Post on 29-May-2018
EMERGENCY GENERATORAND
DATA CENTER HVAC UPGRADES
CAMPUS MAP VICINITY MAP SHEET TITLE INDEX GENERAL PROJECT SCOPE
PROJECT CAMPUS LOCATION
THIS PROJECT ENTAILS MECHANICAL, ELECTRICAL,PLUMBING, AND STRUCTURAL DESIGN INCLUDING CUTTING,PATCHING, AND PAINTING TO PROVIDE FOR A RENOVATEDDATA CENTER OF APPROXIMATELY 2,200 SQ. FLOOR AREAAND NEW EMERGENCY GENERATOR TO SERVE THEADMINISTRATION BUILDING.
1.
2.
4.
DEMOLITION OF EXISTING COOLING UNITS AND INSTALLATIONOF NEW COOLING UNITS TO SERVE THE DATA CENTER ANDASSOCIATED OFFICES.
DEMOLITION AND REMOVAL OF THE EXISTING GASOLINEGENERATOR FROM THE ADMINISTRATION BUILDING ANDINSTALLATION OF NEW EMERGENCY GENERATOR IN THEPARKING LOT AREA NORTH EAST OF THE ADMINISTRATIONBUILDING.
5. INSTALLATION OF NEW EMERGENCY PANELBOARDS ANDAUTOMATIC TRANSFER SWITCHES ASSOCIATED WITH NEWEMERGENCY GENERATOR.
3. ADDITION OF ROOM DIVIDERS AND OPTIMZATION OFCEILING/FLOOR AIR TERMINALS ARRANGEMENT IN DATACENTER TO ENHANCE COOLING PERFORMANCE.
6. NEW CIRCUITING OF ELECTRICAL POWER IN THEADMINISTRATION BUILDING BOARD ROOM.
RIO HONDO COLLEGE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
1 1/2" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
PROJECT COVER SHEET
T001
15-104 T001.DWG
T001.DWG
SM
11/03/15
SM
AH
PF
11/06/2015
PROJECT SHEET INDEX
NUMBER NAME Order
T001 PROJECT COVER SHEET A001
E001 ELECTRICAL GENERAL NOTES AND LEGENDS E001
E002 ELECTRICAL SINGLE LINE DIAGRAM AND SCHEDULES E002
E003 ELECTRICAL PANEL SCHEDULES DATA CENTER E003
E004 ELECTRICAL PANEL SCHEDULES ADMINISTRATIONBLDG.
E004
ED101 ELECTRICAL DEMOLITION FLOOR PLAN - DATACENTER
E051
ED102 ELECTRICAL DEMOLITION FLOOR PLAN -ADMINISTRATION BUILDING
E052
ED202 ELECTRICAL DEMOLITION REFLECTED CEILING PLAN -ADMINISTRATION BUILDING
E062
E100 ELECTRICAL SITE PLAN (FOR REFERENCE ONLY) E100
E101 ELECTRICAL NEW WORK FLOOR PLAN - DATA CENTER E101
E102 ELECTRICAL NEW WORK FLOOR PLAN -ADMINISTRATION BUILDING
E102
E103 ELECTRICAL NEW WORK FLOOR PLAN - NEWGENERATOR LOCATION
E103
E202 ELECTRICAL NEW WORK REFLECTED CEILING PLAN -ADMINISTRATION BUILDING
E202
E501 ELECTRICAL DETAILS E501
E502 ELECTRICAL DETAILS E502
M001 MECHANICAL GENERAL NOTES AND LEGENDS M001
M002 MECHANICAL EQUIPMENT SCHEDULES M002
MD101 MECHANICAL DEMOLITION PLAN - DATA CENTER M051
MD102 MECHANICAL DEMOLITION PLAN - GENERATOR ROOM113C
M052
M100 MECHANICAL SITE PLAN (FOR REFERENCE ONLY) M100
M101 MECHANICAL NEW WORK PLAN - DATA CENTER M101
M501 MECHANICAL DETAILS M501
M502 MECHANICAL DETAILS M502
M503 MECHANICAL DETAILS M503
M601 MECHANICAL CONTROL DIAGRAMS M601
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
S
S
S
24" MAX.
34" MAX.
44" MAX. (FRONT APPROACH) & 46" (SIDE APPROACH)
TOP OF SWITCHES, OUTLETS, & THERMOSTATS
OF OUTLET OR SWITCH15" MIN. BOTTOM
48" MAX. TOP OF
SWITCHES & THERMOSTATS
FINISHED FLOOR
FINISHED FLOOR
OVER OBSTRUCTION
TYPICAL MOUNTING HEIGHT
A
EMERGENCY
EXISTING
EMERGENCY
EXISTING
AFF
<E>
EM
AMPEREAMPERE
LV
WP
CEC
NEC
UNO
AMP OR A
CALIFORNIA ELECTRICAL CODE
ABOVE FINISHED FLOORABOVE FINISHED FLOOR
UNLESS NOTED OTHERWISEUNLESS NOTED OTHERWISE
LOW VOLTAGE
WEATHERPROOF
NATIONAL ELECTRICAL CODE
COPPERCOPPER
GROUNDGROUND
PANELPANEL
TYPICALTYPICAL
LIGHTINGLIGHTING
AIC
CUCU
GFCI
LTGLTG
PNLPNL
TYP.TYP.
GND
WIRE
VOLTS
PULL BOXPULL BOX
W
ATAT
V
AFAF
ASAS
PBPB
NICNIC
UG.
N.C.N.C.
N.O.N.O.
HP
FLAFLA
DPDP
KILOVOLTKILOVOLT
KILOWATTKILOWATT
HVHV
IG
KVKV
Kcmil
KVAKVA
KWKW
AMPERE INTERRUPTING CAPACITYAMPERE INTERRUPTING CAPACITY
UNDER GROUND
AMPERE FRAME/FUSEAMPERE FRAME/FUSE
AMPERE SWITCHAMPERE SWITCH
NORMALLY CLOSED
NOT IN CONTRACTNOT IN CONTRACT
NORMALLY CLOSED
AMPERE TRIPAMPERE TRIP
HORSEPOWER
HIGH VOLTAGE (MEDIUM VOLTAGE)
HORSEPOWER
HIGH VOLTAGE
NORMALLY OPEN
DISTRIBUTION PANEL
FULL LOAD AMPERE
NORMALLY OPEN
DISTRIBUTION PANEL
FULL LOAD AMPERE
GROUND FAULT INTERRUPTERGROUND FAULT INTERRUPTER
THOUSANDS CIRCULAR MILTHOUSANDS CIRCULAR MIL
ISOLATED GROUNDISOLATED GROUND
KILOVOLT AMPEREKILOVOLT AMPERE
MANHOLE
ISC
M.H.
RMS SHORT CIRCUIT CURRENT
MCC MOTOR CONTROL CENTER
PANELBOARD DESIGNATION
1
E-3
FLOOR MOUNTED TRANSFORMER.PROVIDE 6" CONCRETE PAD. (SEE SINGLE LINE DIAGRAM)
T
J
PULL BOXPB
WALL JUNCTION BOX
CEILING JUNCTION BOX
CONDUIT CONCEALED IN WALLS OR ABOVE CEILING
CONDUIT CONCEALED UNDER FLOOR OR BELOW GRADE 3/4" MINIMUM
EMERGENCY LIGHTING FIXTURE
THE SCOPE OF WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, TOOLS AND SERVICESREQUIRED FOR THIS COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS AS INDICATED ANDSPECIFIED.
IN THE EVENT OF A CONFLICT OR INCONSISTENCY BETWEEN ITEMS INDICATED ON THE PLANS AND/ORSPECIFICATIONS OR WITH CODE REQUIREMENTS, THE NOTE SPECIFICATION OR NEC CODE WHICHPRESCRIBES AND ESTABLISHES THE MOST COMPLETE JOB OR THE HIGHER STANDARD SHALL PREVAIL.
THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS, FITTINGS,JUNCTION BOXES, PULL BOXES, AND EXPANSION FITTINGS REQUIRED TO MEET FIELD CONDITIONS.DETERMINE ACTUAL MATERIAL AND HARDWARE REQUIREMENTS AND VERIFY ALL DIMENSIONS BY FIELDINSPECTION.
CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, INSURANCE, EQUIPMENT, INSTALLATION,CONSTRUCTION TOOLS, TRANSPORTATION, ETC. FOR A COMPLETE AND PROPERLY OPERATIONSYSTEM, ENERGIZED THROUGHOUT AND AS INDICATED ON THE DRAWINGS, AS SPECIFIED HEREINAND/OR OTHERWISE REQUIRED.
WHERE WIRE SIZE ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATEDSHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS NOTED OTHERWISE.
BIDDERS SHALL VISIT THE SITE TO VERIFY EXISTING CONDITIONS WHICH CAN AFFECT THE WORK ORCOST THEREOF. FAILURE TO DO SO WILL NOT RELIEVE THE BIDDERS FOR SUCH RESPONSIBILITYFOR ESTIMATING PROPERLY THE DIFFICULTY OR COST OF SUCCESSFULLY PERFORMING THE WORK.
ALL MATERIAL AND EQUIPMENT SHALL BE NEW AND IN PERFECT CONDITION WHEN INSTALLED ANDSHALL BE OF THE BEST GRADE AND OF THE SAME MANUFACTURER THROUGHOUT FOR EACH CLASS ORGROUP OF EQUIPMENT. MATERIALS SHALL BE LISTED AND APPROVED AT UNDERWRITER'S LABORATORYAND SHALL BEAR THE INSPECTION LABEL WHERE SUBJECT TO SUCH APPROVAL.
1.
2.
3.
4.
5.
6.
7.
THE CONTRACTOR SHALL PROVIDE SUPPORT FOR ALL FIXTURES AND ELECTRICAL EQUIPMENT TO COMPLYWITH THE SEISMIC REQUIREMENTS OF THE UNIFORM BUILDING CODE AND ALL LOCAL ORDINANCES.RECESSED FLUORESCENT FIXTURES SHALL BE SUPPORTED DIRECTLY FROM THE FIXTURE HOUSING TO THESTRUCTURE ABOVE WITH A MINIMUM OF (4) #12 WIRES, ONE AT EACH CORNER.
ALL MOUNTING HEIGHTS SHOWN ARE TO CENTER LINE OF OUTLET OR DEVICE AND SHALL APPLYUNLESS INDICATED OTHERWISE.
LOCATION OF LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS. AT OR NEAR DOORS,INSTALL SWITCHES ON SIDE OPPOSITE TO DOOR HINGE. VERIFY FINAL HINGE LOCATIONS INFIELD PRIOR TO ANY WORK.
CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE FINALCONNECTION AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING ELECTRICAL CONNECTION.
DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORKINCLUDED. FOLLOW DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OR OTHER TRADESRELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM ANDMINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES.
NO MORE THAN THREE LIGHTING OR CONVENIENCE OUTLETS CIRCUITS SHALL BE PERMITTED IN ONECONDUIT. PROVIDE SEPARATE CONDUIT FOR EACH HOMERUN INDICATED ON THE DRAWING, UNLESSINDICATED OTHERWISE.
OUTLET BOXES FOR FIXTURES RECESSED IN HUNG CEILING SHALL BE ACCESSIBLE THROUGH OPENINGCREATED BY REMOVAL OF FIXTURES.
LIGHTING, POWER, TELEPHONE AND COMMUNICATIONS OUTLETS SHALL NOT BE PLACED BACK TO BACK. THEOUTLETS SHALL BE SEPARATED MINIMUM OF 18" FOR NON-FIRE RATED WALL AND 24" FOR FIRE RATED WALL.
REFER TO MECHANICAL AND PLUMBING DRAWINGS AND SPECIFICATION FOR ADDITIONAL CONNECTIONREQUIREMENTS TO CONTROL PANELS, CONTROL TRANSFORMERS, 120V FOR CONTROL SYSTEM, TIME CLOCK,RELAYS, DUCK SMOKE DETECTOR LOCATIONS, ETC. INDICATED ON CONTROL WIRING DIAGRAMS. ELECTRICALCONTRACTOR SHALL VERIFY FINAL CONTROL WIRING REQUIREMENTS WITH DIVISION 23 AND 26 CONTRACTORPRIOR TO ANY WORK AND PROVIDE ALL NECESSARY DEVICES AND CONNECTIONS AS REQUIRED.
CONDUIT SHALL NOT BE INSTALLED IN CONCRETE SLAB. ALL CONDUITS WILL BE PLACED IN THEHUNG CEILING UNLESS SPECIFICALLY INDICATED TO BE UNDERGROUND.
WHERE MORE THAN ONE LIGHT SWITCH OCCURS AT SAME LOCATION, SWITCHES SHALL BE MOUNTED IN AMULTIPLE GANG BOX UNDER A SINGLE COVER PLATE. PLATES WITH MORE THAN (3) LIGHT SWITCHES SHALLBE LABELED TO INDICATE THE LIGHT FIXTURES CONTROLLED. SWITCH(ES) CONTROLLING LIGHTS INEMERGENCY CIRCUIT SHALL BE IN A SEPARATE BOX OR GANGED BOXES UNDER THE SAME COVER PLATE ASTHE OTHER SWITCHES.
FURNISH APPROVED EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING EXPANSION JOINTS.
8.
9.
10.
12.
11.
13.
14.
16.
15.
17.
18.
19.
20.
21.
A-1,3
"RUN CONTINUES" INDICATION
HOME RUN TO PANEL "A", CIRCUIT 1,3
THERMOSTAT, +42" TO TOP U.N.O.: FLUSH WALL MOUNTED OUTLET BOX WITH 3/4"C.O. TO ASSOCIATED MECHANICAL EQUIPMENT. REFER TO HVAC DRAWINGS FORLOCATIONS.
T
CLG HUNG EXIT SIGN, DOUBLE SIDED
CLG HUNG EXIT SIGN, SINGLE SIDED
XVAX
LIGHT FIXTURE TAG. FIXTURE POWER CONSUMPTION IS AS INDICATED. SEE LIGHTFIXTURE SCHEDULE.
SINGLE POLE SWITCH +48" A.F.F. TO CENTER
ALL CIRCUIT BREAKERS, FUSES AND ELECTRICAL EQUIPMENT SHALL HAVE AN INTERRUPTING RATING NOLESS THAN THE MAXIMUM SHORT CIRCUIT CURRENT TO WHICH THEY MAY BE SUBJECTED.
PROVIDE TYPE WRITTEN DIRECTORY CARD IN ALL PANELS. IDENTIFY LOAD SERVED BY EACH CIRCUIT BREAKER.
ALL DEVICES INSTALLED OUTSIDE OR IN DAMP LOCATIONS SHALL BE APPROVED WEATHERPROOF. OUTDOORRECEPTACLES SHALL BE GFCI TYPE AND SUITABLE FOR WET LOCATIONS IN A WEATHERPROOF NEMA 3RENCLOSURE.
ALL EQUIPMENT TO BE FURNISHED SHALL BE DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCEWITH THE SEISMIC ZONE IV REQUIREMENTS OF THE CALIFORNIA CODE, TITLE 24, SECTION 2312, AND THEUNIFORM BUILDING CODE. MOUNTING RECOMMENDATION SHALL BE PROVIDED BY THE MANUFACTURER.
DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE DIRECTLY ONEQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.
ALL CONDUIT SHALL BE RUN CONCEALED UNLESS OTHERWISE NOTED.
WIRES AND CABLES SHALL BE FACTORY COLOR CODED BY INTEGRAL PIGMENTATION WITH A SEPARATE COLORFOR EACH PHASE AND NEUTRAL. EACH SYSTEM SHALL BE COLOR CODED AND SHALL BE MAINTAINEDTHROUGHOUT.
FLEXIBLE STEEL CONDUIT SHALL BE GALVANIZED OR CADMIUM-PLATE CONNECTORS OF TWIST-IN-TYPE.FLEXIBLE CONDUIT SHALL ONLY BE USED FOR LIGHT FIXTURE CONNECTION, MOTOR CONNECTION, OR FOREQUIPMENT REQUIRING VIBRATION ISOLATION. MAXIMUM ALLOWED LENGTH OF FLEXIBLE CONDUIT IS 36".REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.
208Y/120VPHASE A = BLACK
PHASE B = REDPHASE C = BLUE
NEUTRAL = WHITESWITCH LEG = PURPLE
EQUIPMENT GROUND = GREENISOLATED GROUND = GREEN W/YELLOW STRIPES
CONVENIENCE OUTLETS SHALL CONSIST OF A DUPLEX CONVENIENCE RECEPTACLE MOUNTED IN ANOUTLET BOX IN THE WALL, FLUSH WITH THE FINISH SURFACE AND SHALL BE COMPLETE BRACESINSTALLED PER PRE-APPROVAL(S) IN ADDITION TO ALL OTHER LOADS. THE STRUCTURAL ENGINEER WITHPLATE.
RECEPTACLES FOR CONVENIENCE OUTLETS, UNLESS OTHERWISE INDICATED, SHALL BE DUPLEX, 3WGROUNDING, 20A, 125 VOLT.
PROVIDE GREEN GROUNDING CONDUCTOR IN EACH RACEWAY INCLUDING CONDUITS, PLUG STRIPS,AND WIREWAY. SIZE OF GROUNDING CONDUCTOR SHALL BE IN ACCORDANCE WITH THE NATIONALELECTRICAL CODE ARTICLE 250.
CONDUITS SHALL BE SUPPLIED AND SUPPORTED PER OSHPD ANCHORAGE PRE-APPROVAL NO. OPA-0120UNISTRUT SEISMIC BRACING SYSTEM OR OPA-0242 POWER-STRUT SEISMIC BRACING SYSTEM OR OPA-0349MASON SEISMIC RESTRAINT GUIDELINES FOR SUSPENDED PIPE. SHOP DRAWINGS OF THE SUPPORTS ANDBRACING SYSTEMS TO BE INSTALLED PER OSHPD PRE-APPROVAL(S) SHALL BE SUBMITTED TO THEARCHITECT OR ENGINEER OF RECORD FOR REVIEW TO VERIFY THAT THE DETAILS ARE IN CONFORMANCEWITH ALL CODE REQUIREMENTS. THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THAT THEBUILDING'S STRUCTURE IS ADEQUATE FOR THE LOADS IMPOSED ON IT BY THE SUPPORTS AND OF RECORDSHALL DESIGN ANY SUPPLEMENT FRAMING THAT IS NEEDED TO RESIST THE LOADS AND/OR MAINTAINSTABILITY.
PROVIDE MINIMUM 3" HIGH CONCRETE HOUSING PAD UNDERNEATH OF EVERY FLOOR MOUNTEDINDOOR ELECTRICAL EQUIPMENT AND 4" HIGH CONCRETE PAD FOR OUTDOOR ELECTRICALEQUIPMENT.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
34.
33.
PIPING, CONDUITS, DUCTWORK, AND MISCELLANEOUS SYSTEM COMPONENTS ARE JUXTAPOSED INVERY CLOSE PROXIMITY TO EACH OTHER. EACH TRADE SHALL PRODUCE SUBMITTAL AND SHOPDRAWINGS CONFORMING ROUTING OF EACH SYSTEM COMPONENT RESPECTIVE TO ITS TRADE ASWELL AS SPACE ALLOCATED TO OTHER TRADES.
CONFLICTS BETWEEN TRADES AND PROPOSED RESOLUTION SHALL BE IDENTIFIED IN SUBMITTALSAND SHOP DRAWINGS.
SUBMIT A SET OF COMPLETE ELECTRICAL "AS-BUILT" DRAWINGS (ON AUTO CAD RELEASE 2015) TO THEENGINEER AT THE COMPLETION OF THE PROJECT, SHOWING ALL CHANGES TO THE WORK PERFORMEDDURING THE CONSTRUCTION PHASE, AND EXACT LOCATIONS OF CONDUITS. ALL DEVIATIONS IN CIRCUITNUMBERS MUST BE RECORDED.
