  • #1

    #2

    PreviousinForum:slipringethernettest NextinForum:Perhapsordinary(primary)batteriescanberecharged.Iwasableto.

    parimalamActiveContributor

    JoinDate:Feb2009Posts:16

    HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/14/20099:24AM

    Hi,Goodday.Thisismyfirstpostonthisforum.wehaveoneofour13.8KV,12.5MW,turbinealternatorhavinghighPDvalues,somespecilistsaysthisalternatorneedstoberewindedtoavoidfailureofwinding.presentlythisgeneratorisrunningonloadabout11MW.myquestionhereis,howexactlytheresultsarePDmeasurements,itisnecessarytodorewindingthisalternatortoavoidunexpectedfailure???isthereanywayonecanprolongthelifeofthisalternatorhavinghighPDvalue.Irequestspecilistinthisforumtorespondtothisqueryasquicklyaspossible,sothatitwillbehelpfultotakedecisiononthisissue.kparimalam@gmail.com,+6592326838

    thanksandbestregardsK.Parimalam

    Interestedinthistopic?ByjoiningCR4youcan"subscribe"tothisdiscussionandreceivenotificationwhennewcommentsareadded.

    JoinCR4,TheEngineer'sPlaceforNewsandDiscussion!

    CommentsratedtobeGoodAnswers:Thesecommentsreceivedenoughpositiveratingstomakethem"goodanswers".

    #5"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/15/200912:24PM(score2)

    Commentsratedtobe"almost"GoodAnswers:Checkoutthesecommentsthatdon'tyethaveenoughvotestobe"official"goodanswersand,ifyouagreewiththem,ratethem!

    #8"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/17/20098:35PM(score1)

    CJMcGillGuru

    JoinDate:Jul2008Location:SoCalUSAPosts:563GoodAnswers:24

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/200912:18AM

    HiParimalam,welcome.

    IthasbeenafewyearssinceIdealtwithlargemotorassessmentandrepair,andIamsurprisedthatyouhavenotreceivedanypostssofar,butIthinkyouwoulddowelltogetinputfromseveralsourcesthatoffertheseservicesprofessionally.

    Partialdischarge(PD)whenidentifiedathighlevels,especiallywhenacontinuousmonitoringhasshowadramaticincreaseinlevels,isaverygoodindicatorofseriousdegradationintheinsulationorcracksinthebarsetc.Sometimeserrorsinplacingthewedgesorflawsinthemetalscanbegintoproducethesedischargepatterns,andusuallyseriousconsequencesarepending.

    HereareafewquicklinksIfoundthatmayhelpyou.

    discussioninformationanddefinitioninformationanda

    supplierofequipmentandservicesspecifictoyourneed

    Hopeyougetwhatinformationyouneedinatimelymanner.

    Regards,CJ

    __________________Idonot'knowitall',butiwilladmitthatIwouldliketo.CJM

    myn1996Commentator

    JoinDate:Jan2009Location:PhilippinesPosts:60

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20092:27AM

    Parimalam,

    AhighPDreadingdoesnotmeanthatthegeneratorneedsrewindingasap.Aswithallothermethodsoftestinganddiagnostics,PDisnotonlyasciencebutratheritisalsoanart.

    Forexample,EquipmentAmightshowahigherPDvaluecomparedtoEquipmentB.However,experiencedoesnotalwaysshowthatEquipmentAfailedsoonerthanEquipmentB.InfactEquipmentAlastedtoitsnormallifespanasifitsPDvalueiswithinnormalrange.

    Additionally,wasthisequipmenttestedbeforewithPD?Ifitwastested,whatwheretheresults?ComparedtothepastPDresults,isthe

    Home News&AnalysisProducts&Suppliers

    StandardsLibrary

    ReferenceLibrary

    EngineeringCommunity

    IHSGlobalSpecisnow

    SearchCommunityCommunity GO

    CR4TheEngineer'sPlaceforNewsandDiscussion Login|Register

  • #4Inreplyto#2

    #6Inreplyto#4

    #3

    #5

    GoodAnswers:4 presentPDvaluetoohigh?Istherateofincreaseacauseofalarm?

