Post on 01-Feb-2021
t\jUPSaE!~!o9.!!!AL'vVAYSFULL OF ENEHGY
The UPS Factory bvAston Martiniaan 963261 NB Oud-Beijerland
Tel: +31 (0) 186 684 088E-mail: info@TheUPSFactory.com
www.TheUPSFactory.com
mailto:info@TheUPSFactory.comhttp://www.TheUPSFactory.com
CERTA Enkel fase UPS p 4 - 17BORRI 3 fase UPS p 18 - 33G TEC Modulaire UPS p 34 - 40G TEC Modulair UPS 19” rack p 41 - 44ELTEK 48Vdc hybride UPS p 45 - 48ADEL 24Vdc DIN-Rail UPS p 49 - 50
Certa
in
fo@
cert
aups
.com
ww
w.
.com
CertaC60800VA - 2000VA
The C60 range is one of the most practical and compact UPS solutions available. Compatible with most operating systems, the intuitive monitoring software provides safe shutdown in the event of an extended power failure with the UPS automatically restarting when power is restored.
Line interactive Compact and ideal for smaller backup power requirements – CCTV, EPOS, small office hardware, security systems and PC workstations.
Line interactive (VI) technology
USB connectivity
MODELS C60-800 C60-1000 C60-1500 C60-2000
Power (VA) max 800 1000 1500 2000
Power (W) max 480 600 900 1200
INPUT
Input Voltage 220/230/240VAC
Acceptable Input Voltage 162-290VAC
Input Frequency 50/60Hz (Auto Sensing)
OUTPUT
Voltage Regulation +/-10% (Battery Mode)
Frequency Regulation +/-1Hz (Battery Mode)
Transfer Time Typical 2-6ms; 10ms max
Waveform Simulated Sinewave (Battery Mode)
PROTECTION
Full Protection Overload, Battery Discharge and Overcharge Protection
DISPLAY
LCD Display AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault & Battery Low
FEATURES
Usable Features Off-Mode Charging, AVR, Auto-Restart, Cold Start, USB, RJ11 & 45 Filters, LCD Display
BATTERY
Runtime 3 minutes 4 minutes 3 minutes 2 minutes
Charging Time 4-6 hours recovery to 90%
MECHANICAL
Dimensions W x D x H (mm) 100 x 285 x 142 146 x 350 x 160 146 x 397 x 205
Net Weight (Kg) 4.9 8 11.1 11.5
Battery Protected Outputs 3 3 5 5
Surge Protected Outputs 1 1 1 1
AC Outlets 3 x IEC C13, 1 x Surge Protected IEC C13 5 x IEC C13, 1 x Surge Protected IEC C13
ENVIRONMENT
Operating Temperature Range UPS: 0°C - 40°C, Batteries: 20 - 25°C
Humidity 0-90% Relative Humidity (Non Condensing)
SOFTWARE
Connection USB Connectivity
Operating System Supports Windows 2008/7/8/10Linux/Unix and MAC
C60
800V
A - 2
000V
A
Full technical specification and product information can be found at www.certaups.com
Prod
uct S
peci
ficat
ion
Certa
info
@ce
rtau
ps.c
om
ww
w.
.com
CertaC2001000VA - 2000VA
The C200 UPS includes an AVR (Automatic Voltage Regulator) as standard, making the UPS enormously effective even in poor mains supply conditions. With its wide input voltage window the UPS regulates a precise output voltage without switching to battery power, even if the input voltage fluctuates by as much as 30% from normal.
Line interactive Ideal for supporting critical equipment. An advanced UPS with a pure sinewave output.
Line interactive (VI) technology
USB connectivity
Pure sinewave output
Developed as a compromise between offline (VFD) and online double conversion (VFI) technology, the C200 utilises digital line interactive technology with a digitised PWM-based controller. This produces a pure sinewave output, which makes it perfect for supporting critical equipment.
MODELS C200-1000 C200-1500 C200-2000
Power (VA) max 1000 1500 2000
Power (W) max 700 1050 1400
INPUT
Input Voltage 220/230/240VAC
Input Voltage Window 162-290VAC
Input Frequency 50/60Hz (Auto Sensing)
OUTPUT
Voltage Regulation +/-10% (Battery Mode)
Frequency Regulation +/-1Hz (Battery Mode)
Transfer Time Typical 2-6ms; 10ms Max
Waveform Pure Sinewave (Battery Mode)
PROTECTION
Full Protection Overload, Battery Discharge and Overcharge Protection
DISPLAY
LCD Display AC Mode, Battery Mode, Load Level, Battery Level, InputVoltage, Output Voltage, Overload, Fault & Battery Low
FEATURES
Usable Features Off-Mode Charging, AVR, Auto-restart, Cold Start, USB, RJ11 & 45 Filters, LCD Display
BATTERY
Runtime 4 minutes 3 minutes 2 minutes
Charging Time 4-6 hours recovery to 90%
MECHANICAL
Dimensions W x D x H (mm) 146 x 350 x 160 146 x 397 x 205
Net Weight (Kg) 9 12.2 13.7
Battery Protected Outputs 3 5
Surge Protected Outputs 1 1
AC Outlets 3 x IEC C13, 1 x Surge Protected IEC C13 5 x IEC C13, 1 x Surge Protected IEC C13
ENVIRONMENT
Operating Temperature Range 0°C - 40°C, Batteries 20°C - 25°C
Humidity 0-90% Relative Humidity (Non Condensing)
SOFTWARE
Connection USB Connectivity
Operating System Supports Windows 2008/7/8/10Linux/Unix and MAC
C20
010
00VA
- 200
0VA
Full technical specification and product information can be found at www.certaups.com
Prod
uct S
peci
ficat
ion
Certa
info
@ce
rtau
ps.c
om
ww
w.
.com
CertaC4001000VA - 3000VA
The C400 series presents the next generation of true online double conversion UPS solutions. Featuring enhanced DSP design for improved precision and reliable control, the C400 range is the most reliable of its kind.
Online double conversion Perfect for small to medium sized offices, telecoms centres and security facilities.
ECO mode function
USB connectivity & HID support
Pure sinewave output
Intelligent communication slot
High efficiency
Additional battery connection
Online double conversion
Virtualisation compatible
Smartphone app monitoring
97%
vfi
vfi
97%
Manufactured using superior quality materials, including high quality solder paste for double layered PCB’s. The C400 units, though sophisticated in their design, are delivered ready for immediate use and are suitable for all loads requiring true uninterrupted power.
Additional battery power options are only available with charger UPS
C40
0100
0VA
- 300
0VA MODELS C400-010-B C400-010-C C400-020-B C400-020-C C400-030-B C400-030-C
Power (VA) max 1000 2000 3000
Power (W) max 900 1800 2700
INPUT
Input Voltage Window 100-300VAC
THDi 0.99
Input Frequency Range 50-60Hz (+/- 10%)
OUTPUT
Output Voltage 220/230/240VAC
Waveform Pure Sinewave
Voltage regulation ±1%
Output Frequency 50-60Hz (+/- 10%)
Battery mode (50/60±0.05)Hz
Voltage Distortion (THDv) 3.5 minutes N/A >3.5 minutes N/A
MECHANICAL
Dimensions W x D x H (mm) 144 x 229 x 345 102 x 228 x 352 190 x 330 x 393 102 x 327 x 396 190 x 330 x 393 102 x 327 x 396
Weight (Kg) 10 4 17 6 23 6
AC Outlets4 x IEC C13 3 x IEC C13 4 x IEC C13 6 x IEC C13
4 x IEC C13,1 x IEC C19
3 x IEC C13+ Terminal
Full technical specification and product information can be found at www.certaups.com
Prod
uct S
peci
ficat
ion
Certa
info
@ce
rtau
ps.c
om
ww
w.
.com
CertaC400R1000VA - 3000VA
The C400R series has been designed to deliver maximum user flexibility. Its compact and ergonomic rack mountable and floor standing design makes it an ideal fit for many server cabinets, particularly in 2000VA and 3000VA configurations.
The advanced technology of the rectifier and inverter utilising online double conversion topology provides a pure sinewave output completely isolated from the input mains power.
Further functionality is achieved through hot swappable internal batteries, which are located in a separate enclosure to allow the user to safely change batteries without the need for a power down.
Affordable, functional and reliable, the C400R also features interactive software, which is compatible with a wide range of operating systems.
Online double conversion A versatile, high power density UPS solution ideal for IT facilities and the telecoms market.