ANY WORK THAT CONFLICTS WITH OTHER TRADES WITHOUT COORDINATION AS DESCRIBED ABOVESHALL BE DEMOLISHED AND PROPERLY RE-INSTALLED.
ATTENTION TO THE DETAIL AND CLOSE COORDINATION BETWEEN MECHANICAL, PLUMBING, ANDELECTRICAL, AND FIRE PROTECTION SHALL BE REQUIRED IN ALL PHASES OF CONSTRUCTION.
PRIOR TO STARTING ANY EXCAVATING OR TRENCHING THE CONTRACTOR SHALL PERFORM ANUNDERGROUND SITE SURVEY UTILIZING AN INDEPENDENT ELECTRONIC LOCATOR SERVICE TO VERIFYEXACT LOCATION OF ALL EXISTING UNDERGROUND PIPING AND CONDUITS.
36.
37.
40.
39.
41.
38.
35.
ORDERING OF MATERIALS, FABRICATION, OR INSTALLATION SHALL NOT TAKE PLACE WITHOUT APPROVEDSUBMITTAL DRAWINGS CONFIRMING DETAILED INSTALLATION ROUTING AND COORDINATION BETWEENTRADES.
SURFACE MOUNTED PANEL +6'-6" TO TOP.
TRANSFORMER (SINGLE LINE DIAGRAM)
MOLDED CASE CIRCUIT BREAKER. AMPACITY AND POLES AS INDICATED.(SINGLE LINE DIAGRAM)
SWITCH AND FUSES, 3 POLE U.N.O. (SINGLE LINE DIAGRAM)
REFER TO DETAIL "1" ON SHEET "E-3".
TBD TO BE DETERMINED
480Y/277VPHASE A = BROWNPHASE B = ORANGEPHASE C = YELLOW
NEUTRAL = NATURAL GRAYSWITCH LEG = PURPLE
EQUIPMENT GROUND = GREENISOLATED GROUND = GREEN W/YELLOW STRIPES
NON-AUTOMATICN.A.
CROSS LINES ON CONDUIT RUNS INDICATE NUMBER OF #12 CURRENTCARRYING CONDUCTORS CONTAINED IN A 3/4"C U.O.N. TWO #12 ANDMINIMUM OF ONE #12 GROUND WIRE ARE INDICATED WHEN CROSS LINESARE NOT SHOWN, NUMERALS ADJACENT TO CROSS LINES ON CONDUITRUNS INDICATE SIZE OF CONDUCTORS IN LIEU OF #12. ALL CONDUITSSHALL CONTAIN ONE GROUND WIRE SIZED PER C.E.C. TABLE 250-95,WITH A MINIMUM SIZE OF #12 AWG.
J
GROUNDING TYPE DUPLEX CONVENIENCE RECEPTACLE FLUSHIN WALL @ +18" A.F.F TO CENTER U.N.O., 20A-120V
ALL ELECTRICAL WORK SHALL CONFORM WITH THE CALIFORNIA ELECTRICAL CODE OR REGULATION(CCR), NATIONAL CODE, AND ALL APPLICABLE LOCAL CODE AND REGULATION.
DOUBLE DUPLEX CONVENIENCE RECEPTACLE FLUSH IN WALL, @+18" A.F.F TO CENTER U.N.O., 20A-120V.
ANY WORK FOUND TO BE IN CONFLICT WITH OTHER TRADES, NOT DETAILED IN COORDINATION PROCESSDESCRIBED ABOVE, SHALL BE DEMOLISHED AND PROPERLY RE-INSTALLED AT NO ADDITIONAL COST TOTHE PROJECT.
CONFLICTS BETWEEN TRADES AND PROPOSED RESOLUTION SHALL BE IDENTIFIED IN SUBMITTALS ANDSHOP DRAWINGS AND SHALL BE RESOLVED BY CONTRACTOR AT NO ADDITIONAL COST TO THE PROJECT.
ORDERING, FABRICATION, OR INSTALLATION OF MATERIALS SHALL NOT TAKE PLACE WITHOUT APPROVEDSUBMITTAL DRAWINGS CONFIRMING DETAILED INSTALLATION ROUTING AND COORDINATION BETWEEN TRADES.
CONTRACTOR SHALL PROVIDE AND INSTALL, AT NO ADDITIONAL COST TO PROJECT, ALL NECESSARYFITTINGS, TRANSITIONS, ELBOWS, AND MATERIALS AS REQUIRED TO AVOID OBSTACLES CREATED BYOTHER TRADES. PIPING, CONDUIT, DUCTWORK AND ASSOCIATED EQUIPMENT ELEVATIONS MAYVARY DUE TO FIELDCONDITIONS.
PIPING, CONDUIT, DUCTWORK AND MISCELLANEOUS SYSTEM COMPONENTS ARE JUXTAPOSED IN VERY CLOSEPROXIMITY TO EACH OTHER. EACH TRADE SHALL PRODUCE SUBMITTAL AND SHOP DRAWINGS CONFIRMING THEROUTING OF EACH SYSTEM AND COMPONENTS RESPECTIVE TO ITS TRADE AS WELL AS SPACE ALLOCATED TOOTHER TRADES. DUCTWORK SHALL BE ROUTED ABOVE PIPING AND PLUMBING LINES U.N.O.
DIVISION 22, 23, AND 26 TRADES SHALL REVIEW AND REFERENCE DRAWINGS AND DOCUMENTS RELATEDTO THESE DIVISIONS AS WELL AS ARCHITECTURAL AND STRUCTURAL DRAWINGS PRIOR TO GENERATIONOF SHOP DRAWINGS AND SUBMITTALS.
THESE PLANS ARE DELIVERED USING A 3D SOFTWARE THAT IS SIGNIFICANTLY DIFFERENT THANFORMER 2D CAD METHODS. THEREFORE IN SOME CASES, SOME MEP ITEMS ARE NOT SHOWN DUE TOPLOTTING PECULARITIES OF THE 3D SOFTWARE AND ITS CAPABILITIES. ROUTING OF MEP SYSTEMSINDICATED ON PLANS ARE SHOWN IN A MANNER TO INDICATE POSSIBLE AND RELATIVE PLACEMENTSOF SYSTEMS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE MEP SYSTEMBASED ON CONSTRUCTION CONDITIONS, AND BASED ON THE INTENT OF THESE PLANS.
5.
7.
6.
4.
2.
3.
1.
DATA OUTLET WITH PORT RJ45 JACK.WALL MOUNTED AT +48". PROVIDE 3/4"CONDUIT TO NEAREST TELECOM ROOM.
OVER OBSTRUCTION DETAILSCALE
NONE 1
ALL PANELBOARDS, SWITCHBOARDS, SWITCHGEAR, AND MOTOR CONTROL CENTERS SHALL HAVE ALL COPPERBUSSING.
42.
PROVIDE ALL CIRCUIT BREAKERS SERVING MULTIWIRE BRANCH CIRCUITS WITH HANDLE TIES SUCH THAT ALLUNGROUNDED CONDUCTORS SHARING A COMMON NEUTRAL ARE SIMULTANIOUSLY DISCONNECTED.
43.
PART 5 - 2013 CALIFORNIA PLUMBING CODE, TITLE 24, C.C.R.
PART 1 - 2013 CALIFORNIA STANDARDS ADMINISTRATIVE CODE, TITLE 24 C.C.R.
PART 3 - 2013 CALIFORNIA ELECTRICAL CODE, TITLE 24, C.C.R.
PART 2 - 2013 CALIFORNIA BUILDING CODE (CBC), TITLE 24, C.C.R. VOLUMES 1,2, AND 2B.
PART 4 - 2013 CALIFORNIA MECHANICAL CODE (CMC). TITLE 24, C.C.R.
PART 9 - 2013 CALIFORNIA FIRE CODE, TITLE 24, C.C.R.
2013 CALIFORNIA BUILDING CODE (FOR SFM) NATIONAL STANDARDS SECTION 3504.1.3.
PART 12 - 2013 CALIFORNIA REFERENCE STANDARDS CODE, TITLE 24, C.C.R.
PARTIAL LIST OF APPLICABLE NFPA STANDARDS:
NFPA 72 - (CALIFORNIA AMENDED) NATIONAL FIRE ALARM CODES, 2013 EDITION
NFPA 14 - STANDPIPE SYSTEMS, 2013 EDITIONNFPA 17A - WET CHEMICAL SYSTEMS, 2012 EDITIONNFPA 24 - PRIVATE FIRE MAINS, 2013 EDITION
NFPA 13 - AUTOMATIC SPRINKLER SYSTEMS, 2013 EDITION
NON-FUSED DISCONNECT SAFETY SWTICH.SWITCH PHASE AND AMPACITY AS REQUIRED.WALL/EQUIPMENT SURFACE MOUNTED +6'-0" TOP OF SWITCH.
FUSED DISCONNECT SAFETY SWITCH.SWITCH AMPACITY AS REQUIRED FUSE AMPACITY PER EQUIPMENT NAMEPLAT REQ.WALL/EQUIPMENT SURFACE MOUNTED +6'-0" TOP OF SWITCH.
F
MEP COMPONENT ANCHORAGE NOTE
ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PERTHE DETAILS ON THE CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWINGCOMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENT REQUIREMENTSPRESCRIBED IN THE 2013 CBC. SECTIONS 1615A.1.12 THROUGH 1645A.1.22 AND ASCE 7-05 CHAPTER 6 AND13.
1. ALL PERMANENT EQUIPMENT AND COMPONENTS.2. TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARD WIRED)TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER.3. MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS ANDHEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARYATTACHMENTS.
THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTS SHALL BE POSITIVELYATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THE PLANS. THESE COMPONENTS SHALLHAVE FLEXIBLE CONNECTIONS PROVIDED BETWEEN THE COMPONENT AND ASSOCIATED DUCTWORK,PIPING, AND CONDUIT.
A. COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASS LOCATED 4FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLY SUPPORT THECOMPONENT.B. COMPONENTS WEIGHING LESS THAN 20 POUNDS OR IN THE CASE OF DISTRIBUTED SYSTEMSLESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF OR FLOOR OR HUNGFROM A WALL.
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THE INSTALLATIONSHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER OR RECORD AND THE DSA DISTRICTSTRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILL VERIFY THAT ALL COMPONENTS AND EQUIPMENTHAVE BEEN ANCHORED IN ACCORDANCE WITH ABOVE REQUIREMENTS.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTE
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THEFORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-05 SECTION 13.3 AS DEFINED IN ASCE 7-05 SECTION13.6.8, 13.6.7, 13.6.5.5, AND 2010 CBC. SECTIONS 1615A.120, 1615A.1.21, AND 1615A.1.22.
THE BRACING AND ATTACHMENTS TO THE STRUCTURE SHALL BE DETAILED ON THE APPROVED DRAWINGSOR THEY SHALL COMPLY WITH ONE OF THE OSHPD PRE-APPROVALS (OPA #) AS MODIFIED TO SATISFYANCHORAGE REQUIREMENTS OF ACI 318 APPENDIX D
COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING ANDBRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEMS.
THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO SUPPORTTHE HANGER AND BRACE LOADS.
2013 CGBC
NOTE: NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT
ALL ITEMS AFFECTED BY DEMOLITION SHALL BE REMOVED UNDAMAGED, AND MADEAVAILABLE TO THE OWNER FOR FIRST RIGHT OF SALVAGE. ANY SUCH ITEMS REFUSED BYOWNER SHALL BE PROPERLY DISPOSED OF BY CONTRACTOR OFF SITE.
CUTTING OR NOTCHING OF STRUCTURAL MEMBERS INCLUDING BEARING/ SHEAR WALLS NOTSPECIFICALLY DETAILED ON STRUCTURAL DRAWINGS, MUST BE APPROVED BY STRUCTURALENGINEER OF RECORD AND AUTHORITIES HAVING JURISDICTION.
PERFORM CUTTING, PATCHING, AND REFINISHING OF THE EXISTING BUILDING SURFACES ANDMATERIALS REQUIRED OT PERFORM THE WORK INDICATED IN THE DRAWINGS ANDSPECIFICATIONS. SUCH AREAS AFFECTED BY THIS WORK SHALL BE REFURBISHED TO AS-NEW CONDITION AND MATCH SURROUNDING SURFACE FINISH IN COLOR, TEXTURE, ANDAPPEARANCE.
1.
2.
3.
ELECTRICAL SHEET INDEXABBREVIATIONSMEP COORDINATION NOTESELECTRICAL LEGENDGENERAL NOTES
CODES AND STANDARDS
ANCHORAGE NOTES
DEMOLITION NOTES
600A
3P
2DUPLEX SWITCH +48" A.F.F. TO CENTER
GROUNDING BUS BAR.
AREA NOT IN CONTRACT.N.I.C.
UC UNDERGROUND CONDUIT
44. ALL CONDUCTORS, PANEL BUS BARS, AND TRANSFORMER COILS SHALL BE COPPER UNLESS NOTEDOTHERWISE.
45. ALL CONDUIT INSTALLED AS A PART OF THIS PROJECT SHALL BE RIGID METALLIC CONDUIT (RMC). RMCWIRING SHALL COMPLY WITH AND SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THENATIONAL ELECTRIC CODE.
DDIMMER SWITCH +48" A.F.F. TO CENTER
EXISTINGNEW<N>
GROUNDING TYPE SIMPLEX RECEPTACLE FLUSH IN WALL.
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
N.T.S.
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL GENERAL NOTESAND LEGENDS
E001
15-104 E001.DWG
E001.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
ELECTRICAL SHEET INDEX
NUMBER NAME ORDER
E001 ELECTRICAL GENERAL NOTES AND LEGENDS E001
E002 ELECTRICAL SINGLE LINE DIAGRAM ANDSCHEDULES
E002
E003 ELECTRICAL PANEL SCHEDULES DATACENTER
E003
E004 ELECTRICAL PANEL SCHEDULESADMINISTRATION BLDG.
E004
ED101 ELECTRICAL DEMOLITION FLOOR PLAN -DATA CENTER
E051
ED102 ELECTRICAL DEMOLITION FLOOR PLAN -ADMINISTRATION BUILDING
E052
ED202 ELECTRICAL DEMOLITION REFLECTEDCEILING PLAN - ADMINISTRATION BUILDING
E062
E100 ELECTRICAL SITE PLAN (FOR REFERENCEONLY)
E100
E101 ELECTRICAL NEW WORK FLOOR PLAN - DATACENTER
E101
E102 ELECTRICAL NEW WORK FLOOR PLAN -ADMINISTRATION BUILDING
E102
E103 ELECTRICAL NEW WORK FLOOR PLAN - NEWGENERATOR LOCATION
E103
E202 ELECTRICAL NEW WORK REFLECTEDCEILING PLAN - ADMINISTRATION BUILDING
E202
E501 ELECTRICAL DETAILS E501
E502 ELECTRICAL DETAILS E502
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
G
<E> DISTRIBUTION BOARD DR1500 A 480/277 V 3P 4W
<N> STANDBY GENERATOR125 kVA 100 kW480/277 V 3P 4W
500 A
3P
<E> INCOMING POWER UTILITY SERVICE500 A 480/277 V 3P 4W
225 A 3P
F225
120 V POWERCOMMAND 1.1WITHIN <N> GENERATOR
F175
1
175 A
3P
EXISTING
N E<N>
ATS-1EHL/1ELL125 A
1EHL
100 A
1ELL
100 A
LIFE SAFETY
125 A
3P
125 A
3P
40 A
3P
F40
F40
F40
F30
N E<N>
ATS-AHU-170 A
AIRHANDLER
UNIT
70 A
3P
70 A
3P
F30
F30
F30
50 A 3P FUSE DISCONNECTTO AHU-1 IN
MECHANICAL ROOM
F
1NHL1ELP
N E<N>ATS-1ELP/1NHL
150 A
100 A250 A
IT UPS&
RECEPTACLES
150 A
3P
F60
150 A
3P
75 kVA TRANSFORMER<N> 1ELP TRANSFORMER480 V- 120/208V, 60 Hz, 3P
F60
F175
250 A
3P40 A
3P
150 kVA TRANSFORMER<E> AP TRANSFORMER
480 V- 120/208V, 60 Hz, 3P
<E> PANELBOARD AP600 A 120/208V 3P 4W
30 A
1P
EXISTING
F175
1
30 kVA TRANSFORMER<N> 1ELL TRANSFORMER480 V- 120/208V, 60 Hz, 3P
80 A
3P
F60
120 V POWERCOMMAND 1.1IN EMERGENCGY POWER
DISTRIBUTION ROOM
FIRST FLOOR ELECTRICAL ROOM A123
F175
STAFF PARKING LOT F
EMERGENCY POWER DISTRIBUTION ROOM A113C
# _ _ _
### A
LEVEL (1 = FIRST FLOOR, 2 = SECOND FLOOR)
VOLTAGE (H = 480/277, L = 120/208)
LOAD TYPEL = LIGHTING LOADSM = HVAC LOADSP = PLUG LOADS
POWER CLASSIFICATION (E = EMERGENCY, N = NORMAL)
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL SINGLE LINEDIAGRAM AND SCHEDULES
E002
15-104 E002.DWG
E002.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
N.T.S.1
FEEDER SCHEDULE
N.T.S.2
ADMIN BUILDING SINGLE LINE DIAGRAM
FEEDER SCHEDULE - COPPER CONDUCTORS THHW 600V (AWG)
FEEDERTYPE
CONDUITQTY
CONDUITSIZE (IN)
FEEDERQTY
FEEDERSIZE
FEEDERGND
RATEDAMP IN
CONDUIT
F30 1 3/4" 4 #10 #10 128
F40 1 1" 4 #8 #10 176
F50 1 1-1/2" 4 #6 #10 240
F60 1 1-1/2" 4 #4 #10 304
F80 1 1-1/2" 4 #2 #8 416
F125 1 2" 4 #1/0 #6 544
F150 1 2" 4 #1/0 #6 544
F175 1 2" 4 #2/0 #6 624
F200 1 2-1/2" 4 #3/0 #6 720
F225 1 2-1/2" 4 #4/0 #4/0 832
F250 1 3" 4 250 MCM #4 928
F300 1 3" 4 350 MCM #4 1024
F350 1 3-1/2" 4 500 MCM #3 1376
F400 1 3-1/2" 4 500 MCM #3 1376
F450 2 2-1/2" 4 #4/0 #2 1665
F500 2 3" 4 250 MCM #2 1856
F600 2 3" 4 350 MCM #1 2240
F800 2 3-1/2" 4 500 MCM #1/0 2752
F1000 4 3" 4 250 MCM #2/0 5504
F1200 3 4" 4 600 MCM #3/0 4560
F1600 4 4" 4 600 MCM #4/0 6080
GENERATOR SCHEDULE
MARK
MFR MODELCAPACITY
(KVA)CAPACITY
(KW) VOLTAGE FUELFUEL CONSUMPTION
(AT FULL LOAD) remarks
GDA 1 CUMMINS DSGAA 125 100 480/277V Y DIESEL 8.87 GPH PROVIDE WITH LEVEL 2 SOUND ENCLOSURE AND 225 A CIRCUITBREAKER OPTION.
1/8" = 1'-0"3
PANEL LEGEND
A
LB ART
TRANSFERED CIRCUITS SHALL NOT BE REUTILIZED ON <E>PANELS AND SHALL BE BLOCKED OFF FROM <E> BREAKERS.SPARE PLATE SHALL BE INSTALLED TO CIRCUIT BREAKERSWITH THE LAMENATED AFFIXED LABEL: "DO NOT USE ORCONNECT".
