Post on 18-May-2020
Applied Materials | Hannover Fair 2015
Impedance on Demand
Solid State SSFCL Superconducting SCFCL
Superconducting and Solid-State Electronic
Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions
Dr. Detlev Kirsten & Herbert Piereder
© Applied Materials | Hannover Fair 2015
Contents
The Fault Current Challenge
Fault Current Limiters
Applied Materials
Projects
2
© Applied Materials | Hannover Fair 2015
The Fault Current Challenge
3
Generation Transmission Distribution Customers
New Energy Sources
Renewable Power – Wind, Solar, Biomass
Increased Grid Meshing for Reliability and
Power Quality
Distributed Generation
Increased Load
Transportation - Electric Cars, Trains
Urbanization - Population Growth
Modern Conveniences
More Demanding Operations
Increased Duty Cycles
Disappearing Off-Peak Periods
Aging Infrastructure
Trends in Electricity networks increase Fault Current Levels
© Applied Materials | Hannover Fair 2015
Split
the network
G
Generator Feed Transformer Feed
Bus Coupling
Sensitive Loads
Conventional Fault Current Mitigation
4
Upgrade
Circuit Breakers
Install
Reactors
Install High
ImpedanceTransformers
132kV
33kV
220/380kV
110kV
© Applied Materials | Hannover Fair 2015
G
Generator Feed Transformer Feed
Bus Coupling
Sensitive Loads
Use of Fault Current Limiters
5
FCL Fault Current Limiter
132kV
33kV
220/380kV
110kV
© Applied Materials | Hannover Fair 2015
Desired Characteristics of an Ideal FCL
Increase the impedance on the
line well before the first fault peak
(when the most damage occurs)
In normal operation, it is virtually
"transparent“ (no power or voltage
loss) to the network
Diminish the fault current by at
least a factor of 2 for its duration
Return the source impedance to
its original value when fault is
cleared
Normal Load Current Prospective Fault Current Limited Fault Current
Recovery Fault Normal Operation
Fault Inception
Without FCL (Prospective Fault Current)
Typical current waveforms due to fault
Curr
en
t
Fault C
learing
td (Fault duration time) tr (recovery time)
Fault Current Limiters Reduce Fault Currents Without the Need for Mitigation
6
© Applied Materials | Hannover Fair 2015
Fault Current Limiter Solution Platform
Transmission System FCL
– Superconducting Fault Current Limiter (SCFCL)
– 66 kV to 230 kV transmission voltage levels
Distribution System FCL
– Solid State Fault Current Limiter (SSFCL)
– Up to 66 kV distribution voltage levels
Proprietary Design Features
– FCL units can withstand long duration faults and remain in parallel with shunt for
extended periods.
– Solid-State Devices are protected against known failure modes including
cascading failures due to aging and timing differences.
– Modular design allows FCL components (shunt, FCL unit, instruments,
cryogenics) to be separated to accommodate site conditions.
– Modular design allows easy spares provisioning of field replaceable units.
– SC and SS elements can be upgraded or repurposed as requirements change.
Shunt Reactor, ZSH = RSH + j XSH
SC unit
Superconductor Unit
ZSC = RSC + j XSC
ISH
ISC
Shunt Reactor, ZSH = RSH + j XSH
SS unit
Solid State Unit
ZSS = RSS + j XSS
ISH
ISS
SCFCL
SSFCL
7
© Applied Materials | Hannover Fair 2015
Common Operating Principles
Normal Operation
– Load current flows through FCL unit.
– FCL introduces nearly zero impedance and voltage drop.
– System ( FCL unit, shunt, remaining components) is designed to
handle the maximum load current at all times – even under
contingencies.
Fault Condition
– FCL unit responds to fault current. – Superconducting material
quenches or solid-state path switches; both insert high resistance in
≈ 0.001second.
– Load transfers to high-impedance shunt path that limits fault
current.
Post-Fault
– Recovery is fast and automatic after fault clears.
– SCFCL transitions (recovers) under load in about 3 seconds.