ECO mode function
USB connectivity & HID support
Pure sinewave output
Intelligent communication slot
High efficiency
Additional battery connection
Online double conversion
Virtualisation compatible
Smartphone app monitoring
97%
vfi vfi
97%
MODELS C400R-010-B C400R-010-C C400R-020-B C400R-020-C C400R-030-B C400R-030-C
Power (VA) max 1000 2000 3000
Power (W) max 900 1800 2700
INPUT
Cold Start Yes, Default Frequency=50Hz
Input Voltage Window 120VAC-276VAC
THDi 5 minutes 0 minutes >5 minutes 0 minutes
Max External Battery Modules 6
Charging current max 1.5A for “B” models 6A for “C” models
MECHANICAL
Dimensions W x D x H (mm) 438 x 436 x 86.5 (2U) 438 x 604 x 86.5 (2U)
Weight (Kg) 15 12 20 15 29 20
AC Outlets 8 x IEC C13 8 x IEC C13, 1 x IEC C19
*Derate to 90% with 208V voltage. **Derate to 70% during Frequency Converter Mode.
C40
0R10
00VA
- 300
0VA
Full technical specification and product information can be found at www.certaups.com
Prod
uct S
peci
ficat
ion
Certa
info
@ce
rtau
ps.c
om
ww
w.
.com
CertaC5006kVA - 10kVAOnline double conversionSuitable for industry applications where space is limited, in particular within medical and IT environments.
Designed using the highest level of protection (Online Double Conversion), the CertaUPS C500 tower series delivers up to 25% more usable power than other manufacturers thanks to a 0.9 output power factor. The C500 comes complete with internal batteries as standard, eliminating the need for external batterycabinets on standard run times, minimising the footprintand therefore maximising floor space for other equipment. This range is extremely low maintenance and has beendesigned as a genuine ‘easy parallel’ UPS solution, whereup to four C500 units can be connected in parallel as andwhen required. This added flexibility to enable furthercapacity or redundancy, makes the new C500 range a truefuture proof investment.
ECO mode function
USB connectivity & HID support
Pure sinewave output
Intelligent communication slot
High efficiency
Additional battery connection
Parallel connection
Online double conversion
Virtualisation compatible
Smartphone app monitoring
Maintenance bypass switch 97%
vfivfi
97%
MODELS C500-060-B C500-060-C C500-100-B C500-100-C
Power (kVA) max 6 10
Power (kW) max 5.4 9
INPUT
Input Voltage Window 110-276VAC
THDi 96%
Overload Capability (Normal operation) 125% for 10 minutes; 150% for 1 minute; >150% for 10 seconds
Parallel Up to 4 units for capacity or redundancy
BATTERY
DC Voltage 240VDC
Back-up time (full load) >7 minutes Charger only >5 minutes Charger only
Charging current (max) 1.2A 4.0A 1.2A 4.0A
Charging time 5h charge to 90% depending on the capacity of external batteries
MECHANICAL
Dimensions W x D x H (mm) 260 x 550 x 708
Weight (Kg) 80 26 84 30
AC Outlets Hardwired
*Derate to 90% with 208V voltage. **Derate to 60% during Frequency Converter Mode.
C50
06k
VA - 1
0kVA
Full technical specification and product information can be found at www.certaups.com
Prod
uct S
peci
ficat
ion
Certa
info
@ce
rtau
ps.c
om
ww
w.
.com
CertaC500E10kVA - 20kVAOnline double conversionSuitable for industry applications where space is limited, in particular within medical and IT environments.
Designed using the highest level of protection (OnlineDouble Conversion), the CertaUPS C500E tower series delivers up to 25% more usable power than other manufacturers thanks to a 0.9 output power factor. This range is extremely low maintenance and has beendesigned as a genuine ‘easy parallel’ UPS solution, whereup to four C500E units can be connected in parallel as andwhen required. This added flexibility to enable furthercapacity or redundancy, makes the new C500E range a truefuture proof investment. The CertaUPS C500E series can have either a three phase or single phase input applied to the UPS. The decision doesn’t have to be made until the point of installation and can then be changed should an electrical supply need to be upgraded or electrical loads have to be balanced.
ECO mode function
USB connectivity & HID support
Pure sinewave output
Intelligent communication slot
High efficiency
Additional battery connection
Parallel connection
Dual input
Online double conversion
Virtualisation compatible
Smartphone app monitoring
Maintenance bypass switch
97%
vfi
vfi
97%
MODELS C500E-100 C500E-200
Power (kVA) max 10 20
Power (kW) max 9 18
INPUT
Input Voltage Window 110-276/190-478VAC
THDi 96%
Overload Capability (Normal operation) 110% for 5 minutes; 130% for 1 minute; 150% for 10 seconds
Parallel Up to 4 units for capacity or redundancy
BATTERY
DC Voltage 288VDC
Back-up time (full load) 7 minutes
Charging current (max) 4.0A / 8.0A optional
Charging time Internal battery 3h charge to 90% Internal battery 5h charge to 90%
MECHANICAL
Dimensions W x D x H (mm) 350 x 650 x 890
Weight (Kg) 127 188
AC Outlets Hardwired
*Derate to 90% with 208V voltage. **Derate to 60% during Frequency Converter Mode.
C50
0E10
kVA
- 20k
VA
Full technical specification and product information can be found at www.certaups.com
Prod
uct S
peci
ficat
ion
Certa
info
@ce
rtau
ps.c
om
ww
w.
.com
CertaC500R6kVA - 10kVA
When positioned in rackmount form, the C500R has a capacity of 6kVA/5.4kW contained within 3U and 10kVA/9kW contained within 5U, which includes internal batteries to provide standard runtime.
Its online double conversion topology completely isolates the output voltage and frequency supplied to the users valuable load from incoming mains power anomalies. In addition, sophisticated ECO functions enable the C500R to achieve an industry leading 97% efficiency.
For a more resilient solution, an additional UPS unit can also be connected in parallel to share the critical load and provide N+1 redundancy.
Online double conversion Main applications include small data centres, server rooms, IT facilities, telecoms and networking.
ECO mode function
USB connectivity & HID support
Pure sinewave output
Intelligent communication slot
High efficiency
Additional battery connection
Parallel connection
Online double conversion
Virtualisation compatible
Smartphone app monitoring
Maintenance bypass switch 97%
vfi
vfi
97%
MODELS C500R-060-B C500R-060-C C500R-100-B C500R-100-C
Power (kVA) max 6 10
Power (kW) max 5.4 9
INPUT
Input Voltage Window 120VAC-276VAC
THDi 150% for 100 milliseconds
Overload Capability (battery mode) 130% for 10 seconds; >130% for 1 second
Crest Ratio 3:1
Parallel N + 1 for capacity or redundancy
BATTERY
DC Voltage 180VDC 240VDC
Back-up time (full load) >2.5 minutes Depends on the capacity of external batteries
>3.5 minutes Depends on the capacity of external batteries
Charging current (max) 1.0A 8.0A 1.7A 8.0A
MECHANICAL
Dimensions W x D x H (mm) 438 x 698 x 129 (3U) 438 x 704 x 215 (5U)
Weight (Kg) 48 19 83 26
AC Outlets 2 x IEC C13, 1 x IEC C19 + Terminal
2 x IEC C13, 2 x IEC C19 + Terminal
4 x IEC C19+ Terminal
4 x IEC C13,2 x IEC C19 + Terminal
*Derate to 90% with 208VAC output voltage. **Derate to 80% during Frequency Converter Mode.
C50
0R6k
VA - 1
0kVA
Full technical specification and product information can be found at www.certaups.com
Prod
uct S
peci
ficat
ion
FleXible and SmartPerformance, compactness and reliability for critical applications
10 to 40 kVAB8031FXS 10-20kVA 3-ph input / 1-ph output UPSB8033FXS 10-40kVA 3-ph input / 3-ph output UPS
B8000FXSIndustrial Power Solutions
LOW THDi and POWER FACTOR PERFORMANCE ENHANCE COMPATIBILITY with INPUT MAINS and GENERATORS
The BORRI B8000FXS UPS uses a modern input IGBT rec-tifier and Power Factor Control (PFC) technology ca-
pable of keeping the input current Total Harmonic Distortion (THDi) at a very low level (
PARALLEL SYSTEMS for REDUNDANCY or CAPACITY INCREASING with “HOT SWAP” MODULARITY
The B8000FXS UPS solution offers parallel options in both redundancy and capacity modes, providing the possibility for both extra system resilience and increased capacity.The parallel control circuitry associated with these units is fully digi-tal and acts on both active and reactive power on each of the three output phases. This allows accurate load current sharing among the UPS units even during transient conditions.Parallel control is distributed between all units and communication is achieved through the use of a CAN BUS connection loop. This has the effect of producing a highly reliable system with “no single points of failure”.Intelligent design of the system connections allow for easy instal-lation and easy future upgrades, this allows for upgrading the field without difficulty.In the modular arrangement, units can be added or removed “hot” without load disturbances or the need to switch to bypass. Smart Parallel functions facilitate the automatic switching off of units where the total power requirements of the load is provided by fewer than the total number of UPS units attached. . This is com-monly known as ‘load based shutdown’ and maximises the efficiency of the complete system by keeping the load on each module at an optimum level.Two independent paralleled systems can be synchronized (Sync Con-trol) in order to feed downstream STS’ for seamless transfers.