1
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL PANELSCHEDULES DATA CENTER
E003
15-104 E003.DWG
E003.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
TOTAL (AMPS) 2 A
TOTAL (VA) 693 VA
Motor - Largest 75 VA X 125.00% = 93 VA
Receptacle 120 VA X 100.00% = 120 VA
L.C.L. 0 VA X 0.00% = 0 VA
N.C.L. 480 VA X 100.00% = 480 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 115 VA
φB 200 VA
φA 360 VA
Space -- 47 0 VA 0 VA 48 -- Space
Space -- 45 0 VA 0 VA 46 -- Space
Space -- 43 0 VA 0 VA 44 -- Space
Space -- 41 0 VA 0 VA 42 -- Space
Space -- 39 0 VA 0 VA 40 -- Space
Space -- 37 0 VA 0 VA 38 -- Space
Space -- 35 0 VA 0 VA 36 -- Space
Space -- 33 0 VA 0 VA 34 -- Space
Space -- 31 0 VA 0 VA 32 -- Space
Space -- 29 0 VA 0 VA 30 -- Space
Space -- 27 0 VA 0 VA 28 -- Space
Space -- 25 0 VA 0 VA 26 -- Space
- -- 23 0 VA 0 VA 24 -- EXISTING LOAD
PORTABLE AC -- 21 0 VA 0 VA 22 -- EXISTING LOAD
EXISTING LOAD -- 19 0 VA 0 VA 20 -- EXISTING LOAD
- -- 17 0 VA 0 VA 18 -- EXISTING LOAD
UPS -- 15 0 VA 75 VA 16 20 A/1 SF-1
Space -- 13 0 VA 115 VA 14 -- --
Space -- 11 0 VA 115 VA 12 20 A/2 MCU-2
Space -- 9 0 VA 125 VA 10 -- --
OTHER 20 A/1 7 120 VA 125 VA 8 20 A/2 MCU-1
ALAN -- 5 0 VA 0 VA 6 -- Spare
MARK -- 3 0 VA 0 VA 4 -- LIGHTS
MTG OFFICE -- 1 0 VA 0 VA 2 -- HEATHER
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 100 A
MAIN BREAKER: 80 A MOUNTING: SurfacePANEL: PANEL #1
LOCATION: COMPUTER CENTER 10 VOLTAGE: 120/208
TOTAL (AMPS) 46 A
TOTAL (VA) 38010 VA
Motor - Largest 0 VA X 0.00% = 0 VA
Receptacle 0 VA X 0.00% = 0 VA
L.C.L. 0 VA X 0.00% = 0 VA
N.C.L. 38010 VA X 100.00% = 38010 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 12670 VA
φB 12670 VA
φA 12670 VA
Spare -- 47 0 VA 0 VA 48 -- Spare
Spare -- 45 0 VA 0 VA 46 -- Spare
Spare -- 43 0 VA 0 VA 44 -- Spare
Spare -- 41 0 VA 0 VA 42 -- Spare
Spare -- 39 0 VA 0 VA 40 -- Spare
Spare -- 37 0 VA 0 VA 38 -- Spare
Spare -- 35 0 VA 0 VA 36 -- Spare
Spare -- 33 0 VA 0 VA 34 -- Spare
Spare -- 31 0 VA 0 VA 32 -- Spare
Spare -- 29 0 VA 0 VA 30 -- Spare
Spare -- 27 0 VA 0 VA 28 -- Spare
Spare -- 25 0 VA 0 VA 26 -- Spare
Spare -- 23 0 VA 0 VA 24 -- Spare
Spare -- 21 0 VA 0 VA 22 -- Spare
Spare -- 19 0 VA 0 VA 20 -- Spare
-- -- 17 4129 VA 0 VA 18 -- Spare
-- -- 15 4129 VA 0 VA 16 -- Spare
CAC-2 20 A/3 13 4129 VA 0 VA 14 -- Spare
-- -- 11 388 VA 4129 VA 12 -- --
-- -- 9 388 VA 4129 VA 10 -- --
CCU-2 20 A/3 7 388 VA 4129 VA 8 20 A/3 CAC-1
-- -- 5 3636 VA 388 VA 6 -- --
-- -- 3 3636 VA 388 VA 4 -- --
VCU-1 20 A/3 1 3636 VA 388 VA 2 20 A/3 CCU-1
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 500 A
MAIN BREAKER: 200 A MOUNTING: SurfacePANEL: KILN/DOCK CONTROL PANEL
LOCATION: KILN 3 VOLTAGE: 277/480V 3Ø, 4W
15 A/3 15 A/3
25 A/3
25 A/3
EXISTING TO REMAIN EXISTING TO REMAIN
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL PANELSCHEDULES ADMINISTRATION
BLDG.
E004
15-104 E004.DWG
E004.DWG
SM
12/28/15
SM
PF
PF
11/06/2015
TOTAL (AMPS) 5 A
TOTAL (VA) 1660 VA
Motor - Largest 0 VA X 0.00% = 0 VA
Receptacle 0 VA X 0.00% = 0 VA
L.C.L. 0 VA X 0.00% = 0 VA
N.C.L. 0 VA X 0.00% = 0 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 0 VA
φB 700 VA
φA 960 VA
Spare -- 47 0 VA 0 VA 48 -- Spare
Spare -- 45 0 VA 0 VA 46 -- Spare
Spare -- 43 0 VA 0 VA 44 -- Spare
Spare -- 41 0 VA 0 VA 42 -- Spare
Spare -- 39 0 VA 0 VA 40 -- Spare
Spare -- 37 0 VA 0 VA 38 -- Spare
Spare -- 35 0 VA 0 VA 36 -- Spare
Spare -- 33 0 VA 0 VA 34 -- Spare
Spare -- 31 0 VA 0 VA 32 -- Spare
Spare -- 29 0 VA 0 VA 30 -- Spare
Spare -- 27 0 VA 0 VA 28 -- Spare
Spare -- 25 0 VA 0 VA 26 -- Spare
Spare -- 23 0 VA 0 VA 24 -- Spare
Spare -- 21 0 VA 0 VA 22 -- Spare
Spare -- 19 0 VA 0 VA 20 -- Spare
Spare -- 17 0 VA 0 VA 18 -- Spare
Spare -- 15 0 VA 0 VA 16 -- Spare
Spare -- 13 0 VA 0 VA 14 -- Spare
Spare -- 11 0 VA 0 VA 12 -- Spare
Spare -- 9 0 VA 0 VA 10 -- Spare
Spare -- 7 0 VA 0 VA 8 -- Spare
Spare -- 5 0 VA 0 VA 6 -- Spare
LIGHTING - LOBBY 20 A/1 3 300 VA 400 VA 4 20 A/1 LIGHTING - LOBBY...
LIGHTING - BOARD... 20 A/1 1 480 VA 480 VA 2 20 A/1 LIGHTING - BOARD...
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 100 A
MAIN BREAKER: 80 A MOUNTING: SurfacePANEL: 1ELL
LOCATION: EMERGENCY POWER... VOLTAGE: 120/208
TOTAL (AMPS) 21 A
TOTAL (VA) 7500 VA
Motor - Largest 0 VA X 0.00% = 0 VA
Receptacle 5500 VA X 100.00% = 5500 VA
L.C.L. 0 VA X 0.00% = 0 VA
N.C.L. 0 VA X 0.00% = 0 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 4000 VA
φB 4000 VA
φA 6500 VA
Spare -- 47 0 VA 0 VA 48 -- Spare
Spare -- 45 0 VA 0 VA 46 -- Spare
Spare -- 43 0 VA 0 VA 44 -- Spare
Spare -- 41 0 VA 0 VA 42 -- Spare
Spare -- 39 0 VA 0 VA 40 -- Spare
Spare -- 37 0 VA 0 VA 38 -- Spare
Spare -- 35 0 VA 0 VA 36 -- Spare
Spare -- 33 0 VA 0 VA 34 -- Spare
Spare -- 31 0 VA 0 VA 32 -- Spare
Spare -- 29 0 VA 0 VA 30 -- Spare
Spare -- 27 0 VA 0 VA 28 -- Spare
Spare -- 25 0 VA 0 VA 26 -- Spare
Spare -- 23 0 VA 0 VA 24 -- Spare
Spare -- 21 0 VA 0 VA 22 -- Spare
Spare -- 19 0 VA 0 VA 20 -- Spare
Spare -- 17 0 VA 0 VA 18 -- Spare
Spare -- 15 0 VA 0 VA 16 -- Spare
Spare -- 13 0 VA 2000 VA 14 -- --
RECEPTACLE 20 A/1 11 500 VA 2000 VA 12 25 A/2 EATON UPS
RECEPTACLE 20 A/1 9 1000 VA 1500 VA 10 -- --
RECEPTACLE 20 A/1 7 1000 VA 1500 VA 8 20 A/2 APC UPS
RECEPTACLE 20 A/1 5 1000 VA 500 VA 6 20 A/1 RECEPTACLE
RECEPTACLE 20 A/1 3 1000 VA 500 VA 4 20 A/1 RECEPTACLE
RECEPTACLE 20 A/1 1 1000 VA 1000 VA 2 20 A/1 RECEPTACLE
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 250 A
MAIN BREAKER: 250 A MOUNTING: SurfacePANEL: 1ELP
LOCATION: EMERGENCY POWER... VOLTAGE: 120/208
TOTAL (AMPS) 3 A
TOTAL (VA) 2783 VA
Motor - Largest 0 VA X 0.00% = 0 VA
Receptacle 0 VA X 0.00% = 0 VA
L.C.L. 2226 VA X 125.00% = 2783 VA
N.C.L. 0 VA X 0.00% = 0 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 422 VA
φB 388 VA
φA 1416 VA
Spare -- 47 0 VA 0 VA 48 -- Spare
Spare -- 45 0 VA 0 VA 46 -- Spare
Spare -- 43 0 VA 0 VA 44 -- Spare
Spare -- 41 0 VA 0 VA 42 -- Spare
Spare -- 39 0 VA 0 VA 40 -- Spare
Spare -- 37 0 VA 0 VA 38 -- Spare
Spare -- 35 0 VA 0 VA 36 -- Spare
Spare -- 33 0 VA 0 VA 34 -- Spare
Spare -- 31 0 VA 0 VA 32 -- Spare
Spare -- 29 0 VA 0 VA 30 -- Spare
Spare -- 27 0 VA 0 VA 28 -- Spare
Spare -- 25 0 VA 0 VA 26 -- Spare
Spare -- 23 0 VA 0 VA 24 -- Spare
Spare -- 21 0 VA 0 VA 22 -- Spare
Spare -- 19 0 VA 0 VA 20 -- Spare
Spare -- 17 0 VA 0 VA 18 -- Spare
Spare -- 15 0 VA 0 VA 16 -- Spare
Spare -- 13 0 VA 0 VA 14 -- Spare
Spare -- 11 0 VA 0 VA 12 -- Spare
LIGHTING -... 20 A/1 9 228 VA 40 VA 10 20 A/1 EXIT SIGN - LOBBY
EXIT SIGNS -... 20 A/1 7 120 VA 116 VA 8 20 A/1 LIGHTING -...
LIGHTING -... 20 A/1 5 190 VA 232 VA 6 20 A/1 LIGHTING -...
LIGHTING - BOARD... 20 A/1 3 40 VA 80 VA 4 20 A/1 EXIT SIGNS - BOAR...
LIGHTING - BOARD... 20 A/1 1 1140 VA 40 VA 2 20 A/1 LIGHTING - BOARD...
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 80 A
MAIN BREAKER: 40 A MOUNTING: SurfacePANEL: 1EHL
LOCATION: EMERGENCY POWER... VOLTAGE: 277/480V 3Ø, 4W
TOTAL (AMPS) 3 A
TOTAL (VA) 2383 VA
Motor - Largest 0 VA X 0.00% = 0 VA
Receptacle 0 VA X 0.00% = 0 VA
L.C.L. 1906 VA X 125.00% = 2383 VA
N.C.L. 0 VA X 0.00% = 0 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 228 VA
φB 348 VA
φA 1330 VA
Space -- 47 0 VA 0 VA 48 -- Space
Space -- 45 0 VA 0 VA 46 -- Space
Space -- 43 0 VA 0 VA 44 -- Space
Space -- 41 0 VA 0 VA 42 -- Space
Space -- 39 0 VA 0 VA 40 -- Space
Space -- 37 0 VA 0 VA 38 -- Space
Space -- 35 0 VA 0 VA 36 -- Space
Space -- 33 0 VA 0 VA 34 -- Space
Space -- 31 0 VA 0 VA 32 -- Space
Space -- 29 0 VA 0 VA 30 -- Space
Space -- 27 0 VA 0 VA 28 -- Space
Space -- 25 0 VA 0 VA 26 -- Space
Space -- 23 0 VA 0 VA 24 -- Space
Space -- 21 0 VA 0 VA 22 -- Space
Space -- 19 0 VA 0 VA 20 -- Space
Space -- 17 0 VA 0 VA 18 -- Space
Space -- 15 0 VA 0 VA 16 -- Space
Space -- 13 0 VA 0 VA 14 -- Space
Space -- 11 0 VA 0 VA 12 -- Space
Space -- 9 0 VA 0 VA 10 -- Space
Space -- 7 0 VA 0 VA 8 -- Space
LIGHTING -... 20 A/1 5 228 VA 0 VA 6 -- Space
LIGHTING -... 20 A/1 3 232 VA 116 VA 4 20 A/1 LIGHTING -...
LIGHTING - BOARD... 20 A/1 1 1140 VA 190 VA 2 20 A/1 LIGHTING -...
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 100 A
MAIN BREAKER: 40 A MOUNTING: SurfacePANEL: 1NHL
LOCATION: EMERGENCY POWER... VOLTAGE: 277/480V 3Ø, 4W
TOTAL (AMPS) 38 A
TOTAL (VA) 31811 VA
Motor - Largest 13989 VA X 125.00% = 17486 VA
Receptacle 5500 VA X 100.00% = 5500 VA
L.C.L. 4132 VA X 125.00% = 5165 VA
N.C.L. 0 VA X 0.00% = 0 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 8913 VA
φB 9856 VA
φA 19959 VA
-- -- 29 4022 VA 0 VA 30 -- --
-- -- 27 4845 VA 0 VA 28 -- --
<N> ATS-1EHL/1ELL 125 A/3 25 7731 VA 0 VA 26 -- SPACE
-- -- 23 0 VA 4663 VA 24 -- --
-- -- 21 0 VA 4663 VA 22 -- --
EXISTING LOAD -... -- 19 0 VA 4663 VA 20 70 A/3 <N> ATS-AHU
-- -- 17 228 VA 0 VA 18 -- --
-- -- 15 348 VA 0 VA 16 -- --
<N> ATS-1ELP/1NHL 150 A/3 13 1330 VA 0 VA 14 -- EXISTING LOAD -...
-- -- 11 0 VA 0 VA 12 -- --
-- -- 9 0 VA 0 VA 10 -- --
PANEL AP 175 A/3 7 6235 VA 0 VA 8 -- EXISTING LOAD -...
-- -- 5 0 VA 0 VA 6 -- --
-- -- 3 0 VA 0 VA 4 -- --
EXISTING LOAD -... -- 1 0 VA 0 VA 2 -- EXISTING LOAD -...
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 500 A
MAIN BREAKER: 500 A MOUNTING: SurfacePANEL: DR1
LOCATION: ELEC. 123 VOLTAGE: 277/480V 3Ø, 4W
TOTAL (AMPS) 0 A
TOTAL (VA) 0 VA
Motor - Largest 0 VA X 0.00% = 0 VA
Receptacle 0 VA X 0.00% = 0 VA
L.C.L. 0 VA X 0.00% = 0 VA
N.C.L. 0 VA X 0.00% = 0 VA
LOAD CLASSIFICATION CONNECTED (VA) X DEMAND FACTOR = DEMAND (VA)
φC 0 VA
φB 0 VA
φA 6235 VA
-- -- 29 0 VA 0 VA 30 -- --
-- -- 27 0 VA 0 VA 28 -- --
EXISTING LOAD -... -- 25 0 VA 0 VA 26 -- EXISTING LOAD -...
-- -- 23 0 VA 0 VA 24 -- --
-- -- 21 0 VA 0 VA 22 -- --
SPACE -- 19 0 VA 0 VA 20 -- EXISTING LOAD -...
SPACE -- 17 0 VA 0 VA 18 -- --
SPACE -- 15 0 VA 0 VA 16 -- --
GDA-1 30 A/1 13 6235 VA 0 VA 14 -- SPACE
-- -- 11 0 VA 0 VA 12 -- --
-- -- 9 0 VA 0 VA 10 -- --
EXISTING LOAD -... -- 7 0 VA 0 VA 8 -- EXISTING LOAD -...
-- -- 5 0 VA 0 VA 6 -- --
-- -- 3 0 VA 0 VA 4 -- --
EXISTING LOAD -... -- 1 0 VA 0 VA 2 -- EXISTING LOAD -...
LOCATION LTG REC MIS BKR CKT A B C A B C CKT BKR MIS REC LTG LOCATION
PANEL AND DEVICE MINIMUM AIC RATING: BUS RATING: 600 A
MAIN BREAKER: 175 A MOUNTING: SurfacePANEL: AP
LOCATION: ELEC. 123 VOLTAGE: 120/208
EXISTING TO REMAIN EXISTING TO REMAIN
NEWNEW
NEW NEW
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
DN
KILN
3
STORAGE
4
COMPUTERCENTER
10
OFFICE
1
OFFICE
2
OFFICE
3
IT #1
IT #2 PANEL #1
RACK 1
RACK 2
SERVER 7
IT #3
FIBER PANEL#1
B-1
BUSINESSCHW/HW
B-3
CABINET B
PANEL #2
FIBER PANEL#4
FIBER PANEL#3
SERVER 1
SERVER 2
SERVER 3
SERVER 4
SERVER 5
SERVER 6
SERVER 8
RACK 3
KILN/DOCKCONTROL
PANEL
<E> SOFFITT
<E> SOFFITT
N.I.C.
2
KILNTRANSFORMER
2
KILNTRANSFORMER
1
ELECTRICKILN 1
ELECTRICKILN 2
1
1
1
1
1
1
<E> AC UNITSUSPENDED INLOADING DOCK
1
<E> AC UNITSUSPENDED INLOADING DOCK
<E> CONDENSERUNIT SUSPENDED INLOADING DOCK
<E> WALL MOUNTEDFAN COIL UNIT
<E> COMPUTERROOM AIR
CONDITIONING UNIT
<E> DUCTED AIRCONDITIONING UNIT
<E> AC UNIT INCEILING SPACE
<E> SERVERS
HALF-WALL AREA
9
GAS KILN 1 GAS KILN 2
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/4" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL DEMOLITIONFLOOR PLAN - DATA CENTER
ED101
15-104 ED101.DWG
ED101.DWG
SM
11/19/15
SM
PF
PF
11/06/2015
1/4" = 1'-0"1
ELECTRICAL DEMOLITION PLAN - DATACENTER
1 REMOVE <E> MECHANICAL EQUIPMENT INCLUDING ALL CONDUCTORSAND CONDUITS BACK TO SOURCE.
1. HATCHED PATTERN INDICATES ITEMS TO BE DEMOLISHED.
2 REMOVE (2) <E> SERVERS SHOWN INCLUDING ALL CONDUCTORS ANDCONDUITS BACK TO SOURCE.
A
LB ART
2. CAMPUS SHALL HAVE FIRST RIGHT OF REFUSAL OF ALLEQUIPMENT REMOVED AND DEMOLISHED.
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
D
B
B
C
C
D
D
E
E
<E> GEN
<E> ATS-FIREALARM
<E> ATS-HAEM
ATSATS
F
F
G
G
BOARD ROOM
102
IT ROOM
109
ELEC.
123
EMERGENCYPOWER
DISTRIBUTIONROOM
113C<E> I.T.
PULLBOX
BOARD ROOMPROJECTOR
BOX
1
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.N.I.C.
