Form No. S3515-516Supersedes S3515-1015Page 1 of 12
Aluminum Finned Copper Coils: Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.
Twin Blowers: Move air quietly. Most models feature multispeed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.
Air Conditioner Compressor: Scroll Compressors eliminate need for crankcase heater. Standard on all models, except 5-Ton.
R-410A Refrigerant: Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.
Phase Rotation Monitor: Standard on all 3-phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.
Galvanized 20 Gauge Zinc Coated Steel Cabinet: Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.
Foil Faced Insulation: Standard on all units.
Full Length Mounting Brackets: Built into cabinet for improved appearance and easy installation. NOTE: Bottom mounting bracket included to assist in installation.
Electrical Components: Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or toggle disconnect switch.
Electric Heat Strips: Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed.
Filter Service Door: Separate service door provides easy access for filter change.
Two Inch, MERV 8 Pleated Air Filters: Are standard equipment. Factory or field installed.
Condenser Fan and Motor Shroud Assembly: Slides out for easy access.
Barometric Fresh Air Damper: Standard on all units. Allows up to 25% outside fresh air. Optional ventilation packages available.
Optional Circuit Breakers: Standard on all electric heat versions of single (230/208 volt) and three phase (230/208 volt) equipment. Toggle disconnects are standard on all electric heat versions of three phase (460 volt) equipment.
Slope Top: Standard feature for water run-off.
Top Rain Flashing: Standard feature on all models.
Freezestat: Standard on W72 models. Optional field installed CMC-29 can be used on all other models.
The Solair Wall-Mount Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.
THE WALL-MOUNT™ AIR CONDITIONERS 10.0 EER, (60HZ)
Liquid Line Filter Drier: Standard on all units. Protects system against moisture.
Compressor Control Module: Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.
High & Low Pressure Switches are Auto-Reset: Standard on all units. Built-in lockout circuit resets from the room thermostat. Provides commercial quality protection to the compressor.
Models J18AA to J72AA Right-Side Control PanelModels J18LA to J72LA Left-Side Control Panel1.5 to 6 Ton (17,000 to 71,000 Btuh)
Engineered Features
• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2013.• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition.• Commercial Product - Not intended for Residential application.
Green refriGerant
r-410a
Form No. S3515-516Supersedes S3515-1015Page 2 of 12
Capacity is certified in accordance with ANSI/ARI Standard 390-2003. EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003. All ratings based on fresh air intake being 100% closed (no outside air introduction).
Capacity and Efficiency Ratings
Specifications 1-1/2 Ton through 3 Ton
Specifications 3-1/2 Ton through 6 Ton
Models J18AAJ18LA
J24AAJ24LA
J30AAJ30LA
J36AAJ36LA
J42AAJ42LA
J48AAJ48LA
J60AAJ60LA
J72AAJ72LA
Cooling Capacity BTUH 17,000 24,600 30,000 36,400 41,500 48,000 59,000 71,000
EER 10.00 10.20 10.30 10.00 10.00 10.00 10.00 10.00
MODELS J18AA-AJ18LA-A
J24AA-AJ24LA-A
J24AA-BJ24LA-B
J24AA-CJ24LA-C
J30AA-AJ30LA-A
J30AA-BJ30LA-B
J30AA-CJ30LA-C
J36AA-AJ36LA-A
J36AA-BJ36LA-B
J36AA-CJ36LA-C
Electrical Rating – 60 Hz 230/208 - 1 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3 230/208 - 1 230/208 - 3 460 - 3
Operating Voltage Range 197-253 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506
Compressor--Circuit A
Voltage 230/208 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460 Rated Load Amps 6.0/6.8 9.2/10.6 6.0/6.9 4.3 10.5/12.0 6.6/7.5 3.6 13.4/15 9.9/11.1 5.1 Branch Circuit Selection Current
9.0 12.8 8.3 5.1 16.0 10.0 4.7 17.9 13.2 6.0
Lock Rotor Amps 48/48 64/64 58/58 28 77/77 71/71 38 112/112 88/88 44 Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor & Condenser
Fan Motor--HP--RPM 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 Fan Motor--Amps 1.2 1.2 1.2 0.8 1.5 1.5 0.8 1.5 1.5 0.8 Fan--DIA/CFM 18" - 1800 18" - 1800 18" - 1800 18" - 1800 20" - 2400 20" - 2400 20" - 2400 20" - 2200 20" - 2200 20" - 2200
Blower Motor & Evap.
