Safely Reducing Outside Air in Laboratories...ANSI Z9.5 – 2012 ACH / Dilution Rates “An air...

Post on 03-Mar-2021

3 views 0 download

Transcript of Safely Reducing Outside Air in Laboratories...ANSI Z9.5 – 2012 ACH / Dilution Rates “An air...

Safely Reducing Outside Air in LaboratoriesDavid Warner, PE, CEMHTS Chicago

What is a lab?

OSHA 29

“It is a workplace where relatively small quantities of hazardous chemicals are used on a non-production basis.”

- CFR 1910.1450, subpart 2, paragraph 191.1450) [4]

Primary Purpose

SAFETYComfort (Productivity)

Efficiency

Sustainability

Flexibility

other

Lab Safety

#1 Most Important Factor for Lab Safety

Primary Mechanism for Protection

• Ventilation Systems

• Typically 100% OA

• Continuous Operation

Impact of Continuous Ventilation

Lab Energy Usage ~ 3 to 8 times office

Campus Energy Usage< 20% sq. footage

> 40% energy usage

http://www1.eere.energy.gov/buildings/commercial/bba_laboratories_team.html

Why Focus on Ventilation?

Ventilation > 40% energy usage

HVAC> 65% energy usage

Drivers of Laboratory Ventilation

ThermalACH / DilutionHoods

Why Ventilation Drives Lab Energy Cost

Constant Volume Fume Hood

1000 cfm x $3/cfm/year = $3,000

Average US Home

10,000 kWh/year x $0.10 /kWh = $1,000

Why Ventilation Drives Lab Energy Cost

Constant Volume Fume Hood

One

Average US Home

Three>

Why Ventilation Drives Lab Energy Cost

Constant Volume

20 ACH3 cfm /sf

Primary Drivers of Laboratory Ventilation

Hoods Thermal Load

VAV ACH

VAV Hoods

ACH / Dilution Requirement

VAV Supply

2-4 ACH Min

To achieve goal all flow requirements need to be reduced

Min Flow

Min Load

Safely Reducing Outside Air in Laboratories

Agenda• Historical Background

• High Payoff Strategies

• Case Study

• Q & A

Oracle at Delphi

1876 - First R&D Lab in US

1899 – Classroom, Mechanical Ventilation

Lab - 1916

Lab - 1920’s

Lab - 1941

New Lab

“Typical” Lab?

The “Human Factor”

Lab Safety

Most Important Device for Lab Safety

Exposure Control Devices

Fume HoodBiological Safety Cabinet

Point Exhaust

Flammable Storage Cabinet

Expensive Storage

Step 1. Reduce Fume Hood Airflow

• Eliminate Unused Hoods

• Reduce Hood Size

Step 1. Reduce Fume Hood Airflow

Fundamental ApproachVAV Hoods (most labs)

Step 1. Reduce Fume Hood Airflow

Strategies• Reduce Design Opening

• Reduce FH Min. NEW ANSI Z9.5

• Reduce Face Velocity

• Close the Sash

• Use Diversity

Design Opening

Design Opening

e.g. 60” x 30” = 12.5 sf

12.5 sf x 100 fpm = 1250 cfm

Reduce Design Opening

e.g. 60” x 18” = 7.5 sf

7.5 sf x 100 fpm = 750 cfm

Vertical Sash Stop

Vertical Rising Sash

Reduce Design Opening

e.g. 30” x 30” = 6.25 sf

6.25 sf x 100 fpm = 625 cfm

Horizontal or Combination Sash

Left Side Open

Reduce Design Opening

Center Open

Horizontal or Combination Sash

Reduce Design OpeningHorizontal or Combination Sash

Right Side Open

Reduce Design Opening

Max Horizontal Opening

22” x 22”, 336 cfm

Low Flow Hood

Reduce FH Minimum Flow Rate

Fume Hood Min:• For VAV hoods

• Only affects hood flow for small or closed sash positions

• Independent of face velocity

• Changing min will not reduce face velocity

Old Min (250 CFM)

Reduce FH Minimum Flow Rate

Fume Hood Min:• For VAV hoods

• Only affects hood flow for small or closed sash positions

• Independent of face velocity

• Changing min will not reduce face velocity

Old Min (250 CFM)

New Min 150 ACH

Reduce FH Minimum Flow Rate

Fume Hood Min:• For VAV hoods

• Only affects hood flow for small or closed sash positions

• Independent of face velocity

• Changing min will not reduce face velocity

New Min (100 CFM)

Old Min (250 CFM)

Reduce Face Velocity

e.g. 60” x 18” = 7.5 sf

7.5 sf x 100 fpm = 750 cfm

Vertical Sash Stop

Vertical Rising Sash

Reduce Face Velocity – Design 80 fpm

e.g. 60” x 18” = 7.5 sf

7.5 sf x 80 fpm = 600 cfm

Vertical Sash Stop

Vertical Rising Sash

Reduce Face Velocity – Design 80 fpm

750 cfm

600 cfm

Savings150 cfm at Max

0 cfm at Min

Why not?

Reduce Face Velocity – Unocc . 60 fpm

Reduce Face Velocity – Unocc . 60 fpm

750 cfm

450 cfm

Savings300 cfm at Max

0 cfm at Min

Diversity Diversity Assured

Close the Sash – Automatic Closer

Close the Sash – Increase Awareness

Energy Usage “Dashboards”

Close the Sash – Increase Awareness

Close the Sash - Influence Behavior

Close the Sash – Results

Close the Sash – Does it Work?

