Sensibilidad (A) Sensivity
P23261WRU-10 K
0.03-3A 0.03 , 0.1, 0.3 , 0.5 , 1 , 3 INS , SEL , 0.02 , 0.1, 0.2 , 0.3 , 0.4 , 0.5 , 0.75 , 1
Electronic earth leakage protection relay with earth leakage reclosing WRU-10 K 0.03 - 3A
M049A01-03-18A
PRELIMINARY CONSIDERATIONS VERIFICATION UPON RECEPTION
Ensure that : - The unit meets the specifications described in your order. - The unit has not suffered any damage during transport.
You may download more information from our website: www.circutor.es
SAFETY PRECAUTIONSIn order to ensure that the unit is used safely, all people installing or handling it must follow the general safety measures and warnings described in this quick guide.
The WRU-10k is a unit designed specifically to be installed in an electric panel or enclosure, and is attached to the DIN rail or panel via an accessory. It has an LED (ON) indicating the presence of voltage. Even if this LED is not on, the user must still verify that the unit is disconnected from all power supplies
INSTALLATION AND START-UP
IMPORTANT !
!
GENERAL DESCRIPTION
Installation on the DIN rail. All active conductors that supply the loads, or the section of the installation that requires earth leakage protection with this unit must pass through the hole. In single-phase installations (phase and neutral, L and N), three-phase installations (phases L1, L2, and L3) or three-phase plus neutral (L1, L2, L3 and N). Depending on the insulation level of the wiring, four cables with a cross-section of 35
2 2mm can be passed through, but 25 mm cables are recommended. All connections must remain inside the electric panel. Remember that when the unit is connected, touching the terminals, opening the covers or removing elements may provide access to parts that are hazardous to touch. Do not use the unit until it is fully installed. The unit must be connected to a fuse-protected power circuit in accordance with its power supply range and consumption. In turn, the power circuit must be equipped with a circuit breaker switch or
2equivalent device to disconnect the unit from the power supply network. A cable section of 1-1.5 mm is recommended for wiring. The recommended torque is 0.5-0.6 Nm and insulation should be removed from 7 mm of cable
This quick guide contains information and warnings that must be followed by the user to ensure safe operation of the unit. The unit should not be used under normal operating conditions until it is installed in its final location in the electric panel.
When it is likely that the unit has lost its safety protection (visible signs of damage), it should be disconnected from the power supply. In such a case, contact a qualified service technician or our S.A.T. (Technical Assistance Service).
UNIT INSTALLATION
Technical Assistance Service (S.A.T.)If you have any questions about the operation of the unit or any failures, contact our technical assistance service
Tel: 902 449 459 (Barcelona), SPAIN Tel: (+34) 93 745 29 00 (out of SPAIN)email: sat@circutor.com
Vial Sant Jordi s/n08232 Viladecavalls (Bacelona) SPAIN
Wheight : 168 gr
REC
- DELAY SETTINGS - SETUP MENU ROTATION
- AUTO/MAN SETTINGS
- UNIT LOCKING SETTINGS
REC
REC
REC
R
. DESCRIPTION OF THE LEDS AND BUTTONS
Indication of the unit status via display and 2 LEDs. Settings and programming of the unit via 5 buttons. TEST and RESET of the unit via 2 buttons.
- SETUP PROGRAMMING
- CHANGE SCREEN
- GREEN LED: Unit ON- RED LED, trip.
- blinking LED: Manual reclosing.l- LED Interlocking ofReclosings
- RESET BUTTON
- TEST BUTTON
LED / DISPLAY INDICATIONS.- RELAY TRIPPED. The display/LED changes from green to red. The cause for the trip is shown.
- STATUS BETWEEN RECLOSINGS.LED indicates interlocking when blinking.
- . INTERLOCKING SIGNALS LED not blinking. The maximum number of automatic reclosings, as configured, has been reached.- NO. OF RECLOSINGS, Partial, by pressing the PROG button (floating page), it indicates the configured reclosing sequence. Total, by pressing the PROG button twice (set page).