Blower Motor--HP-RPM-SPD 1/6-1100-2 1/6-1100-1 1/6-1100-1 1/6-1100-1 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2 Blower Motor--Amps 0.8 1.1 1.1 .45 2.0 2.0 1.0 2.0 2.0 1.0 CFM Cooling & E.S.P. w/Filter (Rated-Wet Coil)
600 - .35 800 - .30 800 - .30 800 - .30 1000 - .45 1000 - .45 1000 - .45 1100 - .30 1100 - .30 1100 - .30
Filter Sizes (inches) STD. 16x25x1 16x25x1 16x25x1 16x25x1 16x30x1 16x30x1 16x30x1 16x30x1 16x30x1 16x30x1
Shipping Weight --LBS. 330 320 320 320 360 360 360 385 385 385
+Barometric Fresh Air Damper-Lbs 3.5 3.5 3.5 3.5 4.0 4.0 4.0 4.0 4.0 4.0
+Economizer-Lbs 69.0 69.0 69.0 69.0 75.0 75.0 75.0 75.0 75.0 75.0
MODELS J42AA-AJ42LA-A
J42AA-BJ42LA-B
J42AA-CJ42LA-C
J48AA-AJ48LA-A
J48AA-BJ48LA-B
J48AA-CJ48LA-C
J60AA-AJ60LA-A
J60AA-BJ60LA-B
J60AA-CJ60LA-C
J72AA-AJ72LA-A
J72AA-BJ72LA-B
J72AA-CJ72LA-C
Electrical Rating – 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506
Compressor--Circuit A
Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460 Rated Load Amps 15.1/16.9 10.4/11.6 5.2 17.3/19.6 11.8/13.3 5.8 21.8/23.2 13.9/14.8 7.4 27.7/30.4 16.9/18.5 8.8 Branch Circuit Selection Current
19.9 13.6 6.1 21.4 14.5 6.3 23.2 14.8 7.4 36.9 22.4 10.6
Lock Rotor Amps 109/109 83.1/83.1 41 135/135 98/98 55 130/130 110/110 55 185/185 149/149 75 Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor & Condenser
Fan Motor--HP--RPM-SPD 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1 1/2-1075-1 1/2-1075-1 3/4-1075-1 Fan Motor--Amps 2.6 2.6 1.3 2.6 2.6 1.3 2.5 2.5 1.3 4.0 4.0 1.7 Fan--DIA/CFM 24" - 2900 24" - 2900 24" - 2900 24" - 3000 24" - 3000 24" - 3000 24" - 3100 24" - 3100 24" - 3100 24" - 4000 24" - 4000 24" - 4000
Blower Motor & Evap.
Blower Motor--HP-RPM-SPD 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/2-1070-2 1/2-1070-2 1/2-1070-2 3/4-1035-2 3/4-1035-2 3/4-1035-2 Blower Motor--Amps 2.3 2.3 1.2 2.3 2.3 1.2 3.5 3.5 2.1 6.3 6.3 1.7 CFM Cooling & E.S.P. w/Filter (Rated-Wet Coil)
1350 - .40 1350 - .40 1350 - .40 1550 - .35 1550 - .35 1550 - .35 1800 - .30 1800 - .30 1800 - .30 2000 - .25 2000 - .25 2000 - .25
Filter Sizes (inches) STD. 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1
Shipping Weight --LBS. 475 475 475 485 485 485 550 550 550 550 550 550
+Barometric Fresh Air Damper-Lbs 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5
+Economizer-Lbs 91.5 91.5 91.5 91.5 91.5 91.5 91.5 91.5 91.5 91.5 91.5 91.5
Form No. S3515-516Supersedes S3515-1015Page 3 of 12
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory or field-installed at a later date.
Barometric Fresh Air Damper
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.
ECONOMIZER – WECO Series OPTIONAL The built-in economizer system is internally mounted behind the service door and allows outside ventilation air, up to 100% of the total airflow rating of the unit, to be introduced through the air inlet openings. It includes a built-in exhaust air damper. The economizer is designed to provide “free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
Standard Features:• Fully modulating• Honeywell Hi-Torque Actuator• 7" intake hood with filter• Simple single blade design• Positive shut-off with non-stick gaskets• Electronic DB and/or Enthalpy sensors depending upon version• Honeywell JADE electronic economizer module with precision settings and diagnostics• DB or Enthalpy economizer versions available
Ventilation System Packages
MIS-3754
MIS-3757
Economizer
Form No. S3515-516Supersedes S3515-1015Page 4 of 12
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized over-current protection and conductor wires in accordance with the National Electrical Code and all local codes.
MODELRated Volts & Phase
No. Field Power
Circuits
Single Circuit Multiple Circuit
Minimum Circuit
Ampacity
Maximum
External Fuse or Ckt. Brkr.