    Now,thisiswheretheexperienceofthetestingengineercomesin.HistoricalPDdatawouldgreatlyhelpinanalyzingthepresentone.Awisetestingengineerwouldnotdependononlyjustonetestingmethod.Weretheretestsperformedonthisgeneratorbyyourspecialist?Whatarethesetests?Whatdidtheresultsimply?

    AdditionaltestishighlyrecommendedtoconfirmthePDfindings.AnFDS(frequencydomainspectroscopy)orDFR(dielectricfrequencyresponse)ifyouwanttheotherterminology,isstronglyrecommendedforthissituation.

    __________________Patriotismisthelastrefugeofscoundrels

    parimalamActiveContributor

    JoinDate:Feb2009Posts:16

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20099:44AM

    DearCJMcGillPoweruser,myn1996Associate,InstruformParticipant,

    Ithankallofyoufortakingtimeandprovidingguideline,andIamveryhappytoheartheresponsesandnowIwillfurtherexploreasperyourrecommendationsandalsotolookforthetestsuchasFDS(frequencydomainspectroscopy)orDFR(dielectricfrequencyresponse).canyoupleaseadvicemethebestmethodforPDmeasurement,asofnowwehavemeasuredwithonlinePDmeasurementonlyonceusingtoshibaequipmentandusedinternalsinglewindingtemperatureresistorasasensingelementforthistest.AlsowefoundlotsofwhitepowderonrunningturbinegeneratorandthiswhitepowderbecauseofPDactivityisitnot??.willCO2cleaningonrunninggeneratortoremovethesewhitepowderisnecessary,supposeweuseCO2cleaningisthereanychancethatwemaydamageinsulationfurtherleadingtoPD???advicerequired.

    Thanksandbestregards

    K.Parimalam

    CJMcGillGuru

    JoinDate:Jul2008Location:SoCalUSAPosts:563GoodAnswers:24

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20091:34PM

    BynowyouhavereadtheexcellentinformationfromSiswanto,withgreatdetailedphotos.(GA)

    Inoticedthementionofwhitepowderspecificallyinconnectionwithgreasewhenloosetiesontheleadswerefound.

    MyinstinctsleadmetorecognizethatthispowderwillhelpintheidentificationoflocationsaffectedbythePD,andcleaningmayerasetheevidence.Asfarascleaning,thatwoulddependonthepowderpropertiesandwhetherthepowderitselfwillcausefurtherproblems.

    Iwillleavethefurtherdiscussionaboutthepowdertomoreexperiencedindividualswithspecificknowledge

    __________________Idonot'knowitall',butiwilladmitthatIwouldliketo.CJM

    InstruformAssociate

    JoinDate:Feb2009Posts:35

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/20096:53AM

    Ihaveover40yearsofPDtestingexperienceandwouldsupportwhatMyn1996&CJMcGillrecommend.PDlimitvaluestandardsaresetfornewmachinesandhaveonlybeensetinthelast5yearsaftersome20yearsoftrial.Forlifeexpectancyyouneedtoascertainthechangefrompreviousresults/reportstoevaluateyoursituation.Thatiswhywhentestingforservicelifeexpectancytheinception,extinctionvoltagesandthedischargeshapeareimportantreadings&observationsandtogetsomeconsistencythesameprofessional&experiencedtestershouldbeusedonaregularbasisifpossible.UnfortunatelyPDtestingisstillbothascience&aseatofthepantsfeel.Makepreparationsbyallmeans,havecoilsavailabletolimityouroutagetime,butdon'tpanicyoucouldstillhaveyearsofservicefromthemachine.

    SiswantoCommentator

    JoinDate:Mar2008Location:JAKARTA.INDONESIAPosts:73GoodAnswers:15

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/15/200912:24PM

    Dearparimalam:

    Welcometothisforum

    ourcolleagueCJMcGillandmynhasgiveagoodsharing,IwouldliketotryoffersolutionbasedonmyexperiencesduringrepairofGeneratorsinINDONESIA.