EASY INSTALLATION, OPERATION and MAINTENANCE
The B8000FXS has a high power to space ratio, this results in a very small footprint allowing the client to achieve maximum power in a relatively small space. The unit is fitted with wheels making it easy to move in and out of position.The B8000FXS series is based on light power modules which can be with-drawn from the front of the machine. This feature makes for incredibly easy servicing and dramatically reduces any potential down time.
USER INTERFACE and ACCESSORIES
B8000FXS
Removable power modules
Removable internal batteries (10-20kVA)
10 to 40 kVAB8031FXS 10-20kVA 3-ph input / 1-ph output UPSB8033FXS 10-40kVA 3-ph input / 3-ph output UPS
Performance, compactness and reliability for critical applications
Mains
Load
User-friendly Interface
OPZIONI• Parallel capacity/redundancy • Isolation transformer• Sync control for dual feed systems• External bypass• External battery cabinets• Battery switch box• Battery thermal probe• Transformers/ autotransformers for voltage adaption
COMUNICAZIONE• RS232 serial port• USB port• Remote EPO• External Manual Bypass status• Battery Switch status• Diesel Mode
OPZIONALI• Web/SNMP • ModBus• Relays• Modem• Remote panel
Monitoring, managing and shutdown software
Positioning via wheels
Small footprint
MODEL B8031FXS B8033FXS
Rating 10 kVA 15 kVA 20 kVA 10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Capacity (kVA) 10 15 20 10 15 20 30 40
Dimensions WxHxD (mm) 450x1200x640
Weight (kg) w/o battery Weight (kg) with battery
100 110 110 100 110 110 140 140
250 260 260 250 260 260
Input/output connection Hardwired (dual input) Hardwired (optional dual input)
Battery Internal or external, 360-372 cells External, 360-372 cells
INPUT
Nominal voltage 220/380, 230/400, 240/415 Vac three phase
Voltage range -20%, +15% from nominal
Frequency 50/60 Hz (45–65 Hz)
Power factor 0,99
Current distortion (THDi)
INGENIO 30 to 50 kVA Three phase
On-line double conversion
Transformer free Full IGBT technology
Paralleling up to 300 kVA
INGENIO 30-50 kVA
For server rooms TLC equipment
Emergency and safety systems
Industrial automation
Main options● Isolation transformer.
● Transformers/autotransformers for voltage adjustment.
● Battery voltage temperature compensation.
● External maintenance bypass wall-mounted box.
● Battery fuse switch wall-mounted box.
● Associated battery cabinets for long autonomy times.
● Parallel kit.
● Load-sync for single UPS units.
● Input terminals for remote EPO, external manual bypass auxiliary contact, diesel mode.
● Separate bypass input.
● Backfeed protection bypass contactor.
Features and benefits● High double conversion efficiency and ECO mode for low running costs and environmental impact.
● Transformer free design for light small size layout.
● Removable power modules architecture and built-in diagnostics for easy maintenance and very low MTTR.
● Hot connection/disconnection of parallel units for easy system resizing.
● Full IGBT technology and electronic PFC, ensuring 0.99 input PF and THDi
*according to IEC/EN 62040-3
INGENIO technical data Rating (kVA) 30 40 50
Nominal power (kW) 27 36 45
UPS dimensions WxDxH (mm) 500x940x1500
UPS weight (kg) 140 150 190
UPS weight 500 510 550
with int. battery (kg)
Battery configuration Internal or external, 360÷372 cells, VRLA (other options)
Max autonomy with int. battery 24 16 12 70% load (min)
Input
Connection type Hardwired 4w (separate bypass input available on request)
Nominal voltage 400 Vac 3-phase with neutral (rectifier)
380/400/415 Vac 3-phase with neutral (bypass)
Voltage tolerance -20%, +15% (rectifier) ±10% (bypass)
Frequency and range 50/60 Hz, 45÷65 Hz
Power factor 0.99
Current distortion (THDi) 150% for 100 ms, bypass: 150% continuous, 1000% for 1 cycle
Efficiency (AC/AC)* up to 98%
Classification as per VFI-SS-111
IEC/EN 62040-3
Connectivity and function extensions
Front panel Graphic display, mimic LED panel and keyboard, local EPO
Remote communication Included: RS232 card, USB; terminal block for battery breaker auxiliary contact Optional: input terminal block (remote emergency power off, external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software
Optional function extension Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse switch box; battery thermal probe; parallel kit and load-sync for single UPS
System
Protection degree IP 20
Colour RAL 9005
Installation layout Wall and side by side installation allowed; 50 cm clearance on one side with internal battery
Environmental
Operating temperature range 0°C ÷ +40°C
Storage temperature range -10°C ÷ +70°C
Altitude (AMSL) < 1000 m without power reduction, > 1000 with reduction of 0.5% per 100 m
Audible noise at 1 m (dBA)
INGENIO 30-40-50 kVA series options
Parallel kit When the unit is to be paralleled for load sharing
Description When do I use it
LOAD
Internal battery temperature probe When the unit has internal batteries, for charging voltage compensation with temperature
External battery temperature probe
Internal battery + UPS temperature probe
When the unit has external batteries, for charging voltage compensation with temperature (10 m cable length)
When the unit has internal batteries, for charging voltage compensation with temperature and
UPS temperature monitoring
Battery fused switch box
Input isolation transformer To galvanically isolate UPS from load or to change system’s earth arrangement
To disconnect and protect an external battery pack (wall mounted box)
Backfeed protection bypass contactor To be fully protected against backfeed energy upon static bypass failure
Input terminal block for remote EPO When the Emergency Power Off (EPO) has to be commanded by a remote control button
When the Emergency Power Off (EPO) has to be commanded by a remote control button
Input terminal block for diesel mode contact
Input terminal block for external battery switch auxiliary contact
When there is an external maintenance bypass switch, for state monitoring
When battery recharge has to be inhibited over genset operation
When there is an external battery switch, for state monitoring
Dry contact relay card
Remote monitoring panel
RS485 ModBus-RTU port
Web/SNMP Adapter
To send UPS status to PLC’s, SCADA’s or AS400’s by voltage free SPDT contacts
To monitor UPS status by a LED panel from a remote control room
To send UPS status to BMS’s by RS485 connection and ModBus-RTU protocol.
For telemonitoring and teleservice
To send UPS status to BMS’s by Ethernet connection and SNMP or ModBus over IP protocol. To monitor UPS status by any
internet browser from workstations. To receive SMS or e-mail alerts from the UPS on any portable device
Load-sync for single units To synchronize single units’ output for no-break load transfers by downstream static transfer switches
LOAD A LOAD B
INCLUDED
OM
G60
125r
evA
-- 07-20
15 -
Due
to o
ur p
olic
y of
con
tinuo
us d
evel
opm
ent,
data
in th
is do
cum
ent i
s su
bjec
t to
chan
ge w
ithou
t not
ice
and
beco
mes
con
tract
ual o
nly
afte
r writ
ten
confi
rmat
ion
Borri S.p.A. Via 8 Marzo, 2 · 52011 Bibbiena (AR) Italy · Tel. +39 0575 5351 · Fax +39 0575 561811 · sales@borri.it · www.borri.it
ww
w.b
orr
i.it
da 60 a 160 kVA
Low TCO, efficient and compact solution for supplying reliable uninterrupted quality power to all critical applications in networking and small to medium datacenter, health, finance, industrial processing, building and transportation markets and for TLC. Featuring Green Conversion patented technology, INGENIO PLUS provides high efficiency even at light loads and ensures 100% battery expected life, thus ensuring low opex and capex savings.
Features and benefits● Continuous savings with Green Conversion patented technology, providing high efficiency and UPS critical components’ life care
● Clean mains and full compatibility with Genset operation due to its low input current distortion and soft start features
● No oversizing and power factor correction related costs thanks to its 0.99 input power factor
● Reduced commissioning and floor space related costs and lower environmental footprint with transformer free design and common battery management
● Capital expenditure protection thanks to hot expandability and load based shutdown in parallel systems
● High flexibility with full output power rating and different operating modes
Green ConversionGreen Conversion technology is based on a patented control algorithm, managing the battery-inverter subsy-stem in order to enhance double conversion efficiency and to extend battery life.The innovative Green Conversion inverter design increases efficiency and reduces switching stress on all components subject to wear.The new Green Conversion battery charger completely filters voltage ripple and floating voltage micro currents to the battery:main causes for early battery ageing.Benefits are 30% saving on maintenan-ce cost and battery’s operating life extension by as much as 40%. Energy saving operating
modesSet the best mode of operation for any application according to mains quality, load immunity grade to mains disturbances and system features, to always deliver the best reliable quality power at the highest efficiency.
● On line double conversion: VFI (Voltage Frequency Independent) double conversion total protection with up to 96% efficiency thanks to our Green Conversion patented technology.
● ECO mode: suitable for stable mains, in VFD (Voltage Frequency Dependent) mode of operation, achieving 98% efficiency.