Field Power
Wire Size
Ground
Wire
MinimumCircuit
Ampacity
MaximumExternal Fuse or Ckt. Breaker
Field Power Wire Size
Ground
Wire SizeCkt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
J18AA-A00,A0ZA05A08A10
230/208-1
1111
16304656
20305060
121086
12101010
J24AA-A00, A0ZA04A05A08A10
230/208-1
11111
2125304656
3030305060
10101086
1010101010
J24AA-B00, B0ZB06
230/208-311
1522
2025
1210
1210
J24AA-C00, C0ZC06
460-311
911
1515
1414
1414
J30AA-A00, A0ZA05A08A10A15
230/208-1
1111
1 or 2
2632475884
3535506090
88864
101010108 58 26 60 30 6 10 10 10
J30AA-B00, B0ZB06B09B15
230/208-3
1111
19243351
20253560
121086
12101010
J30AA-C00, C0ZC06C09C12C15
460-3
11111
912172126
1515202530
1414121010
1414121010
J36AA-A00, A0ZA05A08A10A15
230/208-1
1111
1 or 2
2932475884
3535506090
88864
101010108 58 26 60 30 6 10 10 10
J36AA-B00, B0ZB06B09B15
230/208-3
1111
23243351
30303560
101086
10101010
J36AA-C00, C0ZC06C09C12C15
460-3
1111
1112172126
1515202530
1414121010
1414121010
J42AA-A00, A0ZA05A10A15A20
230/208-1
111
1 or 21 or 2
32325884
110
50506090
125
88642
10101086
5858
2652
6060
3060
66
106
1010
1010
J42AA-B00, B0ZB09B15B18
230/208-3
1111
25335160
35356060
8866
10101010
J42AA-C00, C0ZC09C15
460-3111
121726
152030
141210
141210
J48AA-A00, A0ZA05A10A15A20
230/208-1
111
1 or 21 or 2
34345884
110
50506090
125
88642
10101086
5858
2652
6060
3060
66
106
1010
1010
J48AA-B00, B0ZB09B15B18
230/208-3
1111
26335160
35356060
8866
10101010
J48AA-C00, C0ZC09C15
460-3111
121726
152030
141210
141210
J60AA-A00, A0ZA05A10A15A20
230/208-1
111
1 or 21 or 2
38386086
112
60606090
125
88632
10101086
6060
2652
6060
3060
66
106
1010
1010
J60AA-B00, B0ZB09B15B18
230/208-3
1112
273553N/A
404060N/A
886
N/A
101010N/A 35 28 40 30 8 10 10 10
J60AA-C00, C0ZC09C15
460-3111
141827
202030
121210
121210
J72AA-A00, A0ZA05A10A15A20
230/208-1
11
1 or 21 or 21 or 3
58586288
114
60607090
125
66632
1010886
585858
265252 52
606060
306060 60
666
1066 6
101010
101010 10
J72AA-B00, B0ZB09B15B18
230/208-3
1112
404055N/A
606060N/A
886
N/A
101010N/A 40 28 60 30 8 10 10 10
J72AA-C00, C0ZC09C15
460-3111
181827
252530
101010
101010
Electrical Specifications — J**AA Series (Field Installed Elec. Heat Only)
Form No. S3515-516Supersedes S3515-1015Page 5 of 12
MODELRated Volts & Phase
No. Field Power
Circuits
Single Circuit Dual Circuit
Minimum Circuit
Ampacity
Maximum
External Fuse or Ckt. Brkr.
