DAM FAILURESand

CONSTRUCTION INSPECTION

by

Hal Van AllerMaryland Dam Safety

Embankment Dam Schematic

Medford Quarry Wash Pond CMP failure

Velvet Hills sinkhole

Sinkhole in crest of new MD dam

WCC (Joe Kula) Testpit along pond CMP spillway

AACounty CMP with void

Loveton Dam Failure (1989) Breach

Anti-seep collars do

not prevent seepage failures!

Loveton 78” CMP viewed from downstream

78 inch CMP viewed from downstream

Failed PVC pipe with anti-seep collar

Annap Mall collapsed CMP d.s. of Riser

Annap Mall u.s. view

What caused these failures?• Design• Construction• Inspection• All of the

above??

Spillways are “Confined Space”

Ray Martin cave

Typical Problems schematic

Compaction in Haunches

Pipe Installation in DamDam Embankment

Filter Diaphragm

Flowable FillPipe in vertical trench

Excavation through dam

• Side slopes must be 2(H):1(V) or flatter

15 ft

FILTER DIAPHRAGM

Centennial Park dam chimney drain construction

Filter Diaphragmflooding with water for

compaction

Merkle Filter Diaphragm with vibrator

CONSTRUCTIONExperienced contractor desired

• must realize that ponds are different from roads and utilities

• must work with design engineer• compaction along spillway is critical--

don’t construct embankment and then cut trench

• spillway joints must be watertight

Alternative Designs• Avoid large diameter CMP• User weir or drop box structure• If pipes unavoidable, use:

– Concrete pressure pipe (min. ASTM C-361)– Complete concrete cradle or flowable fill– Watertight joints– Filter diaphragm

• Avoid combining pond with road embankment

CHUTE SPILLWAYS SCHEMATIC

Concrete flumes on embankment have problems too

CMP spillway on steep slope through dam embankment

Tasker’s Chance concrete weir

Crooksville, OHIO-COMPLETED WEIR

Parker Pond new sheet pile spillway

Do's and Don’ts for Pond Design and Construction

• Don’t use anti-seep collars to “stop” leakage• Do use filter diaphragms• Don’t allow spillway installation in trench• Do require watertight joints• Do inspect each pipe joint as it is put together

so it can be redone if necessary• Do consider alternative spillway design that

eliminates pipe through dam or foundation

InspectionMore than just testing Compaction!

• Inspector should:! work for the design engineer, not the

contractor! understand design assumptions and effects

of unanticipated conditions! not allow deviation from design without

design engineer’s approval! observe and document: pipe mfg marks, joint

type, gasket material and size, and installation procedure

Foundation

• Proof rolling• Inspection by Geotechnical Engineer

Compaction

• Use STANDARD Proctor (ASTM D-698 or AASHTO T-99)

• Do Not use MODIFIED Proctor (ASTM D-1557 or AASHTO T-180)

• Nuclear gage readings need to be corrected to match lab moisture & density

Utility Conduits(water, sewer, gas)

• Pipes through the dam must meet spillway requirements

• No granular backfill for pipes parallel to the dam axis

Pre-cast riser structures

Anchor Plates

Movement

Leaky Joints

Concrete Pipe Installation

• Pipe supports• Clean and Lubricate joints• Lubricate Gasket• Tension Gasket• Full concrete cradle, not just bedding• If not o-ring gaskets then owner and

engineer must approve

Prepare foundation and supports

Mudmat is a good idea

Clean joints

Lubricate joints

Lubricate o-ring

Tension o-ring withround-shaft screwdriver

Mis-aligned o-ring ...

...causes broken bell

Gaskets for Concrete PipeTraditional O-ring joint

•Deep joint allows for substantial extensibility

•Symmetric design accommodates internal or external pressure

Newer “Profile Gaskets”

Press-Seal Gasket Company states these “advantages” over o-rings:

•Stepped joint is cheaper to manufacture than groove for confined o-ring gasket

•Easier to install, less force needed to “home” joint

•Less bell breakage

Gaskets for Concrete PipeNew style “Profile Joint”

•Smaller joint separation allowance

•Designed for internal pressure

Gaskets for Concrete PipeNew style “Profile Joint”

Formed concrete cradle

Cradle poured against

soil

Poor installation

Take Pictures!

Dam on Soft Foundation

Spillway pipe atend of construction

Same pipe after excessive foundation settlement