2
MECHANICAL
120
PRESIDENT'SOFFICE
101A
HALL
101D
ADMIN
101B
LOBBY
A100
DR1
AP
APTRANSFORMER
AHU-1 MOTOR
APC UPS
EATON UPS
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/8" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL DEMOLITIONFLOOR PLAN -
ADMINISTRATION BUILDING
ED102
15-104 ED102.DWG
ED102.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
1/8" = 1'-0"1
ELECTRICAL DEMOLITION WORK PLAN -ADMINISTRATION BUILDING
1
1. HATCHED PATTERN INDICATES ITEMS TO BE DEMOLISHED.
COMPLETELY REMOVE AND DEMOLISH <E> GENERATOR,INCLUDING EXISTING CIRCUIT BREAKER AND ASSOCIATEDCONDUIT/WIRING BACK TO POINT OF DISTRIBUTION.
2 COMPLETELY REMOVE AND DEMOLISH <E> CONDUCTORS ANDCONDUIT BACK TO SOURCE PANEL FOR ALL <E> TO REMAINRECEPTACLES LOCATED IN THIS AREA. PREPARE <E> TOREMAIN RECEPTACLES FOR POWERING VIA <N>CONDUCTORS AND CONDUIT.
A
LB ART
2. CAMPUS SHALL HAVE FIRST RIGHT OF REFUSAL OF ALLEQUIPMENT REMOVED AND DEMOLISHED.
3. TRANSFERED CIRCUITS SHALL NOT BE REUTILIZED ON <E>PANELS AND SHALL BE BLOCKED OFF FROM <E> BREAKERS.SPARE PLATE SHALL BE INSTALLED TO CIRCUIT BREAKERSWITH THE LAMENATED AFFIXED LABEL: "DO NOT USE ORCONNECT".
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
B C D E F G
BOARD ROOM
102
IT ROOM
109
ELEC.
123
EMERGENCYPOWER
DISTRIBUTIONROOM
113C
N.I.C.
N.I.C.
N.I.C.
N.I.C.N.I.C.
N.I.C.
N.I.C.
MECHANICAL
120
LOBBY
A100
ADMIN
101B
HALL
101D
PRESIDENT'SOFFICE
101A
1
1
1
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/8" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL DEMOLITIONREFLECTED CEILING PLAN -ADMINISTRATION BUILDING
ED202
15-104 ED202.DWG
ED202.DWG
SM
11/23/15
SM
PF
PF
11/06/2015
1/8" = 1'-0"1
ELECTRICAL DEMOLITION REFLECTEDCEILING PLAN - ADMINISTRATIONBUILDING
1. HATCHED PATTERN INDICATES ITEMS TO BE DEMOLISHED.
A
LB ART
2. CAMPUS SHALL HAVE FIRST RIGHT OF REFUSAL OF ALLEQUIPMENT REMOVED AND DEMOLISHED.
1 LUMINOUS CEILING WITH EXISTING NORMAL AND EMERGENCY LIGHTINGAND CIRCUITS.
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
E103
1
E103
1
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL SITE PLAN (FORREFERENCE ONLY)
E100
15-104 E100.DWG
E100.DWG
SM
11/09/15
SM
AH
PF
11/06/2015
1/2" = 1'-0"2
ELECTRICAL SITE PLAN (FORREFERENCE ONLY) ADMINISTRATION
GENERAL NOTES:
1. ALL KEYED NOTES NOT USED THIS SHEET.
3/4" = 1'-0"3
ELECTRICAL SITE PLAN (FORREFERENCE ONLY) DATA CENTER
3/8" = 1'-0"1
ELECTRICAL SITE PLAN (FORREFERENCE ONLY)
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
DN
J
J
J
J
J
JJ
J
JJ
J J
JJ
J
J
J
J
J
J
J
J
KILN
3
STORAGE
4
COMPUTERCENTER
10
OFFICE
1
OFFICE
2
OFFICE
3
IT #1
IT #2
PANEL #1
OFFICE
7
OFFICE
8
OFFICE
6
OFFICE
5
OFFICE
4
CABINET B
B-3
BUSINESSCHW/HW
B-1
FIBER PANEL#3
FIBER PANEL#1
PANEL #2
KILN/DOCKCONTROL
PANEL
2
CCU
1
CCU
2
CAC
1
CAC
N.I.C.
3
KILNTRANSFORMER
2
KILNTRANSFORMER
1
HALF-WALL AREA
9
KILN/DOCK CONTROLPANEL-8,10,12
KILN/DOCK CONTROLPANEL-13,15,17
ELECTRICKILN 1
ELECTRICKILN 2
GAS KILN 2GAS KILN 1
1
WC
3
TC
2
TC
1
TC
4
TC
5
TC
7
TC
6
TC
8
TC
1
VCU
<E> TO REMAINEMERGENCY GENERATORAND EQUIPMENT PAD
2
MCU
1
MCU
2
PANEL #1-12,14
PANEL #1-8,10
(TYP. 5)(TYP. 5)
2 3
(TYP. 6)(TYP. 6)
KILN/DOCK CONTROLPANEL-7,9,11
KILN/DOCK CONTROLPANEL-2,4,6
KILN/DOCK CONTROLPANEL-1,3,5
4
PANEL #1-16
1
SF
5
7
7
6
8
8
9
9
1
PANEL #1-7
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/4" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL NEW WORKFLOOR PLAN - DATA CENTER
E101
15-104 E101.DWG
E101.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
1. GRAYED LINES INDICATE EXISTING CONSTRUCTION,DARKENED LINES INDICATE NEW CONSTRUCTION.
1/4" = 1'-0"1
ELECTRICAL NEW WORK FLOOR PLAN -DATA CENTER
2. ALL <E> AND <N> CONDUIT WHICH PASSES THROUGH A FIRERATED PARTITION SHALL BE PROVIDED WITH A FIRESTOPSYSTEM WHICH MAINTAINS THE FIRE RATING OF THEPARTITION. ALL <E> CONDUIT WHICH DO NOT CURRENTLYHAVE A CODE COMPLIANT FIRESTOP SYSTEM INSTALLEDSHALL BE REPAIRED TO A CONDITION SUCH THAT THE FIRERATING OF THE PARTITION IS MAINTAINED.
PROVIDE A SIMPLEX RECEPTACLE DEDICATED TOCONDENSATE PUMP. COORDINATE RECEPTACLE LOCATIONWITH PUMP.
1
2 PROVIDE 4" SQ. JUNCTION BOX AND MAKE FINAL POWERCONNECTIONS FOR ALL INDOOR VRF UNITS. CONNECT PERMFR REQUIREMENTS.
3 PROVIDE 4" SQ. JUNCTION BOX FOR INDOOR VRF UNITSCONTROL CONNECTION. PROVIDE 1-1/2" (C) HOMERUN TOHVAC CONTROL PANEL. COORDINATE FINAL LOCATIONSWITH MECHANICAL CONTROL TRADES. CONNECT PER MFRREQUIREMENTS.
A
LB ART
4 POWER TO <N> VCU-1 SHALL BE VIA <N> 4" RMC. ONCE THE4" RMC PENETRATES INTO THE BUILDING SPACE, TRANSITIONTO A 2" RMC AND CONTINUE ROUTE BACK TO SOURCE PANEL.
5 CONTROL WIRING SHALL BE ROUTED IN 1" EMT. THIS 1" EMTSHALL BE ROUTED WITH THE REFRIGERANT LINES IN THE <N>4" RMC. ONCE THE 4" RMC PENETRATES INTO THE BUILDINGSPACE, CONTROL WIRING SHALL BE ROUTED IN 1" RMC TO MCUUNITS.
6 3/4" C - 1 #10 + #10 GND
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
7 3/4" C - 2 #10 + #10 GND
8 3/4" C - 3 #10 + #10 GND
9 3/4" C - 4 #10 + #10 GND
2
ATSATS
J
J
J
J
AT
SA
TS
ATS
D
J
B
B
C
C
D
D
E
E
F
F
G
G
EMERGENCYPOWER
DISTRIBUTIONROOM
113C
BOARD ROOM
102
ELEC.
123
105ASSIST SUPT.
101F
1ELL
PRESIDENT'SOFFICE
101A SECRETARIAL &WAITING
101
OFFICE
101G
OFFICE
104
IT ROOM
109
ADMIN
173
ADMIN
101B
SECRETARY &WAITING
103
PLAN & WORK
122F
OFFICE
122E
OFFICE
122D
PURCHASING
122J
OFFICE
122H
OFFICE
122G
BUSINESS OFFICEAREA
122
VAULT
109
MICROFILM ANDPHOTOGRAPHY
AREA
108
VAULT
107
BOARDCONFERENCE
ROOM
106
IBM CENTER
113
OFFICE
113B
STORAGE
114
LOBBY
A100
MENS RR
111
WOMENS RR
110
<E> ATS-FIREALARM
<E> ATS-HAEM
1ELP
2
7
713
3 5
11
5
9
9
1
2
1ELP-1,3,5
1NHL
1EHL
<N>ATS-1EHL/1ELL
<N>ATS-AHU-1
BOARD ROOMPROJECTOR
BOX
<N>ATS-1ELP/1NHL
1ELLTRANSFORMER
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.N.I.C.
1ELP-7,9,11
1ELP-2,4,6
6
4
MECHANICAL
120
HALL
101D
DR1
AP
APC UPS
EATON UPS
APTRANSFORMER
1ELP-12,141ELP-8,10
2 2
1ELPTRANSFORMER
F2
1
1
50 A 3P FUSETO <N> ATS-AHU
AHU-1 MOTOR
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/8" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL NEW WORKFLOOR PLAN -
ADMINISTRATION BUILDING
E102
15-104 E102.DWG
E102.DWG
SM
11/19/15
SM
PF
PF
11/06/2015
ALL <E> AND <N> CONDUIT WHICH PASSES THROUGH A FIRERATED PARTITION SHALL BE PROVIDED WITH A FIRESTOPSYSTEM WHICH MAINTAINS THE FIRE RATING OF THEPARTITION. ALL <E> CONDUIT WHICH DO NOT CURRENTLYHAVE A CODE COMPLIANT FIRESTOP SYSTEM INSTALLEDSHALL BE REPAIRED TO A CONDITION SUCH THAT THE FIRERATING OF THE PARTITION IS MAINTAINED.
1/8" = 1'-0"1
ELECTRICAL NEW WORK FLOOR PLAN -ADMINISTRATION BUILDING
A
LB ART
2 3/4" C - 4 #10 + #10 GND
1
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
ATS ATSJ
AT
SA
TS
ATS
D E
GDA-1
1
3
UC
2
5
4
CONCRETEPAD
TO BEINSTALLED
MANHOLEACCESS
TO VAULT
D
D
E
E
F
F
G
G
EMERGENCYPOWER
DISTRIBUTIONROOM
113C
ELEC.
123
105
1ELL
ADMIN
173
IBM CENTER
113
<E> ATS-FIREALARM
<E> ATS-HAEM
1ELP1NHL
1EHL
<N>ATS-1EHL/1ELL
<N>ATS-AHU-1
<N>ATS-1ELP/1NHL
1ELLTRANSFORMER
N.I.C.DR1
AP
APTRANSFORMER
1ELPTRANSFORMER
UG
GDA-1
PB
5
6
5
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL NEW WORKFLOOR PLAN - NEW
GENERATOR LOCATION
E103
15-104 E103.DWG
E103.DWG
CT
11/19/15
CT
SM
PF
11/06/2015
N.T.S.1
EMERGENCY GENERATOR
1. ALL <E> AND <N> CONDUIT WHICH PASSES THROUGH A FIRERATED PARTITION SHALL BE PROVIDED WITH A FIRESTOPSYSTEM WHICH MAINTAINS THE FIRE RATING OF THEPARTITION. ALL <E> CONDUIT WHICH DO NOT CURRENTLYHAVE A CODE COMPLIANT FIRESTOP SYSTEM INSTALLEDSHALL BE REPAIRED TO A CONDITION SUCH THAT THE FIRERATING OF THE PARTITION IS MAINTAINED.
2. SEE SHEET E002 FOR ELECTRICAL SCHEDULES.
1 UNDERGROUND CONDUITS PER SLD ON SHEET E002.
2 GROUNDING WELL WITH ROD 1#3/0 TO GENERATOR SET GROUNDBUSBAR. SEE DETAIL 2 SHEET E502 FOR FURTHER DETAILS. (TYP. 3)
3 PROVIDE NEW REMOVABLE TRAFFIC BOLLARD WITH PADLOCK. SEEDETAIL 1 SHEET E502 FOR FURTHER DETAILS. (TYP. 4)
A
LB ART
5 3 2-1/2" C - 4 #4/0 + #4/0 GND & 2 2" C - 4 #2/0 + #6 GND
N.T.S.2
EMERGENCY GENERATOR CONDUITROUTING
4 PROVIDE VAULT FOR GENERATOR CONDUIT. SEE DETAIL 5 SHEET E502FOR FURTHER DETAILS. (TYP. 4)
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
6 CONTROL SINGALLING BETWEEN <N> GENERATOR AND GENERATORCONTROL BOARD SHALL BE INSTALLED THROUGH 2" C WITHIN 21"CONCRETE ENCASEMENT. SEE DETAIL 9 SHEET E501 FOR FURTHERDETAILS.
2
B C D E F G
ELEC.
123
IT ROOM
109
BOARD ROOM
102
EMERGENCYPOWER
DISTRIBUTIONROOM
113C
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.
N.I.C.N.I.C.
MECHANICAL
120
PRESIDENT'SOFFICE
101A
HALL
101D
ADMIN
101B
LOBBY
A100
1
1
1
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/8" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL NEW WORKREFLECTED CEILING PLAN -ADMINISTRATION BUILDING
E202
15-104 E202.DWG
E202.DWG
SM
11/23/15
SM
PF
PF
11/06/2015
1/8" = 1'-0"1
ELECTRICAL NEW WORK REFLECTEDCEILING PLAN - ADMINISTRATIONBUILDING
1. ALL <E> AND <N> CONDUIT WHICH PASSES THROUGH A FIRERATED PARTITION SHALL BE PROVIDED WITH A FIRESTOPSYSTEM WHICH MAINTAINS THE FIRE RATING OF THEPARTITION. ALL <E> CONDUIT WHICH DO NOT CURRENTLYHAVE A CODE COMPLIANT FIRESTOP SYSTEM INSTALLEDSHALL BE REPAIRED TO A CONDITION SUCH THAT THE FIRERATING OF THE PARTITION IS MAINTAINED.
A
LB ART
1 LUMINOUS CEILINGS WITH EXISTING NORMAL AND EMERGENCY LIGHTINGAND CIRCUITS.
2. <N> RECEPTACLE AND LIGHTING SHALL BE REWIRED TO THENEW EMERGENCY POWER DISTRIBUTION ROOM IN THE EOCREMODEL PROJECT.
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
BONDING CLAMP
BONDING CLAMP
CADWELD BOND
COLD WATER PIPE
NATURAL GAS
BLDG. STEEL
3/8" NC x 3/4" HHCS
3/8" LOCK WASHER
TYPICAL 2.7KVINSULATOR
COPPER BAR WITH 1/4"HOLES AND 3/8" SLOT
2" O.C.
TYPICAL SUPPORTBRACKET
1/4"
4"
20"
BUILDING STEEL, 1/E-501
COLD WATER PIPE, 1/E-501
NARTUAL GAS, 1/E-501
UFER GROUND, 2/E-501
#3/0 GND
#3/0 GND
GND PERFEEDERSCHEDULE
#6 GND
EQUIPMENT GROUND BUS"1NHL" 480/277V
GROUNDING BUS BAR.
REFER TO 3/E-501GENERATORROOM 113C
EQUIPMENT GROUND BUS"1ELP" 120/208V
EQUIPMENT GROUND BUS"DR1"
BLDG.XFMR
EQUIPMENT GROUND BUS"1EHL" 480/277V
BLDG.XFMR
EQUIPMENT GROUND BUS"1ELL" 120/208V
3"
3"3"
3"
3"
95% COMPACTED BACKFILL.FREE FROM LARGE ROCKS& DEBRIS
3" MIN. CONCRETEENCASEMENT (W/ ORANGEPIGMENTATION IN THE TOP 2"2500LB TEST MIN.
PATCH OR PAINT TOMATCH EXISTING
12" WIDE YELLOWDETECTABLE WARNING TAPE
36" MIN.
NUMBER 5 REBAR CONTINUOUS(TYP.) PROVIDE #3 U-SHAPE
REBAR EVERY 24" ON CENTER.PROVIDE 3" CLEARANCE
AROUND ALL REBAR.
NOTES:
1. CONDUIT SHALL BE RIGID METAL CONDUIT.2. ARRANGE CONDUIT WITH INTERLOCKING PLASTIC SPACERS 8'-0" O.C.
12" MIN.
3"3"
BARE COPPER CABLE EMBEDDED IN CONCRETE FOOTINGFOR CONTINUOUS STRAIGHT DISTANCE OF FIFTY (50) FEET OFFOUNDATION FOOTING.
CADWELD COPPERTO VERTICAL TIE ROD
10'-0" O.C.
REBAR OR TIERODS (TYP.)
GRADE
METALLIC GROUNDING BUSHING.
EXTERIORBUILDING WALL
BONDINGWIRES
1" CONDUIT ABOVESTUBBED-UP FLOORSLAB
FLOOR SLAB
GROUNDINGCONDUCTORTO FOOTING
BONDING CLAMP
GROUNDINGWIRES, LENGTHAS REQUIRED
1.
2.
3.
3
2
1A
1B3
A
FRONT VIEW
SECTION A-A
4" DIA. OR SMALLER AT(E) CMU WALL EMT ORELECTRICAL CONDUIT.
2
A
1 OR 2-HR. FIRERATED GYPSUMWALL ASSEMBLYOR CMU WALLWHERE NOTED. U.L. SYSTEM NO. WL 1001
NOTE: MAX. DIA. OF OPENING IS 4" MAX AT CMU WALLANNULAR SPACE OF MIN. 1/4" DIA. BEAD IS REQUIRED.
MIN. 1/4" TO 1/2" DIA. ANNULAR SPACEW/FIRE STOP SEALANT (CAULK)APPLIED TO PERIMETER OF CONDUITAT ITS EGRESS FROM WALL
GENERAL NOTES:
CONDUIT SIZE PER DRAWINGS
FIRE STOP SYSTEM - ONE HOUR CAULK #3MCD25WB4.APPLY TO INTERFACE WITH WALL SURFACE.
WALL CONSTRUCTION:A. STEEL STUDS PER STRUCTURAL.B. 5/8" TYPE X GYPSUM BOARD
AT CMU WALL CONDITION, CONTRACTOR SHALLLOCATE EXISTING REINFORCEMENT PRIOR TOCORING OPENING BY SCANNING.DO NOT DAMAGE OR CUT EXISTING REBAR.EDGE OF NEW CORE HOLE SHOULD BE 1-1/2" MIN.CLEAR FROM EDDGE OF EXISTINGREINFORCEMENT.
H"
MINIMUM 12 BOLT DIAMETERS SHALL BEMAINTAINED FROM BOLT TO EDGE OFHOUSE KEEPING PAD.
EXPANSION ANCHORS SHALL BE HILTI-KWIKBOLT II, ICBO#4627.
3.
2.
L"
SPECIAL INSPECTION OF EXPANSIONANCHOR INSTALLATION IS REQUIRED.
NOTE:
1.
KEY NOTE:
D"
1/2" THICK X REQUIRED SIZE ELAST.ZORE SHEET AT CORNER
(-"H x -"L x -"D)
DRY TYPETRANSFORMER
x LBS.
4.5" HOUSE KEEPING PAD. (5,000 PSICONCRETE).