Field Power
Wire Size
Ground
Wire
MinimumCircuit
Ampacity
MaximumExternal Fuse or Ckt. Breaker
Field Power Wire Size
Ground
Wire SizeCkt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
J18LA-A00,A0ZA05A08A10
230/208-1
1111
16304656
20305060
121086
12101010
J24LA-A00, A0ZA05A08A10
230/208-1
1111
21304656
30305060
101086
10101010
J24LA-B00, B0ZB06
230/208-311
1522
2025
1210
1210
J24LA-C00, C0ZC06
460-311
911
1515
1414
1414
J30LA-A00, A0ZA05A08A10A15
230/208-1
1111
1 or 2
2632475884
3535506090
88864
101010108 58 26 60 30 6 10 10 10
J30LA-B00, B0ZB09B15
230/208-3111
193351
203560
1286
121010
J30LA-C00, C0ZC09C15
460-3111
91726
152030
141210
141210
J36LA-A00, A0ZA05A10A15
230/208-1
111
1 or 2
29325884
35356090
8864
1010108 58 26 60 30 6 10 10 10
J36LA-B00, B0ZB09B15
230/208-3111
233351
303560
1086
101010
J36LA-C00, C0ZC09C15
460-3111
111726
152030
141210
141210
J42LA-A00, A0ZA05A10A15
230/208-1
111
1 or 2
32325884
50506090
8864
1010108 58 26 60 30 6 10 10 10
J42LA-B00, B0ZB09B15
230/208-3111
253351
353560
886
101010
J42LA-C00, C0ZC09C15
460-3111
121726
152030
141210
141210
J48LA-A00, A0ZA05A10A15
230/208-1
111
1 or 2
34345884
50506090
8864
1010108 58 26 60 30 6 10 10 10
J48LA-B00, B0ZB09B15
230/208-3111
263351
353560
886
101010
J48LA-C00, C0ZC09C15
460-3111
121726
152030
141210
141210
J60LA-A00, A0ZA05A10A15
230/208-1
111
1 or 2
38386086
60606090
8863
1010108 60 26 60 30 6 10 10 10
J60LA-B00, B0ZB09B15
230/208-3111
273553
404060
886
101010
J60LA-C00, C0ZC09C15
460-3111
141827
202030
121210
121210
J72LA-A00, A0ZA05A10A15
230/208-1
11
1 or 21 or 2
58586288
60607090
6663
101088
5858
2652
6060
3060
66
106
1010
1010
J72LA-B00, B0ZB09B15
230/208-3111
404055
606060
886
101010
J72LA-C00, C0ZC09C15
460-3111
181827
252530
101010
101010
Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing. Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized over-current protection and conductor wires in accordance with the National Electrical Code and all local codes.
Electrical Specifications — J**LA Series (Field Installed Elec. Heat Only)
Form No. S3515-516Supersedes S3515-1015Page 6 of 12
Abo
ve d
ata
is w
ith
1"
stan
dard
thr
owaw
ay fi
lter
and
1"
was
habl
e fil
ter.
For
opti
onal
2"
plea
ted
filte
r -
redu
ce E
SP
by
.15
in.
See
ins
talla
tion
ins
truc
tion
s fo
r m
axim
um E
SP
inf
orm
atio
n on
var
ious
KW
app
licat
ion.
Spe
edJ1
8J2
4J3
0J3
6J4
2J4
8J6
0J7
2
Hig
hLo
w
Sin
gle
Hig
h
Low
Hig
h
Low
Hig
hLo
w
Hig
h
Low
Hig
h
Low
Hig
h
Low
ES
P(I
nch
H2
0)
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
Dry
Coi
lW
etC
oil
0.0
10
00
98
57
20
72
01
01
09
75
14
45
13
80
94
09
30
14
00
13
10
96
59
55
19
80
19
40
18
00
17
05
20
00
19
40
17
50
17
00
21
05
20
10
15
40
14
60
22
55
21
55
0.1
96
59
50
70
06
90
96
09
25
13
85
13
20
93
09
20
13
40
12
60
94
09
30
19
05
18
80
17
00
16
40
19
10
18
65
16
75
16
15
20
45
19
60
14
80
13
95
21
85
20
95
0.2
93
59
00
66
56
60
90
58
70
13
05
12
40
92
09
10
12
65
11
85
90
58
90
18
20
17
60
16
15
15
65
18
20
17
70
16
00
15
40
19
70
18
85
14
00
13
15
21
15
20
35
0.3
88
08
45
63
56
25
83
58
00
12
20
11
50
89
58
80
11
80
11
00
86
08
50
17
35
16
65
15
30
14
50
17
20
16
05
15
00
14
25
18
95
18
00
13
00
12
20
20
50
19
70
0.4
79
57
60
59
05
75
75
07
20
11
25
10
55
85
08
30
10
80
10
10
80
07
85
16
15
15
65
14
25
13
50
15
75
15
00
13
75
13
20
18
00
17
00
12
20
11
50
19
85
19
20
0.5
68
06
45
52
05
10
64
06
10
10
20
95
07
85
75
09
70
89
57
05
68
01
51
01
38
01
10
09
80
14
20
11
90
10
75
10
30
17
05
16
05
11
10
10
70
19
25
18
55
Nom
inal
KW
At
24
0V
(1)
At
20
8V
(1)
At
48
0V
(2)
At
46
0V
(2)
Kw
1-P
h A
mps
3-P
h A
mps
Btu
hK
w1
-Ph
Am
ps3
-Ph
Am
psB
tuh
Kw
3-P
h A
mps
Btu
hK
w3
-Ph
Am
psB
tuh
4.0
4.0
16
.71
3,6
52
3.0
01
4.4
10
,23
9
5.0
5.0
20
.81
7,0
65
3.7
51
8.0
12
,79
9
6.0
6.0
14
.42
0,4
78
4.5
01
2.5
15
,35
96
.07
.22
0,4
78
5.5
26
.91
8,8
40
8.0
8.0
33
.32
7,3
04
6.0
02
8.8
20
,47
8
9.0
9.0
21
.73
0,7
17
6.7
51
8.7
23
,03
89
.01
0.8
30
,71
78
.28
10
.42
8,2
60
10
.01
0.0
41
.73
4,1
30
7.5
03
6.1
25
,59
8
15
.01
5.0
62
.53
6.1
51
,19
51
1.2
55
4.1
31
.23
8,3
96
15
.01
8.0
51
,19
51
3.8
01
7.3
47
,09
9
18
.01
8.0
43
.36
1,4
34
13
.50
37
.54
6,0
76
18
.02
1.7
61
,43
41
6.5
62
0.8
56
,51
9
20
.02
0.0
83
.36
8,2
60
15
.00
72
.15
1,1
95
(1)
Thes
e el
ectr
ic h
eate
rs a
re a
vaila
ble
in 2
30
/20
8V
unit
s on
ly.
