BRICK

CMU

CONCRETE

METAL

EARTH

MORTAR, GROUT, SAND

GYPSUM BOARD

ROUGH LUMBER OR BLOCKING(CONTINUOUS)

ROUGH LUMBER OR BLOCKING(DISCONTINUOUS)

WOOD FINISH

PLYWOOD

BATT INSULATION

RIGID INSULATION

1

A1.1

.

CUTS CONSTRUCTION

SECTION IDENTIFICATION

SHEET WHERE SECTION APPEARS

DETAIL

DETAIL IDENTIFICATION

SHEET WHERE DETAIL APPEARS

ROOM

100ROOM NAME

ROOM NUMBER

101 DOOR NUMBER/OPENING MARK

ELEVATION MARKER

DETAIL MARKER

ROOM MARKER

DOOR MARKER

WINDOW/STOREFRONT/LOUVER MARKER

A1 PARTITION TYPE

PARTITION MARKER

LEVEL0'-0" HEIGHT, ELEVATION MARKER

? GENERAL NOTE MARKER

1

REVISION MARKER

AREA OF REVISION

REVISION IDENTIFICATION

0 BUILDING LINE

A4.2

1

SHEET WHERE ELEVATION APPEARS

ELEVATION IDENTIFICATION

SECTION MARKER

INTERIOR ELEVATION MARKER

A4.2

1

SHEET WHERE ELEVATION APPEARS

ELEVATION IDENTIFICATION2 4

3

1

A1.1

1.

A

B

C

D

E

F

G

H

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

I

@ ATACT ACOUSTICAL CEILING TILESADJ ADJACENTAFF ABOVE FINISHED FLOORALUM ALUMINUMALT ALTERNATE

BARR. BARRIERBLDG BUILDINGBLK/BLKG BLOCKINGBIT. BITUMINOUSBM. BEAMBOT. BOTTOMB.U. BUILT-UP

C CHANNELCAB CABINETCIP CAST-IN-PLACECL CENTERLINECLG CEILINGCMU CONCRETE MASONRY UNITSCOL. COLUMNCONC. CONCRETECONST. CONSTRUCTIONC.J. CONTROL JOINTCONT. CONTINUOUSCORR. CORRIDORCPT CARPETCT CERAMIC TILE

Ø, D DIAMETERD. DEEPDET. DETAILDIA. DIAMETERDISP. DISPENSERDIM. DIMENSIONDN DOWND.S. DOWNSPOUTDTLS. DETAILSDWGS DRAWINGS

EA EACHE.F. EXHAUST FANELEC. ELECTRICALELEV. ELEVATOREL. ELEVATIONEQ EQUALEQUIP. EQUIPMENTE.T.R. EXISTING TO REMAINEXIST. EXISTINGEXP. EXPOSEDEXP. JT. EXPANSION JOINT.EXT. EXTERIOR

F.D. FLOOR DRAINFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETFEC02 FIRE EXTINGUISHER CARBON DIOXIDEFHC FIRE HOSE CABINETFIN. FINISHEDFIXT. FIXTUREFL. FLOORFOS FACE OF STUDFP FIREPROOFINGFTG FOOTINGFURR. FURRING

GA GAUGEGALV. GALVANIZEDGEN. GENERALGL. GLASSGWB GYPSUM WALL BOARDGYP BD GYPSUM BOARD

HM HOLLOW METALHB HOSE BIBHC HANDICAPPEDHORIZ. HORIZONTALH.P. HIGH POINTHR HOURHT HEIGHT

INSUL. INSULATIONINT. INTERIOR

J.C. JANITOR'S CLOSETJ.O. JAMB OPENINGJT JOINT

KIT. KITCHEN

LAM. LAMINATELAV. LAVATORYL.F. LINEAR FEETL.P. LOW POINT

M. MEN'S TOILETMACH. MACHINEMAINT. MAINTENANCEMAS. MASONRYMANF. MANUFACTURERMAX MAXIMUMMECH. MECHANICALM.H. MANHOLEMIN MINIMUMM.R. MOISTURE RESISTANTM.O. MASONRY OPENINGMISC. MISCELLANEOUSMTG MOUNTINGMTL METALMULL. MULLION

N.I.C. NOT IN CONTRACTNO. NUMBERNOM. NOMINALNTS NOT TO SCALE

O.C. ON CENTERO.D. OUTSIDE DIAMETEROPER. OPERATINGOPG. OPENINGOPP. OPPOSITE

PART. PARTITIONPASS. PASSAGEPERIM. PERIMETERPL PLATE, PROPERTY LINEPLAS. PLASTERPLAM PLASTIC LAMINATEPOLY. POLYETHELYNEPREFAB PREFABRICATEDPREP. PREPARATIONP.T. PRESSURE TREATEDPTD PAINTED

Q.T. QUARRY TILE

R RISERR.A. RETURN AIRRAD. RADIUSRCP REFLECTED CEILING PLANR.D. ROOF DRAINREF REFERENCE, REFRIGERATORREINF. REINFORCINGRM ROOMR.O. ROUGH OPENINGRQD. REQUIRED

SCHED. SCHEDULESECT. SECTIONSHT SHEETSIM SIMILARS.P. STANDPIPESPECS SPECIFICATIONSSQ. SQUARESS STAINLESS STEELSTL STEELST./STOR/ STORAGESTRUCT. STRUCTURALSUSP. SUSPENDEDSW STORM WATER

T TREADTEL. TELEPHONETH THRESHOLDTHK. THICKNESST.O. TOP OFT&B TOP AND BOTTOMT&G TONGUE AND GROOVETS TRANSITION STRIPTYP TYPICAL

U.L. UNDERWRITER'S LABORATORYU.N.O. UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITION TILEV.B. VAPOR BARRIERVERT. VERTICALVEST. VESTIBULEV.R. VAPOR RETARDER