FINISHED FLOOR
(4) BOLTS, 1/2" DIA. EXPANSIONANCHORS, 2-1/2" MINIMUM EMBEDMENT.(MINIMUM GRADE, SAE1)
x"
1"
y"
FRONT VIEW SIDE VIEW
1"
1
1
2
2
3
3
A
A
ELECTRICAL
PULL BOX
PULLBOX GENERAL NOTES:
CONDUITSEE PLANS.
48" MIN.
SECTION A-A
12" GRAVELBASE
1.
2.
TOP OF NEW17" X 30" PULLBOX
AC PATCHASPHALT
18" MIN.
PROVIDE 6'-0", #6 GROUND BOND JUMPER TO COVERFROM SERVICE GROUND CONDUCTOR WITH NECESSARYAPPROVED HARDWARE.
WATER TIGHT INSTALLATION-FOAM SEAL CONDUITOPENINGS.
12" PULLBOXEXTENSION
SLURRY
4"
4"
KEYNOTES:
PULL BOX BASE. SET ON PEA GRAVEL BASE BENEATHPULL BOX. (PROVIDE EXTENSIONS AS REQ'D. IN FIELD)MIN. OF (1) EXTENSION.
POUR 4" CONCRETE OR AC PATCH PAD AROUND EACHPULL BOX TO PREVENT SINKING BELOW GRADE, ANDSLURRY COAT AROUND. SEE SECTION A-A.
30"
LABEL COVER: A) CONNUNICATION PULLBOX
DO NOT MIX POWER & L.V. COMM. CONDUITS.
DIRT
1
4"4"
17"
4"
1
1
1
2
2
3
3
4
4
APPROX. 21"
3"MIN
3"MIN
CONCRETEENCASEMENT
2-1/2"C. 2-1/2"C. 2-1/2"C.
3"MIN
3"MIN
3" MIN
3" MIN
VARYINGDEPTH60" MAX
GRADE
FINISH SURFACE PER PLANNATIVE SOIL BACKFILL COMPACTED TO
90% OF MAXIMUM DENSITY WITHINPLANTED AREAS.
SLURRY BACKFILLWITH REDPIGMENTATION
SURFACE OVER TOMATCH EXISTING
APPROX.36" MIN.
3"MIN
2"C. 2"C.
8"
BACKFILL MATERIAL DENSITYCOMPACTED TO 90%CAST IRON
TRAFFIC COVER
GALVANIZEDSTEEL STEPS
36"
2"GRADE
10'-0"
12"
12"
12"
8"
8"
48"
MIN
.
4" DRAINAPPROXIMATELIMIT OFEXCAVATIONAROUND
CONCRETEENCASEDDUCT (TYP.)
12"12"
4"
72"
72"
REFER TO MANHOLE RACKON THIS SHEET.
STEEL LADDER GROUNDWITH #4/0 WIRE, ANCHORLADDER TO FLOOR
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL DETAILS
E501
15-104 E501.DWG
E501.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
N.T.S1
TYP. GROUNDING DETAIL
N.T.S3
TYP. GROUNDING BUS BAR
N.T.S5
GROUINDING DIAGRAMN.T.S
7TYP. TRENCH DUCT DETAIL
N.T.S2
TYP. UFER GROUND
N.T.S.8
TYP. STOP CONDUIT PENETRATIONN.T.S.
9FLOOR MOUNT TRANSFORMER DETAIL
N.T.S6
PULLBOX DETAIL
N.T.S.10
DUCT BANK DETAIL
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
N.T.S4
TYP. MANHOLE DETAIL
6"
CONCRETE
GRADE
3"
36"
30"
4" GALVANIZED STEELPIPE FILLED WITHCONCRETE
4/0 BARE COPPER STANDARDCABLE SIZED FOR "GK"CONNECTOR (TYP. 2)
OPEN BOTTOM
PRE-CAST CONCRETE BOX10"W x 17"L x 12"D BROOKS,OR EQUAL
BOND CONDUCTOR TOADDITIONAL GROUNDINGBUSHING AS REQUIRED
1 CUBIC FT MIN. 3/4" GRAVEL
3/4" X 10'-0" COPPER CLADSTEEL GROUND ROD
WATER PIPE CLAMPT & B OR EQUAL
BURNDY TYPE "SK"
EXTERNAL CONNECTION TOSUBSTATION GROUND BUS
COVER SHALL HAVE CASTLETTERING "GROUND"
GROUNDING BUSHING
1 EACH ROD MUST HAVE A SEPARATION DISTANCE OF 6 FT. AWAY FROMOTHER TWO RODS OF 6 FT. EACH OF THE THREE RODS MUST BE INSTALLEDIN ACCORDANCE WITH THIS DETAIL WITH ACCESSORIES AS SHOWN.
1
EXISTING
C045
6'
6'
1'-6"
MAX
7'-4"
3'-9"
METAL SCREEN
(E) RETAININGWALL
HSS6x6x1/4BEAM, TYP
HSS6x6x1/4COLUMN
FOOTING
TWO SACK SLURRY CONTAINMENT.
CONDUIT SHALL BE PVC SCHEDULE 80 WHERE EXPOSED. BURIED CONDUITCAN BE EITHER SCHEDULE 40 OR SCHEDULE 80.
ATTACH CONDUIT TO UNISTRUT FRAME USING UNISTRUT CLAMPS.
MAINTAIN A 48"RADIUS MINIMUM FOR ALL TURNS. CONDUIT BUNDLE MUST EXITPULLBOX AND DROP IN ELEVATION TO ATTAIN THE 48"RADIUS TURNS.
CORE NEW PENETRATIONS AND ROUTE CONDUIT BANK AS INDICATED.
1
1
2
2
3
3
3
4
4
5
5
5'
UNDERGROUNDPULLBOX
(6)4"C & (4)2"CWITH SLEEVES
FINISHED GRADE
35'-0"POSSIBLE PULL BOXFOR 2"C
PROVIDE 4' RADIUSCURVE TO AVOID ANY
OBSTRUCTIONS.
UNDERGROUNDPULLBOX
15'-0"
PNEUMATIC TUBESYSTEM
SLURRY MIXENCASEMENT
5'-9"
3'-9"
4'-1"
3'-6"
7"
12"
5'-0"3'-0"
5'-6"MINIMUMOVERALLHEIGHT
2" DUCTTERMINATORS4 TOTAL
2.5" DUCTTERMINATORS6 TOTAL
12" RISERPG&E CODE
04-3362
12" DIA. SUMP
SC3048-TSRAL, ONE PIECE SLIP RESISTANT TRAFFIC COVER, MARKEDAS REQUIRED, RED PRIMER & ALUMINUM PAINT FINISH.
C
A
B D
A
C
DB
SECTION A-A
PLAN VIEW
SECTION B-B
SECTION D-DSECTION C-C
82"
154"
60"
32-1/2"
21-1/2"
7"
7"
5"
5"
72"
144"
46"
48"60"
5" 144" 5"
154"
5"
72"
5"
82"
60"
48"
5" 144" 5"
154"
7"
23"
23"
7"
46" 60"
GRD.
GRD.
GRD.
BOTTOM OF VAULT, 42" BOTTOM SECTION. WT. 15,913 LBS.
MIDDLE OF VAULT, 42" TOP SECTION W/4'x5'. WT. 14,163 LBS.
12" x 13" DIA. SUMP x 5" DEEP, W/RECESS TO ACCOMMODATE SUMP COVER, BOTTOM SECTION (1) CORE MTD.
6" DIA. CONTERMS, BOTTOM SECTION (8) SHELL MTD.; TOP SECTION (8) SHELL MTD.
TOP OF VAULT TO REMAIN MIN. 6" ABOVE GROUND.
7/8" DIA. x 3-3/8" GALV. PULL IRON, BOTTOM SECTION (3) CORE MTD.
1/2" THR'D. BRONZE INSERT BRAZED TO STRUCTURAL STEEL, "GRD" SHALL BE STENCILED IN RED LETTERS (1-1/2" MIN - 2" MAX) ON THE CONCRETE ABOVE INSERT. BOTTOM SECTION (2) CORE MTD.; TOP SECTION (2) CORE MTD.
1" DIA. THR'D. INSERT, BOTTOM SECTION (4) CORE MTD.
GRD.
GRD.
82"
5"72"5"
3" TYP.
7"
23"
23"
7"
46" 60"60"46"
7"
23"
23"
7"
154"
5"144"5"
1" DIA. BLIND GROUND ROD HOLE, BOTTOM (4) CORE MTD.
3" TYP.
3" TYP.
82"
5"72"5"
7"
23"
23"
7"
46" 60"
1
1
2
3
4
5
6
7
8
9
11
1
1
1
2
22
5
2 2
3
3
3
3
3
4
4
4
4
4
6
6
6
6
6 6
7
77
7
7
7
8
8
8
8
8
9
6"5
6"
6"
5
5
6"5
6"5
O
AINRIFO LAC
Exp. 12-31-17
CL IE RTCTS
AT
E
E
A
F
L
NEERI
E
AL
GN
OIOF
SEG
IED
R
P
TE
R SES
No. E 018957
N
R
AMO
AP
LU
NUF D
TNE
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
ELECTRICAL DETAILS
E502
15-104 E502.DWG
E502.DWG
CT
03/11/16
CT
PF
PF
11/06/2015
N.T.S1
BARRIER POST DETAILN.T.S.
2GROUND ROD DETAIL (TYP. OF 3)
N.T.S.3
FIBER OPTIC SUPPORT DETAIL
N.T.S.4
CONDUIT INSTALLATION DETAIL
N.T.S.6
PULL BOX DETAIL (TYPICAL)
N.T.S.5
GENERATOR VAULT DETAIL
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
GENERAL NOTES
MECHANICAL SHEET INDEX
PIPING NOTES
DUCT NOTES
DDC / CONTROLS NOTES
ABBREVIATIONS
MECHANICAL LEGEND
GENERAL NOTES:
ALL MECHANICAL EQUIPMENT WITH OSA INTAKES SHALL BE PROVIDED WITH MOISTURE ELIMINATORS.
CONTRACTOR SHALL COMPLY AND ADHERE FULLY TO RESTRICTIONS AND LIMITATIONS OF WORKSCHEDULING AND ACCESS TO RESTRICTED AREAS. CONTRACTOR SHALL COORDINATE ALLSCHEDULING AND ACCESS ISSUES WITH OWNER.
PRESSURE TEST ALL DUCTWORK IN ACCORDANCE WITH SMACNA "HVAC AIR DUCT LEAKAGE TESTMANUAL.", LATEST EDITION. TAKE ALL CORRECTIVE ACTION TO ENSURE THAT DUCT LEAKAGE DOESNOT EXCEED 3%. SEE SPECIFICATION SECTION 233113.
ALL AIR MOVING EQUIPMENT SHALL BE CHECKED AND BALANCED BY A CERTIFIED INDEPENDENTBALANCING COMPANY THAT SPECIALIZES IN THIS TYPE OF WORK. BALANCING CONTRACTOR SHALLNOT BE AFFILIATED WITH OR A MEMBER OF ANY OTHER CONTRACTOR ON THIS PROJECT. BALANCING CONTRACTORSHALL BE AABC CERTIFIED ONLY.
COORDINATE ALL INTERRUPTION OF BUILDING UTILITY SERVICES WITH OWNER PRIOR TO ANY ANDALL SHUTDOWN. NOTICE OF AT LEAST 7 CALENDAR DAYS SHALL BE GIVEN FOR ALL UTILITYINTERRUPTIONS.
SHOULD CONFLICT OCCUR BETWEEN DRAWINGS AND SPECIFICATIONS THE MOST STRINGENTOCCURRENCE SHALL APPLY. PLANS SHALL BE REVIEWED THOROUGHLY PRIOR TO BID. ALLDISCREPANCIES/CONFLICTS FOUND SHALL BE INDICATED AND REQUESTS FOR CLARIFICATION SHALLBE MADE BY THE CONTRACTOR TO THE DISTRICT PRIOR TO SUBMISSION OF BID. ALLDISCREPANCIES/CONFLICTS BETWEEN DRAWINGS AND OR SPECIFICATIONS NOT BROUGHT TO THEATTENTION OF THE DISTRICT SHALL CONFIRM THAT THE MOST STRINGENT REQUIREMENT HAS BEENINCLUDED IN THE CONTRACTOR'S BID PRICE AND WILL NOT BE ALLOWED AS A CHANGE ORDER TOTHE PROJECT. (TYP.)
PROVIDE AND INSTALL CEILING ACCESS DOORS FOR ALL DUCT MOUNTED SMOKE DETECTORS MINIMUM SIZEAS REQUIRED FOR SERVICE AND MAINTENANCE. COORDINATE SELECTION WITH ADJACENT CEILING.COORDINATE MASKING AND PAINTING WITH PAINTING CONTRACTOR.
CONTRACTOR SHALL COORDINATE WORK WITH ALL TRADES PRIOR TO START OF WORK AND SHALLGENERATE COORDINATED SHOP DRAWINGS USING REVIT BIM SOFTWARE.
MANUFACTURER'S SERVICE AND OPERATING CLEARANCES SHALL BE MAINTAINED ON ALL MECHANICALAND ELECTRICAL EQUIPMENT.
1. THESE DRAWINGS AND SPECIFICATIONS ARE DIAGRAMMATIC TO THE EXTENT THAT SOME ITEMSSHOWN ON PLANS ARE IN A MANNER TO TO PROVIDE CLARITY ONLY. ACTUAL FIELD ROUTING ANDINSTALLATION SHALL BE PROVIDED IN COORDINATION WITH OTHER TRADES AND ACTUAL FIELDCONDITIONS. CONTRACTOR SHALL PROPERLY INTERFACE WITH STRUCTURE AND ALL OTHER SYSTEMS TOACCOMPLISH THE INTENT OF THIS DESIGN. LOCATIONS OF HVAC EQUIPMENT AND DUCTING MAY VARYDUE TO ACTUAL FIELD CONDITIONS. CONTRACTOR SHALL NOT SCALE OFF OF THESEDRAWINGS TO PLACE OR OTHERWISE LOCATE EQUIPMENT HANGERS, ANCHORS OR ANY OTHERSUPPORT SYSTEM. FIELD VERIFY ALL DIMENSIONS, EQUIPMENT WEIGHTS, LOCATIONS AND CONDITIONSPRIOR TO COMMENCEMENT OF WORK AND ORDERING MATERIALS. MAKE ALL NECESSARYACCOMMODATIONS TO PROVIDE FOR A COMPLETE AND OPERATING SYSTEM AS INTENDED BY THESEDRAWINGS AND SPECIFICATIONS.
2.
3.
4.
5.
6.
7.
8.
9.
10.
NFPA 13, 2013 Edition, Automatic Sprinkler Systems
2013 California Referenced Standards, Part 12, Title 24 C.C.R.
2013 California Fire Code, Part 9, Title 24 C.C.R.
2013 California Electrical Code (CEC), Part 3, Title 24 C.C.R.
CODES AND STANDARDS
2013 California Building Code (CBC), Part 2, Title 24 C.C.R.
2013 Building Standards Administrative Code, Part 1, Title 24 C.C.R.
(2015 International Building Code Volumes 1&2 and 2013 California Amendments)
(2014 National Electrical Code and 2013 California Amendments)
2013 California Mechanical Code (CMC), Part 4, Title 24 C.C.R.
(2015 Uniform Mechanical Code and 2013 California Amendments)
2013 California Plumbing Code (CPC), Part 5, Title 24 C.C.R.
(2015 Uniform Plumbing Code and 2013 California Amendments)
2013 California Energy Code, Part 6, Title 24 C.C.R.
NFPA 72, 2013 Edition, National Fire Alarm Code (California Amended)
(2015 International Fire Code and 2013 California Amendments)
CONTRACTOR SHALL PROVIDE AND INSTALL ISOLATION VALVES FOR ALL PIPING SYSTEM SERVICES ATEACH FLOOR BEING SERVED AND AT MAIN ENTRANCE INTO BUILDING.
A.
B.
PROVIDE DIELECTRIC UNIONS, COUPLINGS, AND OR FITTINGS AT ALL PIPE CONNECTIONS WHEREDISSIMILAR METALS OCCUR.
PIPING MATERIALS SHALL BE PROVIDED AS FOLLOWS (REFER TO DRAWINGS AND SPECIFICATIONS FORADDITIONAL REQUIREMENTS):
CONDENSATE DRAIN LINES SHALL BE SCHEDULE 40 PVC PLASTIC PIPE AND FITTINGS.
REFRIGERANT PIPING SHALL BE PER MFR REQUIREMENTS.
CONTRACTOR SHALL COORDINATE REFRIGERANT LINE SIZES WITH CONDENSING UNIT MANUFACTURERBASED ON PROPOSED FIELD ROUTING AND ALLOWING FOR PRESSURE LOSSES AT ELBOWS, FITTINGSAND SPECIALTIES (TYP)
CONDENSATE LINES WITHIN THE BUILDING ENVELOPE SHALL BE INSULATED WITH RUBATEX, ARMAFLEX,OR EQUAL INSULATION. JOINTS & SEAMS SHALL BE SEALED PER INSULATION MANUFACTURER'SINSTALLATION INSTRUCTIONS.
PROVIDE UNION FITTING, P-TRAP, AND FLEXIBLE CONNECTION WHERE CONDENSATE LINES CONNECTTO EQUIPMENT.
PROVIDE AND INSTALL BRASS, CHROME PLATED ESCUTCHEONS WHERE PIPING PENETRATES BUILDINGENVELOPE.
1.
2.
3.
4.
5.
6.
7.
MAXIMUM FLEXIBLE DUCTWORK LENGTH SHALL BE 7'-0". FLEX DUCT SHALL NOT BE USED TO MAKE ATURN GREATER THAN 90° IN ANY CIRCUMSTANCE AND SHALL ONLY BE USED AS FINAL CONNECTIONSTO DIFFUSERS.
ALL SUPPLY AND RETURN DUCTWORK ON THIS PROJECT SHALL BE CONSTRUCTED OF A MINIMUM 22 GAUGEMETAL. (U.N.O.)
PROVIDE ALL INTERNALLY LINED PLENUMS AS REQUIRED TO CONNECT ROUND DUCTWORK TO SQUARE
NECK OF DIFFUSERS. PROVIDE AND INSTALL ALL DIFFUSER PLENUMS AS REQUIRED WHERE TYPICAL
RADIUS ELBOWS CANNOT BE INSTALLED (TYP.). ANY RUNNING CHANGE BETWEEN ROUND AND SQUARE
PROVIDE TURNING VANES IN RECTANGULAR DUCTS WHERE CHANGE IN DIRECTION RESULTS IN ANGLESEQUAL TO OR GREATER THAN 90 DEGREES. USE ONLY LONG RADIUS ROUND ELBOWS ON THISPROJECT. NO SHORT RADIUS ELBOWS ALLOWED.
DUCT TRANSITIONS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE MOST RECENT SMACNASTANDARDS AND SHALL BE CLASSIFIED AS "LOW-LOSS FITTINGS".
ROUND DUCT ELBOWS SHALL BE EITHER SMOOTH DIE STAMPED OR 5-PIECE. THREE-PIECE ELBOWSWILL NOT BE ACCEPTABLE.
CONTRACTOR SHALL TRANSITION DUCTWORK WHERE REQUIRED TO AVOID EXISTING OBSTACLES. ALLNEW DUCTWORK SHALL BE SIZED USING THE EQUAL FRICTION METHOD AND SIZED AT 0.08"PRESSURE DROP PER 100 FEET OF DUCTWORK. ALL NEW TRANSITIONS SHALL BE SHOWN ONCONTRACTOR SHOP DRAWINGS. (TYP.)
PROVIDE AND INSTALL LOCKING QUADRANT MANUAL VOLUME DAMPERS AT EACH DUCT BRANCHSERVING A DIFFUSER, REGISTER, GRILLE, OR OTHER OUTLET, AS REQUIRED FOR BALANCING AIRFLOW.