    Since10yearsagoIjustfound2casesofPDFailureonGenerators,duetoitsnotdetectedandsettledatearlierstage.

    HaveyoutestPDbefore?ifyes,plscomparedtheresulthowfastthePDlevelacceleration,andyouknowwhereisthePDactivitieslocation?

    Attheendwinding?

    intheslot?

    attheoverhang?

    intheinternalwindinginsulation?

    IfPDactivitieshasfoundattheendwinding,slotandoverhang,itslittlebiteasytorepair,butiffoundwithinintheinsulationduetovoidsitsverydifficultandalmostimpossibletorepairexceptrewinding.

    CanyoutoldmethePDlevelandlocation?whichbarsthathavehighPDlevel?

    Followingarticlemaycanhelpyoutomadeadecision.Plsforgivemeifitsnotsufficientinformationforyou..

    PARTIALDISCHARGEphenomenononElectricmachine

    2

  • Coronaactivity

    Coronaisdefineastheionizationofgaswhenexposedtoanintenseelectricfield,thedischargehaveawiderangeoffrequencies[40kHzto100MHz].

    PartialDischarge(PD)inthelargegeneratorapplication,isusuallyassociatedwiththehighvoltagestatorconductorbars.

    Coronaactivityintherotatingmachine:

    SurfacedischargeduetoCoronaatendwinding(EndwindingDischarge)

    InternaldischargeduetoCoronaatinsideoftheinsulation(voidsordelamination)

    SlotdischargeCoronaatgroundwallinsulationresultingfromlosscontactbetweenbarandcore.(damagedonthesemiconductivecoatingonthestatorbar)

    SurfacedischargeduetoCoronaatoverhangofwindingresultingfrombarvibration

    Aproblemcommontomachineswiththermoplasticinsulationisthatthenormalthermalcyclingiscausescoilmovementintheslot,tendtogeneratecrackwithinthegroundwallinsulation.

    Atapeseparationisaseparationoftapecoveringthewallinsulationofthecoilduetoaxialexpansionandcontractionoftheconductorsandtheopposingforcesoftheslotappliedtothewallinsulation.

    Insomecasesonlythearmortapeisseparated,inothercasesthemicatapecomprisingthegroundwallinsulationisalsoaffected,whenthisoccurafewlayermaybeaffectedandthewholetapewillmovecreating"aneck"inthecoil.

    FollowingaretypicalinsulationfailureduetoPDactivitiesbasedonoursiterepairexperiencesonGeneratorsinINDONESIA.basedonourexperiencessince10yearsago,wefound2caseswindingbreakdownduetoundetectedPDactivitiesonstatorwindinggenerators,wedomuchtorepairofsemiconductivecoatingandstressgradingtominimizeandpreventthePDonthewinding

    A.PDInspection,

  • PDinspectiononAlstom87.5MVAafter18topbarscompletedremovedfromslot

    Coronaprobemeasurements

    Coronaprobetestingcanpinpointpartialdischargelocationineachslot.Itsupplementsonline/offlinepartialdischargetestsbypreciselylocatingpartialdischargetoaparticularcoiloraspot.ThecoronaprobecanalsobeusedasatestingtooltomeasurelevelsofPDactivity.Coronaprobetestingcanbeperformedeitherwiththerotorinoroutofthemachine

    EndoscopicPDVisualinspectiononAlstom87.5MVA

    PDVisualinspectionbyUVcameraon6.6KVMotors(figtakenfromOfil)

    WindingInspection

    FollowingaretypicalrootcauseofPDactivities

  • StatorwedgelooseonGEgenerator49,5MVA

    WhenStatorwedgehasloose,followingpartsmayaffectedloosetoduetomovement.

  • FillerslipoutonMitsubishiGenerator125MVA.

    Endwindingmovementduetostatorwedgesloose(notsufficienttokeepstatorcoilstayinplace)onGEGenerator237MVA

  • Loosesupportduetovibration

  • Typicalwindinginstallmentintheslot

    Whenties,wedge,supporthasloose,statorbarswillmovementanddamaged.