W. WOMEN'S TOILETWD WOODW/ WITHW/O WITHOUTW.C. WATER CLOSETW.P. WATERPROFFINGWWF WELDED WIRE FABRICWWM WELDED WIRE MESH

ROOF SECTION 1

ROOF SECTION 8

(BID ALTERNATE)

ROOF SECTION 9

(BID ALTERNATE)

ROOF SECTION 2 ROOF SECTION 5

ROOF SECTION 6

ROOF SECTION 7 (CANOPY)

ROOF SECTION 3

ROOF

SECTION 4

ROOF SECTION 7 (CANOPY)1969

1961

ROOF SECTION 1

1961

NO WORK THIS AREA

NO WORK THIS AREA

NO WORK THIS AREA

1971

19681937

1963

1963

1986

1986

1963ROOF SECTION 1

YEAR BUILT

ROOF TYPE, REFERENCE SPECIFICATIONS

M

PROFESSIONAL CERTIFICATION: I CERTIFY THAT THESE DOCUMENTS WERE

PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF MARYLAND

LICENSE NUMBER:

EXPIRATION DATE:

no. date revision

© Hord Coplan Macht, Inc.

9

ARCHITECTURE

LANDSCAPE ARCHITECTURE

PLANNING

INTERIOR DESIGN

Drawing

Scale

Date

ARCHITECT

Hord Coplan Macht, Inc.700 E. Pratt St, Suite 1200Baltimore, MD 21202p. 410. 837. 7311 f. 410. 837. 6530

ENVELOPE CONSULTANT

Construction Systems Group, Inc. 1451 Dolley Madison Blvd., Suite 300 McLean, VA 22101p. 703.917.0055 f. 703.917.0464

Project Number

Project Name

8

7

6

5

4

3

2

1

LKJHGFEDCBA C:\Users\jhagan\Documents\Pinehurst ES - Roof Replacement_jhagan.rvt

2/11/2019 1:34:30 PM

As indicated

PINEHURST

ELEMENTARY

SCHOOL ROOF

REPLACEMENT

520 S Pinehurst, Salisbury, MD 21801

CONSTRUCTION DOCUMENTS

FEBRUARY 11, 2019

WICOMICO COUNTY PUBLICSCHOOLS

218345.00

CS.01

COVER SHEET

PINEHURST ELEMENTARYSCHOOL ROOF REPLACEMENT

DRAWING LIST

PINEHURST ELEMENTARY SCHOOL ROOF REPLACEMENT

520 S Pinehurst, Salisbury, MD 21801

ALTERNATES

1. Alternate Lump Sum Base Bid - Provide a price for the substitution of a torch-grade 2-ply modified bitumen

roof system in lieu of application in hot asphalt.

2. Provide an ADD/DEDUCT price for the substitution of foam insulation adhesive in lieu of hot asphalt (NOTE: At

metal decks, base layer of rigid polyisocyanurate thermal insulation will remain mechanically attached). Amount

will apply to both Base Bid and Alternate Base Bid

3. Provide price for Base Bid roof replacement of Roof Section 8 and Roof Section 9 in compliance with the

summary of work and specifications.

4. Provide price for Alternate Base Bid roof replacement of Roof Section 8 and Roof Section 9 in compliance with

the summary of work and specifications

SheetNumber Sheet Name

CS.01 COVER SHEET

ROOF

A1.01 ROOF PLAN

A1.02 ROOF DETAILS

A1.03 ROOF DETAILS

A1.04 ROOF DETAILS

A1.05 ROOF DETAILS

MATERIAL FILL PATTERNS

SYMBOL LEGEND

ABBREVIATIONS

IFB # 91066-192.

ROOF KEY PLAN

APPLICABLE CODES

• 2015 INTERNATIONAL BUILDING CODE• 2015 INTERNATIONAL MECHANICAL CODE• NATIONAL STANDARD PLUMBING CODE (MBPS) 2015 EDITION • 2015 INTERNATIONAL ENERGY CONSERVATION CODE• 2015 INTERNATIONAL EXISTING BUILDING CODE

3E

A1.03

3J

A1.03

3A

A1.03

6J

A1.03

6E

A1.03

RD

RD

RD RD

RD RD

RD RD

RD RD

RD RD

RD RDRD RD RD RD

RD

EX. FAN EX. FAN

GV GV

VTR

VTR

GV

GV

GV

GV

EX. FAN

EX. FAN

VTR

VTR

VTRVTR

EX. FAN

2F

A1.04

2J

A1.04

TYP.

TYP.

2D

A1.04

TYP.

2J

A1.04

TYP.

EXISTING ACCESS LADDER WITH CAGE

GV

GV

GV

EX. FAN

VTR

VTR

GV

GV

GV

EX. FAN

EX. FAN

GV

VTR

VTR

VTR

EXPANSION JOINT

EXPANSION JOINT

EXPANSION JOINT

9J

A1.03

9A

A1.03

3E

A1.03

9J

A1.03

6A

A1.03

9H

A1.04

VTR VTR

EX. FAN

GUTTER

GUTTER

DSDS DS DS

EX. FAN

RTU

PIPE/ELEC. PENETRATIONS

EX. FAN

EXISTING ACCESS LADDER WITH CAGE

RTU

DSVTR

GUTTER

DS

VTR

EX. FAN

PIPE PENETRATION

ELEVATED PVC PIPE

SPLIT SYSTEM UNITS (3)

DUCT PENETRATION (4)