ALL DUCTWORK EXPOSED TO VIEW SHALL BE INTERNALLY LINED. DUCT LINER SHALL BE 1" MINIMUMTHICKNESS AND SHALL BE COATED WITH ANTI-MICROBIAL MEDIUM AND RATED FOR 4000 FPMVELOCITY. (TYP.)
THE AIR DISTRIBUTION DUCTS SHALL BE CONSTRUCTED, INSTALLED, SEALED, AND INSULATED ASPROVIDED IN SMACNA DESIGN GUIDE FOR DUCTWORK CONSTRUCTION, LATEST EDITION.
INSTALL ALL DUCTWORK & PIPING AS HIGH AS POSSIBLE. WHERE DUCTWORK & PIPING ARE TO BELOCATED IN SAME AREA, PIPING SHALL BE INSTALLED BELOW DUCTWORK. (U.N.O.)
ALL DUCT DIMENSIONS SHOWN ARE NET CLEAR INSIDE DIMENSIONS. MAKE ALLOWANCES FOR DUCTLINER THICKNESSES WHEN CONSTRUCTING DUCTWORK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
ALL CONTROLS AND CONTROLS INSTALLATION SHALL BE ALERTON PER CAMPUS STANDARD. CONTROLSSYSTEMS SHALL INTERFACE AND FULLY INTEGRATE WITH EXISTING CAMPUS-WIDE STANDARD SYSTEM.
THERMOSTATS AND TEMPERATURE SENSORS LOCATED ON EXTERIOR WALLS OR ADJACENT TOUNCONDITIONED SPACES SHALL BE MOUNTED ON 1" THICK FIBERGLASS OR CORK PAD.
1.
2.
3.
ALL CONTROLS ON THIS PROJECT SHALL INTEGRATE INTO THE EXISTING CAMPUS CONSOLE. PROVIDE A FULLACCESS USER ACCOUNT AND PASSWORD TO THE ENGINEER AS REQUIRED FOR CONTROLS TESTING ANDCOMMISSIONING DURING PROJECT STARTUP.
4.
MANUFACTURERS REQUIRING SOFTWARE OR HARDWARE LOCKS, DONGOLS, OR OTHER RESTRICTIVEDEVICES WILL NOT BE ALLOWED ON THIS PROJECT.
5.
ALL EQUIPMENT WITH MOTORS SHALL BE ISOLATED FROM THE BUILDING WITH SPRING ISOLATORS, NEOPRENEPADS, OR OTHER SUITABLE MEANS.
PROVIDE AND INSTALL FLEXIBLE DUCT CONNECTIONS ON ALL FAN OUTLETS AND INLETS. MAINTAIN AMINIMUM OF 1" OF MOVEMENT IN FLEXIBLE CONNECTIONS TO ISOLATE CONNECTED DUCTWORK FROMTHE EQUIPMENT. (TYP.)
11.
12.
ISOLATION VALVE
TURNING VANES
DUCT TRANSITION
DDC
RA
N.T.S.
SA
E.S.P.
EA
VRF
E.A.T.
VARIABLE REFRIGERANT FLOW
ENTERING AIR TEMPERATURE
EXHAUST AIR
EXTERNAL STATIC PRESSURE
DUCT (1ST FIGURE, SIDE SHOWN 2ND FIGURE, SIDE NOT SHOWN.)24x8
POINT OF CONNECTION / POINT OF REMOVAL
TRANSITION FROM SQUARE TO ROUND
SYMBOL
DIRECT DIGITAL CONTROL
NOT TO SCALE
RETURN AIR
SUPPLY AIR
DUCT RISE/ DUCT DROP
SUPPLY AIR REGISTER/ GRILLE
ABBREVIATION DESCRIPTION
NOT ALL SYMBOLS OR ABBREVIATIONS MAY BE USED ONTHIS PROJECT.
NOTE:
CO2CARBON DIOXIDE SENSOR/TRANSMITTER
CONTRACTOR SHALL PROVIDE ALL GRAPHICS PROGRAMMING AT BOTH THE OPERATOR WORKSTATIONAND CENTRAL CAMPUS CONSOLE.
6.
ALL CONTROLS SHALL BE OPEN PROTOCOL BACNET AND SHALL COMPLY WITH TIER ONE AND TIERTWO LEVELS.
7.
DUCT SHALL REQUIRE A TRANSITION AND ALL ROUND TAKE OFFS REQUIRE A DIVERSION FITTING.
MEP COORDINATION NOTES
1. THESE PLANS ARE DEVELOPED USING A 3D SOFTWARE THAT IS SIGNIFICANTLY DIFFERENT THAN FORMER 2D CAD METHODS.THEREFORE IN SOME CASES, SOME MEP ITEMS ARE NOT SHOWN DUE TO PLOTTING PECULARITIES OF THE 3D SOFTWARE AND ITSCAPABILITIES. ROUTING OF MEP SYSTEMS INDICATED ON PLANS ARE SHOWN IN A MANNER TO INDICATE POSSIBLE AND RELATIVEPLACEMENT OF SYSTEMS. IT SHALL BE THE RESPONSIBILTY OF THE CONTRACTOR TO INSTALL THE MEP SYSTEMS BASED ONCONSTRUCTION CONDITIONS, AND BASED ON THE INTENT OF THESE PLANS.
2. DIVISION 22, 23, AND 26 TRADES SHALL REVIEW AND REFERENCE ALL DRAWINGS AND DOCUMENTS RELATED TO THESE DIVIONSPRIOR TO GENERATION OF SHOP DRAWINGS AND SUBMITTALS.
3. PIPING, CONDUIT, DUCTWORK AND MISCELLANEOUS SYSTEM COMPONENTS ARE JUXTAPOSED IN VERY CLOSE PROXIMITY TO EACHOTHER. EACH TRADE SHALL PRODUCE SUBMITTAL AND SHOP DRAWINGS CONFIRMING THE ROUTING OF EACH SYSTEM ANDCOMPONENTS RESPECTIVE TO ITS TRADE AS WELL AS SPACE ALLOCATED TO OTHER TRADES. SUCH SHOP DRAWINGS SHALL BEPRODUCED USING A 3D SOFTWARE SHOWING FINAL AND DETAILED MEP, STRUCTURAL, AND ARCHITECTURAL TRADES.
4. CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY FITTINGS, TRANSITIONS, ELBOWS, AND MATERIALS AS REQUIRED TOAVOID OBSTACLES CREATED BY OTHER TRADES. PIPING, CONDUIT, DUCTWORK AND ASSOCIATED EQUIPMENT ELEVATIONS MAY VARYDUE TO FIELD CONDITIONS.
5. ORDERING, FABRICATION, OR INSTALLATION OF MATERIALS SHALL NOT TAKE PLACE WITHOUT APPROVED SUBMITTAL DRAWINGSCONFIRMING DETAILED INSTALLATION ROUTING AND COORDINATION BETWEEN TRADES.
6. CONFLICTS BETWEEN TRADES AND PROPOSED RESOLUTION SHALL BE IDENTIFIED IN SUBMITTALS AND SHOP DRAWINGS ANDSHALL BE RESOLVED BY CONTRACTOR AT NO ADDITIONAL COST TO THE PROJECT.
7. ANY WORK FOUND TO BE IN CONFLICT WITH OTHER TRADES, NOT DETAILED IN COORDINATION PROCESS DESCRIBED ABOVE, SHALLBE DEMOLISHED AND PROPERLY RE-INSTALLED AT NO ADDITIONAL COST TO THE PROJECT.
DUCT PRESSURE CLASSIFICATIONS AND CONSTRUCTION REQUIREMENTS SHALL BE EQUAL TO OR GREATERTHAN THE HIGHEST EXTERNAL STATIC PRESSURE LISTED ON THE EQUIPMENT SCHEDULES OR SPECIFICATIONSFOR THIS PROJECT. (TYP.)
2013 California Green Building Standards Code (CALGreen), Part 11, Title 24 C.C.R.
ALL MECHANICAL, PLUMBING, AND ELECTRICAL COMPONENTS SHALL BE ANCHORED AND INSTALLED PERTHE DETAILS ON THE CONSTRUCTION DOCUMENTS. WHERE NO DETAIL IS INDICATED, THE FOLLOWINGCOMPONENTS SHALL BE ANCHORED OR BRACED TO MEET THE FORCE AND DISPLACEMENTREQUIREMENTS PRESCRIBED IN THE 2013 CBC. SECTIONS 1615A.1.12 THROUGH 1645A.1.22 AND ASCE 7-05CHAPTER 6 AND 13.
IN.WG. INCHES WATER GAUGE
T THERMOSTAT
S/S
HT
AO
CSR
DI
DO
DDCP
COM
CPA
AI
DDC SYMBOLS LEGEND
DPT
SYMBOL
NOTE: NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT.
HUMIDITY TRANSMITTERHT
S/S START/STOP
DESCRIPTION
CONTROL POINT ADJUST
CURRENT SENSING RELAY
DIRECT DIGITAL CONTROL PANEL
CSR
DI
DDCP
DO
AO
COM
CPA
DIGITAL OUT
DIGITAL IN
COMMUNICATIONS PORT
ANALOG OUT
ABBR.
AI ANALOG IN
DIFFERENTIAL PRESSURE TRANSMITTERDPT
CARBON DIOXIDE TRANSMITTERCO2CO2
DEMOLITION NOTES
ALL ITEMS AFFECTED BY DEMOLITION SHALL BE REMOVED UNDAMAGED, AND MADE AVAILABLE TO THE OWNERFOR FIRST RIGHT OF SALVAGE. ANY SUCH ITEMS REFUSED BY OWNER SHALL BE PROPERLY DISPOSED OF BYCONTRACTOR OFF SITE.
CUTTING OR NOTCHING OF STRUCTURAL MEMBERS INCLUDING BEARING/ SHEAR WALLS NOT SPECIFICALLYDETAILED ON STRUCTURAL DRAWINGS, MUST BE APPROVED BY AUTHORITIES HAVING JURISDICTION.
PERFORM CUTTING, PATCHING, AND REFINISHING OF THE EXISTING BUILDING SURFACES AND MATERIALSREQUIRED TO PERFORM THE WORK INDICATED IN THE DRAWINGS AND SPECIFICATIONS. SUCH AREASAFFECTED BY THIS WORK SHALL BE REFURBISHED TO AS-NEW CONDITION AND MATCH SURROUNDINGSURFACE FINISH IN COLOR, TEXTURE, AND APPEARANCE.
1.
2.
3.
<N> NEW
CONTROL VALVE
P.O.C. / P.O.R.
SAR
T
CO2
RAISED FLOOR SUPPLY DIFFUSER
N.I.C.
NOTE: NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT.
AREA NOT IN CONTRACT.N.I.C.
<E> EXISTING
OUTSIDE AIROSA
N.I.C. NOT IN CONTRACT
LEAVING AIR TEMPERATUREL.A.T.
MOISTURE DETECTORMDMD
MANUAL VOLUME DAMPER
COMPUTER ROOM AIR CONDITIONING UNITCAC
MOISTURE DETECTOR TRANSMITTERMDTMDT
HRG HIGH-PRESSURE REFRIGERANT GAS
RG REFRIGERANT GASRG
HRG
RL REFRIGERANT LIQUIDRL
MODE CONTROL UNITMCU
VARIABLE REFRIGERANT CONDENSING UNITVCU
COMPUTER ROOM CONDENSING UNITCCU
SUPPLY FAN UNITSF
WALL VRF CASSETTE UNITWC
T-BAR VRF CASSETTE UNITTC
MEP ANCHORAGE NOTES
PIPING SHALL BE ROUTED ABOVE CEILING UNLESS NOTED OTHERWISE.8.
ALL PERMANENT EQUIPMENT AND COMPONENTS.
TEMPORARY OR MOVABLE EQUIPMENT THAT IS PERMANENTLY ATTACHED (E.G. HARDWIRED) TO THE BUILDING UTILITY SERVICES SUCH AS ELECTRICITY, GAS, OR WATER.
MOVABLE EQUIPMENT WHICH IS STATIONED IN ONE PLACE FOR MORE THAN 8 HOURS ANDHEAVIER THAN 400 POUNDS ARE REQUIRED TO BE ANCHORED WITH TEMPORARYATTACHMENTS.
THE ATTACHMENT OF THE FOLLOWING MECHANICAL AND ELECTRICAL COMPONENTSSHALL BE POSITIVELY ATTACHED TO THE STRUCTURE, BUT NEED NOT BE DETAILED ON THEPLANS. THESE COMPONENTS SHALL HAVE FLEXIBLE CONNECTIONS PROVIDED BETWEENTHE COMPONENT AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT.
COMPONENTS WEIGHING LESS THAN 400 POUNDS AND HAVE A CENTER OF MASSLOCATED 4 FEET OR LESS ABOVE THE ADJACENT FLOOR OR ROOF LEVEL THAT DIRECTLYSUPPORT THE COMPONENT.
COMPONENTS WEIGHING LESS THAN 20 POUNDS OR IN THE CASE OF DISTRIBUTEDSYSTEMS LESS THAN 5 POUNDS PER FOOT, WHICH ARE SUSPENDED FROM A ROOF ORFLOOR OR HUNG FROM A WALL.
FOR THOSE ELEMENTS THAT DO NOT REQUIRE DETAILS ON THE APPROVED DRAWINGS, THEINSTALLATION SHALL BE SUBJECT TO THE APPROVAL OF THE STRUCTURAL ENGINEER ORRECORD AND THE DSA DISTRICT STRUCTURAL ENGINEER. THE PROJECT INSPECTOR WILLVERIFY THAT ALL COMPONENTS AND EQUIPMENT HAVE BEEN ANCHORED IN ACCORDANCEWITH ABOVE REQUIREMENTS.
COPIES OF THE MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OFHANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL DISTRIBUTIONSYSTEMS.
1.
2.
3.
4.
5.
6.
7.
8.
THE CAMPUS LEGACY CONTROL SYSTEM IS ALERTON.
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
N.T.S.
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL GENERALNOTES AND LEGENDS
M001
15-104 M001.DWG
M001.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
MECHANICAL SHEET INDEX
NUMBER NAME ORDER
M001 MECHANICAL GENERAL NOTES AND LEGENDS M001
M002 MECHANICAL EQUIPMENT SCHEDULES M002
MD101 MECHANICAL DEMOLITION PLAN - DATA CENTER M051
MD102 MECHANICAL DEMOLITION PLAN - GENERATOR ROOM 113C M052
M100 MECHANICAL SITE PLAN (FOR REFERENCE ONLY) M100
M101 MECHANICAL NEW WORK PLAN - DATA CENTER M101
M501 MECHANICAL DETAILS M501
M502 MECHANICAL DETAILS M502
M503 MECHANICAL DETAILS M503
M601 MECHANICAL CONTROL DIAGRAMS M601
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
24x24TITUS301FS
1
DROP IN T-BAR SUPPLY DIFFUSER
24x24 PERFORATED RAISED FLOOR TILES/PANELS TO MATCH EXISTINGRAISED FLOOR
PERF. TILEN/AA
DIFFUSER & GRILLE SCHEDULE
DIFFUSERMODEL
CFM RANGE FACE SIZE NECK SIZE MAX. NCTAG THROW
N/A
REMARKS
RAISED FLOOR SUPPLY DIFFUSERS
PERFORATED GRILLE0-100 N/A
N/A
N/A
N/A N/A
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
N.T.S.
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL EQUIPMENTSCHEDULES
M002
15-104 M002.DWG
M002.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
MAKE-UP AIR SUPPLY FAN SCHEDULE
MARK
MFR MODEL AIRFLOWDRIVETYPE FAN RPM
TOTAL STATICPRESSURE
WHEELTYPE
ELECTRICAL
OPERATINGWEIGHT
ANCHORAGEDETAIL REMARKS
MOTORSIZE V/PH/HZ
SF 1 GREENHECK SQ-90-D 350 CFM DIRECT 1,550 0.5 IN. WG. BACKWARDINCLINED
1/10 HP 115/60/1 80 LBS 8/M502 PROVIDE WITH MFR SLOPED FILTER BOX, 2IN. PLEATED FILTERS,MERV 8 FOR OUTSIDE AIR VENTILATION REQUIREMENTS
COMPUTER ROOM (CRAC) CONDENSING UNIT SCHEDULE
MARK
MFR MODEL SERVICE CFM E.A.T.
REFRIGERANT ELECTRICAL OPERATINGWEIGHT
ANCHORAGEDETAIL REMARKSTYPE CHARGE FLA MCA MOCP V/PH/HZ
CCU 1 LIEBERT MCM040 CAC-1 2,700 105°F R-410A - 1.4 1.9 15 460/3/60 291 LBS 2/M503 INSTALL PER MFR REQUIREMENTS UTILIZING EXISTING LOADING DOCKSUSPENDED FRAME WITH FRAME AUGMENTATION AS INDICATED
CCU 2 LIEBERT MCM040 CAC-2 2,700 105°F R-410A - 1.4 1.9 15 460/3/60 291 LBS 2/M503 INSTALL PER MFR REQUIREMENTS UTILIZING EXISTING LOADING DOCKSUSPENDED FRAME WITH FRAME AUGMENTATION AS INDICATED
COMPUTER ROOM AIR CONDITIONING UNIT SCHEDULE
MARK
MFR MODEL
INDOOR FAN
SENSIBLE COOLINGCAPACITY
DESIGNENVIRONMENT
ELECTRICAL FILTER
MONITORINGCARD
OPERATINGWEIGHT
ANCHORAGEDETAIL REMARKS
AIRFLOWCFM
E.S.P. IN.WG. FLA MCA MOCP
FANMOTOR HP V/PH/HZ SIZE (IN) EFFICIENCY
CAC 1 LIEBERT PX018DA 2,800 0.5 56,300 BTU/H 75°F DB, 45% RH 14.9 17.6 25 4.2 460/3/60 2 MERV 8 IS-UNITY-DP 670 LBS 2/M501 SEE NOTES BELOW THIS SCHEDULE
CAC 2 LIEBERT PX018DA 2,800 0.5 56,300 BTU/H 75°F DB, 45% RH 14.9 17.6 25 4.2 460/3/60 2 MERV 8 IS-UNITY-DP 670 LBS 2/M501 SEE NOTES BELOW THIS SCHEDULE
PROVIDE WITH INTEGRAL LIEBERT CONDENSATE PUMP AND 12" MFR SEISMIC FLOOR STAND WITH FIELD INSTALLED SKIRT AROUND EXPOSED AREA ABOVE RAISED FLOOR. AIR DISCHARGE SHALL BE DOWNFLOW INTO <E> RAISED FLOOR SYSTEM.PROVIDE WITH INTEGRAL LIEBERT SMOKE AND HIGH-TEMPERATURE, AIR AND COMPRESSOR SENSORS, AND DEVICES PER MFR RECOMMENDATIONS AND REQUIREMENTSPROVIDE LIBERT EQUIPMENT CONNECTIONS TO BUILDING AUTOMATION SYSTEM. ALL CRAC UNIT PARAMETERS SHALL BE SET TO READ/WRITE TO AND FROM BUILDING AUTOMATION
NOTES:
OUTDOOR VRF CONDENSING UNIT SCHEDULE
MARK
MFR MODEL SERVICE TONCOOLINGCAPACITY CFM
REFRIGERANT ELECTRICAL
OPERATING WEIGHTANCHORAGE
DETAL REMARKSTYPE CHARGE V/PH/HZ MCA MOCP
VCU 1 TRANE 4TVR0072B400NB MCU UNITS, WC UNIT, TC UNITS 6 72000 7240 R410A 12.125 460/3/60 16.4 20 450 LBS 4/M501 INSTALL PER MFR REQUIREMENTS
INDOOR VRF FAN COIL UNIT EQUIVALENT SCHEDULE
MARK
MFR MODEL TONCOOLINGCAPACITY
MIN OSACFM
UNIT CFMMAX
REFRIGERANT ELECTRICAL
OPERATING WEIGHT REMARKSTYPE FLA V/PH/HZ
WC 1 TRANE 4TVW0007B100NC 3/4 7500 BTU/h 30 275 R410A .23 208/1/60 18 LBS WALL MOUNTED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS
TC 1 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 25 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
TC 2 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 25 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
TC 3 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 25 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
TC 4 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 25 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
TC 5 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 25 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
TC 6 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 25 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
TC 7 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 25 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
TC 8 TRANE 4TVB0009B100NB 3/4 9500 BTU/h 35 350 R410A .17 208/1/60 27 LBS CEILING RECESSED CASSETTE UNIT. INSTALL PER MFR REQUIREMENTS. PROVIDE WITH BUILT-IN CONDENSATE PUMP.
