Post on 30-Apr-2020
RIP Transformer Bushing Type DTOI10/15/2009 Seite 1
Bushings
TRAVESCA® transformer bushingsFully insulated capacitive bushings for voltages up to 170kV
Company Overview
10/15/2009
Oil-Oil Bushing Type DTO25.8kV 2000A Oil-Air Bushing Type DTOI 72.5kV 800A
RIP Transformer Bushing Type DTOI10/15/2009 Seite 2
TRAVESCA®
Transformer Bushings
Dry, fine graded Bushing with RIP Insulation andSilicone rubber insulator
RIP Transformer Bushing Type DTOI10/15/2009 Seite 3
Why TRAVESCA® ?
In the view of the market
Movement towards silicone insulated dry transformer bushings especially in Switzerland, Germany and Austria
Increasing market volume in the field of silicone insulated transformer bushings
RIP Transformer Bushing Type DTOI10/15/2009 Seite 4
Why TRAVESCA® ?
In the view of MGC Moser-Glaser AG
50 years of experience in RIP Technology and manufacturing RIP wall bushings
40 years of experience in RIP Bushings and busbars with a voltage level 123kV and higher
More than 15 years of Experience with silicone rubber insulators
Manufacturing of 72.5 kV RIP Transformer-Bushings with porcelain insulator in the 1970/80`s
RIP Transformer Bushing Type DTOI10/15/2009 Seite 5
Advantages
Highest possible operational safetyLongest possible lifetimeMaintenance free operationNo oil leakage possible because of dry insulationMounting position 0…90°Weight reduction approx. 30% compared with porcelain insulated bushings
TRAVESCA® Type DTOI
RIP Transformer Bushing Type DTOI10/15/2009 Seite 6
TRAVESCA® Typ DTOITechnical Data
Voltage range ≤ 170 kVNominal current ≤ 2500 ACreepage distance Insulator 31 mm/kVStandard Current Transformer space 0/300/500 mm
RIP Transformer Bushing Type DTOI10/15/2009 Seite 7
TRAVESCA® – Type DTOI
800 A 1250 A 1600 A 2500 A
Conductordimension
– 35 mm 42 mm 65 mm
Type Draw lead
Conductor Conductor Conductor
Removable x x
Fixed x x
RIP Transformer Bushing Type DTOI10/15/2009 Seite 8
TRAVESCA® Typ DTOI
Head Terminal
Alternatively in Aluminium, Copper or Copper silver plated available
RIP Transformer Bushing Type DTOI10/15/2009 Seite 9
TRAVESCA® Typ DTOI
Test Tap
All Bushings are equipped with capacitive 2kV test tap. Used to monitor the capacitance C, partial discharge pC and the dissipation factor tan δ
RIP Transformer Bushing Type DTOI10/15/2009 Seite 10
TRAVESCA® Type DTOI
Arcing horns:
On customer requirement can the DTOI bushing be equipped with arcing horns made of CrNi Steel
RIP Transformer Bushing Type DTOI10/15/2009 Seite 11
TRAVESCA® oil side
Special attention was taken to the oil side of the bushing
RIP Transformer Bushing Type DTOI10/15/2009 Seite 12
Dielectric Test on DTOI 123 kV
Voltage Allowed PD Measured value
1,05 x Um/√3 ≤ 5 pC 1 pC
1,5 x Um/√3 ≤ 10 pC 1 pC
Um ≤ 10 pC 1 pC
1,1 x Up 1 pC
Test value Up 230 kV Up 300 kV
Safety factor 30%
According to IEC 60137
RIP Transformer Bushing Type DTOI10/15/2009 Seite 13
BIL Test DTOI 123 kVAccording to IEC 60137
Test Standard Limit Value Safety factor15+ 550 kV1- 550 kV5 abgeschnitten 633 kV14- 550 kV5 + 660 kV 20 %
U = 633 kV
µs50 %
1.2 500
U = 660 kV
µs
RIP Transformer Bushing Type DTOI10/15/2009 Seite 14
Temperature Rise Test DTOI 123kV / 800A
According to IEC 60137
RatedCurrent of Bushing
800ATest
current1250A
Safetyfactor56%
RIP Transformer Bushing Type DTOI10/15/2009 Seite 15
Cantilever Test DTOI 123 kV
According to IEC 60137
Norm 3150 N
Tested 3750 N
Limit Value 5000 N
Safety factor 59 %
RIP Transformer Bushing Type DTOI10/15/2009 Seite 16
Wet Power frequency Test DTOI 123 kV
According to IEC 60137
Standard 230 kV 60 s
Tested 230 kV 72 s
Tested 253 kV 72 s
Safety factor > 10 %
RIP Transformer Bushing Type DTOI10/15/2009 Seite 17
Temperature Test DTOI 123 kV
According to IEC 60137
Type DTOI
Step 1 -25°C Standard
Step 2 -40°C Optional
Additional temperature test down to -50°C duration 8 Std. with following leakage test on the flange with helium leakage tester
Test itemTest equipment for leakage test
Safety factor
RIP Transformer Bushing Type DTOI10/15/2009 Seite 18
Special Bending testContinuous operation test to on a DTOI 123kV bushing. Simulating 30 years operation time.Total of 50000 lifting's at -30°C and +50°C. Followed by routine test and dry lightning impulse withstand test (BIL) according IEC60 137.
