SmartLineStartup
SmartLine
Initial wirings
Initial Wirings
SmartLine
Balance Zones with a 3.9kΩ resistance
Initial wirings
SmartLine
If Zones aren’t balanced panel displays “Zone open”
Fault 01/04Zone OpenZone 01<Zone 01>
Initial wirings
SmartLine
Balance Dialler with a 10 kΩ resistance(between terminals 19 and 23 )
Initial wirings
SmartLine
If Dialler isn’t balanced panel displays “Fault Dialler”
Fault 01/01FaultDialler
Initial wirings
SmartLine
Balance NAC with a 47kΩ resistance
Initial wirings
SmartLine
If NAC isn’t balanced panel displays “Open I/O Panel NAC”
Fault 01/01Open I/OPanel NAC
Initial wirings
SmartLine
Detectors wiring
3.9 kΩ End of Line resistance on the last detector
Balance other zones with a 3.9 kΩ resistance
Detectors Wiring
SmartLine
Callpoints wiring
3.9 kΩ End of Line resistance on the last callpoint
Balance other zones with a 3.9 kΩ resistance
Callpoints Wiring
SmartLine
NAC
47 kΩ End of Line resistance on the last device
NAC Wiring
NAC output activates on Alarm: it can activate alarm devices
SmartLine
NAC
47 kΩ End of Line resistance on the last device
If panel displays “Short I/O Panel NAC” it will need connect a diode in series (if devices haven’t it)
Fault 01/01Short I/OPanel NAC
SmartLine
Other wirings
17-18 FAULT Terminalsactivated on Fault.
Fault output can activate some devices
Other wirings
SmartLine
Dialer
19-20 DIALER Terminalsactivated on Alarm.
DIALER Output can activate an external dialler.
SmartLine
AUX R
25-26 AUX R Terminalsturn off 24V on Reset
They can reset latching linear beam smoke detector
SmartLine
Relay
27-28-29 RELAY Terminals activated on Alarm (at default)
They can activate some devices
SmartLine
Generic contact
Generic Contact Wiring
680Ω resistance
3.9kΩ resistance
NO Alarm Contact
Alarm contact only
SmartLine
Generic contact
680Ω resistance
NO Alarm Contact
NC Fault Contact
3.9kΩ resistance
Alarm Contact and
Fault Contact
SmartLine
Gas Detector Wiring
Gas Detector Wiring
3.9kΩ resistance
INE55/ING55 Detector
Detection-Line Zone Wiring
It have to program the Zone as “Gas (Relay Output)
SmartLine
Gas Detector Wiring
3.9kΩ zone balancing resistance
INE55/ING55Detector
I/O 4-20mA Input Wiring
150Ω resistance
INA55-101board
It have to program I/O Line as “Gas 4-20mA Input”
SmartLine
Gas Detector Wiring
Generic 4-20mA Gas Detector Wiring
4-20mAoutput
3.9kΩ zone balancing resistance
150Ω resistance
Generic4-20mA
gas detector
Detector have to supply current
It have to program I/O Line as “Gas 4-20mA Input”
SmartLine
To next expansion board
Expansion Boards Wiring
Expansion boards
SmartLine
Expansion boards
Expansion Zones are similar to panel ones
Balance Zones with a 3.9kΩ resistance
SmartLine
Espansions board
Expansion NAC output is programmable(at default output is activated on Alarm)
Balance NAC with a 47kΩ resistance
SmartLine
Expansion boards
It have to configure expansion boards
Enable panel programming phase
Control PanelIN PROGRAMMiING
Ver: 2.0301/01/12 17:45
SmartLine
Expansion boards
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
SettingsDisablementMaintenanceProgramming
ConfigurationProgr. ZoneProgr. OutputProgr. Timer
Acquire int.busAcquire ext.bus
Current DevicesExtin.module OExpansion OOk to execute
Current DevicesExtin.module OExpansion 1Ok to execute
SmartLine
RS485 Bus Wiring
RS485 Bus
Up to4 Repeater2 Power Station
SmartLetUSee/LCD-LiteRepeater
SmartLevelPower Station
SmartLine
RS485 Bus
It have to address RS485 Bus devices
SmartLetUSee/LCD-LiteRepeater
SmartLevelPower Station
Address
DIPSwitchPosition
SmartLine
RS485 Bus
It have to address RS485 Bus devices
SmartLetUSee/LCD-LiteRepeater
View logLED TestResetMaintenance
LED testResetMaintenanceProgramming
BoosterOptionsAddress RS485Default Data
SmartLevelPower Station
Address: 01
Address: 02
Prog
Enable SmartLevel programming phase
SmartLine
RS485 Bus
RipetitoreSmartLetUSee/LCD-Lite
SmartLevelPower Station
Set End of Line jumper in EOL position on the last device
SmartLevelRepeater
SmartLine
RS485 Bus
SmartLetUSee/LCD-LiteRepeater
SmartLevelPower Station
It have to address RS485 Bus devices
Enable panel programming phase
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
SmartLine
RS485 Bus
SmartLetUSee/LCD-LiteRepeater
SmartLevelPower Station
CentraleIN PROGRAMMAZ.!!
Ver: 2.0301/01/12 17:45
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
Control PanelIN PROGRAMMING
Ver: 2.0301/01/12 17:45
SettingsDisablementMaintenanceProgramming
ConfigurationProgr. ZoneProgr. OutputProgr. Timer
Acquire int.busAcquire ext.bus
Current DevicesRepeater OPower Station OOk to execute
Current DevicesRepeater 2Power Station 1Ok to execute