Instrumentation used to perform continuous Fuel / Air trim ... · CCM Benefits • Reduced...

Post on 19-Jul-2020

2 views 0 download

Transcript of Instrumentation used to perform continuous Fuel / Air trim ... · CCM Benefits • Reduced...

Instrumentation used to perform

continuous Fuel / Air trim on coal

fired Power Boilers, and the benefits

of an Online Extractive CO/O2 Grid.

Continuous Combustion Management (CCM) is

measurement and control of parameters previously ignored

that are critical to efficiency and emissions reduction

OFA

IBAM

Pf-FLO

PA SA

O2 and CO

Measurements

Accurate, Continuous, Real Time

Coal Flow and Velocity Measurement

Adjustable Diffusing Coal Valves for Control

to the Burners

Coal Flow Balancing

Coal Mass Flow

Adjustable Valves for Riffles

Individual Burner Airflow - IBAM

IBAM

Individual Burner Airflow Measurement

Secondary Air Measurement

• Wind Tunnel Testing at Air Monitor HQ

Air / Fuel Ratio Control - Dashboard

Optimize Combustion Using CO

Combined CO and O2

Measurement

Why Delta CO ?

DMCC – CO Monitor Is

Designed for Power Plants

Resistant to latent ash

•Probe purge purges the probe and flushes sample line

•Sintered filter at probe head

Multiple (3) stages of

moisture and water vapor separation

Continuously, automatically

zeroes the non-dispersive

infrared analyzer.

Probe Features

Patented “ Extractive Venturi “ Designed to keep

ash out, Sintered Hastelloy filtration makes it last.

PROBE - Venturi Design, and Slip Stream ( Inertia )

effect, reduces ash contact with sintered filter

Separate Sample and Purge Lines, ensures lines and

sintered filter are kept clean.

Multi-Points

in Common

Enclosure

“4-Pack”

Model

Reduce O2

• LOI benefits

• Nox benfits

• Efficiency benefits

0.0%

1.0%

2.0%

3.0%

4.0%

5.0%

6.0%

7.0%

8.0%

9.0%

10.0%

0 1000 2000 3000 4000 5000 6000

Exce

ss O

2 (%

)

Steam Flow (kpph)

Unit 4 O2 Curve

Old Curve

Manual Curve

New Curve

CCM Tuning

CO / O2 Grid on a T-Fired Unit

Locate WHERE CO is being produced

0

500

1000

1500

2000

25001

0:3

0

10

:32

10

:34

10

:36

10

:38

10

:40

10

:42

10

:44

10

:46

10

:48

10

:50

10

:52

10

:54

10

:56

10

:58

11

:00

CO

(P

PM

)

ID FAN EXIT CO NORTHPPMID FAN EXIT CO SOUTHPPMECON CO NORTH A(DELTA)ECON CO NORTH B(DELTA)ECON CO NORTH C(DELTA)ECON CO NORTH D(DELTA)ECON CO SOUTH E(DELTA)ECON CO SOUTH F(DELTA)ECON CO SOUTH G(DELTA)ECON CO SOUTH H(DELTA)Unit MW

Corner E

Corner H

ID Fan Exit

CCM Benefits

• Reduced emissions

• Improved Efficiency

• Reduced (SCR) Ammonia Consumption

• Reduced LOI

• Reduced pulverizer wear

• Reduced wear on Coal Yard equipment.

• Reduced boiler tube & non-pressure part erosion due to lower flue gas velocities. Less Fan required.

• Improved ESP performance due to lower flue gas velocities.

• Reduced potential for slagging and fouling events

• Improved Pressure part life due to improved temperature profile

• Reduced ash disposal costs

• Reduced boiler tube failures due to reducing atmospheres