(2)
Thes
e el
ectr
ic h
eate
rs a
re a
vaila
ble
in 4
80
V un
its
only
.
In
do
or
Blo
wer
Per
form
an
ce (
60 H
z) -
CF
M a
t R
ate
d V
olt
ag
e
Ele
ctri
c H
eat
Ta
ble
- R
efer
to
Ele
ctri
cal
Sp
ecif
ica
tio
ns
for
Av
ail
ab
ilit
y b
y U
nit
Mo
del
F
acto
ry C
onne
cted
Spe
ed.
Form No. S3515-516Supersedes S3515-1015Page 7 of 12
NOTE: Field installed Heater Packages are not approved for use with top supply opening models.
These heater packages approved for use in dehumidification versions with hot gas reheat.
Heater Packages - Field Installed "A" Series Right-Hand Units• Designed for adding Electric Heat to 0 KW Units • ETL US & Canada Listed• Circuit Breaker Standard on 230/208V Models • Toggle Disconnect Standard on 460V Models
AirConditioner
Models
-A00 Models230/208-1
-B00 Models230/208-3
-C00 Models460-3
Heater Model # KW Heater Model # KW Heater Model # KW
J18AAEHWA02-A05BEHW02A-A08BEHWA02A-A10B
58
10N/A N/A
J24AA
EHWA24A-A04BEHWA02-A05BEHW02A-A08BEHWA02A-A10B
458
10
EHWA24-B06B 6 EHWH24B-C06 6
J30AA
EHWA03-A05BEHWA03-A08BEHWA03-A10BEHWA03-A15B
58
1015
EHWA03-B06BEHWA03-B09BEHWA37-B15B
69
15
EHWC03A-C06EHWC03A-C09EHWA03A-C12EHWA03A-C15
69
1215
J36AA
EHWA03-A05BEHWA03-A08BEHWA03-A10BEHWA03-A15B
58
1015
EHW36A-B06BEHWA03-B09BEHWA37-B15B
69
15
EHWC03A-C06EHWC03A-C09EHWA03A-C12EHWA03A-C15
69
1215
J42AAJ48AA
EHW4TA-A05 EHWA05-A10B
EHWA05-A15BEHWA05-A20B
5101520
EHWA05-B09B EHWA05-B15B
EHW4TA-B18
91518
EHW4TA-C09 EHW4TA-C15
915
J60AA
EHW5TA-A05 EHWA05-A10B
EHWA05-A15BEHWA05-A20B
5101520
EHW60A-B09B EHWA05-B15B EHW5TA-B18
91518
EHW4TA-C09 EHW4TA-C15
915
J72AA
EHW5TA-A05EHWA05-A10EHWA05-A15EHWA05-A20
5101520
EHW70A-B09BEHWA05-B15BEHW6TA-B18
91518
EHWA05A-C09EHW4TA-C15
915
AirConditioner
Models
-A00 Models230/208-1
-B00 Models230/208-3
-C00 Models460-3
Heater Model # KW Heater Model # KW Heater Model # KW
J18LAEHWA02A-A05LBEHW02A-A08LBEHWA02-A10LB
58
10N/A N/A
J24LAEHWA02A-A05LBEHW02A-A08LBEHWA02-A10LB
58
10EHWA24-B06LB 6 N/A
J30LA
EHWA03-A05LBEHWA03-A08LBEHWA03-A10LBEHWA03-A15LB
58
1015
EHWA03-B09LBEHWA37-B15LB
915
EHWC03-C09LEHWA03-C15L
915
J36LAEHWA03-A05LBEHWA03-A10LBEHWA03-A15LB
51015
EHWA03-B09LBEHWA37-B15LB
915
EHWC03-C09LEHWA03-C15L
915
J42LAJ48LA
EHW4TA-A05LEHWA05-A10LBEHWA05-A15LB
51015
EHWA05-B09LBEHWA05-B15LB
915
EHW4TA-C09LEHW4TA-C15L
915
J60LAEHW4TA-A05L
EHWA05-A10LBEHWA05-A15LB
51015
EHWA60-B09LBEHWA05-B15LB
91518
EHW4TA-C09LEHW4TA-C15L
915
J72LAEHW6TA-A05LEHWA05-A10LEHWA05-A15L
51015
EHW70A-B09LEHWA05-B15L
915
EHW4TA-C09LEHW4TA-C15L
915
Heater Packages - Field Installed "L" Series Left-Hand Units
Form No. S3515-516Supersedes S3515-1015Page 8 of 12
3"
Side View
High Voltage
Cond.
