Post on 29-Aug-2020
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Inspection Type Last EditedTime InInspectionId
ELEANOR ROOSEVELT HS - MANHATTAN, 411 EAST 76 STREET, MANHATTAN, NY, 10021School:
3485 2020-02-11 07:24AM 2020-08-24 04:36PMARCHITECTURAL - SENIOR
3506 2020-02-11 08:51AM 2020-02-12 02:24PMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Dimitri Saliari
Principal Organization Eleanor Roosevelt HS - Manhattan
Meeting with Principal? Yes
Principal Feedback The principal had no comments on the physical condition of the
building at this time.
Custodian James McKillop
Fireman Israel Santiago
Building Square Footage 66,000
Comments on the Area (Square Feet) None
Comments on the Stories (Floors) plus Basements 5+B
Comments on the Year Built 2003
Comments on the Student Population 530
Comments on the Staff Population 56
Comments on the Number of Classrooms 24
Weather Heavy Rain
Facade Photo
East 76th Street - Southeast view
Main Entrance Photo
Facade A - East 76th Street
Page 1 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural InspectionRoof Photo
Roof 1 - Southeast view
Have any Systems/Major Building Components been upgraded? Systems: Complete Interior renovation (conversation to school
use); Window/Guards, Roofing replacement (full)
Years: 2003
Systems: Coping, Parapet, Exterior Masonry repairs
Years: 2007
Systems: Coping Flashing, Parapet, Roofing repairs (partial)
Years: 2010
Systems: Window Repairs (partial)
Years: 2012
Systems: Partial Roof repairs, Bulkhead repairs; Library
Upgrades; 2nd Floor Corridor Flooring upgrade.
Years: 2019
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? Yes
Year Leased 2003
Inspection Type Full Inspection
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
Other Floor Structure Floor Structure Corridor adjacent
to Room 415FiremanIsrael
Santiago
Page 2 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Accessibility
Accessibility Status Question Response
Is the Primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are All floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,
Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
YesYesCorridor and Lobby H/C Lifts
YesYesInterior Corridor Doors And
Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
YesYesInterior Ramps
Rooms & Spaces
Art Rooms
Yes YesRoom 212
Auditorium
Yes Yes1st Floor Yes Yes
Cafeteria
Yes Yes2nd Floor Yes Yes
Classrooms
Yes Yes2nd - 5th Floors
Computer Rooms
Yes YesRoom 518
NoGymnasium
Library
Yes YesRoom 511
Main Office
Yes YesRoom 108
Multi-purpose Room
Yes YesRoom 218/219 Yes Yes
Nurse's Office
Yes YesRoom 304
NoPool
Science Lab
Yes YesRooms 414 and 417
Toilet Rooms (boys)
Yes Yes1st - 5th Floors
Toilet Rooms (girls)
Page 3 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
Yes Yes1st - 5th Floors
Toilet Rooms (staff)
Yes Yes1st - 5th Floors
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
Does not existAREAWAY
Does not existAWNINGS AND CANOPIES
Does not existCHIMNEY
InspectedCOPING
Condition 4- Between Fair and Poor
CAST STONE:OPEN TRANSVERSE JOINTS WITH
DAMAGED CAULKING
Deficiency
Deficiency Location/Instance
25Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 4 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
COPING
Deficiency Photo 1
Facade A
Violations No violations recorded
TERRA COTTA:OPEN TRANSVERSE JOINTS WITH
DAMAGED CAULKING
Deficiency
Deficiency Location/Instance
60Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Violations No violations recorded
TERRA COTTA:CRACKED/BROKEN PIECESDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 5 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
COPING
Deficiency Photo 1
Facade B
Violations No violations recorded
CAST STONE:CRACKED/BROKEN PIECESDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE-IN-KIND
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
METAL:DETERIORATED DOOR AND FRAME - MINOR
DETERIORATION
Deficiency
Deficiency Location/Instance
3Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 6 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo 1
Exit 1 shown, similar condition at Exit 3
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
STUCCO/PLASTER:MINOR CRACKS/SPALLINGDeficiency
Roof Plan Reference
Elevation
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit 1
Violations No violations recorded
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
20,000Replacement Quantity
Replacement Uom S.F.
Instance on All Facades Inspected
Page 7 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
3- FairInstance Condition
Instance Quantity 20,000
Instance Quantity Uom S.F.
BRICK:MINOR CRACKS AND SPALLINGDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
5Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
STONE:OPEN JOINTSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
20Deficiency Quantity
Quantity Uom L.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 8 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Exit 1
Violations No violations recorded
BRICK:MASONRY SILLS - OPEN JOINTSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
15Deficiency Quantity
Quantity Uom L.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Above main entrance
Violations No violations recorded
STONE:CHIPPED/SPALLED/BROKEN PIECESDeficiency
Roof Plan Reference
Page 9 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Elevation Reference Facade A
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Deficiency Photo 2
Facade A - Street level
Violations No violations recorded
BRICK:DETERIORATED MASONRY SILLSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
15Deficiency Quantity
Quantity Uom L.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 10 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Facade A - 3rd level
Violations No violations recorded
STONE:DETERIORATED CONTROL/EXPANSION JOINTS
WITH DAMAGED CAULKING
Deficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
10Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
Does not existLOADING DOCK
Does not existLOUVER
InspectedPARAPETS
MasonryMaterial Type(s)
6,000Replacement Quantity
Replacement Uom C.F.
