GFx Series

Post on 30-Nov-2021

25 views 0 download

Transcript of GFx Series

• Locked rotor protector• Phase reversal indication• Remote start / deluge valve start provision• Pressure transducer externally mounted with protective cover• Gland plate• Alarm contacts for remote indication

Electric Fire Pump ControllersMODEL

NUMBER

ACROSS-THE-LINE

FULL

100%

STANDARD

3 WIRE

100%

6 X NORMALLOAD CURRENT

VOLTAGETYPICAL VOLTAGE APPLIED

MOTOR STARTINGINRUSH

CURRENTSTARTINGTORQUEMOTORTYPE

# OF WIRECONNECTIONS

GFA

30% (adjustable) 33% OF NORMAL 33% OF NORMAL

SOFT STARTSOFT STOP

REDUCED

30%

STANDARD

3 WIRE

30% (adjustable)

GFS

WYE-DELTACLOSED

TRANSITION

REDUCED

33%

SPECIAL

6 WIRE

100%

GFW

WYE-DELTAOPEN

TRANSITION

REDUCED

33%

SPECIAL

6 WIRE

100%

GFY

Based on NEMA B type motors.

GFx Serie

s

GFx-BRO-002-SIN/E Rev.1 August 2012 info@tornatech.comtornatech.com

Tornatech Pte Ltd.49B Tuas South Ave 1Tuas Cove Industrial CentreSingapore 637252Tel.: + 65 6795 8114 + 65 6795 7823Fax: + 65 6795 3201

Standard Features• ViZiTouch Light operator interface• IP55 enclosure• Pressure and event recorder• Voltage and amperage display• Run test push button• Emergency start handle• Start and stop pushbuttons

380V - 400V - 415V3 ph / 50 hz5 Kw - 90 Kw 850 x 600 x 250 Consult factory

1200 x 800 x 300 Consult factory

Consult factoryConsult factory

110 Kw - 250 Kw

257 Kw - 315 Kw

GFA - GFY GFS - GFW

HOW TO ORDER: GFx - V / HP / Ph / Hz/ Options Ex.: GFA - 208 / 30HP / 3Ph / 60 Options

ViZiTouch Light operator interface Major features include:• Embedded micro-computer with Linux O/S and software PLC• Touch screen operation with 4.2” color display and intuitive graphics• ARM processor• Expandable storage• Multi-language• Upgradable software• Password protected

Pressure Curves

5m2011.04.2008:39:13

2011. Apr . 20History > Pressure Log Curves 08:44:38EN

2011.04.2008:44:13

0

28

56

84

112

140 PSI

Motor RunJockey Pump Run

Discharge Press.Pressure Curves

Indicators

Cut OutCut In

Pressure Activated

600V

591V

AUTO

2011.Apr.18Home 11:18:49

591V

Auto. Ctrl Automatic Shutdown

15AN2

14.8AN1

15.1AN3

M

EN

PSI803000

12590

Electric Fire Pump Controller

• Remote alarm contacts with removable terminals

• Custom designed emergency start mechanism with integrated limit switch

• USB Port interior

• USB Port exterior

GFx Serie

s

• Externally mounted pressure transducer with protective cover

Events2011 Jul . 22History > Events Log 14:40:10EN

1Date Time Message

2011.07.22 14:18:20 User 9 Logger In2 2011.07.22 15:59:27 Under Voltage OCCURED3 2011.07.22 13:59:27 Under Voltage INACTIVE4 2011.07.22 13:58:21 IO Exp1 Comm Error ACTIVE5 2011.07.22 13:54:25 Alarms Resetted6 2011.07.22 13:54:05 Alt. IS Tripped/Open OCCURED7 2011.07.22 13:54:05 Control Voltage Returned8 2011.07.22 13:54:05 User 9 Logger O�9 2011.07.22 13:54:05 Alarms Resetted

10 2011.07.22 13:54:05 IO Tr.Sw. Comm Error OCCURED291

• Gland plate

• Isolating switch and circuit breaker

• Wye delta contactor set

• GFY model shown

Settings2011. Apr .20Con�g 09:07:33EN

ServiceDone 2011.04.20 +

Next On:= 2011.10.20

PSI

300.0

120.0

100.00

Units

Max. Pres

Cut-Out

Cut-In

Pressure

Automatic Shutdown (m) 10

10

Manual TestDuration Advanced

1

History/Statistics2011. May .06History > All Time Statistics 9:13:13EN

First Power Up

First Start Up

On Time

2011.09.16 08:29:04

2011.09.16 08:29:0446.07.43

• ViZiTouch Light operator interface

PANTONE 82-3-2 CBLACK

Pressure Activated

600V

591V

AUTO

2011.Apr.18Home 11:18:49

591V

Auto. Ctrl Automatic Shutdown

15AN2

14.8AN1

15.1AN3

M

EN

PSI803000

12590

Electric Fire Pump Controller