– SSFCL switches in milliseconds (Programmable delay can be
incorporated)
8
Shunt Reactor
FCL Unit
Shunt Reactor
FCL unit
Shunt Reactor
FCL Unit
© Applied Materials | Hannover Fair 2015
Leveraging HV and High Power Expertise
Display Energy and
Environmental
Solutions
Semiconductor Applied Global
Services
The world experts in semiconductor fabrication
9
© Applied Materials | Hannover Fair 2015
The Global Strength of Applied Materials
10
Stock Ticker: Nasdaq: AMAT
Market Cap: $29.6 billion
Fiscal 2014 Revenue: $9.1 billion
Fiscal 2014 R&D: $1.4 billion
Founded: November 10, 1967
Headquarters: Santa Clara, California
Global Presence: 81 locations in
18 countries
Fortune 500 Ranking: 302
RD&E and/or
Manufacturing Centers:
China, Germany, Israel, Italy,
Singapore, Taiwan, United States
Employees*: ~14,000 worldwide
Patents: ~10,500 issued
© Applied Materials | Hannover Fair 2015
Applied Materials FCL Progress
11
2013
Santa Clara 11kV
SCFCL
Central Hudson 13kV SCFCL 15 Faults
AusNet 22kV SSFCL
2014 2015 2016
Thailand 22kV SSFCL
Thailand 115kV SCFCL
US 115kV SCFCL
Ireland 220kV SCFCL
Installed Planned
Contract Signed
Commercial Terms Agreed
Commercial Terms agreed
Commercial Terms
agreed
UK 6kV SSFCL Detailed spec in progress
© Applied Materials | Hannover Fair 2015
SCFCL and SSFCL Extensively Tested
-75
-50
-25
0
25
50
75
100
125
150
175
60 80 100 120 140 160 180 200 220 240
Curr
ent [
kA],
Volta
ge [k
V]
Time [ms]
KEMA Test Trial #46 - 12.5 kV and 56 kA rms (150 kA peak) Prospective Fault Current, limited to 24 kA rms (65 kA
peak), 56 % Current Reduction
Prospective Fault Current [kA] Limited Current[kA]
Superconductor Current [kA] Shunt Current [kA]
Voltage [kV]
Tested for many weeks at full-power at KEMA, Chalfont,
Pennsylvania, USA
“Lifetime” tested for hundreds of bus faults
SCFCL fully qualified against relevant IEEE Standards for 230kV
employment – Demonstrated at over 400kV
SSFCL fully qualified for 45 kV employment – Demonstrated at over
66 kV
Tested to failure to verify reliability and DFMEA Data
Failures are predictable and benign –
Grid remains protected with no cascading or induced secondary
failures
Automatic Recovery under load validated
High-Level DFMEA performed by Core Engineering Team
66 unique failure modes Identified
11 mitigated through design changes
55 mitigated through redundancy
No FCL
With FCL
Under all scenarios power flows and the Grid remains protected
-20
-10
0
10
20
30
40
50
60
70
80
0 10 20 30 40 50 60 70 80 90 100
Curr
ent
[kA
]
Time [ms]
KEMA Trial #32 - SSFCL at 6.35 kV (11 kV system), 26 kA prospective fault current limited to 7.94 kA
(69.5% reduction)
Prospective Fault Current [kA] Limited Fault Current [kA]
No FCL With FCL
12
© Applied Materials | Hannover Fair 2015
SCFCL - 15kV for Silicon Valley Power, CA, US
Normal Operation
– Voltage = 15 kV class
– Load current = 1000A
Fault Current limitation
– 23 kA to 11.5 kA ( at 50%
reduction)
– Or 5 kA to 3.5 kA (at 30%
reduction)
Recovery Under Load (RUL)
– 1 to 3.5 seconds depending on the
fault current level
Installation
– At Applied Materials industrial
substation supplied by Silicon
Valley Power (SVP) – Santa Clara
– Commissioned in July 2013
13
Reactors,
Instrumentation and
other devices under
test
Cryostat –
Superconductor Unit Cryogenics –
Cooling system
© Applied Materials | Hannover Fair 2015
Superconducting Unit
• Neutral to Ground Configuration
• Redundant safety features
Normal Operation
Voltage = 15 kV class
Load current = 400A
Installation
Central Hudson’s Knapps Corner Substation; Poughkeepsie NY
Performance
Limited 15 faults since commissioned June 2014
Refrigeration Units (2)
• N+1 Redundant
• Environmental enclosure
SCFCL - 15kV for Central Hudson, NY, US
14
© Applied Materials | Hannover Fair 2015
SSFCL - 22kV Solution for AusNet, AU
Mitigates Brushfires caused by short-circuited lines
Connected Neutral-to-Ground
Limits 3-8 kA faults to 6, 40, or 70 A Peak (within <1ms)
Fast subsequent reduction to < 2 A
15
© Applied Materials | Hannover Fair 2015 16
SCFCL - 115kV solution for Thailand
2 x 115kV/50%
800A
Gas Insulated
Switchgear
Compact Design
LN2 tank outside
accessible
Interconnects 8th Power Block at
generating site without exceeding fault
current duty
© Applied Materials | Hannover Fair 2015
Summary
Platform of Fault Current Limiting Solutions ranging from 6kV to 230kV
Modular concept with independent designs for
– Power switching functionality (=superconductors or solid state power electronics)
– Current limiting properties (=shunt reactor)
Fast deployment – less outage time
– redeployable
FCLs increase network safety and reliability.
FCLs facilitate meshed network operation and connection of generation.
FCLs sustain network stability and prevent network losses.
FCLs provide impedance when it is needed!
17
18
Contact:
Herbert.Piereder@enovations.co.uk M +31 653 705815
Detlev.Kirsten@accantas.de M +49 170 2309888