Compressed Air Fill Station Operation
By
Tom Curtis
Objectives
• Demonstrate external visual inspection
• Identify safe filling techniques
• Identify safe transportation guidelines
SCUBA cylinder rupture
Riviera beach Florida
February 1, 1998
SCBA Cylinder RuptureAllegan Fire Department
September 4, 1997
Cylinder Inspection
• Cylinder type
Composite Cylinder
• Aluminum liner that is rapped by carbon fiber or fiberglass.
• 4500 or 2216 psi.
Solid Wall Cylinder
• Low pressure • 2216 psi
Cylinder Inspection
• Cylinder type• Service pressure
Look Here for Service Pressure!
Oxygen Cylinder
• Stamped information on the dome.
• Includes: service pressure, serial number, manufacture and permit number.
Low Pressure Cylinder Gauge.
High Pressure Cylinder Gauge
Cylinder Inspection
• Cylinder type• Service pressure• Hydro test date
Stamped Hydro Test Date
• Stamped on dome of solid wall cylinders
Cylinder Inspection
• Cylinder type• Service pressure • Hydro test date• Manufacturer
SCI Cylinder
• Three year hydro
Luxfer Cylinder
• Five year hydro
They May Look the Same!
• Take the time to look for the manufacturer and hydro date.
Aluminum Cylinders
• 5 year hydro
Cylinder Inspection
• Cylinder type• Service pressure • Hydro test date• Manufacturer• Cuts and gouges
Cuts, Gouges and Scrapes.
• .005 inches.• Sent to the shop for
gel coat repair.
BreakJust 10 Min.Be Back At:
Fill Station Operation
Safety rules
• Hearing protection• Respect the “whip”• Keep area clean
SCBA Connection
• Rated at 4500 psi
SCUBA Yoke
• Most rated at 3000 psi
Low Pressure SCBA Adapter
• “Pop off” regulator is set for 2216 psi.
Low Pressure SCBA Adapter
• The adapter has the same 4500 psi rated connection as the high pressure whips.
Station 14 SCBA Fill Station
• Open donor cylinder bank first.
• Crack fill gauge to proper rate.
Oxygen Fill Station
• Regulated fill rate of 300-600 psi/min.
• Will have vacuum system installed.
300 to 600 psi Per Min
• One unit on this gauge is 100 psi
• It should take 10 to 20 seconds for each 100 psi unit
• To fill a high pressure SCBA cylinder from 0 psi it will take @ 10 min.
Filling a Cylinder
1. Cylinder inspection
2. Cylinder connection
3. Open cylinder valve
4. Open lowest donor cylinder bank first
5. Open the fill valve at 300 – 600 psi/min
Handle With Care.
• Would you use an artillery shell as a wheel chock.
• Kinetic energy stored in a full 80 cubic foot cylinder exceeds one million foot pounds.
Transportation of Cylinders
• Regulations for commercial transporters
• Practical application in the fire department would be:– Vertical
– Protected contact with other cylinders