T3 Series Bacnet Programmable Controller
The T3000 controller is a multi-user, including T3-BB, T3-LB and T3-TB, which can stand alone DDC panel with full communications capabilities. They can be used either stand alone, or in a multiple network system. Multiple communication ports allow the controller to simultaneously operate on anetwork, host sub networks, and to communicate to local and remote operators.
Setup and programming are done on a PC without the need to be connected to live hardware as it is the case with many systems. When the program is ready for on-site testing, connect to a live panel and download the T3000 software. Programming can be done remotely over the network and modem connections as well. The network system is very fl exible and also more economical for the installation.
CONTROLS.COMTEMCO
T3-BB
10Year
WARRANTY
T3-LB
T3-TB
Specifications
SoftwareInteractive dynamic color graphicsIndustry standard Bacnet & Modbus protocolsUser programming, built in networking features16 Control Basic programs16 User screen displays8 Weekly routines, 4 annual routines128 User variables16 PID controllers8 passwords or users
HardwareHighly Configurable: any combination of input/output cards totalling up to 64 pointsDigital output: 5V/125VAC, 30DVCAnalog output: 0-10VUniversal input: Thermistor, 0-10V, 0-5V, 0-20mAMechanical relays 2A, 24VAC/DCDiagnostic LEDs & Hand-Off-Auto Switches512K Flash / 512k RamSD Disk slot for trend logs, alarms, graphicsEthernet Port: Bacnet & Modbus supported simultaneously2 x RS485 portsUSB Port only for T3-BB, T3-LBRS232 only for T3-BBZigbee port is optional, only for T3-BB, T3-LBClock with battery backup
• Surge-protected Universal Inputs with 12-bit resolution• UL listed ABS enclosure with rubberized texture creates a high end feel. • Software configure the I/O ranges with the free T3000 software or by writing to the registers with your own software. • Each output has a hand-off-auto switch for easy troubleshooting and overrides. • Each I/O as well as the RS485 connections have a separate screw terminal, there’s no need to gang two wires under one terminal for any of the terminations.• High/Low speed input pulse counters• RS485 sub baudrates: 9600, 19200• RS485 main baudrates: 1200~921600• Transportation methods are RS485, Ethernet, USB, Zigbee but it can, at the same time, support Modbus and Bacnet. • Source code for the modules is available with your first purchase. • T3000 front end is free and open source: http://tinyurl.com/hgxavu5• Compiled version of the front end is here: http://tinyurl.com/hgxavu5• Power Supply Voltage: 24V AC/DC• Relay: 5A/125VAC, 30VDC• Operating Temperature: -30~70°C (-22~158°F)• Maximum Power Consumption T3-BB: 10W T3-LB: 10W T3-TB: 6W• Case Color: Black
Part Number Scheme
T3 Series Bacnet Programmable Controller
1) T3-BB(Big Brother) 2) T3-LB(Little Brother) 2) T3-TB(Little Brother)
Network Diagram
Dimensions
T3 Series Bacnet Programmable Controller
Remote
T3-LB
Expansion I/O
Ethernet
Building
Operator
T3000 Building Automation
System Overview
SUBNET2RS485
T3-BB T3-TB T3-8o
RS485
FAN COIL
VAV
VALVES
BTU METERS
TSTAT8
TSTAT6
TSTAT7
TSTAT8
VALVES BOILERS
CHILLERS
User
MAIN NET1RS485
T3-22i
Wiring Diagram