PIPE/ELEC. PENETRATIONS

DS

VTR

VTR

VTR

VTR

EX. FAN EX. FAN

EX. FAN

CANOPY BELOW

GUTTER

GUTTER

GUTTER

EXISTING ACCESS LADDER WITH CAGE

CANOPY BELOW

RD

RD

RD

RD

VTR

VTR

VTR VTR

VTR

VTRVTR

VTR

EX. FAN

VTRVTR

EX. FAN

EX. FAN

EX. FAN

CANOPY BELOW

GUTTER

5G

A1.04

HIGH ROOF

5A

A1.04

9D

A1.04

9A

A1.04

3G

A1.05

6E

A1.05

6E

A1.056E

A1.05

SIM SIM

9J

A1.05

9J

A1.05

9E

A1.05

9E

A1.05

9E

A1.05

9E

A1.05

6E

A1.02

6E

A1.02@ CANOPY@ CANOPY

6E

A1.02@ CANOPY

3J

A1.02

EXPANSION JOINT

EXPANSION JOINT

3A

A1.02

3A

A1.05

3J

A1.03

SIM

LEGEND

AREA NOT INCLUDED IN SCOPE OF PROJECT

RD

GV

VTR

EX. FAN

ROOF DRAIN LOCATION

VENT STACK LOCATION

EXHAUST FAN LOCATION

GOOSE NECK VENT LOCATION

ROOF SECTION 1

ROOF SECTION 8 (BID ALTERNATE)

ROOF SECTION 9 (BID ALTERNATE)

ROOF SECTION 2

ROOF SECTION 5

ROOF SECTION 6

ROOF SECTION 7 (CANOPY)

ROOF SECTION 3

ROOF SECTION 4

ROOF SECTION 7 (CANOPY)

M

PROFESSIONAL CERTIFICATION: I CERTIFY THAT THESE DOCUMENTS WERE

PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF MARYLAND

LICENSE NUMBER:

EXPIRATION DATE:

no. date revision

© Hord Coplan Macht, Inc.

9

ARCHITECTURE

LANDSCAPE ARCHITECTURE

PLANNING

INTERIOR DESIGN

Drawing

Scale

Date

ARCHITECT

Hord Coplan Macht, Inc.700 E. Pratt St, Suite 1200Baltimore, MD 21202p. 410. 837. 7311 f. 410. 837. 6530

ENVELOPE CONSULTANT

Construction Systems Group, Inc. 1451 Dolley Madison Blvd., Suite 300 McLean, VA 22101p. 703.917.0055 f. 703.917.0464

Project Number

Project Name

8

7

6

5

4

3

2

1

LKJHGFEDCBA C:\Users\jhagan\Documents\Pinehurst ES - Roof Replacement_jhagan.rvt

2/11/2019 1:34:29 PM

1/16" = 1'-0"

PINEHURST

ELEMENTARY

SCHOOL ROOF

REPLACEMENT

520 S Pinehurst, Salisbury, MD 21801

CONSTRUCTION DOCUMENTS

FEBRUARY 11, 2019

WICOMICO COUNTY PUBLICSCHOOLS

218345.00

A1.01

ROOF PLAN

PINEHURST ELEMENTARYSCHOOL ROOF REPLACEMENT

1/16" = 1'-0"A1.01

ROOF PLAN9A

1. STORE AND HANDLE ROOFING SHEETS IN A DRY, WELL-VENTILATED, WEATHER-TITE PLACE. STORE ROLLS OF FELT AND OTHER SHEET MATERIALS ON RAISED SURFACE. STAND ALL ROLL MATERIALS ON END. COVER ROLL GOODS WITH A CANVAS TARPAULIN OR OTHER BREATHABLE MATERIAL (NOT POLYETHYLENE).

2. DO NOT LEAVE UNUSED MATERIALS ON THE ROOF WHEN ROOFING WORK IS NOT IN PROGRESS UNLESS PROTECTED FROM WEATHER AND OTHER MOISTURE SOURCES.

3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO SECURE ALL MATERIAL AND EQUIPMENT ON THE JOB SITE. IF ANY MATERIAL OR EQUIPMENT IS STORED ON THE ROOF, THE CONTRACTOR MUST MAKE SURE THAT THE INTEGRITY OF THE DECK IS NOT COMPROMISED AT ANY TIME.

4. DO NOT APPLY ROOFING INSULATION OR MEMBRANE TO DAMP DECK SURFACE.

5. FULLY COMPLETE ALL MODIFIED BITUMINOUS MEMBRANE ROOFING FIELD ASSEMBLY WORK EACH DAY. PHASED CONSTRUCTION WILL NOT BE ACCEPTED.

6. CONTRACTOR TO SUBMIT PULL OUT TEST DATA WITH FASTENING PATTERNS FOR ALL ROOF AREAS.

NOTES:

1. ALL OF GARLAND'S SHOP FABRICATED MATERIAL WILL BE MANUFACTURED TO THE DIMENSIONS SHOWN, UNLESS OTHERWISE NOTED.

2. IT IS ESSENTIAL THAT ANY NECESSARY CHANGES, NOTATIONS OR REQUESTED INFORMATION BE CLEARLY NOTED ON THE SHOP DRAWINGS.

3. NO MATERIAL WILL BE CONSIDERED RELEASED FOR FABRICATION UNTIL ALL PERTINENT INFORMATION (i.e. COLOR, DIMENSIONS, MATERIAL CONFIG-URATION) HAS BEEN RECEIVED.

CUSTOMER NOTES:

0' - 4"

NOTE: SOLDER EXPANSION JOINT COVER SEAMS/ LAPS

2x6 MIN. WOOD NAILER ATTACHED TO SUBSTRATE. OVERALL THICKNESS TO MATCH INSULATION.

WOOD CANT

26 GA. REGLET-MOUNTED STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE 18" O.C.

SEALANT, SEE SPECIFICATION

MEMBRANE SHEET CLOSURE SECURED AND ADHERED TO WALL

POLYISOCYANURATE INSULATION

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

26 GA. STAINLESS STEEL JOINT COVER WITH T-TYPE CLEAT, SLOPED TO DRAIN

8" M

IN.