Instance on All Parapets Inspected
3- FairInstance Condition
Instance Quantity 6,000
Instance Quantity Uom CF
BRICK:OPEN JOINTSDeficiency
Page 11 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
PARAPETS
Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Violations No violations recorded
BRICK:MINOR CRACKS, SPALLINGDeficiency
Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Violations No violations recorded
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 15,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
Page 12 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOF BARRIER
4- Between Fair and PoorCondition
RAILINGS/PANELS:DETERIORATED, MAJOR RUSTINGDeficiency
Deficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1 - Facade A
Violations No violations recorded
RAILINGS/PANELS:DETERIORATED, MINOR RUSTINGDeficiency
Deficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
Does not existROOF CAGE
Does not existROOF FENCE
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on Modified Bitumen:All Roofs Inspected
3- FairInstance Condition
Instance Quantity 15,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2003
Source of Installation Year Documented
Page 13 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
No deficiencies recordedDeficiency
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
InspectedBULKHEAD/PENTHOUSE
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
InspectedDUNNAGE STEEL
3- FairCondition
MINOR RUSTINGDeficiency
Deficiency Location/Instance
250Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 1
Deficiency Photo 2
Roof 1
Violations No violations recorded
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
Does not existBUILDING CHEEK/FLANK WALLS
Does not existRAILINGS
Does not existSTAIRS/RAMPS
InspectedWINDOWS
6,000Replacement Quantity
Page 14 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
WINDOWS
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Double Hung:All Facades Inspected
3- FairInstance Condition
Instance Quantity 6,000
Instance Quantity Uom S.F.
Installation Year 2003
Source of Installation Year Documented
ALUMINUM - DOUBLE HUNG:INOPERABLE BALANCEDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facade A
15Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE BALANCES
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 219
Violations No violations recorded
ALUMINUM - DOUBLE HUNG:AIR AND WATER
INFILTRATION, OPEN JOINTS WITH DAMAGED
CAULKING
Deficiency
Page 15 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
EXTERIOR
WINDOWS
WINDOWS
Roof Plan Reference
Elevation
Elevation Reference Facade A
40Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 219
Violations No violations recorded
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor (240 Seats) Inspected
Ceiling
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor (240 Seats) Does not exist
Fixed Seating
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
CONCRETE:CRACKSDeficiency
Near StageDeficiency Location/Instance
40Deficiency Quantity
Page 16 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Stage
Violations No violations recorded
Sliding-folding Partition
Instance on 1st Floor (240 Seats) Does not exist
Stage
Instance on 1st Floor (240 Seats) Inspected
Stage
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor (240 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor (240 Seats) Does not exist
CAFETERIA
Instance on 2nd Floor (1200 SF) Inspected
Ceiling
Instance on 2nd Floor (1200 SF) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 2nd Floor (1200 SF) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 2nd Floor (1200 SF) Does not exist
Floor Finish
Instance on 2nd Floor (1200 SF) Inspected
3- FairInstance Condition
Page 17 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Floor Finish
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
South Side, East Side, North Side of RoomDeficiency Location/Instance
70Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
North Side of Room
Violations No violations recorded
Sliding-folding Partition
Instance on 2nd Floor (1200 SF) Does not exist
Stage
Instance on 2nd Floor (1200 SF) Does not exist
Walls
Instance on 2nd Floor (1200 SF) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 2nd Floor (1200 SF) Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Corridor near Room 515Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 515
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 3- Fair
Page 18 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Corridor near Rooms 201, 220, 325, 415, 518 and othersDeficiency Location/Instance
700Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 415
Violations No violations recorded
EPOXY FLOORING:DETERIORATED SUBSTRATEDeficiency
Rooms 414, 417Deficiency Location/Instance
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 414
Violations No violations recorded
InspectedSpecialties
InspectedClassroom Locker(s)
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existFixed Seating
InspectedWalls
Condition 2- Between Good and Fair
GYPSUM BOARD:DETERIORATEDDeficiency
Room 321, Corridor near Main Office, Corridor near Room 516Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 19 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo 1
Corridor near Main Office
Violations No violations recorded
Does not existGYMNASIUM
InspectedINTERIOR DOOR HARDWARE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on 2nd Floor Inspected
Ceiling
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 2nd Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LIBRARY
Instance on Room 511 Inspected
Built-in Furnishing
Instance on Room 511 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Ceiling
Instance on Room 511 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 511 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 511 Inspected
Page 20 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
LIBRARY
Floor Finish
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 511 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
LOCKER ROOM
Instance on 2nd Floor - Boys (78 Lockers) Inspected
NoAlternative Use
Instance on 2nd Floor - Girls (54 Lockers) Inspected
NoAlternative Use
Ceiling
Instance on 2nd Floor - Boys (78 Lockers) Inspected
2- Between Good and FairInstance Condition
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