T3 Series Bacnet Programmable Controller
32
USB
999897
12-24VGND
11
0/2
20
VA
C - IN
24
VA
C - O
UTAC/DC
ETHER
NET
2
3
5
969594
9392
TX
RX
GND 33
3534
RS485 SUBNET PORT1
32 UNIVERSAL INPUTS
3 65
2 66THERMOSTATTEMPERATUREFILTER SWITCHOCCUP SENSORFLOW SENSORFAN STATUSWINDOWCHANGEOVERFREEZE PROTECTPOWER METERBTU METERS
32 UNIVERSAL INPUTS
1 67
36
INP
UT
SR
S2
32 R
S48
5R
S48
5LAN
68
79
122
HEAT PUMP
FAN COIL
AIR HANDLER
112 HYDRONICS
12 ANALOG OUPUTSMODULATING VALVES
MODULATING DAMPERS
80 11124VAC
91 10024VAC
12 DIGITAL OUPUTS
RS485 SUBNET PORT2
POW
ER
T3-BB WIRING DIAGRAM
HEAT PUMP
FAN COIL
AIR HANDLER
HYDRONICS
12 DIGITAL OUPUTS
THERMOSTATTEMPERATUREFILTER SWITCHOCCUP SENSORFLOW SENSORFAN STATUSWINDOWCHANGEOVERFREEZE PROTECTPOWER METERBTU METERS
32 UNIVERSAL INPUTS
1 35
342
333
2016
36 63
ETHERN
ET
T3-LB WIRING DIAGRAM
LAN1817
19
MODULATING VALVES
MODULATING DAMPERS
2ANALOG OUTPUTS
24VAC45 54
16 U
I
GND
4950
11
0/2
20
VA
C - IN
24 V
AC
- OU
T
24VAC/DC
41
4748
46
515253
RS485 SUBNET NETWORK
RS485 MAIN NETWORK
58
6 D
O4 A
O
42 57
T3 Series Bacnet Programmable Controller
T3-TB Output Jumper Settings
1 28
27THERMOSTATTEMPERATUREFILTER SWITCHOCCUP SENSORFLOW SENSORFAN STATUSWINDOWCHANGEOVERFREEZE PROTECTPOWER METERBTU METERS
2
263
1811
11INPUTS
151617
29 52
30 51
31 50
4DIGITAL OUTPUTS
ETHE
RNET
T3-TB WIRING DIAGRAM
LAN1314
12
HEAT PUMP
FAN COIL
AIR HANDLER
HYDRONICS
MODULATING VALVES
MODULATING DAMPERS
2ANALOG OUTPUTS
24VAC
AO
G36 45
11 IN
PU
TS
8 OU
TPU
TS
GND
4140
11
0/2
20
VA
C - IN
24
VA
C - O
UT
24VAC/DC
32
34
33 2UNIVERSAL OUTPUTS
35 46
3839
37
424344
RS485 SUBNET NETWORK
RS485 MAIN NETWORK
Highlight
ControllerT3-BB
Big BrotherT3-LB
Little BrotherT3-TB
Tiny BrotherTotal Channels: 56 26 19 Universal Input 32 16 11 Analog Output 12 4 2 Relay Output 12 6 4 Universal Output 2*Comm ports: RS485 2 2 2 RS232 1 0 0 Ethernet 1 1 1 USB 1 1 0 Option port** 1 1 0
These units transportation methods are RS485, Ethernet, USB, Zigbee but it can, at the same time, support Modbus and Bacnet. The T3-BB unit features 32 channels input and 24 channels output including 12 channels analog output and 12 channels digital output. As for the T3-LB, there are 16 channels input and 10 channels output including 4 channels analog output and 6 channels digital out-put. For T3-TB, it includes 11 inputs and 8 outputs which contain 2 analog outputs, 4 digital outputs and 2 universal outputs. All these channels can be controlled directly by the mini panel through the use of input and output cards.
* The 2 universal output can be jumper selected as either 1-10V analog or relay outputs.
** zigbee module.
1.Click to scan Device detected 2.Click to close
T3000 Operation Instructions
1. Download T3000 software http://tinyurl.com/zsjv39y and install it.2. Take an example of T3-BB here, connect T3-BB to PC by RS485 network at pin 94, 95, and 96 or Ethernet. 3. Open T3000 software, and click icon building, an popup window will appear, set protocol to Auto, then close it. Click scan icon which is next to the icon building to find the connected unit.
Then click the device log what have been connected, T3000 software will show the info in righ hand place. You can click Input, Output and other icon.