FLA

SH

ING

HE

IGH

T

EPDM EXTENDED BACKER/VAPOR RETARDERFASTENERS APPROX. 8" O.C.

EXTEND FIELD PLIES ABOVE TOP OF CANT STRIP

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

SEALANT, REFERENCE SPECIFICATION

SEAL TOP EDGE OF EXPANSION JOINT COVER TO MASONRY WITH COMPRESSIVE BEAD OF BUTYL SEALANT

BASE SHEET & VAPOR BARRIER

EXISTING TECTUM DECK

26 GA. STAINLESS STEEL PITCH

PAN SOLDERED WATERTIGHT 4" MIN HEIGHT

OPT: WOOD NAILERS; VARIES DEPENDING

UPON SIZE OF PENETRATION

POURABLE SEALANT,

2 PART, 2" MIN.

NON-SHRINK GROUT, 2" MIN.

PREPARE AND PRIME PROJECTION

NOTE: MINIMUM 1" CLEARANCE FROM PENETRATION TO OUTER EDGE OF PITCH PAN. PMMA LIQUID FLASHING IS ACCEPTABLE.

SEALANT, REFERENCE SPECIFICATION

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

POLYISOCYANURATE INSULATION

1/2" SECUROCK

BASE SHEET & VAPOR BARRIER

SEAL GAP AROUND PENETRATION WITH FOAM

4" MIN.

EXISTING TECTUM DECK

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN CAP SHEET

SEAL GAPS AT ALL PERIMETERS WITH FOAM

CANT STRIP

TORCH BASE FLASHING PLY 6" MIN. ON FIELD. EXTEND PLIES UP & OVER WOOD NAILER

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD. EXTEND PLIES UP & OVER WOOD NAILER.

GASKETED FASTENERS @ 24" O.C.

22 GA. GALVANIZED STEEL CONTINUOUS CLEAT FASTENED @ 6" O.C.

26 GA. STAINLESS STEEL STANDING SEAM COPING COVER. PROVIDE POSITIVE SLOPE.

GRANULAR-SURFACED MODIFIED BITUMEN CAP SHEET IN HOT ASPHALT ADHESIVE

MODIFIED BITUMEN BASE SHEET IN HOT ASPHALT ADHESIVE

1/4:12 TAPERED POLYISOCYANURATE INSULATION BOARD IN HOT ASPHALT ADHESIVE

(1) LAYER OF 1.5" POLYISOCYANURATE INSULATION IN HOT ASPHALT ADHESIVE. STAGGER ALL JOINTS.

EXISTING TECTUM DECK

MODIFIED BITUMEN VAPOR BARRIER IN HOT ASPHALT ADHESIVE

1/2" SECUROCK IN HOT ASPHALT ADHESIVE

MECHANICALLY FASTEN BASE SHEET ACCORDING TO WIND UPLIFT CALCULATIONS

GRANULAR-SURFACED MODIFIED BITUMEN CAP SHEET IN HOT ASPHALT ADHESIVE

MODIFIED BITUMEN BASE SHEET IN HOT ASPHALT ADHESIVE

1/4:12 TAPERED POLYISOCYANURATE INSULATION BOARD IN HOT ASPHALT ADHESIVE

(1) LAYER OF 1.5" POLYISOCYANURATE INSULATION IN HOT ASPAHLT ADHESIVE ACCORDING TO WIND UPLIFT CALCULATIONS. STAGGER ALL JOINTS.

EXISTING METAL DECK

MECHANICALLY-ATTACHED 1/2" SECUROCK ON STEEL DECK WITH MODIFIED BITUMEN VAPOR BARRIER IN HOT ASPHALT OVER 1/2" SECUROCK

1/2" SECUROCK IN HOT ASPHALT ADHESIVE

GRANULAR-SURFACED MODIFIED BITUMEN CAP SHEET IN HOT ASPHALT ADHESIVE

MODIFIED BITUMEN BASE SHEET IN HOT ASPHALT ADHESIVE

EXISTING TECTUM DECK

MECHANICALLY FASTEN BASE SHEET ACCORDING TO WIND UPLIFT CALCULATIONS

EXISTING BULB T WELDED TO STRUCTURE

EXISTING ROOF DECK

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

SEAL GAPS AT ALL PERIMETERS WITH FOAM

CANT STRIP

SEALANT, REFERENCE SPECIFICATION

26 GA. REGLETMOUNTED STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE 18" O.C.

SEALANT, SEE SPECIFICATION

EXISTING THRU WALL FLASHING

SEALANT, SEE SPECIFICATION

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

EXISTING WOOD BLOCKING

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

22 GA. GALVANIZED STEEL CONTINUOUS CLEAT FASTENED 6" O.C.

26 GA. STAINLESS STEEL GRAVEL STOP SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

2x TREATED WOOD CURB

BASE FLASHING

CANT STRIP

METAL CAP PER SMACNA-ASMM 4TH EDITION PLATE 80 FIG. B

2X TREATED WD BLOCKING AND TREATED PLYWOOD AS REQUIRED. ANCHOR TO DECK. DEPTH OF BLOCKING VARIES WITH LOCATION ON ROOF (TYP).

M

PROFESSIONAL CERTIFICATION: I CERTIFY THAT THESE DOCUMENTS WERE

PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF MARYLAND

LICENSE NUMBER:

EXPIRATION DATE:

no. date revision

© Hord Coplan Macht, Inc.