RIP Transformer Bushing Type DTOI10/15/2009 Seite 19
Special “Cook Test”
“Cook Test“ on 145kV Bushing. 42 hours at +98°C with 1% salt solution followed by dry lightning impulse withstand test (BIL)Target: To ensure that no humidity is taken up by the direct cast silicone insulator and RIP insulating body.
RIP Transformer Bushing Type DTOI10/15/2009 Seite 20
Production process
123 kV Type DTOI after impregnation process with flange
RIP Transformer Bushing Type DTOI10/15/2009 Seite 21
Silicone Rubber Insulator
Manufactured at MGC, reduces delivery time Standard 31mm/kV
RIP Transformer Bushing Type DTOI10/15/2009 Seite 22
123 kV Type DTOI after the casting process of the insulator
123 kV Type DTOI at MGC test laboratory during routine test according to IEC 60137 (2003-08)
RIP Transformer Bushing Type DTOI10/15/2009 Seite 23
Long term storing of TRAVESCA® Transformer bushings
Sealing bolt on head of bushing
Aluminium tank with sealing flange
RIP Transformer Bushing Type DTOI10/15/2009 Seite 24
Application:Type: DTOIUn: 123kVIr: 1000ADraw lead typeInsulator: Silicone Creepage distance: 31mm/kV
Project Venezuela Transformer manufacturer Starkstromgerätebau Regensburg Germany
RIP Transformer Bushing Type DTOI10/15/2009 Seite 25
Application:Type: DTOIUm: 123 kVIr: 400 ADraw lead typeInsulator: Silicone Creepage distance: 31mm/kV
Utility EnBW Energie AG Stuttgart Germany Transformer Manufacturer Siemens AG Dresden
RIP Transformer Bushing Type DTOI10/15/2009 Seite 26
Application
Typ: DTOIUm: 123 kV, Ir: 800 ADraw lead typeInsulator: Silicone Creepage distance: 31mm/kVFrequency 16 2/3Hz Deutsche Bahn Energie AG Transformatorhersteller ABB Oy Vaasa Finnland
RIP Transformer Bushing Type DTOI10/15/2009 Seite 27
Application:Type: DTOIUm: 123 kVIr: 1250 AFixed conductor versionInsulator: Silicon Creepage distance: 31mm/kV
RWE AG Transformer manufacturer Areva Schorch Mönchengladbach , Germany
RIP Transformer Bushing Type DTOI10/15/2009 Seite 28
Application:Type: DTOIUm: 123 kVIr: 400 ADraw lead typeInsulator: Silicone Creepage distance: 31mm/kVTemperatur range -45°C
Transformer manufacturer ETD TRANSFORMATORY a.s. Plzen, Czeck Republic
RIP Transformer Bushing Type DTOI10/15/2009 Seite 29
Application:Type: DTOIUm: 123 kVIr: 1250 AFixed conductor versionInsulator: Silicon Creepage distance: 31mm/kV
Utility ERW Worms Transformer manufacturer Starkstromgerätebau Regensburg Germany
RIP Transformer Bushing Type DTOI10/15/2009 Seite 30
MGC Moser Glaser List of Transformer Bushings Customers and Users
Transformer Manufacturers:ABB Oy Vaasa Finland Areva Schorch Mönchengladbach GermanyETD TRANSFORMATORY a.s. Czech Republic ETRA 33 SloveniaGanz Transformers HungaryPauwels Trafo Belgium N.V. Mechelen Belgium Siemens AG Dresden GermanySiemens AG Nürnberg Germany Siemens AG Linz AustriaStarkstrom-Gerätebau GmbH Regensburg Germany
RIP Transformer Bushing Type DTOI10/15/2009 Seite 31
MGC Moser Glaser List of Transformer Bushings Customers and Users
Enduser / UtilitiesDB Energie AG Frankfurt GermanyEnBW Regional AG Stuttgart Germany EnBW Service GmbH Karlsruhe GermanyEon-Avacon Braunschweig Germany Hydro Exploitation Sion Switzerland JSC “Astrakhanenergo”. Russia Meralco, Manila PhilipienesNational Power Corp. PhilipienesRWE AG GermanyStadtwerke Coesfeld Germany Stadtwerke Worms Germany Statoil Norway Scottish Power Energy Networks Great BritainHärnösand Elnet AB Sweden