T3 Series Bacnet Programmable Controller
3.Click to select minipanel
4.Click input to show table right
T3-BB T3-LB T3-TB SpeedLow Speed Input channels 1-32 1-16 1-11 1 HzHigh Speed Input channels 27-32 11-16 3-11 1M Hz
For T3-BB, T3-LB, T3-TB, all the inputs channels have pulse counters. High speed counters capable of 1M Hz. Low speed inputs channels reach to 1 hz per channel.
Here we take an example of T3-BB, showing how to configure the high speed and low speed coun-ters in T3000 software.
4. Click input icon, it will show all inputs in T3000 software.
T3 Series Bacnet Programmable Controller
5.Click input to show table below
Click input to show table below
5. Click output icon, it will show the output view.
T3 Series Bacnet Programmable Controller
*6.Steps to get zigbee information by T3000.
2.Click to see table below
3.Zigbee setting here now
1.Click the device with zigbeeZ
oom
Register List
Address Num Length Description0~3 1 4 Reserved for serial numbler4~5 1 2 firmware Version Number6 1 1 Modbus device address7 1 1 Prodouct model8 1 1 Hardware Version Number9 1 1 PIC rev10 1 1 Temporary address for plug-n-play addressing scheme11 1 1 reserved12 1 1 UART0 Baudrate. 5 - 9600 , 6 - 1920013 1 1 Enable node plug and play14 1 1 ISP Version15 1 1 Reserved16 1 1 Update status 17 1 1 reserved18 1 1 UART1 Baudrate. 5 - 9600 , 6 - 1920019 1 1 UART2 Baudrate.(UART_1200 = 0, UART_2400 = 1, UART_3600 = 2,
UART_4800 = 3, UART_7200 = 4, UART_9600 = 5, UART_19200 = 6, UART_38400 = 7, UART_57600 = 8, UART_115200 = 9, UART_921600 = 10
33 1 1 test cmd, write 77 - reboot, 100 - set default paramer, 111 - erase prg, 150 - clear tstat db
34 1 1 board type, big or small. 1 - big , 2 - samll,3-tiny,4-vav35 1 1 instance number36 1 1 station number39 1 1 EN clear tstat db42 1 1 USB MODE43 1 1 EN DYNDNS ,// 0 - no 1 - disable 2 - enable44 1 1 DYNDNS provider, // 0- www.3322.org 1-www.dyndns.com 2 - www.no-
ip.com 45 1 1 dyndns update timer46 2 1 NETWORK: MSB, MSB-147 2 1 MSTP NETWORK: MSB, MSB-151 1 1 TOP hardware52 1 1 c8051f023 firmware rev53 1 1 sm5964 firmware rev59 1 1 "com0 configure MAIN_MSTP = 0,MAIN_MODBUS
= 1,MAIN_PTP = 2,SUB_GSM = 3,MAIN_ZIG = 4,SUB_ZIG = 5,SUB_MODBUS = 6 "
T3 Series Bacnet Programmable Controller
Address Num Length Description60 1 1 com1 configure MAIN_MSTP = 0,MAIN_
MODBUS = 1,MAIN_PTP = 2,SUB_GSM = 3,MAIN_ZIG = 4,SUB_ZIG = 5,SUB_MODBUS = 6
61 1 1 com2 configure MAIN_MSTP = 0,MAIN_MODBUS = 1,MAIN_PTP = 2,SUB_GSM = 3,MAIN_ZIG = 4,SUB_ZIG = 5,SUB_MODBUS = 6
62 1 1 write flash time after changed setting. Unit is minute93 1 1 Reserved100~105 1 6 reg100, MAC address, read only106 1 1 reg106, DHCP setting. 0=static IP; 1= DHCP107~110 1 4 IP address: MSB, MSB-1, MSB-2, LSB111~114 1 4 SUBNET MASK address: MSB, MSB-1, MSB-2, LSB115~118 1 4 GATEWAY address: MSB, MSB-1, MSB-2, LSB119 1 1 reg119, 0, TCP server120 1 1 reg120, listen port at TCP server mode200~206 1 6 200 201 202 203 204 205 206