South Side of RoomDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
South Side of Room
Violations No violations recorded
Instance on 2nd Floor - Girls (54 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 2nd Floor - Boys (78 Lockers) Inspected
3- FairInstance Condition
METAL:DAMAGED LOUVERDeficiency
EntranceDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Page 21 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
LOCKER ROOM
Door(s)
Entrance
Violations No violations recorded
Instance on 2nd Floor - Girls (54 Lockers) Inspected
3- FairInstance Condition
METAL:DAMAGED LOUVERDeficiency
EntranceDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
Floor Finish
Instance on 2nd Floor - Boys (78 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls (54 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Locker Room Lockers
Instance on 2nd Floor - Boys (78 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls (54 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 2nd Floor - Boys (78 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 2nd Floor - Girls (54 Lockers) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
MULTI-PURPOSE ROOM
Instance on Room 218/219 Inspected
Ceiling
Instance on Room 218/219 Inspected
2- Between Good and FairInstance Condition
TECTUM:DAMAGED/MISSINGDeficiency
Center of RoomDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Page 22 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Ceiling
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Center of Room
Violations No violations recorded
Door(s)
Instance on Room 218/219 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Room 218/219 Does not exist
Floor Finish
Instance on Room 218/219 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on Room 218/219 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage
Instance on Room 218/219 Does not exist
Walls
Instance on Room 218/219 Inspected
2- Between Good and FairInstance Condition
MIRRORS:BROKEN/DAMAGEDDeficiency
East Side of RoomDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
East Side of Room
Violations No violations recorded
GYPSUM BOARD:DETERIORATEDDeficiency
North Side, West Side of RoomDeficiency Location/Instance
60Deficiency Quantity
Page 23 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Walls
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West Side of Room
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on Room 218/219 Does not exist
Does not existPOOLS
SCIENCE DEMO ROOM
Instance on Rooms 402, 403, 409 Inspected
NoAlternative Use
Fixed Equipment
Instance on Rooms 402, 403, 409 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE LAB
Instance on Rooms 414, 417 Inspected
NoAlternative Use
Fixed Equipment
Instance on Rooms 414, 417 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
SCIENCE PREP ROOM
Instance on Room 415 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 415 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? Yes
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 24 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
InspectedStairs and Landings
Condition 2- Between Good and Fair
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Stairs A/2, B/2Deficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/2
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 3- Fair
STEEL COLUMNS/BEAMS:DETERIORATED CONCRETE
FIREPROOFING
Deficiency
BasementDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Electrical Room
Violations No violations recorded
InspectedFLOOR STRUCTURE
Condition 4- Between Fair and Poor
CONCRETE:CRACKS/SPALLED/REINFORCEMENT
EXPOSED
Deficiency
1st floorDeficiency Location/Instance
5Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Page 25 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo 1
Ejector room
Violations No violations recorded
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
BasementDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Room 132A
Violations No violations recorded
CONCRETE SLAB ON GRADE:THRU CRACKSDeficiency
BasementDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Room 132A
Violations No violations recorded
CONCRETE:CRACKS/SPALLED/REINFORCEMENT
EXPOSED
Deficiency
4th floorDeficiency Location/Instance
180Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 5Urgency of Action
LEVEL 5Purpose of Action
Page 26 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo 1
Corridor Near Room 415
Violations No violations recorded
METAL DECK AND CONCRETE:DETERIORATEDDeficiency
BasementDeficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Room 132A
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Masonry
Condition 3- Fair
BRICK:OPEN JOINTSDeficiency
BasementDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Electrical Room
Violations No violations recorded
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedVAULTS-BUNKERS
Does not existFoundation Walls
Page 27 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Does not existSlab Structure
Does not existVault/Ash Hoist Doors and Framing
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existStalls
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
ACOUSTIC TILES:DAMAGED/MISSINGDeficiency
Room 407Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 407
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
Page 28 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
SITE Inspected
Does not existCONTAINERIZATION
Does not existDRAINAGE SYSTEM FOR ASPHALT
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Concrete Covering
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
Does not existFENCES
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along East 76th StreetDeficiency Location/Instance
125Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along East 76th Street
Violations No violations recorded
HEAVINGDeficiency
Along East 76th StreetDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along East 76th Street
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
Does not existAsphalt
InspectedConcrete
Page 29 of 30 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
M855Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
Does not existStudent Non-Use
Does not existStudent Use
Does not existPLAYGROUNDS
Does not existPLAYING SURFACE
Does not existRETAINING WALLS
Does not existSEATING
Does not existSITE WALLS (NOT RETAINING WALLS)
Does not existSTAIRS/RAMPS: EXTERIOR