● Ultra High Efficiency: the most innovative power protection techno- logy for high immunity grade applications, up to 99,0% efficiency, with the lowest TCO
Battery life careProtecting capital expenditure on batteries, whilst ensuring full availabi-lity of mission critical applications can only be achieved by keeping them in perfect condition. INGENIO Plus comes with advanced charging and battery managing features, providing best battery performance and exten-ded lifetime:
● Intermittent charging, with adjustable charging cycle (27-3 typical), to extend battery operating life and to achieve maximum energy savings
● Dynamic Charging Mode (DCM): automatic setting of battery charging current, with feeding priority to output loads, ensuring low charging times for long autonomy applications
● Battery charging voltage tempera- ture compensation: to prevent excess battery charging and overheating
● Automatic and manual battery test: to detect any battery performance deterioration
● Common battery management: the right feature when pricing and footprint are important factors
Application●
Networkingand telecommunication
●
Data server●
Process automation●
Medical equipment ●
Emergency and safety systems
●
Continuous cooling
One to one power factor INGENIO PLUS features both input and output unity power factor. Its “full-IGBT” technology makes it a linear and power factor corrected load for the upstream mains, whilst being capable of feeding its loads at any output power factor, up to full rated real power..
Backfeed protectionPlus series comes with backfeed ener-gy detection circuit and output contact for remote tripping coil. Local tripping device for bypass disconnector can be fitted as an option, for total upstream protection and operator safety, without additional installation costs.
Smart parallelSmart-parallel control continuously monitors load power requirements and maximizes system efficiency, by turning off all unnecessary units.
Advanced connectivityLCD graphic display or 7” touch screen display (optional) front panel ensure clear and quick access to all UPS status. Remote communication is managed through most common protocols and interfaces such as voltage free relay contacts, RS485 ModBus-RTU, Ethernet ModBus over IP or SNMP protocol, as well as dedicated web server for remo-te UPS monitoring from any workstation or web based mobile device.
Low total cost of ownershipINGENIO PLUS is designed to reduce TCO. Transformer-free architecture and internal battery layout cut commissio-ning costs and footprint. High efficiency double conversion and advanced energy saving modes ensure low operating costs. Green Conversion control dramatically reduces maintenan-ce costs, extending all critical components and battery’s life. Full rated output power results in optimal UPS sizing and utilization.
INGENIO PLUS technical data Rating (kVA) 60 80 100 125 160
Nominal power (kW) 60 80 100 125 160
UPS dimensions WxDxH (mm) 560x940x1800
UPS weight (kg) 250 300 320 360 380
UPS weight with int. battery (kg) 800 850 - - -
Battery confi guration Internal or external, 360÷362 cells, Esternal 360÷372 cells, VRLA (other options)
VRLA (other options)
Max autonomy with int. battery 12 11 - -
70% load (min)
Input
Connection type Hardwired 4w (rectifi er), 4w (bypass)
Nominal voltage 400 Vac 3-phase (rectifi er) 380/400/415 Vac 3-phase with neutral (bypass)
Voltage tolerance -20%, +15% (rectifi er) ±10% (bypass)
Frequency and range 50/60 Hz (45÷65 Hz)
Power factor >0.99
Current distortion (THDi) 150% for 0.1 s; bypass: 150% continuous, 1000% for 1 cycle
Effi ciency (AC/AC)* up to 99%
Classifi cation as per VFI-SS-111
IEC/EN 62040-3
Connectivity and function extensions
Front panel Graphic display, mimic LED panel and keyboard, local EPO
Remote communication Included: serial RS232 and USB, backfeed protection monitoring contact. Optional: input terminal block (remote emergency power off, battery circuit breaker aux. cont., external maintenance bypass circuit breaker aux. cont., diesel mode aux. cont.); SNMP adapter (Ethernet), Web interface (Ethernet), from ModBus-RTU to PROFIBUS DP adapter; SPDT contact relay board; remote system monitoring panel; UPS managing and server shutdown software
Optional function extension Isolation transformer; transformers/autotransformers for voltage adjustment; external maintenance bypass; custom battery cabinets; wall-mounted battery fuse battery thermal probe; parallel kit for load sharing
System
Protection degree IP20
Colour RAL 9005
Installation layout Wall and side by side installation allowed, 80 cm clearance on one side only with internal battery
Accessibility Front access, side access (only with internal battery), bottom cable entry
*according to IEC/EN 62040-3
Environmental
Operating temperature range 0°C ÷ +40°C
Storage temperature range -10°C ÷ +70°C
Altitude (AMSL) < 1000 m without power reduction, > 1000 with reduction of 0.5% per 100 m
Audible noise at 1 m (dBA)
Autonomy with different internal batteries
60 kVA
80 kVA
0 5 10 15minutes
Who we areBorri is a company specializing in the custom design, manufacturing and servicing of power supply protection systems in key sectors such as ICT, industrial processes and service, oil & gas and energy, utilities, also of static conversion for renewable energy sources.The Borri research and development department is among the most complete regarding the coverage of the various disciplines involved in power conversion.On the strength of proven expertise in product customization and a continuous quest for excellence, Borri is named in more than 40 vendor lists and enjoys a position of prominence in the oil & gas sector.Similarly, with extensive experience in various branches of power electronics such as UPS systems for data centres, inverters for renewable energy projects and storage systems.Borri is a dependable partner able to offer power supply solutions used in ICT applications, in the process industry and
For more information, visit our website: www.borri.it
for services, with numerous installations to its credit UPSaver®, the most recent three-phase solution, based on Green Conversion patent technology, is able to guarantee unparalleled energy savings, and the best PUE for data centres with lower environmental impact, proof of the ongoing company commitment to innovation.Under the Astrid brand, Borri offers a wide range of renewable energy solutions, reflecting its commitment to our pursuit of sustainable development.Headquartered in Italy, with 15,000 m² of production area and a fully equipped inspection and testing area, the company is able to count on more than 80 years of experience, multidisciplinary R&D and a highly application specialized custom engineering capability.Borri has a presence on all 5 continents with thousands of installations worldwide, professional staff and a network of partners able to provide you value added technical support and services.
LOAD
INGENIO PLUS 60-160 kVA series options
Parallel kit When the unit is to be paralleled for load sharing
Description When do I use it
Load-sync for single units To synchronize single units’ output for no-break load transfers by downstream static transfer switches
Load-sync box for two sets of paralleled UPSTo synchronize the output of two paralleld UPS systems
for no-break load transfers by downstream static transfer switches
Tripping coil for bypass disconnector To be fully protected against backfeed energy upon static bypass failure. Detection circuit is included
Input transformer(to be installed internally or in extended cabinet)
To galvanically isolate UPS from load or to change system’s earth arrangement
Battery fused switch box To disconnect and protect an external battery pack (wall mounted box)
Internal battery temperature probeWhen the unit has internal batteries, for charging voltage
compensation with temperature and UPS temperature monitoring
External battery temperature probe
Internal battery + UPS temperature probe
When the unit has external batteries, for charging voltage compensation with temperature (10 m cable length)
When the unit has internal batteries, for charging voltage compensation with temperature and
UPS temperature monitoring
Dry contact relay card (8 contacts)
Remote monitoring panel
RS485 ModBus-RTU port
Web/SNMP Adapter for telemonitoring and teleservice
To send UPS status to PLC’s, SCADA’s or AS400’s by voltage free SPDT contacts
To monitor UPS status by a LED panel from a remote control room
To send UPS status to BMS’s by RS485 connection and ModBus-RTU protocol
To send UPS status to BMS’s by Ethernet connection and SNMP or ModBus over IP protocol. To monitor UPS status by any
internet browser from workstations. To receive SMS or e-mail alerts from the UPS on any portable device
Input terminal block for remote EPO When the Emergency Power Off (EPO) has to be commanded by a remote control button
Input terminal block for external manual bypass switch auxiliary contact
Input terminal block for diesel mode contact
Input terminal block for external battery switch auxiliary contact
When there is an external maintenance bypass switch, for state monitoring
When battery recharge has to be inhibited over genset operation
When there is an external battery switch, for state monitoring
LOAD A LOAD B
LOAD SYNCBOX
LOAD A LOAD B
High feature solutions for large, mission-critical systems
400 - 500 - 600 - 800 kVAThree-phase UPS
B9600FXSIndustrial Power Solutions
FleXible and Smart
LOW THDi and POWER FACTOR PERFORMANCE ENHANCE COMPATIBILITY with INPUT MAINS and GENERATORS
The BORRI B9600FXS model UPS uses a completely new IGBT input rectifier design, encompassing an
advanced PFC (Power Factor Control) which is capa-ble of keeping input current THDi (Total Harmonic Distortion) at a level of less than 3% and the input power factor within 1% of unity, even when only
small loads are applied.The key benefits are that the UPS is therefore com-
patible with the upstream source, the mains or any kind of generator and the transfer of power between
source and load is more efficient. This results in a saving in terms of scale of sources, cables and protective devices.