9

ARCHITECTURE

LANDSCAPE ARCHITECTURE

PLANNING

INTERIOR DESIGN

Drawing

Scale

Date

ARCHITECT

Hord Coplan Macht, Inc.700 E. Pratt St, Suite 1200Baltimore, MD 21202p. 410. 837. 7311 f. 410. 837. 6530

ENVELOPE CONSULTANT

Construction Systems Group, Inc. 1451 Dolley Madison Blvd., Suite 300 McLean, VA 22101p. 703.917.0055 f. 703.917.0464

Project Number

Project Name

8

7

6

5

4

3

2

1

LKJHGFEDCBA C:\Users\jhagan\Documents\Pinehurst ES - Roof Replacement_jhagan.rvt

2/11/2019 1:34:29 PM

1 1/2" = 1'-0"

PINEHURST

ELEMENTARY

SCHOOL ROOF

REPLACEMENT

520 S Pinehurst, Salisbury, MD 21801

CONSTRUCTION DOCUMENTS

FEBRUARY 11, 2019

WICOMICO COUNTY PUBLICSCHOOLS

218345.00

A1.02

ROOF DETAILS

PINEHURST ELEMENTARYSCHOOL ROOF REPLACEMENT

1 1/2" = 1'-0"A1.01 A1.02

ROOF EDGE DETAIL 1986 BUILDING @ 1937 BUILDING3J 1 1/2" = 1'-0"A1.02

PITCH POCKET DETAIL3E

1 1/2" = 1'-0"A1.02

ROOF EDGE DETAIL TYPICAL COPING CAP DETAIL6J

1 1/2" = 1'-0"A1.02

TYPICAL ROOF CROSS SECTION - INSULATED TECTUM DECK9J 1 1/2" = 1'-0"A1.02

TYPICAL ROOF CROSS SECTION - STEEL DECK9E 1 1/2" = 1'-0"A1.02

TYPICAL ROOF CROSS SECTION - TECTUM DECK (CANOPY ROOFS)9A

1 1/2" = 1'-0"A1.01 A1.02

ROOF EDGE DETAIL 1971 BUILDING CANOPY6E

1 1/2" = 1'-0"A1.01 A1.02

ROOF AREA DIVIDER - BU/MOD BIT3A

NOTE: APPLY THIS ASSEMBLY TO ALL STEEL ROOF DECK AREASNOTE: APPLY THIS ASSEMBLY TO ALL TECTUM ROOF DECK AREAS

NOTE: APPLY THIS ASSEMBLY TO ALL CANOPY DECK AREAS

2-1/2" STRUCTURAL INSULATING DECK

WINDOW

EXISTING 3/4" PLYWOOD

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

SEAL GAPS AT ALL PERIMETERS WITH FOAM

EXISTING WOOD BLOCKING

NEW WOOD BLOCKING

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

22 GA. GALVANIZED STEEL CONTINUOUS CLEAT FASTENED 6" O.C.

SEALANT, SEE SPECIFICATION

26 GA. STAINLESS STEEL GRAVEL STOP SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

MODIFIED MEMBRANE

BASE PLY

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

EXISTING TECTUM DECK

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

SEAL GAPS AT ALL PERIMETERS WITH FOAM

EXISTING WOOD BLOCKING

NEW WOOD BLOCKING

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

22 GA. GALVANIZED STEEL CONTINUOUS CLEAT FASTENED 6" O.C.

SEALANT, SEE SPECIFICATION

26 GA. STAINLESS STEEL GRAVEL STOP SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

MODIFIED MEMBRANE

BASE PLY

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

2-1/2" STRUCTURAL INSULATING DECK

WINDOW

EXISTING 3/4" PLYWOODWITH SPRAY COATING

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

SEAL GAPS AT ALL PERIMETERS WITH FOAM

EXISTING WOOD BLOCKING

NEW WOOD BLOCKING

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

22 GA. GALVANIZED STEEL CONTINUOUS CLEAT FASTENED 6" O.C.

SEALANT, SEE SPECIFICATION

26 GA. STAINLESS STEEL GRAVEL STOP SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

MODIFIED MEMBRANE

BASE PLY

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

2-1/2" STRUCTURAL INSULATING DECK

POLYISOCYANURATE INSULATION

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

CANT STRIP

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE 18" O.C.

SEALANT, SEE SPECIFICATION

EXISTING TECTUM DECK

BASE SHEET & VAPOR BARRIER

EXISTING 2-1/2" STRUCTURAL INSULATING DECK

0' - 2"

1961 PASSAGE1961 BUILDING

EXPANSION JOINT

POLYISOCYANURATE INSULATION

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

A1.04

2A

BASE SHEET & VAPOR BARRIER

EXISTING 2-1/2" STRUCTURAL INSULATING DECK

EXISTING METAL DECK

EXPANSION JOINT

POLYISOCYANURATE INSULATION

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

A1.04

2A

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

CANT STRIP

SEALANT, REFERENCE SPECIFICATION

26 GA. REGLET MOUNTED STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE 18" O.C.

SEALANT, SEE SPECIFICATION

BASE SHEET & VAPOR BARRIER

1/2" SECUROCK

EXISTING 2-1/2" STRUCTURAL INSULATING DECK

EXISTING WINDOW

EXISTING 3/4" PLYWOOD

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

SEAL GAPS AT ALL PERIMETERS WITH FOAM

EXISTING WOOD BLOCKING

NEW WOOD BLOCKING

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

22 GA. GALVANIZED STEEL CONTINUOUS CLEAT FASTENED 6" O.C.

SEALANT, SEE SPECIFICATION

26 GA. STAINLESS STEEL GRAVEL STOP SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

MODIFIED MEMBRANE

BASE PLY

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

METAL DECK

WINDOW

EXISTING 3/4" PLYWOODWITH SPRAY COATING

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

EXISTING WOOD BLOCKING

NEW WOOD BLOCKING

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

22 GA. GALVANIZED STEEL CONTINUOUS CLEAT FASTENED 6" O.C.

SEALANT, SEE SPECIFICATION

26 GA. STAINLESS STEEL GRAVEL STOP SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

MODIFIED MEMBRANE

BASE PLY

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

BASE SHEET & VAPOR BARRIER

1/2" SECUROCK

M

PROFESSIONAL CERTIFICATION: I CERTIFY THAT THESE DOCUMENTS WERE

PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF MARYLAND

LICENSE NUMBER:

EXPIRATION DATE:

no. date revision

© Hord Coplan Macht, Inc.