Electrical
Drain
InletAir
PanelAccessHeater
4° PitchRain Hood
Built In
(Lockable)Access Panel
Disconnect
EntranceElectrical
Low Voltage
Entrance
C. Breaker/
Hood for CRV andECON modelsonly
1.250
H
D
J
C
2.13
A
I
K7.00
MIS-3796
ElectricHeat
Ventilation Air
Front View
Air OutletCondenser
Filter Access Panel
Standardflush ventdoor for non-ERV/CRVEcon.models
1
F
G
W
5.88
Supply Air Opening
ShippingLocation
Return Air OpeningEntrancesElectricalOptional
(Built In)BracketsMountingSide Wall
Top RainFlashing
Bottom InstallationBracketBack View
T
OE
R
S
S
S
S
SM
.44
NQ
B
P
L
Dimensions of J18-72AA Basic Unit for Architectural & Installation Requirements (Nominal)
MODELWIDTH
(W)DEPTH
(D)HEIGHT
(H)SUPPLY RETURN
A B C B E F G I J K L M N O P Q R S T
J18AAJ24AA 33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00 9.00
J30AAJ36AA 38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 4.19 12.00 9.00
J42AAJ48AA 42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
J60AAJ72AA 42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
Clearances Required for Service Accessand Adequate Condenser Inlet AirflowMODELS LEFT SIDE RIGHT SIDE
J18AA, J24AA, J30AA, J36AA 15" 20"
J42AA, J48AA, J60AA, J72AA 20" 20"
NOTE: For side-by-side installation of two (2) JA models, there must be 20" between units. This can be reduced to 15" by using a JL model (left side compressor and controls) for the left unit and JA (right side compressor and controls) for right unit.
Minimum Clearances Required to Combustible Materials
MODELS SUPPLY AIR DUCT FIRST THREE FEET CABINET
J18AA, J24AA 0" 0"
J30AA, J36AA 1/4" 0"
J42AA, J48AA, J60AA, J72AA 1/4" 0"
Refer to the Installation Manual for more detailed information.
Not used when WECO Economizers installed. Filter access is through the WECO hood.
Form No. S3515-516Supersedes S3515-1015Page 9 of 12
1.250I
A
C
K
2.13
H
J
NQ
PM
L
OE
.44 W
3"F
G
R
S
S
S
S
S
T
D
B
5.88
Hood for CRV andECON modelsonly
7.000
1
BottomInstallation
(Built In)
Supply Air Opening
MIS-3737
Air Air Outlet
Bracket
Front ViewDrainElectricalEntrance
Entrances
Inlet
Side ViewHigh Voltage
Cond.