HIGH EFFICIENCY REDUCES OVERALL COST of OWNERSHIP
The B9600FXS has a new SOL (Smart On-Line) function which enables a total operating efficiency of between 96% and 98%. This mode re-ferred to as “Intelligent ECO mode” significantly reduces the utility costs associated with operating a device of this type. Moreover, this increase in efficiency results in the production of less waste heat, minimising cooling/air-conditioning costs. This represents a double saving to the energy conscious user. The SOL function uses continual monitoring techniques to review the input characteristics of the supply. This means that if the supply line drops or fluctuates outside of acceptable conditions the UPS uses the inter-nal inverter to support the load. This is achieved through a fast, fully static transition from VFD to VFI mode.
DOUBLE CONVERSION TOPOLOGY OFFERS “GREEN” DOUBLE PROTECTION for EVERY APPLICATION
The VFI Online double conversion topology implemented in this equip-ment offers built in inverter galvanic protection completely isolating the output power from all the input power anomalies, delivering fully conditioned pure sine-wave output. In this pure on-line mode the unit delivers a excellent certified 96% efficiency.Because of the technology and topology used, no additional losses are generated to get low input harmonics or input/output galvanic isolation. The B9600FXS unit is designed to provide excellent output voltages suited to very demanding applications with either 100% step load, unbalanced, non-linear or modern IT loads. It also provides excep-tional performance: with a power factor of up to 0.9 (lagging or lead-ing), there is no requirement to de-rate the unit.
TRIPLE INTELLIGENCE: FleXible and Smart
If the application requires extremely flexible and reliable UPS protec-tion, the B9600FXS is ideal. It delivers advanced features based on state-of-the-art total digital control. This control incorporates dual DSP (Digital Signal Processing) and µC (Micro controller) technologies.The system design ensures that auxiliary power supplies and proces-sors are no longer single points of failure which could compromise the availability of clean power to the load. The B9600FXS is designed to overcome the limitations imposed by other, older, designs. With its distributed control architecture, the B9600FXS will always have a UPS circuit protecting the load; furthermore, the status of most criti-cal components is constantly monitored, allowing predictive mainte-nance and avoiding unexpected breakdowns.B9600FXS working state can be easily monitored by any Building Management System and via LAN/WAN.
ACCURATE BATTERY MANAGEMENT
Batteries are electro-chemical devices, which store charge chemi-cally; as such their performance degrades with time. The B9600FXS performs ABM (Accurate Battery Management) according to battery manufacturer requirements.Following a UI characteristic curve, the charger charges at a constant current appropriate for the battery type used, preventing detrimental excess charging. In addition to the float voltage level, boost charge can be set, optimising the recharge time when there is the possibility of consecutive power outages within a short period. ABM also reduces the residual ripple current (one of the causes of pre-mature battery wear), as well as protecting the battery from damag-ing deep discharges.Automatic battery temperature compensation charge voltage may be implemented, charging the battery more appropriately and increas-ing battery life.By means of the DCM (Dynamic Charging Mode) very long battery au-tonomies can be achieved without increasing total charge time. This is achieved through the implementation of an intelligent increase in maximum battery charge current when the maximum inverter power is not being drawn by the load.An integrated periodical battery testing function tests and monitors battery health, providing advanced warning to guide the application of preventive maintenance.
PARALLEL SYSTEMS for REDUNDANCY or CAPACITY INCREASING with “HOT SWAP” MODULARITY
The B9600FXS UPS solution offers parallel options in both redundancy and capacity modes, providing the possibility for both extra system resilience and increased capacity.The parallel control circuitry associated with these units is fully digital
The innovation and design of the BORRI B9600FXS high power UPS has resulted in the unit being the most
technologically advanced in its class. It delivers an incredible combination of low input current distortion, unity input power
factor and high overall efficiency. These advances in design offer numerous benefits, including lower running costs and
substantially increased reliability.
INFORMATION AND COMMUNICATION TECHNOLOGY
• Large data centers
• Server farms
• Telecommunication installations
• Broadcasting and entertainment
• Internet Service Providers (ISP)
CRITICAL ELECTRICAL ENGINEERING
• Industrial systems
• Financial and banking
• Security operations
• Transportation systems
• Medical/Healthcare
and acts on both active and reactive power on each of the three out-put phases. This allows accurate load current sharing among the UPS units even during transient conditions.Parallel control is distributed between all units and communication is achieved through the use of a CAN BUS connection loop. This has the effect of producing a highly reliable system with “no single points of failure”.Intelligent design of the system connections allow for easy installation and easy future upgrades, this allows for upgrading the field without difficulty.In the modular arrangement, units can be added or removed “hot” without load disturbances or the need to switch to bypass. Smart Parallel functions facilitate the automatic switching off of units where the total power requirements of the load is provided by fewer than the total number of UPS units attached. This is commonly known as ‘load based shutdown’ and maximises the efficiency of the complete system by keeping the load on each module at an optimum level. Two independent paralleled systems can be synchronized (Sync Con-trol) in order to feed downstream STS’ for seamless transfers.
EASY INSTALLATION, OPERATION and MAINTENANCE
The B9600FXS can easily be moved within areas not wider than 1200mm, and can be installed up close to walls or other cabinets as cooling air is expelled through vents on the top of the unit.This new design gives the user a significant saving in floor utilisation. This makes the B9600FXS an ideal solution where space is at a premium. Despite this modern compact design, all critical components, are ac-cessible from the front of the unit; this improves accessibility to allow regular maintenance and reducing Mean Time to Repair (MTTR).The B9600FXS also incorporates a unique back-feed power protection system, where in the event of the output of the UPS being fed back into the mains, the unit will immediately isolate itself. This in turn, re-moves the need for additional MCBs or other similar safety devices.
USER INTERFACE and ACCESSORIES
User-friendly Interface
OPTIONS• Parallel capacity/redundancy• Sync control for dual feed systems• Isolation transformer• External bypass• External battery cabinets• Battery switch box• Battery thermal probe• Transformers/ autotransformers for voltage adaption• Top cable entry
COMUNICATION• RS232 serial port• USB port• Remore EPO• External Manual Bypass status• Battery Switch status• Diesel Mode
OPTIONAL• Web/SNMP • ModBus• Relays• Modem• Remote panel
Monitoring, managing and shutdown software
400 - 500 - 600 - 800 kVAThree-phase UPS
Bypass and switchgear section
Power conversion section
Removable blowers
Front access
B9600FXS
Load
Bypass
Mains
Parallel ...n
RATING 400 kVA 500 kVA 600 kVA 800kVA
Capacity (kVA) 400 500 600 800
Dimensions WxHxD (mm) 1990x1920x990 2440x2020x990 3640x1920x990
Weight (kg) 1820 2220 2400 3600
Input/output connection Hardwired (dual input)
Battery External, 300 - 312 cells
INPUT
Nominal voltage 220/380, 230/400, 240/415 Vac three phase
Voltage range -20%, +15% from nominal
Frequency 50/60 Hz (45-65 Hz)
Power factor 0,99
Current distortion (THDi) < 3%
OUTPUT
Nominal voltage 220/380, 230/400, 240/415 Vac three phase
Frequency 50/60 Hz
Voltage regulation ±1% static; ± 5% dynamic 100% load change, 95% (certified TÜV NORD)96-98% (>98%)
OPTIONS Parallel capacity/redundancy, sync control, isolation transformer, external bypass, external battery cabinets, battery switch box, battery thermal
probe, transformers / autotransformers for voltage adaption, top cable entry
USER INTERFACE
Front pannel Graphical LCD display, mimic with LED’s and keyboard
Standard communication ports RS232 serial, USB, Remote Emergency Power Off input, Battery Switch status monitoring,
External Manual Bypass status monitoring, Diesel Mode
Optional Web/SNMP, ModBus, relay, modem cards; remote panel; monitoring, managing and shutdown software
ENVIRONMENTAL
Operating temperature 0°C ÷ +40°C
Storage temperature -10°C ÷ +70°C
Altitude
efficiency and reliability in power supply solutions
MUST 10 - 400Modular UPS
Datacenter & servers
Internet centers
Local Area Networks (LAN)
Telecommunication devices,
Emergency application
10 – 200 kVA modular UPS, up to 400kVA
MUST 10 - 400
MUST 10-400 series is modular and online double conversion UPS for sensitive equipments. The power rating covers from 10kVA to 400kVA which delivers the best combination of reliability, functionality, hot-swappable and flexibility at a competitive price.
Product overview
ModUlar deSign, hoT Swappable
STrong load adapTabiliTy for linear and nonlinear load
inTelligenT ModUle and SySTeM proTecTion deSign
low noiSe SySTeM deSign
aVailable parallel conTrol for cabineTS
Solutions comparisonModular solution MUST 10-400 (N+1) vs standalone UPS in parallel
aVailabiliTy• Modularsolutionguaranteesmuchmoreavailability
than a traditional standalone parallel solution• MTTRMUST=3minutes • MTTRstandalone=480minutes• MUST10-400isanhotswappablesolution!
coST, efficiency and flexibiliTyIn MUST 10-400 you can adapt the UPS with needed power capacity, step by step (small steps), keeping efficiency always at maximum level: in standalone solution, you have to add one more unit, with the same power, to the previous unit (big steps): that means low efficiency (more energy and cost) and spending more money to achieve the same needed steps, without gradual investment cost.