Last Time Sync second min hour day day of week month year
299 1 1 number of device which is connected to T3 controller300~400 1 100 id of sub tstat500~504 1 5 500 501 502 503 504
Number of AV AI AO BI BO
7000~7049 2 50 test 8000~8007 1 8 8000 8001 8002 8003 8004 8005 8006 8007
output input variable controller WR AR PRG TBL
8008~8015 1 8 8008 8009 8010 8011 8012 8013 8014 8015TZ AMON GRP ARRAY UNIT USER
NAMEALARM
SETTSTAT
8020~8083 2 64 output value, (digital output, ON - 512, OFF - 0)8084~8147 2 64 output swith status (SW_OFF - 0, SW_AUTO - 1, SW_HAND - 2)8148~8211 1 64 "output range (0 - unused) { UNUSED=0,
OFF_ON, CLOSED_OPEN, STOP_START, DISABLED_ENABLED, NORMAL_ALARM, NORMAL_HIGH, NORMAL_LOW, NO_YES, COOL_HEAT, UNOCCUPIED_OCCUPIED, LOW_HIGH, ON_OFF , OPEN_CLOSED, START_STOP, ENABLED_DISABLED, ALARM_NORMAL, HIGH_NORMAL, LOW_NORMAL, YES_NO, HEAT_COOL, OCCUPIED_UNOCCUPIED, HIGH_LOW, custom_digital1, custom_digital2, custom_digital3, custom_digital4, custom_digital5, custom_digital6, custom_digital7, custom_digital8 } Digital_units_equate;"
T3 Series Bacnet Programmable Controller
Address Num Length Description8212~8275 1 64 output auto or manual (0 - auto, 1- manual)8276~8339 1 64 output type, digital or analog (0 - digital 1 - analog)8340~8403 2 4 input value8404~8467 1 4 input filter8468~8531 1 4 input calibration8532~8595 1 4 input sign calibration8596~8859 1 64 "input range (not_used_input = 0, Y3K_40_150DegC,
Y3K_40_300DegF, R10K_40_120DegC, R10K_40_250DegF, R3K_40_150DegC, R3K_40_300DegF, KM10K_40_120DegC, KM10K_40_250DegF, A10K_50_110DegC, A10K_60_200DegF, V0_5, I0_100Amps, I0_20ma, I0_20psi, N0_2_32counts, N0_3000FPM_0_5V, P0_100_0_5V, P0_100_4_20ma, P0_255p_min, table1, table2, table3, table4, table5,100 - HI_SPEED_COUNTER )"
8660~8671 2 6 high speed counter1~68672~8677 1 6 high speed counter1~6 flag, 0 - start, 1 - stop, 2 -clear8678~8741 1 64 input type, 0- thermistor, 1- 5v, 2-10v, 3- 20ma8820~8947 1 128 value of VAR1-VAR1288948~9075 1 128 A/M of VAR1-VAR128
18000~ for test, tatst information30000~ for test, monitor task
Support BACnet Object Type:analog-input, analog-output, analog-value, binary-input, binary-output, device
Support BACnetService:who-is, i-am object-identifier, object-name, object-type, present-value, units, object-list, vendor-id, vendor-name, system-status, confirmed-service, unconfirmed-service
T3 Series Bacnet Programmable Controller
BIP objectT3-BB T3-LB T3-TB
Analog-variable AV1-10 AV1-10 AV1-10Analog-input: AI1~32 AI1~16 AI1~11
For BB, LB, TB, if add expansion modules, maximum inputs can reach to 64Analog-output: AO1~12 AO1~4 AO1~4Binary-output: BO1~12 BO1~6 BO1~2
Outputs: For BB, LB, TB, if add expansion modules, maximum outputs can reach to 64. T3-TB itself has total 8 outputs, while there are 2 universal ouputs can be used as analog output, or binary output.
Device: obect-identifierobject-nameobject-list
T3 Series Bacnet Programmable Controller