9

ARCHITECTURE

LANDSCAPE ARCHITECTURE

PLANNING

INTERIOR DESIGN

Drawing

Scale

Date

ARCHITECT

Hord Coplan Macht, Inc.700 E. Pratt St, Suite 1200Baltimore, MD 21202p. 410. 837. 7311 f. 410. 837. 6530

ENVELOPE CONSULTANT

Construction Systems Group, Inc. 1451 Dolley Madison Blvd., Suite 300 McLean, VA 22101p. 703.917.0055 f. 703.917.0464

Project Number

Project Name

8

7

6

5

4

3

2

1

LKJHGFEDCBA C:\Users\jhagan\Documents\Pinehurst ES - Roof Replacement_jhagan.rvt

2/11/2019 1:34:30 PM

1 1/2" = 1'-0"

PINEHURST

ELEMENTARY

SCHOOL ROOF

REPLACEMENT

520 S Pinehurst, Salisbury, MD 21801

CONSTRUCTION DOCUMENTS

FEBRUARY 11, 2019

WICOMICO COUNTY PUBLICSCHOOLS

218345.00

A1.03

ROOF DETAILS

PINEHURST ELEMENTARYSCHOOL ROOF REPLACEMENT

1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1961 BUILDING @ EAST3E 1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1961 BUILDING @ NORTH3J 1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1961 BUILDING @ EAST PASSAGE3A

1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1961 BUILDING @ 1937 BUILDING6J 1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1961 BUILDING @ PASSAGE6E

1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1968 BUILDING @ SOUTH9A 1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1968 BUILDING @ EAST9J

1 1/2" = 1'-0"A1.01 A1.03

ROOF EDGE DETAIL 1986 BUILDING @ PASSAGE6A

CL

ALL PLIES EXTEND UNDER CLAMPING RING

INSULATED LEADER

EXISTING TECTUM DECK

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

TAPERED 8'X8' SUMP,MINIMUM THICKNESS IS 2"

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

4 LB. LEAD FLASHING (30" MIN.) SET IN MASTIC, WRAPPED DOWN 2" MIN., PRIME BOTH SIDES

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET ROOF DRAIN

8" M

IN.

UNIT MOUNTING CURB

CANT STRIP, FASTENED TO NAILER POLYISOCYANURATE

INSULATION

BASE SHEET & VAPOR BARRIER

EXISTING TECTUM DECK

METAL COUNTERFLASHING FASTENED 8" O.C. SCREW OR RIVET TO FLASHING RECEIVER ONLY

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

SEALING MATERIAL MUST BE CONTINUOUS ON THE PERIMETER

SEALANT, REFERENCE SPECIFICATION

FLASHING RECEIVER

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE

4" MIN

MIN

.

1' -

0"

SEAL GAP AROUND PIPES WITH FOAM

EXISTING TECTUM DECK

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN CAP SHEET

ROLL DOWN TOP PIECE LEAD FLASHING 1" MIN. DOWN INTO PIPE

PLUMBING VENT STACK

SEALANT, REFERENCE SPECIFICATION

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

SET SOFT METAL FLANGE IN MASTIC, PRIME FLANGE BEFORE STRIPPING

NOTE: MANUFACTURER'S REINFORCED PMMA FLUID APPLIED FLASHING IS ACCEPTABLE

8" M

IN.

EXP JT WIDTH

2" M

IN.

FLEXIBLE VAPOR RETARDER TO SERVE AS INSULATION RETAINER ATTACH TO TOP OF CURB

EXISTING TECTUM DECK

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

COMPRESSIBLE INSULATION

WOOD CANT1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN CAP SHEET

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

26 GA. STAINLESS STEEL CLEAT FASTENED 12" O.C.

COVER SECURED 12" O.C. W/ FASTENERS & NEOPRENE WASHERS

FLEXIBLE WATERPROOF MEMBRANE CLOSURE

26 GA. STAINLESS STEEL EXPANSION JOINT COVER

FLASHING FASTENED 8" O.C.

EXP./ CONT.

EXP./ CONT. +1/2"

EXP./ CONT.

1/2"

METAL DECK

POLYISOCYANURATE INSULATION

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

EXISTING ROOF TO REMAIN

SEAL GAPS AT ALL PERIMETERS WITH FOAM

CANT STRIP

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE 18" O.C.

SEALANT, SEE SPECIFICATION

BASE SHEET & VAPOR BARRIER

1/2" SECUROCK

NOTE: ADJUST WOOD BLOCKING AS NECESSARY TO ACCOMODATE HEIGHT OF INSULATION.

EXISTING DECK

26 GA. STAINLESS STEEL D-STYLE GUTTER

EXISTING WOOD BLOCKING

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

4" MIN.

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO

MATCH GUTTER

SEAL GAPS AT ALL PERIMETERS WITH FOAM

GUTTER CLEAT FASTENED 6" O.C.

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

26 GA. STAINLESS STEEL DRIP EDGE SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

26 GA. REGLETMOUNTED STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE 18" O.C.

SEALANT, SEE SPECIFICATION

26 GA. STAINLESS STEEL D-STYLE GUTTER

EXISTING WOOD BLOCKING

4" MIN.

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

SEAL GAPS AT ALL PERIMETERS WITH FOAM

GUTTER CLEAT FASTENED 6" O.C.

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

26 GA. STAINLESS STEEL DRIP EDGE SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

SECUROCK

BASE SHEET & VAPOR BARRIER

1/2" SECUROCK

BASE SHEET & VAPOR BARRIER

WING WALL BEYOND

EXISTING 1/2" PLYWOOD

EXISTING 3/8" PLYWOOD

EXISTING DECK

26 GA. STAINLESS STEEL D-STYLE GUTTER

EXISTING WOOD BLOCKING

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

4" MIN.