Low VoltageElectrical
Back View
Condenser
OptionalElectrical
Entrance
BracketsMountingSide Wall
LocationShippingFlashing
Return Air Opening
Standard flush
Disconnect
ElectricHeat
Top Rain
HeaterAccess
Filter Access Panel
vent door for
Panel
Econ. modelsnon-ERV/CRV
(Lockable)Access Panel
Ventilation Air
C. Breaker/
Built InRain Hood4° Pitch
Dimensions of J18-72LA Basic Unit for Architectural & Installation Requirements (Nominal)
MODELWIDTH
(W)DEPTH
(D)HEIGHT
(H)SUPPLY RETURN
A B C B E F G I J K L M N O P Q R S T
J18LAJ24LA 33.300 17.125 74.563 7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00 9.00
J30LAJ36LA 38.200 17.125 74.563 7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14 4.19 12.00 9.00
J42LAJ48LA 42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
J60LAJ72LA 42.075 22.432 93.000 9.88 29.88 15.88 29.88 43.88 13.56 37.00 30.00 40.81 35.06 42.81 40.56 3.37 43.00 31.00 10.00 1.44 16.00 10.00
Clearances Required for Service Accessand Adequate Condenser Inlet AirflowMODELS LEFT SIDE RIGHT SIDE
J18LA, J24LA, J30LA, J36LA 15" 20"
J42LA, J48LA, J60LA, J70LA 20" 20"
NOTE: For side-by-side installation of two (2) JL models, there must be 20" between units. This can be reduced to 15" by using a JL model (left side compressor and controls) for the left unit and JA (right side compressor and controls) for right unit.
Minimum Clearances Required to Combustible Materials
MODELS SUPPLY AIR DUCT FIRST THREE FEET CABINET
J18LA, J24LA 0" 0"
J30LA, J36LA 1/4" 0"
J42LA, J48LA, J60LA, J70LA 1/4" 0"
Refer to the Installation Manual for more detailed information.
Not used when WECO Economizers installed. Filter access is through the WECO hood.
Form No. S3515-516Supersedes S3515-1015Page 10 of 12
ModelReturn Air(DB/WB)
Cooling Capacity 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F
J18
75/62Total Cooling
Sensible Cooling1740013900
1670013700
1620013600
1550013400
1480013200
1430013000
1360012800
1290012500
1230012100
1170011600
1100011000
80/67Total Cooling
Sensible Cooling1850013400
1820013400
1790013400
1750013400
1700013300
1660013200
1600013100
1540012900
1480012600
1410012400
1330012000
85/72Total Cooling
Sensible Cooling2210013800
2130013600
2060013500
1980013300
1890013100
1820012800
1730012500
1640012100
1560011600
1470011200
1370010700
J24
75/62Total Cooling
Sensible Cooling2810022100
2600020600
2410019400
2240018400
2090017600
1980016900
1880016500
1800016200
1730016000
1690016000
1660015900
80/67Total Cooling
Sensible Cooling3000021400
2830020200
2670019200
2530018400
2460017700
2300017200
2210016900
2140016700
2080016600
2040016700
2020017000
85/72Total Cooling
Sensible Cooling3580021900
3310020500
3070019300
2860018300
2670017400
2520016700
2390016100
2280015700
2190015300
2120015100
2080015100
J30
75/62Total Cooling
Sensible Cooling3250024500
3080023600
2910022800
2760022100
2610021400
2490020900
2370020400
2260019900
2150019500
2060019200
1960018900
80/67Total Cooling
Sensible Cooling3470023700
3350023100
3230022600
3120022100
3000021600
2900021200
2790020900
2690020500
2580020300
2490020100
2390019900
85/72Total Cooling
Sensible Cooling4140024300
3920023500
3710022700
3530022000
3340021200
3170020500
3010019900
2860019200
2710018700
2590018200
2460017600
J36
75/62Total Cooling
Sensible Cooling3950029100
3730028100
3520027200
3350026300
3180025600
3040025000
2910024400
2790023900
2690023600
2600023200
2520022900
80/67Total Cooling
Sensible Cooling4210028200
4060027500
3910026900
3780026300
3640025800
3540025400
3430025000
3330024700
3230024500
3150024300
3070024100
85/72Total Cooling
Sensible Cooling5020028900
4750027900
4490027000
4270026100
4060025300
3870024600
3700023900
3550023200
3400022600
3280022000
3160021300
J42
75/62Total Cooling
Sensible Cooling4360034000
4160033200
3970032200
3800031400
3620030600
3450029900
3290029200
3130028600
2980027900
2830027300
2690026700
80/67Total Cooling
Sensible Cooling4650033000
4530032500
4410031900
4290031400
4150030900
4020030400
3880029900
3730029500
3580029000
3430028600
3270028100
85/72Total Cooling
Sensible Cooling5540033800
5300033000
5070032100
4850031200
4610030300
4400029400
4190028500
3970027700
3760026700
3570025900
3370024900
J48
75/62Total Cooling
Sensible Cooling5050038700