VRF MODE CONTROL UNIT SCHEDULE
MARK
MFR MODEL SERVICE
REFRIGERANT ELECTRICAL
OPERATING WEIGHT SERVICETYPE V/PH/HZPOWERINPUT
MCU 1 TRANE 4MCUCUY6NCE000 TC-4, TC-5, TC-6, TC-7, TC-8 R410A 208/1/60 55 W 60 LBS INSTALL PER MFR REQUIREMENTS. PROVIDE TRANE 4YDK2512B0138A Y-JOINT
MCU 2 TRANE 4MCUCUY4NCE000 WC-1, TC-1, TC-2, TC-3 R410A 208/1/60 55 W 53 LBS INSTALL PER MFR REQUIREMENTS. PROVIDE TRANE 4YDK1500B0080A Y-JOINT
PROVIDE EACH INDOOR MINI-VRF UNIT WITH A MFR WIRELESS REMOTE FOR INDIVIDUAL FAN SPEED CONTROL.NOTES:
VERIFY REFRIGERANT PIPE SIZES WITH THE MFR AND SUBMIT TO PROJECT MECHANICAL ENGINEER OF RECORD FOR REVIEW.NOTES:
VERIFY REFRIGERANT PIPE SIZES WITH THE MFR AND SUBMIT TO PROJECT MECHANICAL ENGINEER OF RECORD FOR REVIEW.NOTES:
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
DN
T
T T T
COMPUTERCENTER
10
OFFICE
1
OFFICE
2
OFFICE
3
1
1
1
1
2
1
OFFICE
7
OFFICE
8
OFFICE
6
OFFICE
5
OFFICE
4
FLOOR GRILLES UNDERAND IMMEDIATELYINFRONT OF SERVERSSHALL REMAIN.(TYP.)
3
1
<E> AC UNITSUSPENDED INLOADING DOCK
1
<E> AC UNITSUSPENDED INLOADING DOCK
<E> CONDENSERUNIT SUSPENDED INLOADING DOCK
<E> WALL MOUNTEDFAN COIL UNIT
<E> COMPUTERROOM AIR
CONDITIONING UNIT
<E> DUCTED AIRCONDITIONING UNIT
<E> AC UNIT INCEILING SPACE
HALF-WALL AREA
9
P.O.R.
P.O.R.
P.O.R.
4
4
4
2
32
32
2 2
22
2
2
REMOVE FLOORGRILLES AS INDICATED.(TYP.)
COMPUTERCENTER
10
OFFICE
1
OFFICE
2
OFFICE
3
OFFICE
4
OFFICE
6
OFFICE
5
OFFICE
7
OFFICE
8
2
2
HALF-WALL AREA
9
2
2
2
22
22
2
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/4" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL DEMOLITIONPLAN - DATA CENTER
MD101
15-104 MD101.DWG
MD101.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
1.
1/4" = 1'-0"1
MECHANICAL DEMOLITION PLAN - DATACENTER
1 REMOVE <E> MECHANICAL EQUIPMENT AND DEMOLISH ALLASSOCIATED DUCTWORK, DUCT ACCESSORIES, PIPING, AND PIPINGACCESSORIES UP TO THEIR SOURCE EQUIPMENT.
2 DEMOLISH ALL EXISTING DUCTWORK, DUCT SUPPORTS, DUCTACCESSORIES, DUCT FITTINGS, DIFFUSERS, HYDRONIC PIPING ANDACCESSORIES, AND ALL OTHER ASSOCIATED MECHANICAL ITEMSSERVING THIS AREA AND REMOVE BACK TO THEIR SOURCEEQUIPMENT.
CAMPUS SHALL HAVE FIRST RIGHT OF REFUSAL OF ALL EQUIPMENTREMOVED AND DEMOLISHED.
HATCHED PATTERN INDICATES ITEMS TO BE DEMOLISHED,INCLUDING CEILING DIFFUSERS, GRILLES, AND ALLASSOCIATED RIGID AND FLEXIBLE DUCTWORK.
2.
1/4" = 1'-0"2
MECHANICAL DEMOLITION REFLECTEDCEILING PLAN - DATA CENTER
3 BLANK OFF ALL UNDERFLOOR SYSTEM DIFUSERS IN THIS AREA WITHPANELS TO MATCH EXISTING FLOOR SYSTEM. AREA WILL BECONDITIONED FROM NEW CEILING VRF UNIT.
A
LB ART
4 DEMOLISH CONDENSATE UP TO P.O.R. AS INDICATED. PREPARE FORCONNECTION OF <N> CONDENSATE LINE.
REMOVE ALL DUCTWORK AND ACCESSORIES OF SUSPENDED ACUNITS. THIS SHALL INCLUDE DUCTWORK FROM AC UNITS AND ALL INCEILING DUCTWORK.
3.
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
F
F
G
G
2
<E> TO BE REMOVEDGASOLINE EMERGENCYGENERATOR
EMERGENCYPOWER
DISTRIBUTIONROOM
113C
N.I.C.
N.I.C.
N.I.C. N.I.C. N.I.C.
N.I.C.
1
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/4" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL DEMOLITIONPLAN - GENERATOR ROOM
113C
MD102
15-104 MD102.DWG
MD102.DWG
SM
11/19/15
SM
PF
PF
11/06/2015
1/4" = 1'-0"1
MECHANICAL DEMOLITION WORK PLAN -ADMINISTRATION BUILDING
1. HATCHED PATTERN INDICATES ITEMS TO BE DEMOLISHED.
1 COMPLETELY REMOVE AND DEMOLISH ALL ASSOCIATED DUCTWORK,DUCT ACCESSORIES, PIPING, AND PIPING ACCESSORIES CONNECTEDTO <E> TO BE DEMOLISHED GENERATOR BACK TO PENETRATIONINTO ROOM. CAP AND ABANDONDED DUCTWORK AND PIPING ATWALL/CEILING PENETRAITON.
A
LB ART
2. CAMPUS SHALL HAVE FIRST RIGHT OF REFUSAL OF ALLEQUIPMENT REMOVED AND DEMOLISHED.
2 CAP OR INSTALL PLUG ON NATURAL GAS CONNECTION TO LOCATIONOUTSIDE BUILDING. SEAL PENETRATION IN BUILDING.
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
VCU
1
CCU
1
CCU
2
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
N.T.S.
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL SITE PLAN (FORREFERENCE ONLY)
M100
15-104 M100.DWG
M100.DWG
SM
11/09/15
SM
AH
PF
11/06/2015
GENERAL NOTES THIS SHEET:
THIS SHEET INDICATES APPROXIMATE LOCATION OF VCU-1, CCU-1 AND CCU-2 AT THE BUSINESS FACILITY ANDLOADING DOCK
N.T.S.2
MECHANICAL SITE PLAN
1.
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
DN
C02
C02
C02
C02
C02
C02
C02C02
C02
OFFICE
1
OFFICE
2
OFFICE
3
COMPUTERCENTER
10
OFFICE
7
OFFICE
8
OFFICE
5
OFFICE
6
OFFICE
4
5
(TYP. 5)
1
2
8"x
8"
2
CCU
1
CCU
2
CAC
1
CAC
2
REFRIGERANT PIPING PERMFR REQUIREMENTS (TYP.)
REFRIGERANT PIPING PERMFR REQUIREMENTS (TYP.)
1
HALF-WALL AREA
9
1
TC
2
TC
3
TC
4
TC
5
TC
7
TC6
TC
8
TC
1
WC
6"ø
6"ø
6"ø
6"ø6"ø
12"x
12"
6"ø
6"ø
6"ø6"ø
6"ø
6"ø
3/4"ø CD
7
12"x12"
8"x8"
3
1
VCU
1
MCU
2
MCU
P.O.C. 1"ø CD
P.O.C.1"ø CD
6
3/4"ø CD
<E> CD
3/4
"ø C
D
10'-0" WIDEWALKWAY
9
9
11
9
4
CLEAR
MIN. 4' - 0"
A
350
AA
45
AA
45
10
<E> TO REMAINEMERGENCY GENERATORAND EQUIPMENT PAD
1
SF
5/8"ø HRG3/4"ø RG
3/8"ø RL
3/4
"ø C
D3/8
"ø R
L3/4
"ø R
G
3/8"ø RL3/4"ø RG
3/8"ø RL3/4"ø RG
5/8"ø HRG
1/2"ø RL7/8"ø RG
1/2"ø RL7/8"ø RG
3/8
"ø R
L3/4
"ø R
G(T
YP
.)(TY
P.)
3/4
"ø C
D
1/2
"ø R
L7/8
"ø R
G
12
13
5/8"ø HRG
3/4"ø RG
3/8
"ø R
L
14
8
CAP AND FILL DEMOLISHEDDUCT PENETRATIONS TO MATCHEXISTING WALL FINISH
3/4"ø CD
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
GENERAL NOTES THIS SHEET:
KEY PLAN:
1/4" = 1'-0"
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL NEW WORKPLAN - DATA CENTER
M101
15-104 M101.DWG
M101.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
1/4" = 1'-0"1
MECHANICAL NEW WORK FLOOR PLAN -DATA CENTER
1. GRAYED LINES INDICATE EXISTING CONSTRUCTION, DARKENEDLINES INDICATE NEW CONSTRUCTION.
1
2 ROUTE CONDENSATE AT 1% SLOPE TO NEAREST LAVATORY/SINK TAIL-PIECE OR FLOOR DRAIN. PROVIDE WITH CONDENSATE PUMP ASREQUIRED.
3 PROVIDE GREENHECK EDJ-601 16"X16" EXTERIOR INTAKE LOUVER OREQUAL OF. SEE DETAIL 9/M502 FOR FURTHER DETAILS.
4 PROVIDE 5 FOOT LONG, 20 GA. G90 GALVANIZED SHEET METAL, BENTTO FORM A 5 FOOT RADIUS ARC, TURNING VANE INSTALLED BELOWTHE <E> RAISED FLOOR SYSTEM. VERIFY AND MODIFY AS REQUIREDTO FIT FIELD CONDITIONS. PROVIDE HILTI ANCHORS TO CONNECTBOTTOM OF SHEET METAL TO BOTTOM OF RAISED FLOOR SYSTEM ANDSELF-TAPPING DUCT SCREWS TO CONNECT TOP OF SHEET METAL TOTHE UNDERSIDE OF THE <E> RAISED FLOOR SYSTEM FRAMING.
5 PROVIDE <N> 6' HIGH MOORECO ROOM DIVIDERS IN LENGTHS ASSHOWN.
<N> CRAC CONDENSING UNITS TO MOUNT AT SAME ELEVATION UTILIZINGSAME EXISTING EQUIPMENT FRAMING AS EXISTING TO BE DEMOLISHEDUNIT IN SAME LOCATION. SEE DETAIL 1/M501 FOR FURTHERINFORMATION.
2. PROVIDE HEPA VACUUM CLEANING OF THE ENTIRE DATA CENTERUNDERFLOOR CAVITIES BEFORE AND AFTER INSTALLATION OF ALLDEVICES AND COMPONENTS.
3.
A
LB ART
6 PROVIDE DUCTWORK 1" INTERNALLY LINED.
7 15 DEGREE TRANSITION TO 12"X12" ABOVE CEILING BELLED OPENINGPER SMACNA. CHAMFER METAL FOLDED TIGHTLY INWARD 1" ON ALLFOUR SIDES.
8
9 SEE DETAIL 4/M501 FOR FURTHER INFORMATION ON <N> EQUIPMENTPAD FOR <N> VCU-1.
PROVIDE 20GA. G90 GALVANIZED SHEET METAL TO PREVENTAIRFLOW IN THE PLAN NORTH, SOUTH, AND EAST DIRECTIONS UNDERRAISED FLOOR. PROVIDE 18" EXTENSIONS AT 45 DEGREES OUTWARDAS SHOWN IN THE PLAN EAST DIRECTION. PROVIDE HILTI ANCHORSTO CONNECT BOTTOM OF SHEET METAL TO BOTTOM OF RAISEDFLOOR SYSTEM AND SELF-TAPPING DUCT SCREWS TO CONNECT TOPOF SHEET METAL TO THE UNDERSIDE OF THE <E> RAISED FLOORSYSTEM FRAMING.
10
SEE DETAIL 12/M502 FOR CONDENSATE PIPING AND PUMP INFORMATION.11
REFRIGERANT PIPING SHALL BE ROUTED UNDERNEATH RAISED FLOOR.12
REFRIGERANT PIPING SHALL BE ROUTED UP WALL TO ABOVE CEILING.13
UTILIZE TWO (2) <N> 4" RIGID METALLIC CONDUIT FOR ROUTING OFREFRIGERANT LINES AND POWER TO VCU-1.
14
PROVIDE WALL PENETRATION WITH SEALED SLEEVES.
FLEXIBLE DUCT CONNECTIONS TO ALL CEILING MOUNTED VRFCASSETTE UNITS (TC) SHALL BE A MAXIMUM OF 6" LENGTH.
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
DDCP
HINGED PANEL DOOR WITH MASTER KEYLOCK. ALL LOCKS SHALL BE ON A SINGLEKEY MASTER.
POWER TO DDCP'S, ASC'S, AND FIELDTRANSMITTERS TO BE FROM DEDICATEDCIRCUITS.
ENCLOSURE TO BE NEMA 12 RATEDFOR ALL INDOOR LOCATIONS,
NEW DDCP'S TO BE CONNECTED TOPANELS WITHRIGID CONDUIT.
2' M
INIM
UM
6' M
AX
IMIM
ANCHOR OR BOLT UNISTRUTTO WALL WITH HILTI (OR EQUAL)ANCHORS, BOLTS AND FAS-TENERS DESIGN FOR TOTALWEIGHT AND WALL TYPE PERMFRR'S RECOMMENDATIONS.
CCU
-
RIBBED NEOPRENEPAD
MECHANICAL UNIT
STEEL WASHER
NEOPRENE GROMMET
CORK PAD
<E> METAL FRAMING
PER MFR REQUIREMENTS(TYP. 2 PER LEG)
BEARING PLATE
SEE BELOW(TYP.)
STEEL WASHER
NEOPRENE GROMMET
CCU
-
<E> METAL FRAMING HIGHIN LOADING DOCK AREA.
<E> METAL FRAMING
FIVE SEGMENTS OF UNISTRUT FRAMINGPER CCU UNIT ATTACHED TO EXISTING
SUSPENDED FRAME. NEW FRAMINGCOMPONENTS SHALL BE FLUSH MOUNTEDAT SAME ELEVATION OF EXISTING FRAME.FIELD VERIFY DISTANCES AND ATTACH AS
REQUIRED.
<E> METAL FRAMING
PLAN VIEW WITH <N> UNIT
<N> ANCHORAGE FRAMING PLAN VIEW
ELEVATION VIEW
VCU
1
SEE BELOW(TYP. 4)
RIBBED NEOPRENEPAD
REFRIGERANT LINESTO INDOOR UNIT.
UNIT
STEEL WASHER
NEOPRENE GROMMET
CORK PAD
6" HIGH CONCRETEPAD WITH SHEET
METAL COVER
3/8" DIA HILTI KWIK BOLT II ANCHOR,MIN. 2" EMBEDMENT. (TYP. 4)
BEARING PLATE
8" MIN.
SIDE ELEVATION
2" MIN.
GRADE
DISCHARGE AIR
SUBTERRANEAN VAULT.SEE DETAIL 4/M503 FORFURTHER DETAILS.
CAC
1,2
SEE BELOW
GALVANIZED 18 GA., G90SHEET METAL SKIRT
FOLDED WITH 1" FOLDED LIP
SIDE ELEVATION
DUCTMATE 440 GASKET TAPE.APPLY WITH ADHESIVE TO FORM AFULL AIR SEAL BETWEEN LIEBERTUNIT AND ELEVATED FLOOR TILES
<E> RAISED FLOOR
12" HEIGHT
8" HEIGHT
8" HEIGHT12" HEIGHT
4" HEIGHT
UTILIZE SAME FRAMINGSYSTEM AS <E>
UNDERFLOOR TO SUPPORTTHE CUT TILES AROUND <N>
CRAC UNIT
LIEBERT 12"HEIGHT FLOOR
STAND
4" HEIGHT
ENLARGED VIEW
CAC UNIT
1/8 DIA 7 X 19 AIR CRAFTCABLE WITH 2 U-CLAMPS EAEND. PROVIDE THIMBLES @LOOPS - INSTALL HAND TAUTWITHOUT SLACK.
1 MAX
1/2" DIA HILTI KWIKBOLT IICARBON ANCHOR. INSTALLPER ICBO ER-4627.
2"
2-1/4
2" MIN.
1-3/4
1
PLAN VIEW - ANCHOR PLATE/ MOUNTING ANGLE
9/16" DIA HOLE1-1/4
3"
1" DIA HOLE
1-3/4
1-1/4
2-1/4
3-1/2
CONCRETE DECK.
L 3-1/2x2-1/2x1/4
1/2" DIA HILTI KWIKBOLT IICARBON ANCHOR. INSTALLPER ICBO ER-4627.MIN. 2" EMBEDMENT
3/4
L 3-1/2x2-1/2x1/4 LENGTH AS REQUIRED TOSPAN MINIMUM OF 3 FLUTES (18" MIN.)
3/8" ASTM 307 MACHINE BOLT
3/8" DIA. THREADED ROD (TYP.)
VIBREX RMXA SPRING ISOLATOR (TYPICAL)
INCREASE LENGTH AS REQUIREDTO SPAN FLUTES FOR HANGER SUPPORTS
NOTES:
1) SEE DETAIL 11 THIS SHEET FOR ANCHORAGE.2) CABLE SHALL BE 7 X 19 AIRCRAFT CABLE.3) CABLES TO BE INSTALLED HAND TAUT W/O SLACK.
3/8" THREADED-RODMAX UNBRACED LEGENTHSHALL BE 18"
SF
1
WEIGHT = 80 LBS.
FLEXIBLE CONNECTOR (TYP.)
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL DETAILS
M501
15-104 M501.DWG
M501.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
N.T.S.3
TYP. DIRECT DIGITAL CONTROL HUMANINTERFACE PANEL
N.T.S1
TYP. COMPUTER ROOM CU ANCHORAGE(CCU-1,CCU-2)
N.T.S4
VRF CU ANCHORAGE
N.T.S2
TYP. COMPUTER ROOM AC UNITANCHORAGE (CAC-1, CAC-2)
N.T.S.6
TYP. FAN CONNECTION TO STRUCTUREN.T.S.
5TYP. CEILING HUNG FAN
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
PIPING
3M #CP 25Wt FIRESTOPCAULKING OR APPROVEDEQUAL
FIRE-RATED WALLASSEMBLY
PIPE INSULATION
1.
2.
3.
3M #CP 25WBtFIRESTOP CAULKING
OR APPROVEDEQUAL
PIPING
PIPE INSULATION
U.L. LISTED SYSTEM NO. W-L-5039
F RATINGS - 1 AND 2 HRT RATINGS - 3/4, 1 AND 1-1/2 HR
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS 1 HR WHENINSTALLED IN A 1 HR FIRE RATED WALL AND 2 HR WHEN INSTALLEDIN A 2 HR FIRE RATED WALL.
