Post on 14-Jun-2020
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S. 311 - BRONX, 1684 WHITE PLAINS ROAD, BRONX, NY, 10462School:
1419 2019-01-14 07:28AM 2019-02-20 12:26PMARCHITECTURAL - ASSOCIATE
1496 2019-01-12 08:33PM 2019-06-17 01:10PMARCHITECTURAL - SENIOR
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? No
Areaway 5,6,7 and 8 along Front FacadeComments on Inaccessible Inspection
Principal(s) Information
Principal Name Katiria Rojas
Principal Organization The Stream Bridge School - Bronx
Meeting with Principal? No
Principal Feedback The Principal’s Information form was returned with following
comments.
1- There is Inadequate ventilations in School Gymnasium that
needs to be addressed.
2- Extreme heat and Cold temperature needs to be balanced
throughout the building.
Principal Name Deborah Alford
Principal Organization District 11 Pre- K Center
Meeting with Principal? No
Principal Feedback This Principals Questionnaire was returned with no comment on
the physical building condition.
Custodian Was not present
Fireman Angel Garcia
Building Square Footage 43,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 2+B
Comments on the Year Built 1952
Comments on the Student Population 270
Comments on the Staff Population 52
Comments on the Number of Classrooms 16
Weather Fair
Facade Photo
Corner of White plains Road and Van Nest Avenue - North view
Page 1 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural InspectionMain Entrance Photo
Facade A - White Plains Road
Roof Photo
Roof 1 - West view
Have any Systems/Major Building Components been upgraded? Systems: Roofing and Flashing replacement on roofs 2, 3 and 4;
Basement Vinyl Flooring replacement; Toilet Room
upgraded to HC Compliant; Windows and Window
Guards replacement; Interior Wall renovation; New
Basement Kitchen.
Years: 2015
1958 + 12600 S.FHave there been any New Building Additions?
Tandem No Tandem
Leased Space? Yes
Year Leased 2015
Inspection Type Full Inspection
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Page 2 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
Exterior Routes
NoExterior Entrances & Exits
SADDLE HEIGHT > 1/2"
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
NoInterior Corridors & Lobbies
CHANGE IN ELEVATION
NoInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
NoArt Rooms
NoAuditorium
Cafeteria
Yes NoBasement
NOT ON ACCESSIBLE ROUTE
Classrooms
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
NoComputer Rooms
Gymnasium
Yes No1st floor
NOT ON ACCESSIBLE ROUTE
Library
Yes NoBasement Room 004
NOT ON ACCESSIBLE ROUTE
Main Office
Yes NoRooms 101 and 200
NOT ON ACCESSIBLE ROUTE
NoMulti-purpose Room
Nurse's Office
Yes NoBasement room 013
NOT ON ACCESSIBLE ROUTE
NoPool
Science Lab
Yes NoBasement room 002
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (boys)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (girls)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Toilet Rooms (staff)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Page 3 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on AW1 - AW4 Inspected
4- Between Fair and PoorInstance Condition
Instance Quantity 9
Instance Quantity Uom EACH
AREAWAY GRATINGS:MAJOR RUSTING AND / OR
BROKEN SUPPORTS
Deficiency
Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Page 4 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
EXTERIOR
AREAWAY
Deficiency Photo 2
Aw2
Violations No violations recorded
InspectedAWNINGS AND CANOPIES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCOPING
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedCORNICE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS
InspectedDOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 5- Poor
WOOD:DETERIORATED DOOR AND FRAME - MINOR
DETERIORATION
Deficiency
Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main entrance
Violations No violations recorded
Page 5 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
EXTERIOR
DOORS
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 3- Fair
WOOD:EXCESSIVELY WEATHEREDDeficiency
Deficiency Location/Instance
16Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main entrance
Violations No violations recorded
Does not existEXTERIOR SOFFITS
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
18,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 18,000
Instance Quantity Uom S.F.
BRICK:DETERIORATED CONTROL/EXPANSION JOINTS
WITH DAMAGED CAULKING
Deficiency
Roof Plan Reference
Elevation
Elevation Reference North side
40Deficiency Quantity
Page 6 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade F and G
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
MetalMaterial Type(s)
3,000Replacement Quantity
Replacement Uom C.F.