.RECLOSING THE UNIT- DUE TO TRIP / INTERLOCKING FROM RECLOSINGS. 1. Enabled.Automatic (TRIP due to leakage current, but not locked). 2. Manually RESET the unit. 3. Remote trip signal. Input 1-2. It only recloses via remote signal. In cases 2 and 3, the partial reclosing system meter goes to zero.
( t , I ,Rec and std/+ )d dRELAY PARAMETER SETTINGS - , t . dTRIP DELAY SETTINGS . When you push and hold the td key, the message and PROG
. two values appear on the screen The smaller indicates the current configured value and t . d the larger indicates the values to be configured which you can toggle through by pressing When the selected value is displayed, wait for the unit to validate the value as having been saved to the settings by showing the SAVE message.- , I . I d dSENSITIVITY SETTINGS Pressing the I key performs the operation with the same modus operandi as the previous setting.- , std/+ . CONTACT STATUS SIGNALLING Pressing this key selects the status of the output relay contacts that signal interlocking. (Std) (+) NA .NC nothing appears on the display and NO the symbol appears- . CONFIGURE AUTOMATIC RECLOSING, MANUAL Before pressing REC you must unlock the security lock. When REC is pressed, the automatic reclosings for differential relay trips are activated on the main screen.
REC
The Test trip (red button) may only be manually reclosed by pressing the RESET key (Case 2)
PROGSETUP SETTINGS
SREC NO. RECLOSINGS SEQUENCE TIMES RESET TIME
REC
2 30 20 seg + 40 seg + 28 x 5 min 15 min
FACTORY PRESETS
The unit can reset to its factory-installed values in a SETUP sub-menu. Press and hold PROG and then press to get to the FACT sub-menu. When the device is reset, the total td
reclosings meter goes to zero and the relay is reset.
By pressing and holding the td and Id keys for more than 2 seconds, you can lock the setup menu. It shows BLOQ YES if it is locked, BLOQ NO if not.
MENU LOCKING/UNLOCKING
Test TEST
Leakage current Instantaneous value
Trip cause Display message
Dif/ valueDifferential
Magnetotérmica MAG
Other display MESSAGES
SAVEEXITOVR
Validates configuration valuesLeaves programming mode
Value reading out of range
Parameters Non-configurable values
Trip current 30 mA
Trip time INS
Código Tipo Sensibilidad (A) Retardo disparo (seg.) Code Type Sensitivity Tripping delay
To operate downstream from the WRU-10 k relay safely, manually lower the Kopps circuit breaker switch
SAT 1 - General unit error. Disconnect the unit and call the Technical Assistance Service (SAT).SAT 2 - Factory-installed values, a memory reading / writing problem has caused the unit to reset to its factory-installed values. The message SAT 2 is shown on the display until an operator pushes the RESET button.
SAFE DISCONNECTION
ERROR MESSAGES
1-2
56
78
9
10
11
12
EXTERNAL RESET
DESCRIPTION OF THE TERMINALS
RELAY OUTPUT CONTACT LOCKING NC RELAY OUTPUT CONTACT LOCKING
POWER SUPPLY 230 Vac (PHASE or NEUTRAL)
POWER SUPPLY 230 Vac ( NEUTRAL or PHASE)
RELAY OUTPUT CONTACT TRIP NO
RELAY OUTPUT CONTACT TRIP SHARED
RELAY OUTPUT CONTACT TRIP NO
CIRCUIT BREAKER STATUS
Voltage-free, uninsulated
Nominal Current: 0.25 Aac
Rated Voltage: 230 Vac
Nominal Load: 62.5 V·A
Protected by varistor: 420 Vc.a.-10Ac.a
l: 5 Ac.aNominal Current
l: 250 Vc.aRated Voltage
: 1.250 V·ANominal Load
- SENSITIVITY SETTINGS
PROG
Type A super-immunised electronic earth leakage relay with 28 mm built-in toroidal. Device with AUTOMATIC EARTH LEAKAGE RECLOSING.