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

SEAL GAPS AT ALL PERIMETERS WITH FOAM

GUTTER CLEAT FASTENED 6" O.C.

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

26 GA. STAINLESS STEEL DRIP EDGE SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

NOTE: ADJUST WOOD BLOCKING AS NECESSARY TO ACCOMODATE HEIGHT OF INSULATION.

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

26 GA. REGLETMOUNTED STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE 18" O.C.

SEALANT, SEE SPECIFICATION

SEALANT

26 GA. STAINLESS STEEL D-STYLE GUTTER

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

WRAP EXISTING WOOD WITH NEW ALUMINUM AS REQUIRED

TAPERED INSULATION

1/2" SECUROCK

WINDOW

1937 BUILDING1963 BUILDING

POLYISOCYANURATE INSULATION

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5' EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

CANT STRIP

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL COUNTERFLASHINGRETURN AT WINDOW SILL

SEALANT, SEE SPECIFICATION

BASE SHEET & VAPOR BARRIER

1/2" SECUROCK

WINDOW

SLOPED ROOF SOFFIT BEYOND TO REMAIN

SCUPPER FROM SLOPED ROOFS ABOVE

SECUROCK

POLUISOCYANURATE INSULATION

EXISTING ROOF DECK

SEALANT

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

CANT STRIP

26 GA. STAINLESS STEEL D-STYLE GUTTER

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

GUTTER CLEAT FASTENED 6" O.C.

26 GA. STAINLESS STEEL COUNTERFLASHINGRETURN AT WINDOW SILL

BASE SHEET & VAPOR BARRIER

1/2" SECUROCK

M

PROFESSIONAL CERTIFICATION: I CERTIFY THAT THESE DOCUMENTS WERE

PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF MARYLAND

LICENSE NUMBER:

EXPIRATION DATE:

no. date revision

© Hord Coplan Macht, Inc.

9

ARCHITECTURE

LANDSCAPE ARCHITECTURE

PLANNING

INTERIOR DESIGN

Drawing

Scale

Date

ARCHITECT

Hord Coplan Macht, Inc.700 E. Pratt St, Suite 1200Baltimore, MD 21202p. 410. 837. 7311 f. 410. 837. 6530

ENVELOPE CONSULTANT

Construction Systems Group, Inc. 1451 Dolley Madison Blvd., Suite 300 McLean, VA 22101p. 703.917.0055 f. 703.917.0464

Project Number

Project Name

8

7

6

5

4

3

2

1

LKJHGFEDCBA C:\Users\jhagan\Documents\Pinehurst ES - Roof Replacement_jhagan.rvt

2/11/2019 1:34:30 PM

1 1/2" = 1'-0"

PINEHURST

ELEMENTARY

SCHOOL ROOF

REPLACEMENT

520 S Pinehurst, Salisbury, MD 21801

CONSTRUCTION DOCUMENTS

FEBRUARY 11, 2019

WICOMICO COUNTY PUBLICSCHOOLS

218345.00

A1.04

ROOF DETAILS

PINEHURST ELEMENTARYSCHOOL ROOF REPLACEMENT

1 1/2" = 1'-0"A1.01 A1.04

ROOF DRAIN - BU/MOD BIT2F 1 1/2" = 1'-0"A1.01 A1.04

EQUIP CURB - BU/MOD BIT2J 1 1/2" = 1'-0"A1.01 A1.04

PLUMB VENT PENETRATION - BU/MOD BIT2D 1 1/2" = 1'-0"A1.03 A1.04

ROOF EXP JT DETAIL - BU/MOD BIT2A

1 1/2" = 1'-0"A1.01 A1.04

ROOF EDGE DETAIL 1968 BUILDING @ SOUTH SLOPED ROOF9H

1 1/2" = 1'-0"A1.01 A1.04

ROOF EDGE DETAIL 1963 BUILDING5G 1 1/2" = 1'-0"A1.01 A1.04

ROOF EDGE DETAIL 1963 BUILDING AT CANOPY5A

1 1/2" = 1'-0"A1.01 A1.04

ROOF EDGE DETAIL 1963 BUILDING @ 1937 BUILDING9D 1 1/2" = 1'-0"A1.01 A1.04

ROOF EDGE DETAIL 1963 BUILDING @ CAFETERIA9A

1961 BUILDING1968 BUILDING

EXPANSION JOINT

POLYISOCYANURATE INSULATION

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

A1.04

2A

BASE SHEET & VAPOR BARRIER

EXISTING TECTUM DECK

EXISTING TECTUM ROOF DECK

EXISTING METAL LATH & STUCCO SOFFIT

EXISTING SOFFIT VENT

EXISTING STRUCTURE

26 GA. STAINLESS STEEL D-STYLE GUTTER

EXISTING WOOD BLOCKING

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

4" MIN.

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

SEAL GAPS AT ALL PERIMETERS WITH FOAM

GUTTER CLEAT FASTENED 6" O.C.

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

26 GA. STAINLESS STEEL DRIP EDGE SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

NOTE: ADJUST WOOD BLOCKING AS NECESSARY TO ACCOMODATE HEIGHT OF INSULATION.

EXISTING WOOD BLOCKINGWITH NEW ALUMINUM WRAP

SEALANT

EXISTING TECTUM DECK

26 GA. STAINLESS STEEL D-STYLE GUTTER

EXISTING WOOD BLOCKING

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

4" MIN.SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

SEAL GAPS AT ALL PERIMETERS WITH FOAM

GUTTER CLEAT FASTENED 6" O.C.

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

26 GA. STAINLESS STEEL DRIP EDGE SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

NOTE: ADJUST WOOD BLOCKING AS NECESSARY TO ACCOMODATE HEIGHT OF INSULATION.