  • HVCoil

    Preventiveaction

    WhenwedgewasfoundlooseandtheaccelerationofPDactivitiesInthewindinghasincreasewithcomparedtotheprevioustestorthePDtesthasoverorclosetothemaxthreshold,followinginspectionmustbedonetomadeadecisiontorepairorreplace.

    1Checkthewedgetightness'foundloosemorethan30%mustbereplaced,concerntoreplacealsoforradialsprings,improvethematerials

    2Checkthecoilblocking,ties,foundloose,break,toodry,missing,mustberepaired

    3Checkthewindingsupport,surgerings,boltsetc,foundloosemustberepairedorretight

    4PDwasfoundhighonthewinding/

    IfPDactivitiescausedbyloosecontactbetweencoilbarstoslotwalls,dorepairthesemiconductivebycoatingorsemicondpainting

    IfPDactivitiescausedbylooseorstressgradingdeteriorationatendwindingportion,dorepairstressgradingbycoating

  • IfPDactivitiescausedbyinternalinsulationvoid,wecan'tdonothingexceptrewinding

    Followingarerepairreferenceswhenwerepaironlargegeneratorupto250MVA(basedonourexperiences).

    Replaceofstatorwedgeandradialspring

    TakenfromIRISEngineering

    Repairblockingcoil,ties,support,etciffoundloose,defect

  • Injectthesideripplebysemiconductivepainting

    Suggestionsolutionforyourproblems

    Followingmysuggestion

    1. IdentifiedthePDsources,trytorepairofsemiconductivecoatingintheslot,beforetorepairallstatorwedges,ripple(topifany),fillersmustberemovedfirst.

    2. DoretestPDbyofflinemethod,andprovidewithbartobarscanningorbyprobetoidentifiedwhichcoilsarehavehighPDlevelwithvoltageUn/1.73(linevoltagetoground)

    3. Inspectallwindingregion,insideslot,endwindingetc,useendoscopic(borescope)toinspectwindingintheslot4. Dotestinsulationtangentdelta,withvoltagetestsameforoflinePDtest.5. Replaceallstatorwedges,toprippleIfprovide)andflatfillers,iftheexistingarenotprovidebytopripple,andifthespaceis

    possibleenoughtoaccommodateoftopspring,providethethespring,andimprovethematerialfromclassBtoclassF,NEMAG11isrecommended

    6. Retightallwindingsupportandreplacethewindingtiesiffoundloose,missing,broken,etc7. Repairtheendwindingregioniffoundstressgradingdefectorreinsulatetheendwindingiffounddelaminationontheseareaand

    applieditbystressgradingpaintafterreinsulation.8. Cleanupallwindingareas,9. DryoutthestatorwindingbyusingDCsupply,keepthetemperatureround8090degreecelround24hrsormoreifmoistureis

    stillpresence10. Recoatingbyvarnishpainting11. Whengeneratorrunning,ifequipmentavailable,dotestPDonline.12. Recordallthetestresultasbasedline

    GoodLuck

    __________________LOVEFORUMANDDISCUSSION

    NomoreGoodAnswers. Gotofirst"Almost"GoodAnswer

  • #7Inreplyto#5

    #8Inreplyto#7

    parimalamActiveContributor

    JoinDate:Feb2009Posts:16

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/17/200910:59AM

    HitoAll,

    ItissimplygreatandInevergetsuchvaluableinformationanywerebutinthisforumitisamazingandIverymuchthankfultoallofyou.Iamgoingthroughalltheinformationandsuggestionandwilltaketimeformetounderstandfully.inthemeantimeIwillreplyfewanswerstothequestionspostedhere.

    thisplant2x12.5MW,13.8KVsteammachines(FSO)runningcontinuouslyforthepast10yearsandnowonealreadyfailedandalsothefailuredamagedthecorelaminationsandendupwiththebigjob,rewindingandlaminationrepairsandthejobisongoingatpresent.Myquestionhereisthereyanywaywecouldhavepreventedcoredamageduetocoilgrounding???intermsoffastswitchingprotectionrelayetc..????