Symbol in the LCD. It has a programmable output relay for tripping the main relay. It REC
has a voltage-free input for external tripping and rearming. Assembly on DIN rail 46277 (EN 50022) or on a 72 x 72 panel using an accessory (M5ZZF1). The display shows settings values and instantaneous leakage current values (TRMS).
If the unit is used in a manner other than that specified by the manufacturer, its protection may be compromised.
Unit power supply Operating conditions Safety
WIRING USING PLUG-IN TERMINALS
Voltage 230 Vc.a. +/- 30% Frequency 50/60 HzPower 4,5 VA
Temperature -20....+ 70º C Relative humidity 5.... 95% Max. working altitude 2.000mProtection IP20
Category III, 300 Vac EN61010Double-insulated electric shock protection class IIImmunised against shock waves up to 2kV
FEATURES
IMPORTANT!
Use the button to move through the sub-menus, PROG and use the button to display the values to be selected. Press to validate a value. The unit PROGsaves the value and displays SAVE, exiting programming mode. If the keypad is inactive for some time, the unit will automatically exit programming mode and show EXIT on the display without changing the configuration.
CONNECTION DIAGRAMS
SETUP MENU
PLUG-IN TERMINALS
Earth leakage protection and automatic reclosing via an external circuit breaker element associated with output 9-11.
Kopps circuit breaker
ACCESSORIES
PROGRAMMING RECLOSING SEQUENCES AND AUTO/MANUAL
Electronic earth leakage protection relay with earth leakage reclosing WRU-10 K 0.03 - 3A
NL1 L2 L3
CARGA / USE
ON / OFF externoExternal ON/OFF
WRU-10
4 5 6 3
9 10 117 8
1 2
3
1
2
12
RECREC
Automatic reclosing activated
CIRCUIT BREAKER MCB. 2 POLES WITH NO EXTERNAL SIGNALLING
CIRCUIT BREAKER MCB. 4 POLES WITH NO EXTERNAL SIGNALLING
Type Code In (A)
MCB.P C-2p -6A [*] P20210 6
MCB.P C-2p -10A [*] P20211 10
MCB.P C-2p -16A [*] P20213 16
MCB.P C-2p -20A [*] P20214 20
MCB.P C-2p -25A [*] P20215 25
MCB.P C-2p -32A [*] P20216 32
MCB.P C-2p -40A [*] P20217 40
MCB.P C-2p -50A [*] P20218 50
MCB.P C-2p -63A [*] P20219 63
Type Code In (A)
MCB.P C-3p+N-10A [*] P20221 10
MCB.P C-3p+N-16A [*] P20223 16
MCB.P C-3p+N-20A [*] P20224 20
MCB.P C-3p+N-25A [*] P20225 25
MCB.P C-3p+N-32A [*] P20226 32
MCB.P C-3p+N-40A [*] P20227 40
MCB.P C-3p+N-50A [*] P20228 50
MCB.P C-3p+N-63A [*] P20229 63
CIRCUIT BREAKER MCB TECHNICAL FEATURES
CIRCUIT BREAKER
REMOTE CONTROL
Control current 1.5 A
Activation impulse 20 ms
Deactivation impulse 20 ms
MECHANICAL FEATURES
Assembled DIN rail
Mechanical w orking life 20000 operations
Weig 2 poles : 375g / 4 poles: 615 g
Dimensions 52.9x85x72,9 mm
Protection degree IP 20 (DIN 40050)
M049A01-03-18A
No CNo
CONTACTS 230V~; 5A
CONTACTS 230V~; 0,25A
R
Gauges In (A)
Nominal cut-off power
Control voltage
Working frequency
Operating temperature
Storage temperature
6 -10 -16 -20 -25 -32 -40 -50 -63
6 …63 A : 10 kA
210... 240 Vac
50/60 Hz
-25....+55 ºC
-40....+ 70 ºC