Instance on All Facades Inspected
3- FairInstance Condition
Instance Quantity 3,000
Instance Quantity Uom CF
BRICK:MAJOR DETERIORATION/CRACKSDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
A
Violations No violations recorded
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 18,300
Page 7 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existROOF BARRIER
Does not existROOF CAGE
Does not existROOF FENCE
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on Modified Bitumen:Roof 1 Inspected
3- FairInstance Condition
Instance Quantity 9,600
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 1987
Source of Installation Year Documented
MODIFIED BITUMEN:ROOFING:DELAMINATIONDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT
REMOVAL
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Violations No violations recorded
MODIFIED BITUMEN:ROOFING:BEYOND USEFUL LIFEDeficiency
Modified Bitumen:Roof 1Deficiency Location/Instance
9,600Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 1Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
Instance on Modified Bitumen:Roofs 2, 3, 4 and 5 Inspected
3- FairInstance Condition
Page 8 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Instance Quantity 8,700
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2015
Source of Installation Year Documented
MODIFIED BITUMEN:ROOFING:MINOR LEAKAGEDeficiency
Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Gymnasium shown also at Stair A/2
Violations 35287089Y
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedRAILINGS
Condition 3- Fair
RUST - MINORDeficiency
Page 9 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Location/Instance
20Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit - 4
Violations No violations recorded
InspectedSTAIRS/RAMPS
Condition 3- Fair
METAL:RUST - MINORDeficiency
Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade H
Violations No violations recorded
InspectedWINDOWS
3,500Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 1- Good
No deficiencies recordedDeficiency
Page 10 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
EXTERIOR
WINDOWS
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Other:All Facades Inspected
1- GoodInstance Condition
Instance Quantity 3,500
Instance Quantity Uom S.F.
Installation Year 2015
Source of Installation Year Custodial Staff
No deficiencies recordedDeficiency
INTERIOR Inspected
Does not existAUDITORIUM
CAFETERIA
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Room 022Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 11 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo 1
Northeast of Room 022
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Rooms 110, 200Deficiency Location/Instance
45Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 200
Deficiency Photo 2
Room 110
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
GYMNASIUM
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Page 12 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Seating
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor Does not exist
Stage
Instance on 1st Floor Does not exist
Walls
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Page 13 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
INTERIOR
LIBRARY
Instance on Room 004 Inspected
Built-in Furnishing
Instance on Room 004 Does not exist
Ceiling
Instance on Room 004 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 004 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 004 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 004 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existLOCKER ROOM
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
SCIENCE LAB
Instance on Room 022 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 022 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSCIENCE PREP ROOM
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
VINYL TILES:WORN-OUT TREAD/NOSINGSDeficiency
Near Entrance to Room 200Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
Page 14 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Entrance to Room 200
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFLOOR STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Page 15 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
InspectedSTEEL STAIRS
Condition 3- Fair
MINOR RUSTINGDeficiency
Exit 4Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 1Purpose of Action
Violations No violations recorded
SITE Inspected
Does not existCONTAINERIZATION
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 3- Fair
DAMAGED COVERDeficiency
Parking AreaDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Parking Area
Violations No violations recorded
Does not existCulverts - Concrete Covering
Page 16 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
SITE
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Van Nest AvenueDeficiency Location/Instance
75Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Van Nest Avenue
Violations No violations recorded
Does not existPavers
Does not existSite Sidewalks & Walkways
InspectedStudent Non-Use
Gravel Exists? No
InspectedAsphalt
3- FairCondition
CRACKS - MINORDeficiency
Parking AreaDeficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West of Parking Area
Violations No violations recorded
Does not existConcrete
Does not existPavers
InspectedStudent Use
Page 17 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X311Architectural Inspection
Question Response
SITE
PAVING
Student Use
Gravel Exists? No
InspectedAsphalt
3- FairCondition
CRACKS - MINORDeficiency
SchoolyardDeficiency Location/Instance
150Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West of Schoolyard
Violations No violations recorded
Does not existConcrete
Does not existPavers
InspectedPLAYGROUNDS
SchoolyardInstance
Benches
Instance on Schoolyard Does not exist
Fence
Instance on Schoolyard Does not exist
Pavement
Instance on Schoolyard Does not exist
Play Equipment
Instance on Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Safety Surfacing
Instance on Schoolyard Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Unpaved Area
Instance on Schoolyard Does not exist
Does not existPLAYING SURFACE
Does not existRETAINING WALLS
Does not existSEATING
Does not existSITE WALLS (NOT RETAINING WALLS)
Does not existSTAIRS/RAMPS: EXTERIOR
Page 18 of 18 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)