SaVe SpaceIn case you need to increase the power capacity of the UPS system, using the MUST solution it’s enough to add one more module (same foot print); in standalone solution you have to add one more cabinet.
lower SerVice coSTFor the MUST 10-400, in site, you spend very little time to do the normal maintenance (cleaning, testing (automatic battery test), check the alarms recorded list, etc). Even the replacement of power module is very fast.
MUST 10 - 400
Connectivity devices
Advancedcommunication
• StandardRS232portandRS485portwithModBusinterfaceprotocol.
• REPO(RemoteEmergencyPowerOff)topowerdowntheUPSthrougha remote emergency push button.
• Web/SNMPcard allows UPS management across a LAN using any of the main network communication protocols - TCP/IP, HTTP and network interface via SNMP. In case of alert it can notify users and administrators via email; when prolonged power failure occurs the protected computer systems can be shutdown in a graceful manner.
• Relay/AS400card is an easy interface for input/output dry contacts and AS400 series computer, the common manner for industrial and building management systems.
As standard the MUST 10-400 has local monitoring software through serial port, the UpSilon provides user-friendly UPS management. The software displays real time information in the form of bar charts and values for critical data such as mains voltage, UPS load and battery charge. It allows remote interrogation of UPS logs and operating parameters to help diagnose alarms and potential fault conditions. When instructed the software performs an automated safe power down of the protected servers and PCs.
operaTing SySTeMS SUpporTed
Windows95-OSR2,98,Me,NT4.0,2000,XP,2003andlatestversions;Linux;NovellNetware3.x,4.x,5.x,6;MacOSX,9.x;IBMOS/2Warpand Server; HP OPEN VMS; The most widelyused UNIX operating systems such as: IBMAIX, HP UNIX, SUN Solaris INTEL and SPARC,SCO Unix and UnixWare, Silicon Graphic IRIX,CompaqTru64UNIXandDECUNIX,BSDUNIXandFreeBSDUNIX,NCRUNIX.
DirectConnectionwithEthernetNetwork
shutdown
LINK
RS232
RS232Terminal
ETHE
RNET
NETW
ORK
SNMPTRAP
WEbPAgE
shutdown
AdministratingWorkstation
WindowsWorkstation Server2
server1
• LARGETOUCHSCREENLCDDISPLAy• ALLMAINSSySTEMANDMODULES
PARAMETERSAVAILABLE• COMMANDSANDSETTINGSAVAILABLEWITH
THREEPASSWORDLEVELS
• LEDSTHATINDICATETHEPOWERFLOWFORANIMMEDIATEACkNOWLEDGEMENTOFTHESySTEMSTATUS
• EPO:EMERGENCyPOWEROFFBUTTON
MUST 60–120
MUST 100–200
MUST 30-60with batteries on board
Thiscabinetisdesignedtohouse6unitsofpowermodule
10kVA/20kVA.Itisanidealsolutionforamediumloadthat
requires redundancy or the possibility to expand the power
in the future.
Its winning advantages against any conventional parallel
UPS involve parallel configuration N+1, hot swappable and
scalability, as well as easy maintenance. It is possible to
expand the power to 360kVA by connecting up to three
cabinets in parallel.
This cabinet is designed to house 10 units of power
module10kVA/20kVA. It is an ideal solution formedium
to large load.
UPS capacity can be doubled to achieve 400kVA by
connecting two cabinets together.
Solution, includingthreemodules(10or20kVA) ,max.4x40batteries9Ah/12V,andbatteriesbreaker, isavailableinto the bigger cabinet (10 modules house).
In 19” ,is possible to house 4 battery modules, just to reach total240+240VDC ,which isequivalent toonebranchplug in system.(see pictures)
Themax.capacityofthissolutionis240+240VDC/36Ah.
The MUST system
MUST 10 - 400
MUST 10 - 400
Powermodule10kVAand20kVAwith rectifier, inverterandbatterycharger.
recTifier: advanced technology with IGBT rectifier. Zeroimpact to the mains thanks to PFC (Power Factor Control) system: input PF 0,99. It means no harmonic distortions through the mains therefore very low THDi, less than 3%. Optimize the upstreaminfrastructure without over rating the supply device (ideal for gen-set and transformer supply).
inVerTer: : last generation technology using 3 level IGBTpower bridge with high frequency modulation with PWM driving. HighperformancedigitalcontrolwithDSP,verystableandperfectsinusoidal waveform even in case of unbalance load. High power densitywithPF=0,9andefficiencyatmaximum levelstarting fromevenlessthan50%ofload.Efficiencyupto96%.
baTTery charger: distributed battery charger in each module.Thepoweris20%oftheratedpower.Itmeansnosinglepointof failure and wide range of battery capacity installable. Smart battery management. Single and double level of battery charger, temperature compensation, end of discharge voltage control. Automatic self batterytesttopreventbatteryfault.OptimizedforthemostcommonbatterytypesassealedVRLA,AGMorwetleadacidandNiCd.
Centralized static bypass sized for the full power of the system.Completely hot swappable reducing at minimum the maintenance process. High quality SCRmounted inside in the auxiliary line andprecise control.The biggest and more complete user friendly touch screen. Easy to use and with wide range of information coming from the system status. With password protected level is possible to set the configuration of the system directly from the touch screen.
The MUST configuration
The highest technology level
10 kVA20kVA
60kVA120kVA
120kVA240kVA
180kVA360kVA
10 kVA20kVA
100 kVA200kVA
200kVA400 kVA
30kVA60kVA
MUST 10 - 400
Benefits in your choice
energy SaVing
The high performance of the series MUST 10-400 is also evident for small percentages of the applied load. Itsefficiencyisduetothe3-levelIGBTarchitecturewhichisstateofthearttechnology.
MUST 10-400 has been designed to achieve the maximum energy saving.Combination of several factors makes this result remarkable.
• High efficiency provided by the most recentelectronic technology.
• Flatcurveofefficiencyinalargepowerrangethatminimizesenergylossesatlowerload.
• Modular structure that allows to achieve therequested power using only the necessary number of modules.
• Excellent inputandoutputelectricalperformancessuch as very low harmonic distortion to the mains, which means a clean electrical network without disturbances to other critical loads, as well as lower energy losses.
Green Technology
100
95
90
85
80
75
70 10 25 50 75 100
%Efficiency
%load
MUST
traditional UPS
The extreme flexibility of use and the superior performance, even at low per-centages of load, mean faster return on investment compared to to the majority of UPS on the market.
MUST 10 - 400
Technical specifications
*It is recommended to refer to the product manual and settings compliant with legal standardsNote: product specifications are subject to change without further notice
MUST 10-400CapaCity 10-400kVa
Main input
input voltage380V/400V/415V(line to line)
220V/230V /240V(line to neutral)
input frequenCy 50/60Hz
power faCtor >0.99
input voltage window -40%~+25%
frequenCy window 40-70HZ
Battery
Battery voltage ±240VDC
Charger power10kVA: 3.1A20kVA: 6.2A
Charger voltage preCision 1%
Bypass
Bypass voltage380V/400V/415V, line to line
220V/230V/240V, line to neutral
Bypass voltage window -20%-+15%, full load
Bypass overload CapaBility
125%, long time operation125%< load
Mini MUST Online UPS
10-40 kVA/kW 3/3, 3/1, 1/1 phase 10-
90 kVA/kW 3/3 phase
SERVERS
DATA CENTERS
MISSION CRITICAL
TELECOMMUNICATIONS DEVICES
INDUSTRIAL APPLICATION
Smart Energy
Solutions
Product Overview 2
The first UPS in a rack that combines compact size, ease of use and installation flexibility
MODULAR DESIGN
HIGH POWER DENSITY
SUITABLE FOR RACK APPLICATION
MULTICONNECTION AVAILABLE (3/3, 3/1, 1/1)
HIGH EFFICIENCY
MiniMUST can be easily adapted to any type of installation thanks to the possibility to operate indifferently as 3/3, 3/1 or 1/1. The Coated
boards make it a solution suitable for harsh environments and it increases the reliability and expected life obtaining a result among the most
important in the market.
Product Topology
Minimust can be installed as stand
alone solution or it can be inserted in
existing standard 19’’ cabinet.
It guarantees maximum flexibility
because of its modularity.
It permits to install the Minimust as
a block or even in single module
configuration inside the cabinet, with
bypass and power modules.
• EASY ACCESS: Whatever the chosen configuration,
the convenience of access is guaranteed by the
positioning of the controls that are always easily
accessible.
• SMART SERVICE MANAGEMENT: maintenance
alert for critical components, such as capacitors and
fans, in order to guarantee proper operation through
preventive interventions.