4820037800
4600036900
4390035900
4180035100
3990034200
3800033400
3610032500
3440031700
3270031000
3100030100
80/67Total Cooling
Sensible Cooling5390037500
5250037000
5110036500
4960035900
4800035400
4650034800
4480034200
4310033600
4140033000
3960032400
3780031700
85/72Total Cooling
Sensible Cooling6420038400
6140037600
5870036700
5600035700
5330034700
5090033700
4830032600
4590031500
4350030400
4120029300
3890028100
J60
75/62Total Cooling
Sensible Cooling6550049600
6190048200
5840046800
5500045300
5180043900
4880042500
4590041000
4310039600
4050038300
3790036800
3530035300
80/67Total Cooling
Sensible Cooling6990048100
6740047200
6480046300
6220045300
5900044300
5690043200
5420042100
5140040900
4870039800
4590038500
4300037300
85/72Total Cooling
Sensible Cooling8330049300
7880047900
7440046500
7020045000
6610043500
6220041800
5840040100
5470038400
5120036700
4770034800
4420033000
J72
75/62Total Cooling
Sensible Cooling7380055500
7080054000
6780052400
6480051000
6180049500
5900048200
5610046900
5320045600
5040044400
4760043200
4480042000
80/67Total Cooling
Sensible Cooling7880053800
7710052900
7530051900
7320051000
7100050000
6870049100
6620048100
6350047100
6070046200
5770045200
5460044200
85/72Total Cooling
Sensible Cooling9390055100
9010053700
8650052100
8260050700
7890049000
7510047500
7140045800
6760044200
6380042600
6000040800
5620039100
Capacity Multiplier Factors% of Rated Airflow -10 Rated +10
Total BTUHSensible BTUH
0.9750.950
1.01.0
1.021.05
Below 65°F (18.3C), unit requires a factory or field installed low ambient control. Return air temperature.
Cooling Application Data - Outdoor Temperature
Form No. S3515-516Supersedes S3515-1015Page 11 of 12
Ventilation OptionsModels J18AA, J24AA
J18LA, J24LAJ30AA, J36AAJ30LA, J36LA
J42AA, J48AA, J60AA, J72AAJ42LA, J48LA, J60LA, J72LA
DescriptionFactory Installed
Code No.Field Installed
Part No.Factory Installed
Code No.Field Installed
Part No.Factory Installed
Code No.Field Installed
Part No.Barometric Fresh Air Damper - Standard X BFAD-2 X BFAD-3 X BFAD-5Economizer w/Plug, Temp Only (7" Hood) Y WECOPT2-X Y WECOPT3-X Y WECOPT5-XEconomizer w/Plug, Enthalpy (7" Hood) Z WECOPE2-X Z WECOPE3-X Z WECOPE5-X
Air Conditioning Control Modules All Models Except As Noted
HPC LPC CCM LAC ALR SK SK Factory Installed Code Field Installed Part
STD STD STD • • J Factory Only
STD STD STD • Field Installed Only CMC-15
STD STD STD • Field Installed OnlySK111 Except J60 & J72
SK121 J72 OnlySK122 J60 Only
SERIES | | CONTROL MODULES (See Chart Below)
REVISION
VOLTS & PHASE A - 230/208/60/1 B - 230/208/60/3 C - 460/60/3
KW
COLOR OPTIONS X - Beige (Standard)
FILTER OPTIONS P - 2-inch Pleated (MERV 8)
| COIL OPTIONS X - Standard
| SUPPLY AIR OUTLET X - Front (Standard)
NOMINALCAPACITY | 18 - 1½ Ton 24 - 2 Ton 30 - 2½ Ton 36 - 3 Ton 42 - 3½ Ton 48 - 4 Ton 60 - 5 Ton 72 - 6 Ton
J 36 A A A 00 X P X X X J
VENTILATION OPTIONS (See Table Below)
Air Conditioning Wall-Mount Model Nomenclature
For 0KW and circuit breakers (230/208 Volt) or toggle disconnects (460 Volt) applications, insert 0Z in the KW field of the model number. See Pages 4 & 5 for available Factory Installed KW options and Page 7 for Field Installed Heater Packages.
A = Compressor & Controls - Right Side
L = Compressor & Controls - Left Side
STD = Standard equipment for these specified models. HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note . LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note . CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2-minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a 2-minute timed bypass for low-pressure control. LAC. Low ambient control permits cooling operation down to 0°F. LAC is fan-cycling control for outdoor fan motor on all models. ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls. SK. PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 or SK121 is used. SK. Start capacitor & potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if CMC-15 is used.
Form No. S3515-516Supersedes S3515-1015Page 12 of 12
NOTES
Due to our continuous product improvement policy, all specifications subject to change without notice. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
Form No. S3515