    ThesemachinesnevercheckedforPDandnowonlyafterfailurewehavecheckedtherunningTAandfoundPDvalueisveryhigh(therewasnoearlierreadingforcomparisson).presneltywearerunningthisTAonlywith10%stationload,duetofear.Myquestionhere,runninglessloadwillhavelessPD???,eventhoughvoltageissame??curioustoknowsomesaynochangeinPDasthevoltageisthecreteriaforPDIamthinkinginotherwaybyhavinglowload,IreducethetemperatureandalsovibrationofcoilsomeextendreducedcanrunlongerperiodtocaterthestationloadtillwerepairanotherfailedTA.needadvice.

    CananyonecansuggestonlindPDmetereconomicalmodelbrandforpurchaseinordertokeepitatsiteforfrequentmonitoring

    restinnextpost.

    SiswantoCommentator

    JoinDate:Mar2008Location:JAKARTA.INDONESIAPosts:73GoodAnswers:15

    Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator02/17/20098:35PM

    Dearparimalam

    Asyouknow,PDisassociatedwiththehighvoltagestatorconductorbars,PDwouldbestillproducedwhengeneratorisenergizeevennoload,ofcourseyes,reducedloadwouldbereducedalsotheaccelerationofPD,becauseyouhavereducedalsothevibrationandthermal.

    Mysuggestion,whenyouscheduledtoshutdown,doinspectonyourwinding,

    InspectthePDbyofflinemethod(probetestisrecommended,itsdesignedtocheckandidentifywhichcoilbarsarehavehighPDlevel,soyoucanrepaired,inmyopinionthehighPDlevelinyourwindingiscausedbysemiconductivedeterioration).YoucanalsocheckthePDactivitybyusingendoscopic(borescope),checkthePDviaventholes(airduct)ofwinding

    ProvidealsoTangentDeltatest,isusefultoanalysisofyourwinding

    Statorwedgetightens,looseonthispartswillcreatebigproblemsonyourwinding,suchas:

    oDeteriorationonsemiconductivelayer,duetothestatorbarcoilswillmovemententireslot

    oLooseendwindingblockingandties,itscancreateendwindingdeteriorationoninsulation,electricfieldconcentrationonendofcorecanoccurringwhenstressgradingfailure,mayalsocancreatedelaminationonscarfjoin,scarfjoinisinsulationtapejoinbetweenoverhangtoendwindingarea,thisistheweaknessinsulationjoin.

    oWhenloosewedgeswasfound,itscanalsocreateinsulationvoidsacceleration,whenPDiscausedbythewindingvoids,youcan'tdoanythingtorepair,exceptrewinding

    Note:torepairsemiconductivelayer,usematerialsasbellow:

    Entireslot,use:"coronapainting",i.e.VonRollIsolaproducttypeP8003orequivalent.

    Endwinding,use:"coronapainting",i.e.vonrollisolaproduct,typeP8001orequivalent

    Cleanfirstanddryoutbeforeappliedthesematerials

    oWhenyoufoundstatorwedgesloose,replaceandimprovethematerials,providewithradialspringsifthespaceispossibletoaccommodateit,forwedgematerialyoucanimprovebyNEMAG11materialorequivalent,andforradialspringimprovetoclassF

    RetightorreplacetheendwindingandblockingcoiltiesbyusingbendingtapeclassF,alsoreplaceifyoufoundlooseormissingofblockingcoils,thefunctionofBlockingcoilsareusedtodeterminetheclearancebetweenthecoilsideattheendregion,toeliminate

  • mechanicalstressesarisingcoilmovement,thatwillberesultingcoiltouchingeachotherattheendwinding,Blockingcoilsarealmostmadefromsolidinsulationmaterials(suchastextolite,felt,etc)whichissoakedinresin.Blockingcoilisalwaysheldinplacewithties.Oftensolidseparatortendtolooseafterlongperiodofoperation,inseverecasesitwillfallfromthewinding.

