum Pressure
21 lpm (5.5 gpm)805 mbar (11.7 psi)
Heating Capacity at 20° C230 V / 50 Hz115 V / 60 Hz220 V / 60 Hz100/50-60 Hz and 220/60 Hz (not available 500 LT/HT)
2.0 kW / 6829 BTU1.2 kW / 4097 BTU1.8 kW / 6146 BTU0.9 kW / 3073 BTU
Temperature Stability ±0 .1°C
Reservoir Volume 2.8 liters (0.74 gallons)
Unit Weight 30 kg (66 lb)
Physical Dimensions (H x W x D) 24.8 x 9.1 x 19.2 in (62.0 x 23.2 x 48.7 cm)
Compliance CE/RoHS/UL
Warranty 2 Years
Specifications obtained at sea level using water (above +5°C) and 50/50 EG/Water (<5°C) as the recirculating fluid at a +20°C process setpoint, +20°C ambient condition, at nominal operating voltage. Other fluids process temperatures, ambient temperatures, altitude or operating voltage will affect performance. Cooling capacity based on units with force pump at max flow. Other pumps and flow rates will affect cooling capacity performance. Pump specifications are nominal values of ±10%. Specifications are for reference only and are subject to change.
Product Cat. No.
Accel 250 LC Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force Pump with USB & Low Level Switch 223312800 223312600 223312100 223312900
Force / Suction Pump with USB & Low Level Switch 223412800 223412600 223412100 223412900
Accel 500 LC Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force Pump with USB & Low Level Switch 223322800 223322600 223322100 223322900
Force / Suction Pump with USB & Low Level Switch 223422800 223422600 223422100 223422900
Accel 500 LT Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force / Suction Pump with USB & Low Level Switch 223432800 223432600 223432100 223432900
Accel 500 LT/HT Cooling/Heating Recirculating Chiller 115V / 60 Hz 100 V / 50-60 Hz 220-230 V / 50 Hz 220 V / 60 Hz
Force / Suction Pump with USB & Low Level Switch 223432801 –– 223432101 ––
Accessories
USB Interface Cable (1.8 m) 1600033
Trolley with Locking Casters 1600122
Magnetic Condenser Air Filter 096270
Supply and Return Tubing - Non-Insulated 1600146
Supply and Return Tubing - Insulated 1600147
Insulated Flex SS Tubing w/M16x1 Threaded Fittings (0.5 m) 3330292
Insulated Flex SS Tubing w/M16x1 Threaded Fittings (1.0 m) 3330293
Insulated Flex SS Tubing w/M16x1 Threaded Fittings (1.5 m) 3330294
Ordering Information
Find out more at thermofisher.com/tc © 2017 Thermo Fisher Scientific Inc. All rights reserved. All trademarks are the property of Thermo Fisher Scientific and its subsidiaries unless otherwise specified. BRTCPOLAR 0217
The Ideal FitTemperature control products for a wide range of applications
Australia +61 39757 4300China +800 810 5118France +33 (0) 1 60 92 48 00Germany +49 (0) 721 4 09 44 44India +91 22 6716 2200Italy +39 02 95059 552Japan +81-3-6832-9270Netherlands +31 76 579 55 55
New Zealand +64 9 980 6700Nordic/Baltic/CIS countries+358 10 329 2200Spain/Portugal +34 93 223 09 18UK/Ireland +44 870 609 9254USA/Canada toll free +1 (800) 258-0830USA +1 (603) 436-9444Countries not listed +49 6184 90 6000
North America info.tc.us@thermofisher.comEurope sales.tc.eu@thermofisher.comChina tc.china@thermofisher.comIndia LSI_Marketing@thermofisher.comJapan info.lpg.jp@thermofisher.com