26 GA. STAINLESS STEEL D-STYLE GUTTER

EXISTING WOOD BLOCKING

BASE SHEET & VAPOR BARRIER

POLYISOCYANURATE INSULATION

4" MIN.

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL CONTINUOUS CLEAT 6" O.C.

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

FRONT LIP 1" LOWER THAN BACK EDGE

2" GUTTER STRAP @ 24" O.C. 1/8" STAINLESS STEEL TO MATCH GUTTER

SEAL GAPS AT ALL PERIMETERS WITH FOAM

GUTTER CLEAT FASTENED 6" O.C.

EXTEND PLY OVER BLOCKING FASTEN 8" O.C.

26 GA. STAINLESS STEEL DRIP EDGE SET IN ROOF CEMENT, NAILED 3" O.C.. STAGGERED, PRIME METAL FLANGE PRIOR TO STRIPPING

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

1/2" SECUROCK

MODIFIED BITUMEN BASE SHEET

MODIFIED BITUMEN MINERAL CAP SHEET

EXISTING WOOD BLOCKINGWITH NEW ALUMINUM WRAP

EXISTING TECTUM ROOF DECK

SEALANT

EXPANSION JOINT

1971 ADDITION1986 ADDITION

POLYISOCYANURATE INSULATION

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE (MIN. 1.5" EMBEDMENT)

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

CANT STRIP

SEALANT, REFERENCE SPECIFICATION

26 GA. STAINLESS STEEL COUNTERFLASHING

LEAD WEDGE @ 18" O.C.

SEALANT, SEE SPECIFICATION

A1.04

2A

8" M

IN.

BASE SHEET & VAPOR BARRIER

EXISTING METAL DECK

SEAL GAPS AT ALL PERIMETERS WITH FOAM

BASE SHEET & VAPOR BARRIER

1/2" SECUROCK

CANT STRIP, FASTENED TO NAILER

POLYISOCYANURATE INSULATION

BASE SHEET & VAPOR BARRIER

EXISTING TECTUM DECK

NEW METAL COUNTERFLASHING. 26 GA. STAINLESS STEEL, 1/8" RIVET EVERY 12"O.C.

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

SEALANT, REFERENCE SPECIFICATION

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE

8" M

IN.

EXISTING METAL EXHAUST COVER

NOTE: INCREASE HEIGHT OF CURB AS NECESSARY TO MAINTAIN MINIMUM FLASHING HEIGHT

CANT STRIP, FASTENED TO NAILER

POLYISOCYANURATE INSULATION

BASE SHEET & VAPOR BARRIER

EXISTING TECTUM DECK

NEW COUNTERFLASHING, 26 GA. STAINLESS STEEL, 1/8" RIVET EVERY 12" O.C.

TORCH MINERAL CAP FLASHING PLY 9" MIN. ON FIELD

TORCH BASE FLASHING PLY 6" MIN. ON FIELD

MODIFIED BITUMEN CAP SHEET

MODIFIED BITUMEN BASE SHEET

1/2" SECUROCK

SEALANT, REFERENCE SPECIFICATION

TERMINATION BAR FASTENED @ 8" O.C. THROUGH BUTYL TAPE

8" M

IN.

4" M

IN.

EXISTING PASSIVE AIR/VENT INTAKE

M

PROFESSIONAL CERTIFICATION: I CERTIFY THAT THESE DOCUMENTS WERE

PREPARED OR APPROVED BY ME, AND THAT I AM A DULY LICENSED ARCHITECT

UNDER THE LAWS OF THE STATE OF MARYLAND

LICENSE NUMBER:

EXPIRATION DATE:

no. date revision

© Hord Coplan Macht, Inc.

9

ARCHITECTURE

LANDSCAPE ARCHITECTURE

PLANNING

INTERIOR DESIGN

Drawing

Scale

Date

ARCHITECT

Hord Coplan Macht, Inc.700 E. Pratt St, Suite 1200Baltimore, MD 21202p. 410. 837. 7311 f. 410. 837. 6530

ENVELOPE CONSULTANT

Construction Systems Group, Inc. 1451 Dolley Madison Blvd., Suite 300 McLean, VA 22101p. 703.917.0055 f. 703.917.0464

Project Number

Project Name

8

7

6

5

4

3

2

1

LKJHGFEDCBA C:\Users\jhagan\Documents\Pinehurst ES - Roof Replacement_jhagan.rvt

2/11/2019 1:34:30 PM

1 1/2" = 1'-0"

PINEHURST

ELEMENTARY

SCHOOL ROOF

REPLACEMENT

520 S Pinehurst, Salisbury, MD 21801

CONSTRUCTION DOCUMENTS

FEBRUARY 11, 2019

WICOMICO COUNTY PUBLICSCHOOLS

218345.00

A1.05

ROOF DETAILS

PINEHURST ELEMENTARYSCHOOL ROOF REPLACEMENT

1 1/2" = 1'-0"A1.01 A1.05

ROOF EDGE DETAIL 1961 BUILDING @ 1968 BUILDING3G

1 1/2" = 1'-0"A1.01 A1.05

ROOF EDGE DETAIL 1968 BUILDING @ NORTH6E

1 1/2" = 1'-0"A1.01 A1.05

ROOF EDGE DETAIL 1968 BUILDING @ EAST & WEST9J 1 1/2" = 1'-0"A1.01 A1.05

ROOF EDGE DETAIL 1971 BUILDING @ EAST & WEST9E

1 1/2" = 1'-0"A1.01 A1.05

ROOF EDGE DETAIL 1986 BUILDING TO 1971 BUILDING3A

1 1/2" = 1'-0"A1.05

EQUIP CURB - BU/MOD BIT6A

1 1/2" = 1'-0"A1.05

EQUIP CURB - BU/MOD BIT9A