$41,000 per year

Diversity

Given 10 Fume Hoods in 10 LabsHow many need Max Airflow at the same

time?

If “Events are independent and random,

• Calculate using Binomial Distribution

• “Hunter’s Curve” concept

Diversity Calculation

Total # of HoodsCertainty level:

10 20 40

% of Time # of FH @ Max

97% 2 4 6

99% 3 5 7

99.9% 4 6 9

99.99% 5 7 10

Hood Airflows Combining Various Strategies

Sash Position

100 fpm 80 fpm 2 hr. Occ.w/ Setback

10 FH@ Max

12,500 10,000 6,333

10 FH @ Stop

7,500 6,000 4,420

3 @ Stop7 @ 9”

4,875 3,900 3,010

3 @ Stop7 closed

4,000 2,640 2,230

e.g. 10 Fume Hoods in 10 Labs

Hood Airflows Combining Various Strategies

Sash Position

100 fpm 80 fpm 2 hr. Occ.w/ Setback

10 FH@ Max

12,500 10,000 6,333

10 FH @ Stop

7,500 6,000 4,420

3 @ Stop7 @ 9”

4,875 3,900 3,010

3 @ Stop7 closed

4,000 2,640 2,230

Combines all Five Strategies

Step 2: Reduce Thermal Load Flow Drivers

Strategies• Right Size the Load

• Use Diversity

• Decouple Thermal from Ventilation

Thermal Load

VAV Supply

Min Load

Right Size the Load

UC Davis – LBNL Study� HPAC Article (Sept & Oct, 2005)

Measured plug loads in labs

Lighting, people ~ 1 w/sf

Step 2: Reduce Thermal Load Flow Drivers

Thermal Load

VAV Supply

Min Load

Labs 21 & UC Davis study: • Avg plug & lighting: 2.5 to 3 W/ft 2

• < 20% of labs loads > 4 W/ft 2

Typical rooms:• Daytime: Loads < 4 ACH

• Nighttime: w/ Temp Setback

can achieve 2 ACH

Diversity for HVAC Capacity

Given 40 Lab Zones,

How many need Max Cooling at the same time?

Life Sciences Lab

Low Load (blue)

Medium Load (yellow)

High Load (red)

Decouple Thermal from Ventilation

For high load labs & more efficiency: Use Hydronic Cooling

(Chilled Beam, Fan Coil Units)

Thermal Load

VAV Supply

Min Load

Step 3: Reduce ACH / Dilution Rate

How?• Occ/Unocc Control

• Active/Demand Based Control

What Rates?

Demand Based Control

ACH Requirement

2 ACH Min

ACH / Dilution Rates

ASHRAE 62.1�Labs: 0.18 cfm /sf (1.2 ACH) of fresh air

City of Chicago Code�Labs: 1.2 cfm /sf (8 ACH with 9 ft. ceiling)

�1/3 of max permissible with VAV (2.67 ACH)

Most fixed ACH values are being reduced:�NFPA 45 – 2011: Rates removed, Refers to ANSI

�ANSI Z9.5 -

ANSI Z9.5 – 2012 ACH / Dilution Rates

“An air exchange rate (air changes per hour) cannot be specified that will meet all conditions.”

“Furthermore, air changes per hour is not the appropriate concept for designing contaminant control systems.

2011 ASHRAE Handbook, Lab Chapter 16

Occ/Unocc Control

� “There should be no entry into the laboratory during unoccupied setback times”

� “…Occupied ventilation rates should be engaged possibly one hour or more in advance of occupancy to properly dilute any contaminants.”

2011 ASHRAE Handbook, Lab Chapter 16

Active/Demand Based Control

“Reducing ventilation requirements in laboratories and vivariumsbased on real time sensing of contaminants in the room environment offers opportunities for energy conservation.”

“This approach can potentially reduce lab air change rates down safely to as low as 2 air changes per hour when the lab air is ‘clean’...”

Demand Based Control

Lab air is “clean” > 98% of the time

Vary based on real time sensing

Safety?• Fixed ACH is either too high or low

• Dilution up to Max

• “Clean” set to 2 ACH at night

Daytime Airflow, 4 ACH� Rates < 4 ACH also used

� Couple with other strategies

DBC provides a safe means to achieve 2 ACH when lab air is clean

Demand Based Control

ACH Requirement

2 ACH Min

The “Human Factor”

“Our goal is to find the sweet spot where we maximize energy savings without compromising safety.”

Marc GomezAssistant Vice Chancellor

Facilities Management/Environmental Health & Safety

University of California, Irvine

Case Study – UC Irvine

Case Study – UC Irvine

Hewitt Hall: Designed in 2001

Exceeded Title 24 by 23.7%

Biomedical Research

Re-Commissioned in 2010

6 ACH fixed minimum76,905 Square Feet

Gross Hall: Designed in 2009

Exceeded Title 24 by 50.3%

Biomedical Research

Submitted: LEED Platinum

DBC: 4/2 ACH Occ/Unocc94,705 Square Feet

Both buildings similar in layout, function, & use

Airflow Savings ~ 1 cfm/sf

Lab Air Flow vs. Time For Both Bldgs

Wendell C. BraseVice Chancellor, Administrative & Business Services, UC Irvine

Chair, University of California

Climate Solutions Steering Group

“Smart Labs”

4/2 ACH

What is Possible?

Design and Benchmarking Resources

Safely Reducing Outside Air in Labs

Questions?

Safely Reducing Outside Air in Labs

Thank you!

Contact me at:

David Warner

david.warner@hts.com