    Inspectalltiesonthesurgeringsupport,ndwindingandsurgeringsaresecuredwithties,aswiththeblockingcoilsties,whenexposedoveralongtimeoperation,tiestendto"dry",becomelooseduetolosevolume,brittle,broken,etcretightorreplaceitbyusingbendingtypeandsoakedwithresin

    Inspecttightensofsupportstructures,foundsludgeorgreasingorwhitepowderisindicateloose,retight.

    Inspectthedustunderwindingclosetocore,extractitandcheckit,foundmetaldustonit,indicatestatorcoreloose,checkthecorelooseness,retighttheboltssupportbasedonmanufacturerspecification,foundbent,brokencoreteeth,repairitandappliedepoxy/resinorRTVonitstopreventorminimizethecorevibration.

    InspectthecorebyusingDigitalELCIDmethod,foundhotspot,repairedassoon,itsmustbedonewhenyouperformrewinding,recordedtheresultasbasedline,doregularlyin5years.

    Corerepairandtest,seethefollowinglink.

    http://cr4.globalspec.com/thread/32530/HowtoRepairaPartialCoreStatorGenerator

    PDInstruments.

    Youcanbrowsingintheinternet,itsmanysuppliercanprovide,orourcolleaguesheremaycanhelpyoutoprovidethetechnicalspecificationandsupplierfortheinstruments.

    PDinstrumentforofflinetest,PDProbemaythecheapest,anditsusefultoquickidentifiedofPDlocation,

    GoodLuck.

    __________________LOVEFORUMANDDISCUSSION

    Nomore"Almost"GoodAnswers.

    RegistertoReply 8commentsBacktotop

    Interestedinthistopic?ByjoiningCR4youcan"subscribe"tothisdiscussionandreceivenotificationwhennewcommentsareadded.

    JoinCR4,TheEngineer'sPlaceforNewsandDiscussion!

    CommentsratedtobeGoodAnswers:Thesecommentsreceivedenoughpositiveratingstomakethem"goodanswers".

    #5"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/15/200912:24PM(score2)

    Commentsratedtobe"almost"GoodAnswers:Checkoutthesecommentsthatdon'tyethaveenoughvotestobe"official"goodanswersand,ifyouagreewiththem,ratethem!

    #8"Re:HighPDvalueon13.8KV,12,5MWsteamturbinegenerator"bySiswantoon02/17/20098:35PM(score1)

  • CopytoClipboardUserswhopostedcomments:CJMcGill(2)Instruform(1)myn1996(1)parimalam(2)Siswanto(2)

    PreviousinForum:slipringethernettest NextinForum:Perhapsordinary(primary)batteriescanberecharged.Iwasableto.Youmightbeinterestedin:ElectricalWindingServices,BevelandMiterGears,WormsandWormGears

    Advertisement

    "Twentyyearsfromnowyouwillbemoredisappointedbythethingsthatyoudidn'tdothanbytheonesyoudiddo.Sothrowoffthebowlines.Sailawayfromthesafeharbor.Catchthetradewindsinyoursails.Explore.Dream.Discover."MarkTwain

    AlltimesaredisplayedinUS/Eastern(EDT)(Registertochangetimezone)

    2015IHS.Allrightsreserved.Reproductioninwholeorinpartwithoutpermissionisprohibited.Theinformationcontainedonthissiteisbyusersforusersandisprovidedforinformationpurposesonlyanddoesnotconstituteadvice.AnyviewsoropinionsexpressedbyusersarepersonaltothemanddonotrepresenttheviewsoropinionsofIHS.Youshouldcheckanyinformationanduseyourownjudgmentorseekexpertadvicebeforedoingornotdoinganythingonthebasisofwhatyoureadhere.IHSdoesnotverifyorwarranttheaccuracyorcompletenessofanyinformationonthissiteand,totheextentpermittedbylaw,IHSshallnotbeliableforanyloss,damageorexpenseincurredbyrelianceonitorforanydealingsyouhavewithusersorotherthirdpartiesthattakeplaceusingorfacilitatedbythissite.