MiniMUST
Product range 3
MAXIMUM FLEXIBILITY IN YOUR HANDS
MINIMUST 10/20 KVA This system is built to host 2 units of power
module 10 kVA . It is an ideal solution for a
low/medium load that requires redundancy
or the possibility to expand the power in the
future.
Maximum power 20 kVA cosphi = 1.
MINIMUST 10/40 KVA This system is built to host 4 units of power
module 10 kVA . It is an ideal solution for
a medium load that requires redundancy or
the possibility to expand the power in the
future.
Maximum power 40 kVA cosphi = 1.
MINIMUST 10/60-15/90 KVA This system is built to host 6 units of power
module 10 kVA or 15 kVA. It is an ideal
solution for a medium load that requires
redundancy or the possibility to expand the
power in the future.
Maximum power 90 kVA cosphi = 1.
Interface
7” colored touch screen easy to use with total control
of parameters, setting and status of the system
Programmable dry contact for easier integration in
local monitoring system
SMNP option for web monitoring
RS232 and RS485 communication port
Green Technology
High efficiency provided by the most recent electronic
technology.
SMART PARALLEL MANAGEMENT: Flat curve of
efficiency in a large power range that minimizes energy
losses at lower load.
Excellent input and output electrical performances such
as very low harmonic distortion to the mains, which
means a clean electrical network without disturbances
to other critical loads, as well as lower energy losses.
Modular structure that allows to achieve the requested
power using only the necessary number of modules.
MiniMUST
Rev
. 3
0/0
6/2
01
6
Technical Specifications
MODEL 10 KVA - 40 KVA 15 KVA - 90 KVA**
10 kW - 40 kW 15 kW - 90 kW MAIN INPUT
Input Voltage 380V/400V/415V(line to line)
220V/230V /240V(line to neutral)
Input frequency 50/60Hz
Power factor >0.99
Input voltage window up 276Vac; down -40% (-20%,-30%, -40% selectable)
-20%~-40% rated power derating from 100%~80%
Frequency window 40-70Hz
BATTERY
Battery voltage ±240VDC
Charger power 20%*Active Power
Charger voltage precision 1%
BYPASS
Bypass voltage 380V/400V/415V(line to line)
220V/230V/240V(line to neutral)
Bypass voltage window -20%-+15% default; -40%-+25% selectable Bypass overload capabiltiy
125%, long time operation 125%< load
See reverse side for specificationsEltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com
DOCUMENT NO: DS-2104924.DS3 v2
Industrial DC Systems IBB 24VDC, 30VDC, 48VDC, 60VDC, 110VDC, 125VDC & 220VDC systems
High Efficiency Industrial Power Solutions
KEY FEATURES ¸ Compact design and easy installation
¸ Industry-leading efficiency; less power consumption and heat dissipation
¸ Modular Hot Plug-in architecture allows: - Redundancy; n+1, n+2 configuration - Very low MTTR: 350.000h
¸ Extensive control & alarm functions with remote control capabilities
¸ Pre-engineered and tested systems and building blocks
¸ Overall size and footprint; 50% less than thyristor systems
¸ Graphical 3.2” TFT high contrast, high resolution color display for easy navigation in user menu
¸ Optional built in VRLA batteries (up to 125VDC)
Eltek IBB Industrial power systems offer end users a significant advantage over current technology in both cost and performance. The modular architecture, industry-leading efficiency, compact size, innovative design and comprehensive monitoring and control features provide significant benefits over the current industry standard. Eltek IBB Power systems and building blocks are built around our Flatpack2 High Efficiency (HE) rectifiers and designed for a number of power-critical Industrial applications, including Power Generation & Distribution, Rail, Marine & Offshore, Oil & Gas and other demanding industries.
INDUSTRY APPLICATIONS
Power Utilities • Low & High Voltage switchgear • Transformer & Substations • Power Generation & Distribution • Control & protection • SCADA Communication • Emergency lighting
Offshore and process industry
• Safety and Automation Systems (SAS)
Marine • Communication systems onboard
ships Railway & Metro infrastructure
• Control & protection • Power conversion • Signaling • GSM-R • Safety Systems • Communication systems
Smartpack2 system controller Flatpack2 HE rectifier
http://www.eltek.com
Eltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com
IBF-UPC4 with DC bulk feed output
IBF-SP2 with DC bulk feed output
Distribution unit
Battery fuse unit
General single line diagram
Building blocks for IBB Systems FPC Cabinets FPC is a family of high-end indoor cabinets, designed for flexibility. With its robust design, removable side panels and variety of options, the FPC cabinet can be used in a wide range of applications. (For additional information about FPC cabinets, please see separate data sheet) IBF-SP2 Power Core A complete 19” & 23” Power core pre-engineered and designed for: 24, 30, 48, 60, 110, 125 and 220 VDC with the following features:
- Power rack housing up to 8 FP2 rectifiers, AC Input fusing and SPD (Surge protection)
- Smartpack2 Controller with 3,2” TFT Color display, including Ethernet and Web interface for remote monitoring
- 300A DC Bus bars - 6 Digital inputs for external alarm management - 6 Relay outputs NO, COM, NC for remote alarm indications - Power Suite Configuration software for easy programming - Battery shunt
IBF-UPC4 Power Core A complete 19” & 23” Power core pre-engineered and designed for: 24, 30, 48, 60, 110, 125 and 220 VDC with the following features:
- Power rack housing up to 8 FP2 rectifiers, AC Input fusing and SPD (Surge protection)
- UPC4 DC Controller with multi module (rectifier, DC/DC Converter, Inverter and STS) control functionality and display
- 300A DC Bus bars - 6 Digital inputs for external alarm management - 6 Relay outputs NO, COM, NC for remote alarm indications - MMT Configuration software for easy programming - Battery shunt
Distribution Unit A complete 23” Distribution unit designed for: 24, 30, 48, 60, 110, 125 and 220 VDC with the following features:
- Up to 12 2-Pole MCBs 6-40A with or without fuse trip alarms Battery fuse Unit A complete battery fuse unit for system mounting designed for: 24, 30, 48, 60, 110, 125 and 220VDC with the following features:
- NH00 and NH1, 63-250A Fuses with fuse trip alarm or - MCCB, 63-250A Circuit breakers with fuse trip alarm
FPC Cabinets
http://www.eltek.com
Eltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com
AVAILABLE 24V/30V RECTIFIERS
Part Number Description Voltage
Efficiency Maximum Current Output
Range 1 Module Max/Syst. protection 241115.205B Flatpack2 24V/40A HE 21.7 – 28.8 V > 95% (30-65% load) 40 A 4/160A Fuse
241115.205 Flatpack2 24V/1800W HE 21.7 – 28.8 V > 95% (30-65% load) 75 A 4/300A Fuse
241115.200 Flatpack2 24V/2000W 21 – 29 V > 89% (25-100% load) 84 A 4/300A Blocking diode
241115.250 Flatpack2 24V/2000W WOR 21.5 – 36 V > 91% (25-85% load) 70 A 4/280A Fuse
AVAILABLE 48V/60V RECTIFIERS
Part Number Description
Voltage
Efficiency
Maximum Current Output Range 1 Module Max/Syst. protection 241115.705B Flatpack2 48-60V/15A HE 39.9 – 72 V > 95.5% (50-100% load) 15 A 8/120A Fuse 241115.705 Flatpack2 48-60V/2000W HE 39.9 – 72 V > 95.5% (25-75% load) 41.6 A 8/166,4A Fuse 241115.100 Flatpack2 48V/2000W 43.2 – 57.6 V > 91.5% (45-95% load) 41.6 A 8/166,4A Blocking diode 241115.105 Flatpack2 48V/2000W HE 43.5 – 57.6 V > 96% (30-70% load) 41.6 A 8/166,4A Fuse
AVAILABLE 110V/125V RECTIFIERS
Part Number Description
Voltage
Efficiency
Maximum Current Output Range 1 Module Max/Syst. protection 241115.805B Flatpack2 110-125V/10A HE 89.2-171.6 V > 94% (45-100% load) 10 A 8/80 A Oring diode 241115.805 Flatpack2 110-125V/2000W HE 89.2-171.6 V > 94% (30-70% load) 16.8 A 8/134,4A Oring diode
24V/30V Systems
Applications The 24V/30V rectifiers are suitable for parallel operation with all types of stationary batteries, including lead acid or nickel cadmium types, and can also operate without batteries. Typical applications:
- Alarm systems - Diesel start float application - PABX systems - Emergency lightning - Industrial control systems
48V/60V Systems
Applications The 48V rectifiers are deigned to meet international telecom standards for safe and reliable operation in telecom environments or any industrial communication system. Typical applications:
- Telecommunication systems; SCADA, GSM-R - PABX systems - Emergency lightning - Industrial control systems
110V/125V Systems
Applications The 110V rectifiers are designed for demanding environments and comply with IEC61000-6.5 (Immunity Power Stations and Substations) for reliable operation in critical applications. Typical applications:
- Low & High Voltage switchgear - Transformer & SUB Stations - Power Generation & Distribution
http://www.eltek.com
Eltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com
AVAILABLE 220V RECTIFIERS
Part Number Description
Voltage
Efficiency
Maximum Current Output
Range 1 Module Max/Syst. protection 241115.815B Flatpack2 220V/5A HE 178,5-297 V > 95% (45-95% load) 5 A 8/40A Oring diode 241115.815 Flatpack2 220V/2000W HE 178,5-297 V > 95% (35-65% load) 9.16 A 8/73.3A Oring diode
GENERAL TECHNICAL SPECIFICATIONS Model Industrial DC Systems IBB 24-220VDC Part number Depending on configuration INPUT DATA Voltage (range) 115 - 400 VAC (∆) or (Y), Derating
1Can be adjusted via PC software mode
All specifications are subject to change without notice
Input: Single-phase 115 – 277 Vac Output Load: power supply 24 Vdc; 3 A Output Battery: charging 24 Vdc; 3 A Suited for the following battery types: Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd Automatic diagnostic of battery status. Charging curve IUoUO, constant voltage and constant current Battery Life Test function (Battery Care) Switching technology, output voltage 22-28.8Vdc Three charging levels: Boost, Trickle and Recovery Protected against short circuit and inverted polarity Signal output (contact free) for discharged or damaged battery Signal output (contact free) for mains or Back-UP Protection degree IP20 - DIN rail; Space saving
Technical features Thanks to the All In One units (DC-UPS), it will be possible to optimize power management. The available power is automatically allocated between load and battery, supplying power to the load is the first priority of the unit thus it is not necessary to double the power, because also the power going to the battery will go to the load if the load so requires. The maximum available current on the load output is 2 times the value of the device rated current In. We call “Battery Care” the concept base on algorithms that implement rapid and automatic charging, battery charge optimization during time, flat batteries recovery and real time diagnostic during installation and operation. The Real Time Auto-diagnostic system, monitoring battery faults such as, battery Sulfated, elements in short circuit, accidental reverse polarity connection, disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis Led; during the installation and after sell. The continuous monitoring of battery efficiency, reduces battery damage risk and allows a safe operation in permanent connection. Each device is suited for all battery types, by means of jumpers it is possible setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd(option). They are programmed for two charging levels, boost and charge, but they can be changed to single charging level by the user. A rugged casing with bracket for DIN rail mounting provide IP20 protection degree. They are extremely compact and cost-effective.
