SSSaaa fff eee tttyyy RRReee lll aaayyy BBBoooaaarrrddd FFFGGGRRR 555222 Universal DIN-Rail Mount Board with two force guided relay

Force Guided Relays International * 161 Clear Road - Oriskany, NY 13424, USA 1-877-736-0304 Right to technical Changes reserved. Fax: 315-736-0874 Duplication requires special permission. E-Mail: info@fgri.com

Wiring Diagram 220: 2NO/2NC

FGR52FGR52 -- 024024 -- 220FS 220FS Relay Switching Data and Wiring Relay Switching Data and Wiring DiagramDiagram

General DataGeneral Data • DIN- Rail mount board with

two force guided relays • Screw mount terminals for

conductor cross section 0.08 to 2.5 mm2 (AWG 28 to 14)

• Board is provided with LED function indication and suppression Diode

Installation Installation RemarksRemarks • Turn off all power supplies

before any installation work • Be aware of all safety rules

and guidelines of OSHA and other associations as they apply.

• Installer and/or operator must

be a qualified professional. • Do not demount the unit or

remove any wires while relay operates.

• Conductor cross section

0.08 to 2.5 mm2 (AWG 28 to AWG 14)

Relay DataRelay Data Relay Version FGR35-024-220FN Contact Set Configuration 220 (2NO/2NC) Contact Material AgCdO10 / 0.2 µm Au Gold Flashed Contact Resistance (when new) < 50 mOhm Coil Resistance 480 Ohm ± 10 % Operating Voltage at 20 oC / (68 oF) 16.8 to 42.0 V DC Admissible Ambient temperature Range / oC (oF) -25 ... +80 oC (-13 … +176 oF) Max. Switched Voltage Rating 230/240 VAC / 300 VDC Max. Switched Current Rating (resistive) 8 A Max. Contact Load (resistive) 1,800 VA / 60 W Mechanical Service Life > 1 x 107 switching operations Electrical Service Life > 1 x 105 switching operations Contact gap in case of malfunction (110% Vnom.) > 0.5 mm Response times: Energized with Vnom. Pull – in 13 ms Drop – out 8 ms Insulation for reference voltage 250V Operational surge voltage 4 kV/3 and Pollution degree 2 Coil-Contact set Reinforced Insulation Contact set - Contact set Reinforced Insulation Vibration resistance 5 g (10 to 55 Hz) Shock resistance 10 g / 11 ms Weight 30 g Approvals UL, CUL, CSA, TÜV (in progress)

Dimensions Dimensions

Width: 64.40 mm (2.54 inch) Length: 92.50 mm (3.64 inch) Height: 61.50 mm (2.42 inch) For conversion: 1 mm = 0.03937 inch 1 inch = 25.40 mm

7 9 5 3 -1