PIPE HANGER INSTALLATION SHALL BE IN ACCORDANCEREQUIREMENTS PER U.L. LISTING OR APPROVED EQUAL.
REFER TO ARCHITECTURAL SHEETS FORLOCATION OF ALL FIRE-RATED WALLS.
NOTES:
PACKING MATERIALPER 3M REQUIREMENTS
FIRE-RATEDCONCRETE DECK
3M #CP25WBtFIRESTOP CAULKINGOR APRROVED EQUAL
PIPING
F RATINGS - 2,3 AND 4 HRT RATINGS - 1 HRL RATINGS AT AMBIENT - 2 CFM/SQ. FT.L RATINGS AT 400 F - LESS THAN 1 CFM/SQ. FT.
U.L. LISTED SYSTEM NO. C-AJ-1044
PIPING
3M #CP25WBtFIRESTOP CAULKING
OR APRROVED EQUAL
1.
2.
NOTES:
REFER TO 3M MANUFACTURER'S LITERATURE FOR ADDITIONALREQUIREMENTS PER U.L. LISTING, OR APPROVED EQUAL.
PIPING SUPPORT NOT SHOWN. REFER TO OTHER DETAILSAND SPECIFICATION. UNLESS SPECIFICALLY SHOWN ON THESE PLANS, NO STRUCTURAL MEMBER SHALL BE CUT, NEITHER
DRILLED NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEERAND THE DIVISION OF THE STATE ARCHITECT.
NOTE:
FILL W/ MASTIC
PIPE, FOR SIZESSEE FLOOR PLAN
SEAL SLEEVEW/ APPROVEDSEALANT
PROVIDE WALLOPENING AS REREQUIRED
1" MIN
SLEEVE
INSULATION
1.
PACKING MATERIALPER 3M REQUIREMENTS
OR APPROVED EQUAL.
FIRE-RATEDCONCRETE DECK
PIPE INSULATION
3M #CP25WBtFIRESTOP CAULKINGOR APRROVED EQUAL
PIPING
U.L. LISTED SYSTEM NO. C-AJ-5001
F RATINGS - 1-1/2, 2 AND 3 HRT RATING - 0, 1/2, 3/4 AND 1 HRL RATING AT AMBIENT - 2 CFM PER SQ. FT.L RATING AT 400 F - LESS THAN 1 CFM PER SQ. FT.
3M #CP25WBtFIRESTOP CAULKING
OR APPROVED EQUAL
PIPE INSULATION
PIPING
NOTES:
REFER TO 3M MANUFACTURER'S LITERATURE FOR ADDITIONALREQUIREMENTS PER U.L. LISTING OR APPROVED EQUAL.
PIPING SUPPORT NOT SHOWN. REFER TO OTHER DETAILSAND SPECIFICATIONS.
REFER TO 3M MANUFACTURER'S LITERATURE FOR ADDITIONALREQUIREMENTS PER U.L. LISTING OR APPROVED EQUAL.
3M #CP25WBtFIRESTOP CAULKINGOR APPROVED EQUAL
PIPING
PRE-RATEDWALL ASSEMBLY
3M #CP25WBTFIRESTOPCAULKING
OR APPROVEDEQUAL
PIPING
REFER TO ARCHITECTURAL SHEETS FOR LOCATION OF ALLFIRE-RATED WALLS.
PRE-RATED WALLASSEMBLY
F RATINGS - 1,2,3 AND 4 HRT RATINGS - 0,1,2,3 AND 4 HRL RATINGS AT AMBIENT - LESS THAN 1 CFM/SQ FT.L RATINGS AT 400 F - LESS THAN 1 CFM/SQ. FT.
U.L. LISTED SYSTEM NO. W-L-1001
NOTES:
1.
2.
PLAN
PIPE
FLOOR
2"
ELEVATION
PIPE SLEEVE (REFERENCE) - 1" MINLARGER THAN PENETRATING PIPE.
ELASTOMERIC SEAL
PIPE CLAMP
SUCTION LINE TOCOMPRESSOR OF
CONDENSING UNIT
U-BEND
FANCOILUNIT
RED. TEE
CONDENSINGUNIT SUCTION
LIQUID
TODX
COIL
FAN COILUNIT
SUCTION
LIQUID
TXV SENSING BULB
SIGHT GLASS
FILTER DRYER
ALL REFRIGERANT LINES SHALL BE WRAPPED WITH RUBITEX INSULATION OR EQUIVALENT.
REFER TO MFR'S INSTALLATION INSTRUCTIONS FOR REFRIGERANT AND INSULATION LINE SIZING.
PROVIDE LONG-LINE APPLICATION INSTALLATION ACCESSORIES WERE APPLICABLE.
NOTES:
1.
2.
3.
FLEXIBLE CONNECTION
<N> GREENHECK MODEL EDJ-601EXTERIOR WALL LOUVER 16"x16".
<E> EXTERIORCONCRETE WALL.
1. COORDINATE OPENINGS IN WALLS WITH ALLAFFECTED TRADES. INCLUDING BUT NOT LIMITED TO FRAMING AND ELECTRICAL.
CHANNEL REINFORCEMENT. SELECT SIZEPER U.M.C. 6.506.2 TABLE A6-5-F CHANNELSELECTION. SECURE TO WALL WITH HILTIBOLTS AND MIN. 2" EMBED.(TYP. 2 PER SIDE OR 12" O.C.)
NOTES:
SEE PLANS FOR DUCT SIZE.
3"
MIN.
'B'
6"
'A'
S.P. = SYSTEM STATIC PRESSURE-INCHES
FLEXIBLE CONNECTOR
HVAC UNIT
UNIT TYPE
DRAW THRU
BLOW THRU
"B"
S.P.x1.5+2"
S.P.x0.5+1"
"A"
S.P.x1.5+2"
S.P.x1.5+2"
0-20
DRAIN LINE SHALL BE ATLEAST THE SAME SIZE ASTHE NIPPLE ON THE UNIT.
NOTES:
1. ALL INTERIOR CONDENSATE DRAINSABOVE CEILING SHALL BE INSULATED.
1/4" MIN. SLOPE TOCODE APPROVEDRECEPTACLESEE PLANS FORCONTINUATION
3.
2.
4. ALL CONDENSATE DRAIN CONNECTIONS SHALL OCCURABOVE ALL EQUIPMENT FRAMING TO ALLOW FORPROPER P-TRAP INSTALLATION.
IF CONDENSATE DRAIN RUNS TOFLOOR SINK, ALLOW A MINIMUM 2"AIR GAP AT ROOF RECEPTOR.
IF HORIZONTAL RUN ISGREATER THAN 15 FT. , INSTALLVENT , SAME SIZE AS DRAIN .
3/4 "
TONS DRAIN SIZE
3/4" TUBING FROMCONDENSATE PUMP.
12"X12"ACCESS
PANEL
FIXED AIR GAP
CONDENSATEDOWN TOCONNECT TO <E>CONDENSATEPIPING..
SECURE CONDENSATE PUMPTO BEAM WITH 3/8"Ø LAGBOLT WITH 2½" IMBEDMENT(TYP. 2 PLACES).
LITTLE GIANT MODELVCMA-15ULS, CONDENSATEPUMP, 1/50 HP, 115 VOLT,60 HERTZ, 25 GPM @ 10FEET OF HEAD, APPROX.OPER. WEIGHT = 8.50LBS.
POINT OFCONNECTION
3/8"OD BARBEDDISCHARGEADAPTER
3/8"ID TUBINGFAN COIL
UNIT
FLEXIBLECONNECTION
NOTE:TRAP DEPTH SHALL BE EQUAL TO THE F/C UNITTOTAL STATIC PRESSURE PLUS 1-INCH BUT NOTLESS THAN 2-INCHES.
3/4" CD RUN AT 1% SLOPEAND CONNECT TO NEWFIXED AIR GAP.
VENT
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL DETAILS
M502
15-104 M502.DWG
M502.DWG
SM
11/04/15
SM
PF
PF
11/06/2015
N.T.S1
TYP. INSUATED PIPE THROUGH FIRERATED WALL
N.T.S3
TYP. NON-INSULATED PIPE THROUGHFLOOR/CEILING
N.T.S2
TYP. INSULATED PIPE THROUGHNON-RATED WALL
N.T.S4
TYP. INSULATED PIPE THRU FIRE RATEDFLOOR
N.T.S5
TYP. NON-INSULATED PIPE THRU FIRERATED WALL
N.T.S.6
TYP. PIPE THRU FLOOR DETAILN.T.S.
7
TYP. DOUBLE SUCTION RISERCONSTRUCTION DETAIL
N.T.S.8
TYP. CCU TO CAC REFRIGERANT PIPING
N.T.S.9
TYP. OSA INTAKE LOUVERN.T.S.
10TYP. CD CONNECTION TO HVAC EQUIP.
N.T.S.11
TYP. FIXED AIR GAPN.T.S
12TYP. WALL MOUNTED FAN COIL (WC-1)
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
THREADED ROD TO EXTENDTHROUGH WEDGE NUT AND BETIGHT AGAINST RIB.
IF PIPE IS INSULATED, USE APPROPRIATEPROTECTION SHIELD OR RIGID INSULATIONBLOCK
PROVIDE DIAGONAL BRACING PER SMACNAREQUIREMENTS, SEISMIC RESTRAINT MANUALLATEST EDITION.
"TOLCO" 2F ORAPPROVED EQUAL
2. PIPE HANGER INSTALLATION SHALL BE IN ACCORDANCEWITH SMACNA RECOMMENDATIONS AS SHOWN IN SEISMICRESTRAINT MANUAL FOR MECHANICAL SYSTEMS,LATEST EDITION.
THREADED ROD TO STRUCTURALABOVE SEE SPECIFICATIONS FOR
ROD SIZING AND DETAIL 7 THISSHEET FOR ADDITIONAL INFORMATION.
NUT
EPIC METALDECK
METAL DECK MFR.S"EPIC WEDGE NUT"
FLAT WASHER
THIS HANGER SHALL BE USED TO SUSPEND SINGLEPIPE LINES 1-1/2" AND SMALLER.
1.
NOTES:
ANCHORS DIFFER DUE TODECK CONSTRUCTION
ROD COUPLING TO MATCHPIPE HANGER ROD SIZE
SPACING AND EMBEDMENT DEPTH PER ICBO 46273.
HILTI KWIK BOLT
EMBED. MIN.
1/2"3/8"BOLT SIZE
KWIK BOLT II EMBEDMENT
5/8" 3/4"
EMBED. STD.
1-5/8" 2-1/4" 2-3/4" 3-3/4"
4-3/4"2-1/2" 3-1/2" 4"
THREADED ROD TO STRUCTURALABOVE SEE SPECIFICATIONS FOR
ROD SIZING AND DETAIL 7 THISSHEET FOR ADDITIONAL INFORMATION.
PIPE HANGER INSTALLATION SHALL BE IN ACCORDANCEWITH SMACNA RECOMMENDATIONS AS SHOWN IN SEISMICRESTRAINT MANUAL FOR MECHANICAL SYSTEMS,LATEST EDITION.
2.
THREADED ROD TO EXTENDTHROUGH WEDGE NUT AND BETIGHT AGAINST RIB.
FLAT WASHER
METAL DECK MFR.S"EPIC WEDGE NUT"
PROVIDE DIAGONAL BRACING PER SMACNAREQUIREMENTS, SEISMIC RESTRAINT MANUALLATEST EDITION.
EPIC METALDECK
NUT
IF PIPE IS INSULATED, USE APPROPRIATEPROTECTION SHIELD OR RIGID INSULATIONBLOCK
"TOLCO" 1F ORAPPROVED EQUAL
ROD COUPLING TO MATCHPIPE HANGER ROD SIZE
ANCHORS DIFFER DUE TODECK CONSTRUCTION
SPACING AND EMBEDMENT DEPTH PER ICBO 46273.
HILTI KWIK BOLT
2-3/4"
2-1/2"
1-5/8"
3/8"
EMBED. STD.
EMBED. MIN.
BOLT SIZE
3-1/2"
2-1/4"
1/2"
4"
5/8"
4-3/4"
3-3/4"
3/4"
THIS HANGER SHALL BE USED TO SUSPEND SINGLEPIPE LINES 2" AND LARGER.
1.
NOTES:
KWIK BOLT II EMBEDMENT
NOTES:
2.
SUPPORT AND BRACING, INCLUDING CONNECTIONS AND FRAMING MEMBERS, SHALL BE DESIGNED BY THE CONTRACTORIN ACCORDANCE WITH SMACNA SEISMIC RESTRAINT MANUAL GUIDELINES FOR MECHANICAL SYSTEMS (LATEST EDITION).
2-1/2" x 12 GA.SHEET METALSTRAP (MIN.)
5'-0"M
AX
TO
ST
RU
CT
UR
AL
SU
PP
OR
TIN
G M
EM
BE
R
W.P.
DU
CT
SIZ
E
2-1/2" x 12 GA.SHEET METALSTRAP (MIN.)
C BOLTS=L
TRANSVERSE BRACING SHALL BE SPACED AT 30 FT AND LONGITUDINAL BRACING SHALL BE AT 60 FT. A MINIMUM OF ATLEAST ONE BRACE OF EACH TYPE SHALL OCCUR PER DUCT RUN.
3. SEE TABLE BELOW FOR SMACNA TABLES.
DUCT SIZE
C ANGLEL
1
1
1
1(TYP.)
(TYP.)
(TYP.)
(TYP.)
1
11-18"
61-84"51-60"
37-50"25-36"
19-24"
10" DN.
DUCTDIAMETER
TABLE 5-2 MINIMUM HANGER SIZES FOR ROUND DUCT
SMACNA HVAC DUCT CONSTRUCTION STANDARDS
TWO 12 GA. OR ONE 8 GA.
12
12
12
12
12
12
MAXIMUM SPACING(FEET)
12
USE ROD'SUSE ROD'S
USE ROD'S
TWO 10 GAUGETWO 10 GAUGE
ONE 12 GAUGE
WIRE DIAMETER
TWO 1"x 16 GA.TWO 1"x 18 GA.
TWO 1"x 20GA.
1/4"
TWO 3/8"TWO 3/8"
TWO 3/8"
3/8"1/4"
ROD(INCH)
1/4"
1"x 22 GA.
1"x 20GA.1"x 22 GA.
1"x 22 GA.
STRAP
85-96"
12
USE ROD'S TWO 1-1/2"x 16 GA.TWO 1/2"
45°
NON-SEISMIC BRACING & SWAYBRACING SECURE TO STRUCTUREABOVE. (TYP. 2 SIDES)MIN. 1" X 22 GAGALVANIZED STEEL STRAP.
3"x2" CHANNELREINFORCEMENT GAUGE SHALLBE SIZED IN ACCORDANCEWITH 2013 C.M.C.
RECTANGULAR DUCT
ROUND DUCT
NON-SEISMIC VERTICAL HANGER STRAPS SHALL BE SIZED AND SPACED PER C.M.C. 2013 SECTION 603.2.
INSTALL ALL DUCTWORK PER SMACNA GUIDELINES. REFER TO "SMACNA DUCT CONSTRUCTIONSTANDARDS," LATEST EDITION.
SPACE HANGERS AT A MAXIMUM OF 6'-0" ON CENTER.
PROVIDE AND INSTALL SUPPORT HANGERS AT ALL FITTINGS.
ALL DUCTWORK, PIPING, AND CONDUIT SHALL BE BRACED IN STRICT ACCORDANCE WITH SMACNASEISMIC RESTRAINT MANUAL, MOST RECENT EDITION.
1.
2.
3.
4.
NOTES:
5.
1/2" HILTI KB-TZMIN. 3-1/2" EMBEDMENT
STRAP CONNECTION TO STRUCTUREA
LOAD RATEDFASTENERS PERSMACNA
LOAD RATEDFASTENERS PERSMACNA (TYP.)
1" X 22 GA MIN.GALVANIZEDSTEEL STRAP HANGARPER SMACNA
A
B
A
B
PLAN VIEW SECTION A-A SECTION B-B
49"
46"
6" 37" 6"
49"
7"
12"
22"
7"
34"48" 48"34"
7"
22"
12"
7"
6" 34" 6"
46"
BOTTOM OF CONCRETE PRECAST VAULT.
TOP OF CONCRETE PRECAST VAULT.
VAULT TO REMAIN MIN. 6" ABOVE GROUND ANDUTILIZED AS EQUIPMENT PAD FOR VCU-1.
46"
49"
48"
19"
29"6"
7"
6"
7"
1
2
3
1
6"
6"6"
3
3 3
2
21
1
2
2
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
As indicated
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL DETAILS
M503
15-104 M503.DWG
M503.DWG
SM
01/05/16
SM
PF
PF
11/06/2015
N.T.S2
TYP. PIPE HANGER UP TO 1-1/2"
N.T.S5
TYP. PIPE HANGER 2" AND LARGER
N.T.S3
TYP. ROUND DUCT SEISMIC BRACING
N.T.S.1
TYP. DUCT SUPPORT
N.T.S.4
VRF CU VAULT DETAIL
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016
DDCP
S/S
CSR
SAOSA
DPT
MAGNAHELIC GAUGE WITHRANGE FROM 0-2 IN.WG.
AI
CO2
AI
CO2
AI
CO2
AI
CO2
AI
CO2
AI
CO2
AI
CO2
AI
CO2
AI
CO2
AI
CO2
AI
MDT
AI
MDT
AI
MDT
AI
MDT
AI
MDT
AI
MDT
DO AOAI
SF
1
OFFICE 1 OFFICE 2 OFFICE 3 OFFICE 4 OFFICE 5 OFFICE 6 OFFICE 7 OFFICE 8 HALF-WALLAREA 9
COMPUTERCENTER 10
MD MD MD MD MD MD
DO
S/S
CCU
1
DO
S/S
CCU
2
COM
VCU
2
DO
<E> FIREALARM
SYSTEM
AI
CPA (700 PPM)
2 2 2 2 2 2 2 2 2 2
1 1 1 1 1 1
FO OIR SE S N
S
SIRET
E RG
O RT E FO F CA L I
C A
AM
C
Exp. 9-30-16
ET AM
IH A N
O
AP
PDE
LU
NUF D
ER
I AN
L
ENITN
E
LA
GNE
No. 24311
SCALESUBMITTAL DATE
SHEET TITLE
SHEET NUMBER
CAD FILEPROJECT NUMBER
APPROVED BY
CHECKED BY
DESIGNED BY
DRAWN BY
FILE NAME
LINE IS 2 INCHES
AT FULL SIZE(IF NOT 2"-SCALE ACCORDINGLY)
DATE DRAWN
AGENCY APPROVAL
PROJECT
KEYED NOTES THIS SHEET:
N.T.S.
EMERGENCYGENERATOR AND
DATA CENTER HVACUPGRADES
RIO HONDO COLLEGE3600 WORKMAN MILL RD.,
WHITTIER, CA 90601
MECHANICAL CONTROLDIAGRAMS
M601
15-104 M601.DWG
M601.DWG
SM
11/03/15
SM
PF
PF
11/06/2015
N.T.S.1
DATA CENTER HVAC DDC DIAGRAM
1 TAPE MOISTURE DETECTORS TO SLAB IN DATA ROOM UNDERFLOORSYSTEM. MOISTURE DETECTORS SHALL FORM A 2X3 GRID WITHEXTREMITIES AT 10' FROM PERIMITER OF DATA CENTER FLOOR.
2 200-1,000 PPM (TRANSMITTED AS 0-10V SIGNAL).
REVISIONS
NUMBER DESCRIPTION DATE
1 50% SD SET 12/04/2015
2 100% CD SET 04/06/2016