Norms and Certifications In Conformity to: IEC/EN 60335-2-29 Battery chargers; EN60950 / UL1950 Electrical safety; EN54-4 Fire Detection and fire alarm systems; 89/336/EEC EMC Directive; 2006/95/EC (Low Voltage); DIN41773 (Charging cycle); Emission : IEC 61000-6-4; Immunity: IEC 61000-6-2. CE.
Climatic Data Ambient temperature (operation) -25 ÷ +70°C
De Rating Ta > 50°C - 2.5%(In) / °C
Ambient temperature Storage -40 ÷ +85°C
Humidity at 25 °C no condensation 95% to 25°C
Cooling Auto convention
General Data Insulation voltage (IN/OUT) 3000 Vac
Insulation voltage (input / ground) 1605 Vac
Insulation voltage (Output / ground) 500 Vac
Protection Class (EN/IEC 60529) IP20
Reliability: MTBF IEC 61709 > 300.000 h
Pollution Degree Environment 2
Connection Terminal Blocks screw Type 2,5mm(24–14AWG)
Protection class (PE Connected) I, with PE
Dimensions (w-h-d) 65x115x135 mm
Weight 0.6 kg approx.
Input Data Nominal Input Voltage Vac 115 – 230 – 277
Voltage range Vac 90 ÷ 305
Inrush Current (Vn – In nom. Load) I2t 11 A 5 msec.
Frequency 47 ÷ 63 Hz
Input Current (115 – 230 Vac) 2.8 – 1.3 A
Internal fuse (not replaceable) 4 A
External Fuse (recommended) MCB curve B 10 A
Output Data (internal power supply) Output Voltage (Vn) / Nominal Current (In) 24 Vdc / 3A
Output Current In 3 A
Efficiency (at 50% of rated current) 90 %
Turn-On delay after applying mains voltage 1 sec. (max)
Start up with Strong Load (capacitive load) Yes, Unlimited
Dissipation power load max (W) 13
Short-circuit protection) Yes
Over Load protection Yes
Over Voltage Output protection Yes (typ. 35 Vdc)
Overheating Thermal protection Yes
Battery Output Boost charge (25 °C) (at In) 28.8 Vdc
Max. time Bust Charge 15 h
Min. time Bust Charge 1 min.
Trickle charge (25 °C) (at In) 27.5 Vdc
Jumper Configuration battery type (V cell) Ni-Cd (optional)
2.23;2,25;2,27;2,3; NiCd:1,5 (20 elem.)
Recovery Charge 2 – 16 Vdc
Charging current max Ibatt 3 A 5%
Charging current limiting Iadj 20 ÷ 100 % / Ibat
Reverse battery protection Yes
Sulfated battery check Yes by Jumper
Detection of element in short circuit Yes
Quiescent Current 5 mA
Charging Curve automatic: IUoUo 3 stage
Remote Input Control (RTCONN cable) Boost /Trickle
Load Output Output voltage (at In) 22 - 28.8 Vdc
Nominal current Iload 1.1 x In A 5%
Continuous current (without battery) Iload= In 3 A
Continuous current ( With battery) Iload= In+ Ibatt 6 A
Max. current Output Load (Main) Iload (4 sec.) 9 A max.
Max. current Output Load (Back Up)Iload (4 sec.) 6 A max.
Push Button or Remote Input Control (RTCONN cable)
Start From Battery Without Main
Time Buffering; min (switch output off without main input)
∞: standard 5 min.: Require SW
Protections against total discharge
19 – 20 Vdc batt
Threshold alarm Battery almost flat
20 – 21 Vdc batt
Signal Output (free switch contacts) Main or Backup Power Yes
Low Battery Yes
Fault Battery Yes
Type of Signal Output Contact Max. Current can be switched (EN60947.4.1): Max. DC1: 30 Vdc 1 A; AC1: 60 Vac 1A Min.1mA at 5 Vdc
Resistive load Min permissive load
Signal Input / Output (RJ45) Temp. Comp. Battery (with external probe) Yes
Remote monitoring display Yes
Can Bus No
CBI243A ALL In One
All specifications are subject to change without notice
No Battery Inside
Final Customer decides type of Battery
For Lead AGM Battery
Output: 24 VDC 1.3 Ah
Protection: Fuse
Connection with screws
Short circuit Protection
IP20
Wall Mount with screws
Din Rail Mount
Feature Battery Bank for DC-UPS “All In One”. Lead AGM, VRLA technology, maintenance-free lead-acid batteries whit serial fuse. Simple connection with screws for Wall mount or DIN rail.
Technical Data Nominal Input Voltage 24 VDC Battery Type for Lead AGM Dimension (WxHxD)
No Battery 43x52x97 mm
Protection Fuse Flat type Mini 25 A Recovery Fuse Flat type Mini 25 A
Charging Data End-of-charge Voltage (trickle charge) 20°C 27.5 VDC End-of-charge Voltage (trickle charge) 30°C 26.8 VDC End-of-charge Voltage (trickle charge) 40°C 26.1 VDC Max. permissible charging current 0.36 A
Discharging Data Battery disconnection from CBI < 19 VDC Max. permissible Discharging current 25 A Self-discharge rate at 20 °C 15% x month
General Data Protection Degree (EN/IEC 60529) IP 20 Protection Class III Connection Terminal Block Screw Type 0.5-16 mm2 (20-6 AWG) Dimension (WxHxD) 67x176x122 mm Weight 1.7 kg DIN Rail Yes Wall mount Yes
Climatic Data Ambient Temperature operation 0 … 40 °C Ambient Temperature Storage 0 … 40 °C Humidity at 25 °C, no condensation 95 %
Norms and certifications The CE mark in According to EMC Directive 2004/108/EC and Low voltage Directive 2006/95/EC.
Electrical Safety In compliance to UL508. According to EN 60950-1/VDE 0805 (SELV) and EN 50178/VDE 0160 (PELV).
Buffering time (min) Battery Size 1.3 Ah 3 Ah 7 Ah 12 Ah
Load 1.5 A 20 60 200 400
Load 3 A 8 30 120 240
Load 5 A 3 15 55 100
Load 7.5 A 2 10 30 60
Load 10 A No 7 20 45
Load 12 A No 3 12 30
Load 15 A No No 9 20
Load 20 A No No 7 13
Electrical Diagram
Drawings
Wall Mount
DIN Rail Mount
Accessory Protection Fuse Flat Type Mini 25 A
BTH 1.2 VRLA Battery Bank
ALWAYS FULL OF ENEHGY